Preview only show first 10 pages with watermark. For full document please download

Presence Detector Opp-pir-1

   EMBED


Share

Transcript

Presence detector OPP-PIR-1 • 24 V AC/DC connection • Shut-off lag: 10s to 30 minutes • Switch-on lag: 0 to 10 minutes • Relay output: one changeover contact • additional temperature monitoring (adjustable) Technical Data Housing: Dimensions: Power supply: Output signal: Ambient conditions: Max. temperature: Min. temperature: Installation height: Accessories: Product description Plastic, white, IP20 66 x 112 x 45 (mm) (L x W x D) 24 ± 2 V AC/DC, 7 mA 1 changeover contact 24 V AC/DC 5 A/NO, 3 A/NC -20 – +50 °C, max. 95 % RH 24°/26°/28 °C adjustable 15°/17°/19 °C adjustable 1.8 – 3.6 m Incl. installation bracket MB 99 for wall or ceiling installation Dimensions The OPP-PIR-1 is a presence detector specifically designed for HVAC applications in a visually appealing, white housing. The lens has a detection angle of 110° to reliably detect motion. The switch-on and switch-off lag is adjustable with jumpers. The OPP-PIR-1 allows the adjustment of max. and min. temperature thresholds. The relay is automatically energized if the room temperature exceeds the max. threshold or drops below the min. threshold. Remove the jumpers from the pins to activate the reset/temperature monitoring function. First switch off the power supply. Connecting diagram 45 mm NC 112 mm NO C Relay output 24V AC/DC, 5A/NO, 3A/NC 66 mm A 2,4 m B C 110° Available detection range 2,5 m 8m 15 m Möglicher Erfassungsraum  Ø Ø 24V AC/DC Remove the circuit board from the base plate before connecting the cables. Switch-on and switch-off lag Detection range Top view Draufsicht Contacts are shown disconnected from power. The relay is energized on motion. Contact C - NO is then closed. Side view Seitenansicht D E F ON OFF 0 Sec 10 Sec 10 Sec 1 Min 30 Sec 5 Min 1 Min 10 Min 5 Min 20 Min 10 Min 30 Min Note! Always switch off the power supply before changing the lag values. Sensor ventilation air conditioning  |  Data sheet No. 15603  |  Version 02-2012  |  1 | 2 Presence detector OPP-PIR-1 Function diagram • Red LED is always on when the sensor detects motion. • Red LED blinks when the lag jumper is removed. Note! The LED blinks if a jumper is not seated properly. MB 99 bracket for wall or ceiling installation Ceiling installation Wall installation Installation instructions All work (such as installation, electrical connection, startup, operation, and maintenance) must only be performed by sufficiently qualified tradesmen. The respectively applicable local rules and regulations (e.g. national building codes, electrical/ VDE regulations, etc.) must be observed. Installers and operating entities are required to sufficiently familiarize themselves before startup. Read the product description before operating the equipment. Verify that the product can be used for the relevant application without restrictions. We are not liable for printing errors and changes after printing. Appropriate use implies compliance with operating and installation instructions. We are not liable for losses due to inappropriate use. Unauthorized or inappropriate manipulations or modifications of the device render the operating permit, the product warranty and warranty claims null and void. Installation: 1. Open the cover with the retaining screw. Remove the circuit board from the main housing. 2. Punch out the appropriate mounting holes and install the main housing at the desired location using the included screw. 3. Position the circuit board and connect the cable with the appropriate terminals. 4. Remember to seal all unused cable punch outs and screw holes to avoid false alarms (due to insects, etc.) 5. Install the cover and perform a function check. 6. Note: Switch off the power supply before changing the lag values. Do not install the device in locations with direct sun irradiation or directly above high heat sources. Ensure that no objects (plants, large pieces of furniture, etc.) that can block the detection grid are located in the monitored space. The PIR sensor is more responsive to transverse motion than to motion toward the sensor. Function check: Set the ON and OFF jumpers to the „A“ position (shortest lag). Switch on the power supply and wait for approx. 45 sec. The LED blinks (long - short) during the warm-up phase. Walk through the detection zone. The LED lights up when the sensor detects motion. Oppermann Regelgeräte GmbH  |  Im Spitzhau 1  |  70771 Leinfelden-Echterdingen, Germany Phone +49 711 72723560  |  Fax +49 711 7280527  | [email protected] | www.oppermann-regelgeraete.de 2 | 2  |  Sensor ventilation air conditioning  |  Data sheet No. 15603  |  Version 02-2012  Specifications subject to change.