PRODUCT GUIDE Industrial Process Cooling
Cooling your industry, optimising your process.
ENERGY FOR THE FUTURE Modern industry’s increasing levels of sophistication and capital investment imply that highest precision with zero downtime are an absolute must for an economically viable process. MTA’s cooling solutions, developed specifically for industrial Users, perfectly answer industry’s need for precise temperature control and absolute reliability, 24 hours a day, 365 days a year. The cost of not implementing the optimised solution far exceeds the cost of an optimised MTA industrial cooling solution.
THE PHILOSOPHY BEHIND “COOLING, CONDITIONIG, PURIFYING” A company built on solid foundations
Pioneering innovation
Founded over 30 years ago with the aim of providing innovative energy solutions, today MTA covers a role of Global leader within the fields of the conditioning of commercial, public or residential ambients, industrial process cooling and compressed air & gas purification. MTA’s energy solutions offer unique answers to individual Customer needs. MTA’s mission is to maximize Customer satisfaction by means of expert support, implementing optimized solutions with a minimal environmental impact.
MTA’s future is founded upon the principals of innovation and excellence. Unique Customer solutions are born from a notable and continuous investment in R&D. Numerous patented products and state-of-the-art testing facilities ensure MTA products are not only highly advanced, but also extremely reliable. MTA’s production facilities offer flexible manufacturing processes with extensive individual testing of each and every product leaving the factory. MTA is ISO9001:2008 certified.
Expert consultancy and service
Environmental commitment
MTA’s energy lies within its people, with a dedicated team of experts focused to a single aim, that of satisfying and exceeding the needs and requests of its Customers. Continuous Business Process updates, coupled with advanced operating procedures, ensure MTA remains at the forefront of corporate development. MTA’s worldwide network of expert personnel receive continuous and extensive training, to ensure that everybody representing MTA assumes the role of expert consultant towards its Customers.
MTA’s very first product, a patented refrigeration dryer offering a new dimension in energy savings, set the path which has been followed ever since. Today MTA boasts novel products ensuring a minimal environmental impact and offers expert consultancy concerning energy savings within Customer applications. MTA’s facilities and processes meet the requirements of ISO 14000 environmental legislations. MTA strives to ensure its success also benefits the ambient in which it operates.
The power of a global team
Application driven Customer solutions
MTA boasts 3 production facilities, Sales Companies covering 4 continents and a network of Partners in over 80 countries worldwide. The expert international service network, is backed up by a comprehensive worldwide spare parts coverage. MTA products, designed for operation worldwide, comply to local legislations. Advanced supervision technology, including web browser and GPRS connectivity, ensures peace of mind wherever you may be.
MTA’s success is based upon understanding Customer applications. At MTA the aim is not to merely supply products, rather to fully maximize Customer potential. Whether it be office buildings, hotels, hospitals, shopping centres, cultural institutions, leisure facilities, telecommunications, public buildings or residential applications, MTA has the answers to each specific air conditioning need. Add to that MTA’s extensive knowledge of industrial air conditioning and process cooling, within a vast array of individual applications.
A partner you can trust MTA’s success has been built upon its reputation within the marketplace, with endless renowned companies worldwide placing their trust in MTA to supply them with the optimum solution to their needs. MTA’s flexibility towards special Customer solutions ensures each and every need can be satisfied. Continuous communication and cooperation with its Partners and Customers ensures MTA creates a team spirit with an aim towards excellence and long-term collaboration.
200 distributors, 80 countries, 30 years of experience, 4 continents… all add up to make us your ideal partner SINCE
OVER
OVER 30 YEARS OF INNOVATION
EMPLOYEES WORLDWIDE
PRODUCTION PLANTS
CHILLERS RANGE
DRYERS RANGE
UNITS BUILT PER YEAR
PRODUCTIVE AREA
Tribano (Padua)
Conselve (Padua)
COUNTRIES
Bagnoli di Sopra (Padua)
CERTIFICATIONS
Eurovent
EAC
UL
ISO 9001:2008
ASME U Stamp
National Board
MTA PROCESS COOLING APPLICATIONS
Automotive
Food
Beverage
Chemical
Pharmaceutical
Laser
Diagnostic
Machine Tools
Wineries
Rent
Plastics
European Conformity Marking
PRODUCT GUIDE Industrial Process Cooling
TABLE OF CONTENTS Product selection ..................................................................
8
TAEevo TECH .......................................................................... 10 TWEevo TECH ......................................................................... 12 HAEevo TECH .......................................................................... 14 TAEevo M ................................................................................ 16 TAEevo LASER ........................................................................ 18 ARIES TECH........................................................................... 20 GALAXY TECH ........................................................................ 22 PHOENIX PLUS ...................................................................... 24 ARIES FREE-COOLING .......................................................... 26 PHOENIX FREE-COOLING ..................................................... 28 AQUAFREE ............................................................................. 30 NEPTUNE TECH .................................................................... 32 AQUARIUS PLUS 2 ................................................................. 34 RWD ....................................................................................... 36 Connectivity ............................................................................ 38 The complete MTA product programme .............................. 40
PRODUCT SELECTION AIR-COOLED WATER CHILLERS
0
150
TAEevo TECH
Pag. 8
R410A
7
TAEevo TECH UL
Pag. 10
R410A
7
TAEevo M
Pag. 12
R134a R407C
ARIES TECH
Pag. 16
R410A
GALAXY TECH
Pag. 20
R410A
PHOENIX PLUS
Pag. 26
R134a
264
1,4 4,4
0
17
R410A
HARIES TECH
Pag. 18
R410A
17 15
ARIES FREE-COOLING
Pag. 28
R407C
PHOENIX FREE-COOLING
Pag. 30
R407C
150
350
2000 KW
150
350
2000 KW
96 90 221 178
AIR-COOLED WATER CHILLERS WITH INTEGRATED FREECOOLING
1668
90
0
Pag. 13
1354
436
AIR-COOLED HEAT PUMPS HAEevo TECH
440 461
R407C
Pag. 12
2000 KW
230
216
AIR-COOLED WATER CHILLERS (LASER VERSION)
TAEevo LASER
350
0
373
150
65
443
350
2000 KW
226 248
662
LEGEND Mode
Fans
Compressors
Cooling
Axial
Rotary
DC Inverter Rotary
Plates
Immersed Finned Coil
Cooling / Heating
High pressure axial
Scroll
DC Inverter Scroll
Shell &Tubes
Finned Coil
Screw
Pistons
Sigle Pass Shell & Tube
Coaxial
Centrifugal
8
Heat Exchangers
MTA | Product Guide | Industrial Process Cooling
ADD-ON FREECOOLING MODULES AQUAFREE
Pag. 36
0
-
242
0
TWEevo TECH
Pag. 14
R410A
-
TWEevo TECH UL
Pag. 14
R410A
-
NEPTUNE TECH
Pag. 32
R410A
-
AQUARIUS PLUS 2
Pag. 34
R134a
-
CONDENSERLESS UNITS
12
Pag. 32
R410A
-
AQUARIUS PLUS 2
Pag. 34
R134a
-
HYDRAULIC AIR TREATMENT TERMINAL UNITS -
-
2000 KW
466
150
Multiple modules
350
2000 KW
231
23
276 300
710
489
0
NEPTUNE TECH
Pag. 37
350
-
WATER-COOLED WATER CHILLERS
RWD
150
150
350
2000 KW
300 278
657 380
0
150
10
1982
427
710 1549 1740
350
2000 KW
372
Cooling your industry, optimising your process. | MTA
9
TAEevo TECH
R410A
Air cooled industrial chillers with Scroll compressors and R410A refrigerant Cooling capacity 7 – 230 kW.
Benefits
Standard features
• The unique evaporator-in-tank configuration has been specifically designed for process cooling applications. It allows high flow rates with low pressure drops and it is furthermore compatible with the presence of contaminated process fluids; • Scroll compressors ensure high efficiency, excellent performance and elevated energy savings; • Extended operating limits: Tw in max = +35 °C; Tw out min = -10 °C; Tamb max = +46 °C; Tamb min = -5 °C; • R410A non ozone depleting refrigerant increase the performance thanks its outstanding heat conductivity; • The oversized hydraulic tank is standard and is able to compensate for the imbalances caused by sudden changes in load demand from the user; • IP54 / IP44 electrical protection rate makes TAEevo Tech suitable for outdoor installation; • Extensive range of accessories and kits, allow each unit to match the specific customer requirements; • Cooling circuit suitable both for atmospheric and pressurized hydraulic circuits (up to 6 barg); • Comprehensive safety equipment, including phase monitor pressure switches, antifreeze sensors, level sensors, crankcase heaters and an internal hydraulic bypass circuit.
• Refrigerant R410A; • Hermetic Scroll compressors; • High-efficiency finned coil evaporator with copper tubes and aluminum fins, installed inside the water storage tank; • Axial fans with with galvanized steel (mod. 015-020) or die-cast aluminum/plastic crescent-shaped blades (mod. 031-802); • Oversized air-cooled condensers (copper tubes /aluminium fins). Air filter standard from mod. 031; • Storage tank (design pressure 6 barg) complete with pump, filling/drain valve, pressure gauge; • Internal hydraulic bypass between the inlet and outlet connections; • Electronic level sensor with water conductivity function; • High and low refrigerant pressure switches; • Refrigerant pressure gauges (mod. 031-802); • Parametric microprocessor control IC208CX; • Protection rating: IP54 (mod. 031-802); IP44 (mod.015-020); • Phase monitor; • Compressor crankcase heater.
Versions • TAEevo Tech HE High efficiency (Mod. 031-802): high efficiency version class A Eurovent (european EN14513). Includes oversized condensing coils, scroll compressors and high efficiency EC brushless axial fans. • Non Ferrous Version (mod. 015-351): stainless steel water tank, copper/brass exchanger, stainless steel pump; • Version for low environmental temperature -20 °C (mod. 031-802): electrical panel heating, electronic fan speed control; • Dual frequency version: power supply 400V/3/50 Hz - 460V/3/60 Hz (mod. 015-161); • 60 Hz version (mod. 015-802): 460/3/60 Hz power supply; electrical panel certified in compliance with UL508A.
10
MTA | Product Guide | Industrial Process Cooling
Main options • P3, P5 pumps, double pumps in stand-by P3+P3 or P5+P5 (mod. 201 802); SP (without pump); • Version with painted fins against corrosion; • Axial fans electronic fan speed control by phase cut; centrifugal fans (031-161); EC brushless axial fans with high head pressure (201-802); • Anti-freezing heaters (on tank and pumps); • Soft starter option: factory fitted (381-802); • Manual filling tank kit: suitable for hydraulic circuits at atmospheric pressure; • Automatic filling kit: suitable for pressurized hydraulic circuits (up to 6 barg); • Remote ON/OFF kit and remote control kit (max 150 m); • Remote control kit VICX620 display LED, VGI890 display LCD (max 150 m); • Supervisor kits: RS485 ModBus, xWEB300D.
Personalize TAEevo Tech to your individual needs Option • The high quality of the standard unit, the wide range of options and kits suitable to develop customized solutions, make TAEevo Tech chillers the ideal choice for every type of industrial cooling application. • Pump options: P3, P5, double P3+P3 or P5+P5 (mod. 201-802); SP (this version without pump includes the electrical devices necessary to supply an external P3 pump); • Condenser option: version with painted fins against corrosion; • Axial fans electronic fan speed control by phase cut (mod. 031-802); • Centrifugal fans (mod. 031-161); • High efficiency EC brushless axial fans with high head pressure (max 150 Pa) and inverter control (mod. 201-802); • Anti-freezing heaters (on tank and pumps) option; • Soft starter option: factory fitted (mod. 381-802); • Axial fans electronic fan speed control kit (mod. 031-802); • Electronic expansion valve (mod 081 - 802); • Painted condensing coils.
Centrifugal pump
Kit • • • • • • • • •
Manual filling tank kit: suitable for hydraulic circuits at atmospheric pressure (mod. 015-802); Automatic filling kit: suitable for pressurized hydraulic circuits (up to 6 barg); Glycol filling kit: suitable for pressurized hydraulic circuits; Automatic glycol pumping group; Centrifugal fans kit (mod. 031-161); Painted condensing coils; Simple remote ON/OFF kit (max 150 m); Remote control kit: VICX620 display LED, VGI890 display LCD semi graphic (max 150 m); Supervisor kits: RS485 ModBus, xWEB300D.
High efficiency EC brushless axial fans (option)
xWEB300D
Fill kits
Connectivity
Atmospheric pressure fill kit
Pressurised fill kit
Remote control options
Supervisor options
This kit is simply installed onto the back of the chiller itself, and features a generous tank with an easy to read water level indication encased within a tough painted steel cabinet. A tap offers easy chiller water tank filling (atmospheric hydraulic circuits).
This kit, is suitable for pressurised hydraulic circuits (up to 6 barg). The pressurised fill kit features all components required for safe and easy operation, including a pressure reducer, water inlet valve, pressure gauge, automatic relief valve, safety valve and expansion tank.
The following kits allow the remote control of the unit: • Simple remote control module (ON/OFF, unit status) for installation at up to 150 m from unit; • Advanced remote control kits VICX620 and VISOGRAPH VGI890, both with LED display (full control), for installation at up to 150 m.
TAEevo Tech can be linked to various external Supervisor systems: • RS485 serial connection to an external Supervisor system (MODBUS and other leading systems); • xWEB300D Supervisor kit, operating via Internet; • xWEB300D + GPRS modem for remote GSM connection directly to a smartphone.
Cooling your industry, optimising your process. | MTA
11
Dual Freq.
50 Hz version
Technical data 015 020 031 051 081 101 121 161 TAEevo Tech 50 Hz Cooling capacity (1) kW 7,00 8,30 13,3 19,4 30,1 39,2 48,3 55,5 Total absorbed power (1) kW 1,95 1,77 3,08 4,29 7,31 8,40 10,6 13,6 Cooling capacity (2) kW 5,00 5,96 9,58 13,9 22,3 29,1 35,9 41,5 Total absorbed power (2) kW 2,16 2,19 3,52 4,95 8,18 9,60 12,0 14,9 TAEevo Tech Dual-frequency - 60 Hz * Cooling capacity (1) kW 8,48 9,98 15,9 22,7 35,4 45,7 55,9 64,2 Total absorbed power (1) kW 2,38 2,17 3,77 5,41 8,98 10,6 13,3 17,0 Cooling capacity (2) kW 6,08 7,19 11,5 16,3 26,2 33,9 41,7 48,1 Total absorbed power (2) kW 2,64 2,66 4,29 6,19 10,1 12,0 15,0 18,5 General data Refrigerant Protection class IP 44 Total installed power 50 Hz (3) kW 3,8 3,9 5,7 7,4 12,0 14,4 18,3 20,5 Total installed power 50 Hz / 60 Hz (3) kW 4,0 / 5,2 4,1 / 5,4 5,6 / 7,4 7,3 / 9,3 12,5 / 15,4 14,9 / 18,3 17,8 / 22,6 20,1 / 25,3 Cooling circuits / Compressors per circuit N° 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 Capacity control % 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 Electrical power supply (3) Power V/Ph/Hz 400 ± 10% / 3 - PE / 50 - (460 ± 10% / 3 - PE / 60 dual-frequency version) Axial fans Fans number N° 1 1 1 1 1 2 2 2 Total airflow m3/h 3500 3150 6500 6150 8150 14200 13600 13600 Power (each) 50 Hz kW 0,203 0,203 0,48 0,48 0,71 0,71 0,71 0,71 Power (each) 50 Hz / 60 Hz kW 0,29 / 0,45 0,29 / 0,45 0,48 / 0,76 0,48 / 0,76 0,69 / 1,03 0,69 / 1,03 0,69 / 1,03 0,69 / 1,03 Centrifugal fans/high pressure axials fans Fans number N° 1 1 2 2 2 2 Total airflow m3/h 6600 6000 9200 12800 12800 12800 Available head pressure Pa 159 188 265 134 115 115 Power (each) kW 1,1 1,1 1,1 1,1 1,1 1,1 Hydraulic group Water flow rate P3 (min/max) m3/h 0,4/4,8 0,4/4,8 0,7/6 0,9/6 1,9/9,1 2,1/9,3 2,6/18 3,2/18 Available pump head pressure P3 barg 3,0/1,4 3,0/1,4 3,1/1,6 3,0/1,5 3,0/1,5 2,9/1,6 2,8/1,7 2,8/1,7 Nominal power P3 kW 0,55 0,55 0,75 0,75 0,9 0,9 1,85 1,85 Water flow rate P5 (min/max) m3/h 0,4/4,8 0,4/4,8 0,7/4,3 0,9/4,5 1,9/12,6 2,1/12,6 2,6/12,6 3,2/12,6 Available pump head pressure P5 barg 5,4/3,0 5,4/3,0 5,3/3,7 5,2/3,5 5,2/3,2 5,2/3,6 5,2/3,6 5,1/3,7 Nominal power P5 kW 1,1 1,1 1,1 1,1 2,2 2,2 2,2 2,2 Water flow rate P3 (min/max) m3/h 0,4/4,8 0,4/4,8 0,4/4,8 0,4/4,8 2,3/9,0 2,3/9,0 3,5/16,2 3,5/16,2 Available pump head pressure P3 (50 Hz) barg 3,1/2,0 3,1/2,0 3,1/2,0 3,1/2,0 3,1/1,9 3,1/1,9 2,4/2,0 2,4/2,0 Available pump head pressure P3 (60 Hz) barg 4,4/2,8 4,4/2,8 4,4/2,8 4,4/2,8 4,3/2,9 4,3/2,9 3,4/2,5 3,4/2,5 Nominal power P3 kW 1,1 1,1 1,1 1,1 2,2 2,2 2,2 2,2 Tank volume l 60 60 115 115 140 255 255 255 Max pressure barg 6 6 6 6 6 6 6 6 Water connections Rp 3/4" 3/4" 1" 1" 1 1/2" 1 1/2" 1 1/2" 1 1/2" Sound levels (3) (4) - 50 Hz Sound pressure with axial fans dB (A) 52,4 52,4 53,1 53,1 53,6 54,1 54,1 55,0 Sound pressure with centr.fans /high pressure axial fans dB (A) 58,8 58,8 61,2 61,2 61,2 61,2 Dimensions and installed weight (5) Width mm 560 560 660 660 761 761 761 761 Length mm 1284 1284 1315 1315 1862 1862 1862 1862 Height mm 795 795 1373 1373 1437 1437 1437 1437 Weight without pump kg 193 198 312 335 470 629 639 655 Weight with P3 kg 205 210 324 347 483 642 656 672 Weight with P5 kg 211 216 329 352 496 655 665 681
(1) Evaporator water inlet/outlet temperature 20/15 °C, external air temperature 25 °C; (2) Evaporator water inlet/outlet temperature 12/7 °C, external air temperature 35 °C; (3) Unit with P3 pump and ON/OFF control; (4) Sound pressure level in free field at 10 m from unit condenser side and 1,6 m from ground; (5) For units with standard power supply, axial fans, ON/OFF fan speed conrol. Max external air temperature 46 °C (with water temperature 12/7 °C). Data declared according to UNI EN 14511:2013. For the technical data regarding HE version and the 60 Hz UL version please refer to the documentation available. * For the performance of the dual-frequency version in 50 Hz see data table of the TAEevo Tech standard version in 50 Hz Higher energy efficiency.
12
Certified performance.
MTA | Product Guide | Industrial Process Cooling
IC208CX microprocessor control.
201
251
301
351
381
64,1 14,7 47,5 16,7
75,7 18,1 55,6 20,6
84,1 19,1 62,0 21,7
96,2 23,7 71,7 26,4
120,6 26,4 88,8 29,1
-
-
-
-
-
R410A 23,7 1/2
27,0 1/2
IP54 31,1 36,3 1/2 1/2 0-50-100
42,1 1/2
400 ± 10% 2 16200 0,71 -
2 16000 0,71 -
3 22200 0,71 -
3 21600 0,71 -
2 37000 1,9 -
2 14600 1 0,9
2 14600 144 0,9
3 20100 150 0,9
3 20100 142 0,9
2 40000 186 2,8
3,4/18 2,8/2,1 1,85 3,4/27 5,2/2,4 4 350 6 2"
3,4/18 2,8/2,1 1,85 3,4/27 5,2/2,4 4 350 6 2"
4,8/27 3,3/0,9 2,2 4,8/27 5,1/2,4 4 350 6 2"
5,6/27 3,3/0,9 2,2 5,6/27 5,1/2,4 4 350 6 2"
7,2/35 3,5/2,5 4 7,2/42 5,3/4,2 7,5 410 6 2 1/2"
56,3 57,0
56,3 57,0
58,0 58,7
58,0 58,7
60,3 61,2
866 2250 2054 931 948 985
866 2250 2054 1014 1031 1068
866 2250 2054 1025 1064 1079
866 2250 2054 1036 1075 1090
1150 2790 2090 1366 1408 1432
3
4
8 3
8 5
2
The capacity correction factors in the following table sh conditions differing from the above the selection softwa Evaporator ∆T ≠ 5 °C Correction factor
°C K2
4 0,994
Ethylene glycol solutions Correction factor - Cooling capacity
% K4
0 1
User friendly.
The perfect solution, whatever your application 401
402
502
602
702
802
136,0 29,0 99,6 32,1
123,2 29,4 91,3 33,3
146,4 33,6 107,7 38,5
166,1 38,8 122,4 44,0
199,8 44,7 150,3 50,2
230,1 52,9 175,3 58,5
-
-
-
-
-
-
47,7 1/2
48,9 2/2
55,5 61,4 70,5 2/2 2/2 2/2 0-25-50-75-100
2 35000 1,9 -
2 45800 1,9 -
2 44400 1,9 -
2 42800 1,9 -
3 63900 1,9 -
3 62100 1,9 -
2 40000 194 2,8
2 40000 198 2,8
2 40000 185 2,8
2 40000 172 2,8
3 60000 191 2,8
3 60000 176 2,8
8,0/35 3,5/2,5 4 8,0/42 5,3/4,2 7,5 410 6 2 1/2"
6,6/48 3,9/1,5 4 6,6/48 5,5/3,1 7,5 500 6 2 1/2"
8,1/48 3,8/1,5 4 8,1/48 5,5/3,1 7,5 500 6 2 1/2"
9,4/48 3,8/1,5 4 9,4/48 5,5/3,1 7,5 500 6 2 1/2"
61,7 62,4
61,5 63,1
61,5 63,1
61,5 63,1
1150 2790 2090 1451 1493 1517
1255 3298 2119 1654 1701 1733
1255 3298 2119 1703 1750 1782
1255 3298 2119 1739 1786 1818
12,5/56 14,9/56 3,3/2,5 3,3/2,5 5,5 5,5 12,5/72 14,9/72 4,8/3,4 4,8/3,4 9,2 9,2 678 678 6 6 3" 3"
1250 3535 2151 2213 2267 2290
Metal working: processing & transformation of precious metals, aluminium working & processing. Mechanical & Engineering: machine tools, welding machines, rolling mills, presses, extruders, cutting, profiling, polishing, electric spark machinery, hydraulic control unit oil cooling, pneumatic transport, heat treatment. Paper & related applications: printers, cardboard, labels, plastic film. Other applications: ceramics, textiles, wood, rental, air compressor cooling, other applications.
79,5 2/2
% / 3 - PE / 50
62,2 63,1
Plastics & rubber: presses, injection moulding, extrusion (sheet & profile), blow moulding, thermoforming, PET. Lasers, with a specific Laser chiller: cutting, welding, profiling, optics, medical, engraving. Food & drinks: confectionary, bakeries, distilleries, breweries, wineries, dairies, bottling, carbonation, meat & fish processing, vegetable & salad processing, storage. Chemical & pharmaceutical: jacketed vessels, polyurethane foam mixers, natural gas, industrial cleaning, laboratories, healthcare, solvents, paints.
Automotive
Food
Beverage
Chemical
Pharmaceutical
Laser
Diagnostic
Machine Tools
Wineries
Rent
Typical configuration for users suitable for closed circuits
Typical configuration for users suitable for open circuit
The below diagram shows a typical closed circuit lay-out. Pressurised closed circuit applications (5) always require an expansion vessel. TAEevo Tech units in standard (evaporator in tank) configurations are ideal for such applications, and offer a pressurised automatic fill kit including the expansion tank (as option).
The below diagram shows a typical open circuit lay-out. For atmospheric circuit applications featuring an open tank (4), the water is in contact with the ambient air, as such no expansion vessel is required. Such applications are suited to TAEevo Tech units in standard (evaporator in tank) configuration but without the tank kit and pump, given that the system typically features an external pump (2).
62,6 63,4
6
~
1250 3535 2151 2233 2287 2310
1
4
2
1 4
3
3
6 1,005
7 1,010
8 1,017
9 1,021
10 0,99
20 0,98
30 0,97
40 0,96
50 0,93
10 1,025
TAEevo Tech 50 Hz standard version (Mod. 015-802).
2
2
5
5 6
~
1
4
2
1
3
3
hould be used as a guide only, for accurate selection at are should be utilised. 5 1
Plastics
1
Accumulation tank
3
Valve
5
User
1
Accumulation tank
3
Valve
2
Pump
4
Non return valve
6
Expansion tank
2
Pump
4
Open tank
TAEevo Tech HE High efficiency (Mod. 031-802).
TAEevo Tech dual-frequency (Mod. 015-161)
5
User
TAEevo Tech 60 Hz (Mod. 015-802).
Cooling your industry, optimising your process. | MTA
13
TWEevo TECH
R410A
Water-cooled process chillers with R410A equipped with scroll compressors Cooling capacity 12,5 – 231 kW.
Benefits • Heat exchangers with low water side pressure drops in order to save pumping costs; • Reduced sound pressure level; • The unique evaporator-in-tank configuration has been specifically designed for process cooling applications. It allows high flow rates with low pressure drops and it is furthermore compatible with the presence of contaminated process fluids; • Scroll compressors ensure high efficiency, excellent performance and elevated energy savings; • Extended operating limits: Tw in max = +35 °C; Tw out min = -10 °C; Tamb max = +46 °C; Tamb min = -5 °C; • R410A non ozone depleting refrigerant increase the performance thanks its outstanding heat conductivity; • The oversized hydraulic tank is standard and is able to compensate for the imbalances caused by sudden changes in load demand from the user; • IP54 electrical protection rate makes TWEevo Tech suitable for outdoor installation; • Extensive range of accessories and kits, allow each unit to match the specific customer requirements; • Cooling circuit suitable both for atmospheric and pressurized hydraulic circuits (up to 6 barg); • Comprehensive safety equipment, including phase monitor pressure switches, antifreeze sensors, level sensors, crankcase heaters and an internal hydraulic bypass circuit.
• Condensing control valve kit (TOWER/WELL); • Remote ON/OFF kit and remote control kit (max 150 m); • Differential hydraulic by-pass kit - evaporator side; • Remote control kit VICX620 display LED; VGI890 display LCD (max 150 m) mod. 031-351; • Supervisor kits: RS485 ModBus, xWEB300D.
Main options
Versions
• P3, P5 pumps, double pumps in stand-by P3+P3 or P5+P5 (mod. 201 802); SP (without pump); • Condensing control option with servo-driven modulating valves or pressure control valves (TOWER/WELL); • Differential hydraulic by-pass valve - evaporator side (Mod. 031-602); • Anti-freezing heaters (on tank and pumps); • Soft starter option: factory fitted (381-802); • Manual filling tank kit: suitable for hydraulic circuits at atmospheric pressure; • Automatic filling kit: suitable for pressurized hydraulic circuits (up to 6 barg);
• Non Ferrous Version (031-351); • UL version: power supply 460/3/60Hz.
14
MTA | Product Guide | Industrial Process Cooling
Standard features • Refrigerant R410A; • Hermetic Scroll compressors; • High-efficiency finned coil evaporator with copper tubes and aluminum fins, installed inside the water storage tank; • High efficiency shell & tubes condensers optimized for R410A refrigerant gas • Storage tank (design pressure 6 barg) complete with pump, filling/drain valve, pressure gauge; • Internal hydraulic bypass between the inlet and outlet connections; • Electronic level sensor with water conductivity function; • High and low refrigerant pressure switches; • Refrigerant pressure gauges (mod. 031-802); • Parametric microprocessor control IC208CX; • Protection rating: IP54 (mod. 031-802); IP44 (mod.015-020); • Phase monitor; • Compressor crankcase heater.
TWEevo Tech model
031
051
081
101
121
161
201
251
301
351
381
401
402
502
602
702
Cooling capacity (1)
kW
12,5
19,1
31,5
38,0
47,9
58,0
65,3
74,9
85,8
98,5
115
130
126
148
168
193
802 231
Total absorbed power (1)
kW
2,9
4,5
7,2
8,4
10,7
12,9
14,8
16,5
19,1
24,0
25,9
29,3
29,3
34,7
37,7
43,3
52,1
Power supply
V/Ph/Hz
Noise level (*)
db(A)
40,0
48,3
42,4
48,0
49,5
50,2
50,0
51,0
52,6
54,2
55,0
58,0
53,6
55,1
56,4
57,5
58,5
Width
mm
660
660
760
760
760
760
865
865
865
865
1150
1150
1255
1255
1255
1251
1251
Depth
mm 1310
1310
1865
1865
1865
1865
2255
2255
2255
2255
2790
2790
3295
3295
3295
3550
3550
Height
mm 1265
1265
1310
1310
1310
1310
1930
1930
1930
1930
2020
2020
2050
2050
2050
1870
1870
Working weight (P3 pump) Tank volume
400 ± 10% / 3 - PE / 50
Kg
358
378
529
696
704
725
978
1061
1094
1105
1438
1523
1731
1780
1816
2297
2317
l
115
115
140
255
255
255
350
350
350
350
410
410
500
500
500
678
678
Condenser water connections
Rp 1 1/4" 1 1/4" 1 1/2" 1 1/2" 1 1/2" 1 1/2"
2"
2"
2"
2"
2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2"
3"
3"
Evaporator water connections
Rp
2"
2"
2"
2"
2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2"
3"
3"
1"
1"
1 1/2" 1 1/2" 1 1/2" 1 1/2"
Data declared according to UNI EN 14511:2013. All data refers to standard units at the following nominal conditions: (1) Evaporator water inlet/outlet temperature 20/15 °C, condenser water inlet/outlet temperature 35/40 °C. (*) Sound pressure level in free field at 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base.
IC208CX sophisticated microprocessor connectable to supervisor systems through RS485 or xWEB300D kits.
High efficiency shell & tubes condensers optimized for R410A refrigerant gas.
Standard Pump P3 (3 barg); optional P5 pump (5 barg). Also available double pumps P3+P3, P5+P5 in stand-by.
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW
The integral yet removable high capacity water tank ensures very precise water temperature control.
Cooling your industry, optimising your process. | MTA
15
HAEevo TECH
R410A
High efficiency air-cooled reversible industrial heat pumps with R410A equipped with scroll compressors Cooling capacity 16,7 – 96 kW Heating capacity 15,5 – 90,5 kW
Benefits
Standard features
• High energy performance thanks to the efficiency class A+ (according to Directive Erp - Ecodesign for energy related products – ENER Lot 1 - Tier 2 09/2017); • The unique evaporator-in-tank configuration has been specifically designed for process cooling applications. It allows high flow rates with low pressure drops and it is furthermore compatible with the presence of contaminated process fluids; • R410A non ozone depleting refrigerant increase the performance thanks its outstanding heat conductivity; • Scroll compressors ensure high efficiency, excellent performance and elevated energy savings; • Extended operating limits (CHILLER mode): Tw in max = +35 °C; Tw out min = -10 °C; Tamb max = +46 °C; Tamb min = -5 °C; • Extended operating limits (HP mode): Tw out max = +55 °C; Tw out min = +30 °C; Tamb max = +20 °C; Tamb min = -10 °C; • The condenser aluminium fins are protected by hydrophilic treatment; • The oversized hydraulic tank is standard useful to compensate the imbalances caused by sudden changes in load demand from the user; • IP54 electrical protection rate makes HAEevo Tech suitable for outdoor installation; • Free contacts available to the customer: ON/OFF remote control, chiller/ heat pump remote working change, double set point, management of heating auxiliary system (boiler/heater), managing of external 3-way valve for sanitary water; • Cooling circuit suitable both for atmospheric and pressurized hydraulic circuits (up to 6 barg); • Comprehensive safety equipment, including phase monitor pressure switches, antifreeze sensors, level sensors, crankcase heaters and an internal hydraulic bypass circuit.
• Refrigerant R410A; • Hermetic Scroll compressors; • High-efficiency finned coil evaporator with copper tubes and aluminum fins, installed inside the water storage tank; • Axial fans with die-cast aluminum/plastic crescent-shaped blades, • Oversized air-cooled condensers with copper tubes and aluminium fins protected by hydrophilic treatment; • Condenser air filter standard; • Double mechanical thermostatic expansion valve with external equalization; • 4-way refrigerant cycle reversing valve; • Storage tank (design pressure 6 barg) complete with pump, filling/drain valve, pressure gauge; • Internal hydraulic bypass between the inlet and outlet connections; • Electronic level sensor with water conductivity function; • High and low refrigerant pressure switches; • Refrigerant high pressure transducer; • Parametric microprocessor control IC208CX; • Protection rating: IP54; • Phase monitor against phase reversal; • Compressor crankcase heater; • Free contacts available to the customer.
Main options • P3, P5 pumps: with nominal head pressure 3 bar or 5 bar; • EC brushless axial fans with inverter technology; • Anti-freezing heaters (on tank and pumps); • Electronic expansion valve; • Manual filling tank kit: suitable for hydraulic circuits at atmospheric pressure; • Automatic filling kit: suitable for pressurized hydraulic circuits (up to 6 barg); • Automatic hydraulic bypass kit: includes adjustable pressure relief valve; • Remote control kit VICX620 display LED, VGI890 display LCD; • Supervisor kits: RS485 ModBus, xWEB300D.
16
MTA | Product Guide | Industrial Process Cooling
Versions • N Version (mod.031-351): basic version equipped with a carbon steel tank suitable for all industrial processes both with hydraulic circuits under pressure and atmospheric; • SN silenced version (mod. 121-351): version with noise reduced of approximately 3 dB(A) vs “N” version, by means of EC fans with inverter technology, insulation of the compressor compartment and jacket on the compressors; • Version with hydraulic circuit suitable for open storage tank systems (mod. 031-351): the pump sucks from the tank the process fluid to be cooled, making it circulate trhough the evaporator of the unit; • Non Ferrous Version: suitable for operation with aggressive process fluids (evaporator in copper protected by a brass frame, storage tank in AISI 304); • Dual-frequency version 400V/3/50 Hz - 460V/3/60 Hz (mod. 031-051).
HAEevo Tech models Cooling capacity (1) Total absorbed power (1) EER (1) Heating capacity (2) Absorbed power (2) COP (2) Energy efficiency class Power supply Noise level (*) Width Depth Height Working weight (P3 pump) Tank volume Evaporator water connections
kW kW kW kW V/Ph/Hz dB(A) mm mm mm Kg l Rp
031 16,7 3,70 4,51 15,5 4,61 3,37 A+
051 21,8 5,09 4,29 19,8 5,92 3,35 A+
081 28,6 6,12 4,67 26,0 7,07 3,68 A+
101 37,6 8,68 4,34 33,3 9,38 3,55 A+
48,8 662 1315 1416 329 115 1"
49,9 662 1315 1416 351 115 1"
50 761 1864 1470 495 140 1 1/2"
50 761 1864 1470 643 255 1 1/2"
121 161 47,3 55,3 10,9 13,5 4,33 4,11 45,0 52,3 13,0 14,6 3,46 3,59 A+ A+ 400 ± 10% / 3 - PE / 50 54 54,5 761 761 1864 1864 1470 1470 665 681 255 255 1 1/2" 1 1/2"
Data declared according to UNI EN 14511:2013. All data refers to standard units at the following nominal conditions: (1) Evaporator water inlet/outlet temperature 20/15 °C, external air temperature 25 °C; (2) Condenser water inlet/outlet temperature 40/45 °C, external air temperature 10 °C; (*) Sound pressure level in free field at 10 m from unit condenser side and 1,6 m from ground.
IC208CX sophisticated microprocessor connectable to supervisor systems through RS485.
A+ energy efficiency class according to Directive Ecodesign Erp 2017.
201 63,9 14,7 4,35 59,7 16,4 3,64 A+
251 75,6 17,5 4,33 68,1 18,9 3,61 A+
301 83,3 19,4 4,29 75,1 21,0 3,57 A+
351 96,0 23,3 4,12 90,5 25,8 3,50 A+
55,6 865 2251 2085 968 350 2"
55,6 865 2251 2085 1051 350 2"
55,9 865 2251 2085 1091 350 2"
57,5 865 2251 2085 1113 350 2"
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW
Standard Pump P3 (3 barg); optional P5 pump (5 barg).
The integral yet removable high capacity water tank ensures very precise water temperature control.
Cooling your industry, optimising your process. | MTA
17
TAEevo M
R134a R407C
Air-cooled process chillers with R407C, R134a equipped with rotary/pistons compressors Cooling capacity 1,4 – 4,4 kW
Benefits
Standard features
• Coaxial evaporator immersed in the tank. This heat exchanger in perfect countercurrent configuration allows excellent heat exchange and is designed specifically for heavy duty industrial applications; • Hydraulic circuit Non Ferrous: buffer tank in AISI 304, brass pump / water side bronze, copper evaporator; • The large buffer tank allows to maintain a constant outlet water temperature even in conditions of highly variable thermal load; • Air-cooled tubeless condenser in painted steel corrosion-resistant; • The pumps and the storage tank are integrated to simplify the operations of installation; • Extended operating limits: temperature range of the fluid from 0 °C up to + 30 °C. Max ambient temperature up to + 43 °C; ambient temperature min. of 0 °C.
• R134a Refrigerant (M03), R407C (M05-M10); • Hermetic reciprocating compressors (M03), rotary (M05-M10); • Coaxial evaporator in copper, installed inside the hydraulic tank; • Tubeless condenser in painted steel; • Axial fan protected by a thermal protector; • Buffer tank in AISI 304, pump P3, exhaust valves, pressure gauge; • Hydraulic security Bypass between water supply and return; • High pressure switch (M05-M10); • Controller: parametric microprocessor (M05-M10); thermostat (M03); • Degree of protection: IP33 (M05-M10); IP20 (M03).
18
MTA | Product Guide | Industrial Process Cooling
TAEevo M models
TAEevo M 03
TAEevo M 05
Cooling capacity (1)
kW
1,4
2,5
4,4
Compressor absorbed power (1)
kW
0,5
0,73
1,32
Water flow (1)
l/h
240
430
756
Cooling capacity (2)
kW
0,9
1,8
3,2
Power absorbed (2)
kW
0,52
0,77
1,36
Water flow (2)
l/h
155
310
550
Cooling circuit
N°
Compressors
N°
1
%
0 - 100
Capacity control Refrigerant Power supply
Total airflow Nominal power (each)
1
-
R134a
V/Ph/Hz
Protection class Fans number
TAEevo M 10
R407C
R407C
230 ± 10% / 1 / 50
-
IP20
IP33
1
1
1
m3/h
900
2200
2100
N°
IP33
kW
0,07
0,15
0,15
Width
mm
325
575
575
Depth
mm
728
652
652
Height
mm
540
805
805
Weight
kg
63
106
113
Data declared according to UNI EN 14511:2013. (1) Inlet water temperature 20 °C, outlet water temperature 15 °C, external air temperature 25 °C. (2) Inlet water temperature 12 °C, outlet water temperature 7 °C, external air temperature 32 °C. The listed noise levels, weights and dimensions refer to base chillers with no options fitted.
Cooling capacity correction factors Outlet water temperature °C Correction factors
Cf1
0
5
7
11
15
20
25
30
32
35
40
0,57
0,73
0,79
0,89
1,00
1,04
1,00
0,95
0,92
0,87
0,83
The capacity correction factors are refered tooutlet water temperature 15 °C and external air temperature 25 °C.
Microprocessor control (M05-M10).
Non ferrous P3 pump water side in bronze.
Coaxial evaporator immersed in the tank.
Air-cooled tubeless condenser in painted steel corrosion-resistant.
Cooling your industry, optimising your process. | MTA
19
TAEevo LASER
R407C
Air-cooled chillers for Laser applications, with R407C equipped scroll or piston compressors. Cooling capacity 17,5 - 90,2 kW.
Non-ferrous water circuit
Well specified hydraulic circuit
The increasing complexity of the laser sources necessitate the use of cooling fluids with an ever greater purity level. TAEevo Laser’s non-ferrous water circuit is suited to operation with demineralised water containing additives. The tank, plate evaporator and high head pressure centrifugal pump are all in stainless steel, and protect the laser source from all forms of contamination.
• Non-ferrous design, allows the use of demineralised water containing additives; • Stainless steel centrifugal multistage pump, including an outlet manometer; • Heating element to maintain the process fluid above the dewpoint, minimizing condensation risks; • Stainless steel atmospheric pressure accumulation tank with integrated drain valve; • Hydraulic circuit fill tank with externally visible water level; • Stainless steel brazed plate evaporator with manual bleed and drain valves; • Electronic level sensor with water conductivity function.
A plug-and-play solution TAEevo Laser always operates, whatever the conditions, thanks to shut-off valves, an adjustable internal by-pass valve, a 43 °C ambient temperature limit, an antifreeze protection and a self-regulating level sensor. Installation is notably simplified thanks to the integration of all components within the unit itself, an IP54 protection rating and the easy transportability of the unit itself.
Robust and reliable A robust frame and components from renowned suppliers, including reliable scroll compressors (models 081-351), ensure absolute peace of mind. Advanced safety devices ensure stable and safe operation, including a heater immersed in the tank (to avoid condensation on the laser’s optics), and an antifreeze function which activates the heater and starts the pump (for stable operation). Metallic condenser pre-filters are mounted as standard. All the units are equipped with a phase monitor which provides protection against phase loss and phase reversal. All the scroll compressors are equipped with crankcase heater as standard.
Easy to use and maintain The sophisticated laser equipment installed within a continuous production cycle needs to be backed up by chillers which are both absolutely reliable and very easy to maintain. MTA’s TAEevo Laser allows the chiller to be serviced even whilst it continues to operate normally, notably reducing downtimes. Easy access is ensured, thanks to the application of removable panels and access doors.
20
MTA | Product Guide | Industrial Process Cooling
Numerous options • 460/3/60 electrical power supply; • Coated condenser coils; • Industrial Westec connectors (Harting compatible); • Automatic water by-pass valve with differential overpressure; • Compressor valves; • Electronic fan speed control (also supplied as kit); • Remote control kit; • Supervisor kits (RS485, GPRS modem, xWEB300D).
Advanced microprocessor The microprocessor features a PID algorithm which controls the hot gas by-pass valve, ensuring a regulation accuracy of less than ± 0,5 °K. The compressors are disactivated during prolonged load absences, offering notable energy savings. RS485 Modbus, GPRS and web connectivity is offered, whilst an optional Westec industrial connector allows direct interfacing with the laser equipment.
Electrical and control circuits TAEevo Laser offers numerous safety and protection features, including anticondensate and antifreeze functions, plus general alarm, remote on/ off and unit status volt free contacts. Automatic circuit breakers for compressors, pump and fans are mounted as standard, as are refrigerant high and low pressure manometers.
TAEevo Laser models
051
081
101
121
161
201
251
301
351
Cooling capacity (1)
kW
17,5
25,5
38,2
47,8
52,6
60,5
73,2
80,7
90,2
Compressor absorbed power (2)
kW
6
7,7
10,5
12,4
15,7
18,7
21,3
23,7
27,8
43
Refrigerant
-
R407C
Power Supply Protection Class
400 ± 10% / 3-PE / 50 -
IP54
Total installed power (6)
kW
8,5
13
17
20
21
28
31
37
N° axial fans
N°
1
1
2
2
2
2
2
3
3
Total nominal power
kW
0,61
0,78
1,56
1,56
1,56
1,56
1,56
2,34
2,34
Total air flow
m³/h
6400
9200
16000
15000
14200
18200
17600
23700
23700
Noise level (5)
dB(A)
50
50,6
51
51
52
53,3
53,3
55
55
Water flow (nom. with ∆T 5 °C / max) (3)
m³/h
3/8
4.4/11
6.6/11
8.2/12
9.1/12
10.4/20
12.6/20
13.9/23
15.6/23
Available head pressure (nom./min.) (4)
bar
5.5/2.7
5.5/2.7
5/2.8
5/3.1
4.8/3.4
4.8/2.2
4.4/2
5.4/2.9
5.2/2.9
Nominal Power
kW
1,85
3
3
3
3
5,5
5,5
7,5
7,5
Width
mm
660
760
760
760
760
866
866
866
866
Depth
mm
1369
1964
1964
1964
1964
2351
2351
2351
2351
Height
mm
1400
1447
1447
1447
1447
2064
2064
2064
2064
kg
343
585
640
683
688
1015
1020
1100
1117
l
115
260
260
260
260
350
350
350
350
BSP
1"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
2"
Operating weight Tank volume Evaporator water connections
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet/outlet temperature 20/15 °C, external air temperature 35 °C; (2) Absorbed power from compressor(s) at reference conditions; (3) Nominal values refer to condition (1); (4) Nominal values refer to condition (1); (5) Sound pressure level in free field at 10m from unit condenser side and 1,2 m from the unit support base; (6) Max installed power with power supply 400/3/50, compressors, pump and fans with functioning working. The listed noise levels, weights and dimensions refer to base chillers with no options fitted.
IC208CX sophisticated microprocessor.
Stainless steel plate exchanger.
Atmospheric pressure fill kit.
Connectivity.
Cooling your industry, optimising your process. | MTA
21
ARIES TECH
R410A
Air cooled water chillers and heat pumps with R410A featuring hermetic scroll compressors. Cooling capacity 216 - 440 kW. Heating capacity 178 - 373 kW.
Benefits
Standard Features
• Reduced noise levels, thanks also to the availability of three differing acoustic versions; • High EER/COP levels, especially at partial loads; • Optimisation of performance also in heat pump mode thanks to hot gas injection and the innovative EcoDefrost defrosting system (min. ambient temperature -10 °C in heat pump mode); • Allows start-up and operation in even the most severe conditions thanks to the unloading function; • Simplified installation and easy access to all components; • User friendly controller with multifunctional buttons and dynamic display icons.
• 4 scroll compressors in parallel within two independent circuits; • Phase monitor against phase reversal; • Compressor crankcase heater; • Single brazed “dual-circuit” stainless steel plate evaporator; • Heat pumps equipped with 2nd thermostatic valve for optimised performance in all operating conditions); • Axial fans with progressive activation for optimised condensing pressure control, installed in two independent aeraulic sections; • Factory tested and supplied with refrigerant charge and antifreeze oil; • IP54 electric protection rating; • Environmentally friendly refrigerant R410A; • xDRIVE is a microprocessor electronic controller with high computing capacity and user friendly graphic interface; • RS485 ModBus interface for connection to supervisor systems; • Ethernet connection featuring pre-programmed HTML supervision pages, allowing local or internet based visualization and modification of the operating parameters.
Main Options • Shell and tube evaporator (AST only); • 1 or 2 high/low head pressure pumps and water pressure gauge; • Storage tank; • Electronic expansion valves (AST only); • Compressor shut-off valves on suction and discharge lines; • High efficiency EC inverter fans that allows an high energy savings, special at partial load; • Condenser coils designed for aggressive atmospheres; • Antivibration dampers; • Anti-freeze heaters on evaporator, pump and tank; • Metal mesh filters for condenser coil protection; • Electric power supplies differing from standard; • Soft starter allows about a 20% reduction of the start-up current than direct start; • Victaulic connections; • Simple remote control; • Replicated remote user terminal; • Serial connection to supervisor systems; • MTA xCONNECT supervision based on internal web pages; • Modularity/web interconnection hub.
22
MTA | Product Guide | Industrial Process Cooling
Versions • AST - Cooling only; • HAST - Reversible heat pump; • Low ambient air temperature - down to -20 °C in cooling mode (AST only); • H version - for high external air temperature / high efficiency (only AST); • Desuperheater 20%; • Heat recovery 100%. • Acoustic configurations: - N - basic acoustic configuration; - SN - low noise acoustic configuration; - SSN - very low noise acoustic configuration.
AST HAST
AST - HAST models Cooling capacity (1) Compressor absorbed power (1) Cooling capacity (2) Compressor absorbed power (2)
Heating capacity (3) Total absorbed power (2) Min external air temperature
kW kW kW kW °C °C kW kW kW kW °C
070 216 57,5 160 66,9 45 49 3,61 3,81 221 163 178 60,8 -7
080 261 64,0 193 74,9 46 49 3,90 4,01 262 193 213 70,4 -7
090 284 67,6 210 79,0 46 48 4,04 4,11 276 204 229 75,0 -6
Power supply Circuits / Compressors Sound pressure level N (4) Sound pressure level SN (4) Sound pressure level SSN (4) Sound pressure level H (4) Depth Width Height Installed weight
V/Ph/Hz N° dB(A) dB(A) dB(A) dB(A) mm mm mm Kg
2/4 65,6 59,2 50,9 64,6 3418 2188 1935 1476
2/4 64,6 58,0 50,9 64,6 3418 2188 1935 1671
2/4 64,6 58,0 49,7 63,7 3418 2188 1935 1852
Max external air temperature version N (2) Max external air temperature version H (2) ESEER (N) ESEER (H) Cooling capacity (1) Compressor absorbed power (2)
100 300 73,3 222 85,9 46 48 4,06 4,16 291 216 243 79,6 -6
110 333 86,0 247 99,5 45 49 3,88 3,78 332 246 276 93,4 -6
400 ± 10% / 3 - PE / 50 2/4 2/4 64,6 64,6 58,0 58,0 49,7 50,7 63,7 65,3 3418 4518 2188 2188 1935 1935 1928 2138
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet-outlet 20-15 °C, external air temperature 25 °C; (2) Evaporator water inlet-outlet 12-7 °C, external air temperature 35 °C; (3) Condenser water inlet/outlet temperature 40/45 °C, external air temperature 7 °C, dry bulb 6 °C wet bulb; (4) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Values with tolerance ± 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions and with circulation pump. The listed noise levels, weights and dimensions refer to base chillers with no options fitted.
Semigraphic user terminal with multifunctional buttons and dynamic display icons.
Also available with shell and tube evaporator (only for AST).
Pump section with or without storage tank.
120 363 100 269 114 44 48 3,95 3,84 380 282 316 101,8 -8
130 414 105 308 120 46 48 3,87 3,97 409 303 338 108,8 -7
140 440 115 327 131 45 48 3,89 3,99 443 329 373 116,2 -8
2/4 64,6 58,0 50,7 65,3 4518 2188 1935 2229
2/4 65,3 58,2 51,1 64,3 4518 2188 1935 2411
2/4 65,3 58,2 51,1 64,3 4518 2188 1935 2532
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW
High efficiency EC axial fans with inverter technology.
Cooling your industry, optimising your process. | MTA
23
GALAXY TECH
R410A
Air-cooled water chillers featuring tandem/triple scroll compressors. Cooling capacity 461 - 1354 kW.
Benefits
Standard Features
• Reduced noise levels, thanks also to the availability of differing acoustic versions; • High EER/COP levels, especially at partial loads; • Allows start-up and operation in even the most severe conditions; • Easy installation with direct access to the water connections and the applications of victaulic connections; • Simple to install and maintain, easily accessible components; • User friendly controller with multifunctional buttons and dynamic display icons.
• Multiple scroll compressors (4, 6, 9 or 12 depending on the model) connected in parallel (tandem or trio) on 2, 3 or 4 independent refrigeration circuits; • Stainless steel brazed plate dual-circuit evaporators “dual-circuit”; • Shut-off valve and solenoid valve on the liquid line in each refrigeration circuit; • xDRIVE is a microprocessor electronic controller with high computing capacity and user friendly graphic interface; • xDRIVE features the ModBUS-RTU communication protocol as standard, allowing connection with the most widely utilised Building Management Systems (BMS). It also features an Ethernet port as standard, with HTML supervision pages preloaded for connection to a company intranet or the Internet. The xDRIVE can manage in master/slave mode up to 8 units; • Phase monitor against phase loss and phase reversal and checks the operating voltage limits; • AC axial fans with die-cast aluminum blades, developed on the basis of bionic principles with progressive starting for condensing pressure control; • High and low pressure transducer; • Water differential pressure switch, air bleed valve and water drain valve; • Water collectors for twin evaporator models; • Factory tested and supplied with refrigerant charge and antifreeze oil; • Environmentally friendly refrigerant R410A with zero ozone depletion potential; • All the compressors are equipped with crankcase heaters.
Main Options • 1 or 2 pumps and water pressure gauge; • Storage tank; • Condenser coils designed for aggressive atmospheres; • Metal mesh filters for condenser coil protection; • High efficiency EC axial fans with inverter technology and integrated speed regulation; • Compressor suction and discharge valves; • Electronic expansion valve; • Antifreeze heater on evaporator, pumps and tank; • Antivibration dampers; • Serial connection to supervisor systems; • MTA xCONNECT supervision based on internal web pages; • Modularity / web interconnection hub; • Replicated remote user terminal; • Soft starter: are installed on each compressor and allow a reduction from 10 to 20% (depending by the model) of the start-up current compared to the direct start; • Compressor housings for acoustic insulation; • Victaulic connections; • Simple remote control; • Special execution with partial or total heat recovery exchangers; • Special execution for water temperatures down to -10 °C; • Special execution with shell and tube evaporator.
Versions • Low ambient air temperature - down to -20 °C in cooling mode; Standard energy efficiency versions: • N - Standard energy efficiency and basic acoustic configuration; • SN - Standard energy efficiency and low noise acoustic configuration; • SSN - Standard energy efficiency and very low noise acoustic configuration; High energy efficiency versions: • HE - High energy efficiency and basic acoustic configuration; • SHE - High energy efficiency and low noise acoustic configuration.
24
MTA | Product Guide | Industrial Process Cooling
GLT Models Cooling capacity (1)
kW
120
135
150
165
180
195
210
225
240
255
270
285
300
315
330
345
360
461
517
574
626
677
751
808
869
921
973
1024
1091
1148
1200
1251
1303
1354
Total absorbed power (1)
kW
116
129
144
155
166
185
201
216
227
239
250
273
288
300
311
322
333
Cooling capacity (2)
kW
343
383
426
465
504
557
600
645
684
723
762
810
852
891
930
969
1008 364
Total absorbed power (2)
kW
126
143
159
170
182
206
222
238
250
262
273
301
317
329
341
352
Max external air temperature (N) (2)
°C
46
46
46
46
46
46
46
45
45
46
46
46
46
46
46
46
46
Max external air temperature (HE) (2)
°C
51
48
48
48
51
48
48
48
48
48
51
48
48
48
48
48
46
ESEER (N)
-
4,01
3,88
3,92
4,02
4,10
3,96
3,98
4,01
4,09
4,13
4,19
3,97
3,98
4,04
4,10
4,13
4,16
ESEER (HE)
-
4,33
4,11
4,12
4,10
4,14
4,21
4,21
4,21
4,29
4,19
4,20
4,19
4,18
4,16
4,16
4,23
4,22
ESEER (SHE)
-
4,55
4,30
4,29
4,39
4,43
4,45
4,41
4,39
4,52
4,47
4,51
4,42
4,39
4,43
4,46
4,55
4,38
Power supply
V/Ph/Hz N°
2/4
2/6
2/6
2/6
2/6
3/9
3/9
3/9
3/9
3/9
3/9
4/12
4/12
4/12
4/12
4/12
4/12
Sound pressure N (2)
dB(A)
69
69
68
68
69
70
70
69
70
70
70
71
71
71
71
71
71
Sound pressure SN (2)
dB(A)
60
60
60
60
60
61
61
62
62
62
62
63
63
63
63
63
63
Circuits / Compressors
400 ± 10% / 3 - PE / 50
Sound pressure SSN (2)
dB(A)
56
56
56
57
57
58
58
57
57
58
58
58
58
58
59
59
59
Sound pressure HE (2)
dB(A)
68
68
68
69
69
70
70
70
70
71
71
71
71
71
72
72
72
Sound pressure SHE (2)
dB(A)
Depth
mm
59
59
60
61
61
61
61
62
63
63
64
64
64
64
64
65
65
4530
4530
4530
4530
4530
6510
6510
6510
6510
6510
6510
8490
8490
8490
8490
8490
8490
Width
mm
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
2190
Height
mm
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
2350
Kg
3120
3458
3476
3512
3548
5146
5164
5189
5430
5665
5887
6781
6799
7038
7268
7508
7737
Installed weight
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet-outlet 20-15 °C, external air temperature 25 °C; (2) Evaporator water inlet-outlet 12-7 °C, external air temperature 35 °C; (3) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Values with tolerance ± 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions and with circulation pump. The listed noise levels, weights and dimensions refer to base chillers with no options fitted. (NB: dimensions for lower noise and/or higher efficiency versions may differ.)
Semigraphic user terminal with multifunctional buttons and dynamic display icons.
Optimisation of performance thanks to the multiscroll logic.
Pump section with or without storage tank.
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW
High efficiency EC axial fans with inverter technology.
Cooling your industry, optimising your process. | MTA
25
PHOENIX PLUS
R134a
Air-cooled chillers with R134a equipped with semi-hermetic twin screw compressors. Cooling capacity 436 - 1668 kW.
Benefits
Standard Features
• High energy efficiency both at full load and at partial load (Eurovent A Class); • High seasonal energy efficiency (ESEER up to 4.34); • The controller provides maximum flexibility to adapt to any operating condition, thanks to the Smart Stepless algorithm specifically developed by MTA; • High reliability and continuity of operation (up to 4 screw compressors and “Smart Stepless” algorithm); • Wide operating range (ambient temperature from -20 °C to +50 °C); • Comprehensive safety equipment, including phase monitor, pressure switches, differential pressure switch, crankcase heaters, compressors operating envelope and oil level; • Wide range of accessories and kits for custom solutions; • Integration with AQUAFree free-cooling modules.
• Environmentally friendly R134a refrigerant; • High efficiency screw compressors with stepless regulation optimized for R134a refrigerant gas; • Compressor crankcase heater; • Air-cooled condensers (copper tubes/aluminium fins) with transverse “V” formation; • AC Axial fans with die-cast aluminum blades, developed on the basis of bionic principles; • Check valve on compressor discharge and shut-off valves on discharge and suction lines; • Electronic expansion valves; • Single pass shell & tubes evaporator optimized for R134a refrigerant gas; • The Electrical panel is made up of IP 54 cabinet with forced ventilation, inside which are installed contactors and circuit breakers; the protection from the phase loss and from the phase reversal is assured by the phase monitor device; • xDRIVE controller programmed with software specifically developed by MTA;high computing capacity and user friendly graphic interface; connectivity and supervision via Ethernet, USB, RS485 Modbus.
Main Options • High efficiency EC axial fans with inverter technology and integrated speed regulation; • Condenser coils with anticorrosion treatment; • Soft starter; • Antivibration dampers; • Special applications with partial or total heat recovery; • Special applications for water temperatures down to -10 °C; • Special very high efficiency applications; • Antifreeze heater; • Metal mesh filters for condenser coil protection; • Compressor housings; • Replicated remote user terminal; • Simple remote control; • Serial connection to supervision systems; • MTA xCONNECT Supervision based on internal web pages; • Modularity / web interconnection hub.
26
MTA | Product Guide | Industrial Process Cooling
Versions • Low ambient air temperature version - down to -20 °C in cooling mode. Standard energy efficiency versions: • N - Standard energy efficiency and basic acoustic configuration; • SN - Standard energy efficiency and low noise acoustic configuration; • SSN - Standard energy efficiency and very low noise acoustic configuration; High energy efficiency versions: • HE - basic acoustic configuration optimized for full load operation (Eurovent A Class); • SHE - low noise acoustic configuration optimized for part load operation (Eurovent A Class).
PNP models
160
170
180
190
200
220
250
265
280
310
330
360
436
457
477
542
560
648
692
757
818
906
975
1017 1098 1171 1256 1326 1358 1390 1530 1668
185
203
222
232
252
269
295
315
336
339
354
370
408
498
538
578
639
684
731
787
827
884
934
961
993
1094 1175
Cooling capacity (1)
kW
Total absorbed power (1)
kW
124
128
131
146
152
169
Cooling capacity (2)
kW
305
324
343
373
401
455
390
405
420
440
470
500
530
560 444
Total absorbed power (2)
kW
125
133
142
148
160
175
196
209
221
244
263
285
307
319
336
356
372
391
422
Max ext. air temperature (N) (2)
°C
44
44
44
44
44
46
44
44
44
46
46
44
44
44
44
45
44
44
44
447 44
Max ext. air temperature (HE) (2)
°C
49
49
49
49
49
49
49
50
50
49
49
49
49
50
50
48
48
47
46
44
ESEER (N)
-
3,31
3,45
3,50
3,54
3,60
3,65
3,35
3,64
3,73
3,67
3,67
3,54
3,61
3,67
3,79
3,68
3,58
3,38
3,66
3,79
ESEER (HE)
-
3,62
3,71
3,71
3,77
3,90
3,76
3,66
3,93
4,01
3,91
3,91
3,81
3,89
3,95
4,02
3,95
3,85
3,66
3,96
4,02
ESEER (SHE)
-
3,51
3,59
3,60
3,66
3,78
3,65
3,54
3,80
3,87
3,79
3,79
3,68
3,76
3,82
3,93
3,78
3,72
3,53
3,81
3,84
Power supply
V/Ph/Hz
400 ± 10% / 3-PE / 50
Circuits / Compressors
dB(A)
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
3/3
3/3
3/3
3/3
3/3
3/3
4/4
4/4
4/4
4/4
4/4
Sound pressure N (3)
dB(A)
68,9
68,9
68,9
70,1
70,1
71,0
71,1
71,0
70,9
72,4
72,7
72,8
72,8
72,7
72,6
74,0
74,1
74,1
74,0
73,9
Sound pressure SN (3)
dB(A)
61,4
61,4
61,4
62,3
62,3
63,0
62,9
62,9
63,0
64,7
64,8
64,7
64,6
64,6
64,6
66,0
66,0
65,9
65,9
65,9
Sound pressure SSN (3)
dB(A)
55,1
55,0
55,0
56,2
56,1
57,0
56,8
56,9
56,9
58,2
58,8
58,7
58,6
58,6
58,6
61,2
61,1
61,1
61,1
61,1
Sound pressure HE (3)
dB(A)
70,2
70,0
69,9
71,6
71,5
72,7
72,6
72,4
72,2
73,7
74,4
74,4
74,2
74,1
73,9
75,3
75,2
75,2
75,0
74,9
Sound pressure SHE (3)
dB(A)
63,1
63,0
62,8
64,3
64,2
65,2
64,9
64,7
64,5
66,3
67,0
66,8
66,5
66,4
66,3
67,8
67,6
67,5
67,3
67,2
Depth Width Height Installed weight
mm mm mm Kg
4530 4530 4530 4530 4530 4530 4530 4530 4530 6510 6510 6510 6510 6510 6510 8490 8490 8490 8490 8490 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2190 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 2360 3467 3509 3554 4137 4288 4702 4866 4949 5033 6511 6907 7286 7391 7472 7627 9085 9306 9349 9833 10000
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet-outlet 20-15 °C, external air temperature 25 °C; (2) Evaporator water inlet-outlet 12-7 °C, external air temperature 35 °C. (3) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Values with tollerance ± 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions and with circulation pump. The listed noise levels, weights and dimensions refer to base chillers with no options fitted. (NB: dimensions for lower noise and/or higher efficiency versions may differ).
Semigraphic user interface with multifunctional buttons and dynamic display icons.
Electronic expansion valves as standard and single pass shell & tubes evaporator.
Maximum accessibility to compressors.
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW
Optimised fans for whisper-quiet operation (SSN version).
Cooling your industry, optimising your process. | MTA
27
ARIES FREE-COOLING
R407C
Air-cooled water chillers with integrated Free-cooling featuring hermetic scroll compressors. Cooling capacity 65 - 226 kW.
Benefits
Standard Features
• Maximum exploitation of free cooling and maximum energy efficiency of the system with respect to conventional solutions, thanks to the independence of the coils in terms of air handling; • Accurate control of water outlet temperature (including at low temperatures down to -15 °C), thanks to the use of a modulating three-way water valve; • Generous sizing of coils for free-cooling; • Operates at high ambient temperatures thanks to the compressor unloading; • Version SSN featuring extremely quiet operation; • Individually tested in a test chamber like all MTA components and products; • User friendly control section with simple readout and graphic display; • Simple to install and maintain, easily accessible components; • Sections featuring complete aeraulic segregation to maximise the use of free-cooling.
• Parallel scroll compressor coupling within single refrigerant circuit; • Finned coil evaporator inside the storage tank (201-301) and shell and tube evaporator (351-751); • Condensers and fans installed in a separate compartment with aeraulic isolation, for maximum Free-Cooling effect and maximum overall energy efficiency; • Axial fans with crescent shaped blades featuring step regulation; • 3-way modulating valve for Free-Cooling (controlled by microprocessor), water connections within chiller; • Total Free-Cooling from approximately 10 °C below the water outlet temperature; • Water differential pressure switch on evaporator (301-751); • High and low pressure transducers; • Single or twin high pressure switches for max condensing pressure control; • Electronic expansion valve with external equalisation, refrigerant filter, sight glass, solenoid valve on liquid line (except 201-301); • Safety valve (except 201-301); • Microprocessor control with advanced software ensuring optimum control in all conditions; • All the units are delivered with a phase monitor which provides protection against phase loss and phase reversal; • The scroll compressors are equipped with cranckcase heaters as standard; • Main switch; • IP54 electric protection rating; • Environmentally friendly refrigerant R407C with zero ozone depletion potential.
Main Options • Compressor suction and discharge valves; • Electronic fan speed control; • Electronic thermostatic expansion valve (except 201-301); • Hydronic group without pump; • Hydronic group with storage tank and single or twin pumps (351-751 only); • High, medium and low head pressure pumps; • Air filter on condenser coils (standard on 201-301); • Antivibration dampers; • Simple remote control; • Replicated remote user terminal; • Supervisor systems; • Victaulic connections.
28
MTA | Product Guide | Industrial Process Cooling
Versions • N - Standard energy efficiency and basic acoustic configuration; • SN - Standard energy efficiency and low noise acoustic configuration; • SSN - Standard energy efficiency and very low noise acoustic configuration; • Low ambient air temperature - down to -15 °C.
Free-Cooling OFF TOTAL Free-Cooling Free-Cooling OFF TOTAL Free-Cooling
AS FC models Cooling capacity (1) Absorbed power (1) Max external air temperature (1) Cooling capacity (1) Absorbed power (1)(*) Total freecooling (1)
kW kW °C kW kW °C
201 65,4 13,9 42 65,4 1,6 4,3
251 70,8 16,2 45 70,8 2,3 4,7
301 88,2 17,0 45 88,2 2,3 2,7
351 104 26,3 39 104 4,0 5,0
401 126 30,2 41 126 4,0 3,7
501 148 35,7 40 148 4,0 2,3
551 170 39,6 40 170 4,0 3,4
601 185 45,4 38 185 4,0 2,2
701 206 47,0 42 206 6,0 4,6
751 226 53,9 41 226 6,0 3,5
Cooling capacity (2) Absorbed power (2) Max external air temperature (2) Cooling capacity (2) Absorbed power (2)(*) Total freecooling (2)
kW kW °C kW kW °C
50,9 16,2 45 50,9 1,6 1,0
54,6 19,3 47 54,6 2,3 1,4
69,3 20,0 47 69,3 2,3 -0,3
80,1 30,1 42 80,1 4,0 1,6
97,6 34,3 44 97,6 4,0 0,5
115 40,1 43 115 4,0 -0,7
133 44,4 43 133 4,0 0,4
146 50,7 41 146 4,0 -0,7
161 52,7 45 161 6,0 1,4
177 60,1 43 177 6,0 0,4
-
4,19
3,82
4,07
3,56
3,73
3,79
3,97
3,94
3,91
3,75
1/2 61,6 55,0 48,7 4595 2188 1989 2536
1/2 61,6 55,0 48,7 4595 2188 1989 2541
1/2 62,3 55,2 49,1 4595 2188 1989 2752
1/2 62,3 55,2 49,1 4595 2188 1989 2803
ESEER Power supply Circuits / Compressors Sound pressure Free-cooling OFF - N (3) Sound pressure Free-cooling OFF - SN (3) Sound pressure Free-cooling OFF - SSN (3) Depth Width Height Installed weight
V/Ph/Hz N° dB(A) dB(A) dB(A) mm mm mm Kg
1/2 60,2 2550 1400 2136 1494
1/2 60,2 2550 1400 2136 1494
1/2 61,5 2550 1400 2136 1509
1/2 62,6 56,2 48,9 3495 2188 1989 1858
400 ± 10% / 3 - PE / 50 1/2 1/2 61,6 61,6 55,0 55,0 48,9 47,7 3495 3495 2188 2188 1989 1989 1980 2276
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet-outlet 20-15 °C, external air temperature 25 °C; glycol water at 30%. (2) Evaporator water inlet-outlet 12-7 °C, external air temperature 35 °C; glycol water at 30%. * In total Freecooling mode the absorbed power is only the fans absorbed power. (3) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Values with tolerance +/- 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions. The sound pressure level is refered at functioning with Free-cooling Off. The listed noise levels, weights and dimensions refer to base chillers with no options fitted.
Availability of Free-Cooling
Energy saving
Annual FC % usuability on daily time from 6 AM till 8 PM
Absorbed power
ermal load
% of freeccoling with water inlet = 12 °C
% of freeccoling with water inlet = 15 °C
Variable th
Berlin
54%
68%
Brussels
51%
69%
ch Traditional
Copenaghen
61%
74%
Milan
47%
54%
Oslo
75%
84%
Stockholm
63%
73%
Vienna
50%
60%
Semi-graphic backlit PGD terminal.
Sections featuring complete aeraulic segregation to maximise the use of free-cooling.
-C o Fr ee
Saving
ol
in
g
iller
0
Servo-controlled three-way hydraulic valve.
Ambient temperature 35
Shell-and-tube evaporator: a reliable solution (mod 351 - 751).
Cooling your industry, optimising your process. | MTA
29
PHOENIX FREE-COOLING
R407C
Air-cooled water chillers with Freecooling system featuring double screw semihermetic compressors. Cooling capacity 248 - 662 kW.
Benefits
Standard Features
• Maximum exploitation of free cooling and maximum energy efficiency of the system with respect to conventional solutions, thanks to the independence of the coils in terms of air handling; • Accurate control of water outlet temperature (including at low temperatures - down to -15 °C), thanks to the use of a modulating three-way water valve; • Generous sizing of coils for free-cooling; • Version SSF featuring extremely quiet operation; • Individually tested in a test chamber like all MTA components and products; • User friendly control section with simple readout and graphic display; • Simple to install and maintain, asily accessible components.
• Twin screw compressors with crankcase heater and oil level control; • Part winding start for reduced current spikes; • Compressor suction and discharge valves; • Shell and tube evaporator; • Independent refrigeration circuits; • Axial fans with sickle-shaped blades; • 3-way modulating water valve for Free-Cooling (managed by microprocessor control) and internal hydraulic connections to the machine; • Total Free-Cooling from approximately 10 °C below the water outlet temperature; • Water differential pressure switch on evaporator; • High and low pressure transducers; • Electronic expansion valve with external equalisation, refrigerant filter, sight glass, solenoid valve on liquid line; • Safety valve; • Microprocessor control with advanced software ensuring optimum control in all conditions; • Main switch; • Protection grade IP54; • SSF fitted silencers, flexible tubing and compressor vibration damping; • Environmentally friendly refrigerants with R407C zero ozone depletion potential; • All the units are delivered with a phase monitor which provides protection against phase loss and phase reversal.
Main Options • Compressor housings for acoustic insulation (for C only, standard on other versions); • Condensing section electronic fan speed regulation; • Electronic thermostatic valve (special); • Electrical protection by means of automatic cut-outs; • Metal mesh protection filters for coils; • Anti-vibration dampers kit; • Replicated remote user terminal kit; • Supervisor kits.
Versions • C - basic acoustic configuration; • SC - low noise acoustic configuration; • SF - low noise acoustic configuration for high ambient temperature; • SSF - very low noise acoustic configuration; • Low ambient air temperature - down to -15 °C.
30
MTA | Product Guide | Industrial Process Cooling
Free-Cooling OFF TOTAL Free-Cooling Free-Cooling OFF TOTAL Free-Cooling
PH FC models Cooling capacity (1) Absorbed power (1) Max external air temperature version (C) (1) Cooling capacity (1) Absorbed power (1)(*) Total freecooling temperature (1) Cooling capacity (2) Absorbed power (2) Max external air temperature version (C) (2) Cooling capacity (2) Absorbed power (2)(*) Total freecooling temperature (2) ESEER Power supply Circuit / Compressors Sound pressure Free-cooling OFF - C (3) Sound pressure Free-cooling OFF - SC (3) Sound pressure Free-cooling OFF - SF (3) Sound pressure Free-cooling OFF - SSF (3) Depth Width Height Installed weight
kW kW °C kW kW °C kW kW °C kW kW °C -
0801 248 63 41 248 6,0 2,8 170 65 45 170 6 -2,1 3,44
0901 287 72 40 287 8,0 1,4 198 75 44 198 8 -3,4 3,72
1101 352 86 39 352 8,0 0,8 239 88 44 239 8 -3,7 3,63
1251 406 98 41 406 10,0 2,4 278 101 45 278 10 -2,4 3,6
V/Ph/Hz N° dB(A) dB(A) dB(A) dB(A) mm mm mm Kg
1/1 62,0 55,4 55,7 49,1 3675 2190 2350 2623
1/1 63,2 56,3 56,1 49,5 4590 2190 2350 3306
1/1 62,6 56,0 56,3 49,8 4590 2190 2350 3814
1/1 63,6 57,0 57,2 50,6 5490 2190 2350 4648
1401 476 109 42 476 12,0 3,2 329 114 45 329 12 -1,8 3,98
1602 495 126 41 495 12,0 2,8 339 130 45 339 12 -2,1 3,48
400 ± 10% / 3-PE / 50 1/1 2/2 65,0 65,5 59,0 59,1 59,1 59,2 51,0 51,5 6425 6425 2190 2190 2350 2350 5003 5273
1702 522 139 39 522 12,0 2,1 360 144 43 360 12 -2,7 3,62
1802 543 151 37 543 12,0 1,6 376 158 42 376 12 -3,1 3,65
2002 621 162 38 621 14,0 2,3 425 167 43 425 14 -2,4 3,55
2202 662 182 36 662 14,0 1,6 449 185 41 449 14 -3,0 3,42
2/2 65,6 59,3 6425 2190 2350 5385
2/2 65,7 59,4 6425 2190 2350 6089
2/2 66,9 60,5 7360 2190 2350 6133
2/2 66,9 60,6 7360 2190 2350 6154
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet-outlet 20-15 °C, external air temperature 25 °C; glycol water at 30%. (2) Evaporator water inlet-outlet 12-7 °C, external air temperature 35 °C; glycol water at 30%. (*) In total Free-cooling mode the absorbed power is only the fans absorbed power. (3) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the side of the condenser coils and at a height of 1.6 m from the unit support base. Values with tolerance +/- 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions. The sound pressure level is refered at functioning with Free-cooling Off. The listed noise levels, weights and dimensions refer to base chillers with no options fitted.
Availability of Free-Cooling
Energy saving
Annual FC % usuability on daily time from 6 AM till 8 PM
Absorbed power
ermal load
% of freeccoling with water inlet = 12 °C
% of freeccoling with water inlet = 15 °C
Variable th
Berlin
54%
68%
Brussels
51%
69%
ch Traditional
Copenaghen
61%
74%
Milan
47%
54%
Oslo
75%
84%
Stockholm
63%
73%
Vienna
50%
60%
Semi-graphic backlit PGD terminal.
Sections featuring complete aeraulic segregation to maximise the use of free-cooling.
-C Fr ee
Saving
oo
lin
g
iller
0
Servo-controlled three-way hydraulic valve.
Ambient temperature 35
Shell-and-tube evaporator: a reliable solution.
Cooling your industry, optimising your process. | MTA
31
AQUAFREE Add-on Freecooling modules for Aries tech, Galaxy tech and Phoenix plus, transforming the Chiller into an all-in-one modular and expandable Freecooling Chiller. Cooling capacity 242 - 466 kW per single module.
Plug & Play
Peace Of Mind
Connect AquaFree to the chiller (AST, GLT and PNP) and set the software parameters comunications between the units. The chiller’s xDRIVE microprocessor will control the chiller / free-cooler combination as a single unit. In case of AQUAfree connection to a chiller previously installed check before the software compability. The AQUAfree / chiller piping kit is available on request.
Each AquaFree module features its own microprocessor, allowing it to operate independently. If one module suffers a fault the others can still operate, if the chiller suffers a fault the modules can continue to operate. AquaFree can operate at ambient temperatures of -15 °C to +46 °C. Each AquaFree module features independent aeraulic sections featuring axial fans with progressive activation (continuos control on request).
Energy Efficient
Versatile
AquaFree can easily obtain savings of 30% or more, offering efficiency levels well beyond the industry norm. The modular design permits additional AquaFree modules to be added, allowing efficiencies to be further increased and tailored to individual applications.
As AquaFree modules are independent, so system transportation is simplified. AquaFree can be positioned separately if space needs dictate it. It is also possible to install AquaFree, or add additional modules, at a later date. Each AquaFree module features its own remote on/off control.
Super Silent
Models & Versions
Choose between 2 noise levels, both extremely quiet, with an electronic fan speed control option to further reduce part load noise levels. Especially during night time, when temperatures drop and freecooling becomes more active, AquaFree’s low noise becomes a notable asset.
• Acoustic versions: - N - basic acoustic configuration; - SN - low noise acoustic configuration; • Modules: - AFW100 (for connection to AST 090-140); - AFV200 (for connection to GLT/PNP); - AFV300 (for connection to GLT/PNP); • Low ambient air temperature - down to -20 °C.
Indipendent Each module features its own electrical connection and 3-way valve, as well as its own electrical panel and microprocessor with independent alarms and water in/out and ambient temperature visualization: consequently each module can operate completely autonomously.
Glycol Free Kit The kit is available on request and is ideal in applications requiring an absence of glycol, such as food and plastics industries. The kit features its own intermediate exchanger and an hydraulic circuit, is simply installed between the chiller and the AquaFree modules.
32
MTA | Product Guide | Industrial Process Cooling
Accessories • Freecooling coils with anticorrosion treatment; • Lateral hydraulic connections (AFW100); • Metal mesh filters for freecooling coils; • Electronic fan speed control; • Antivibration dampers; • On request Chiller-AquaFree interconnection kit (tubing to be supplied by installer); • On request (special) add-on Glycol-free kit; • Replicated remote user terminal; • Victaulic connections.
Technical data Applicable chiller
AFW100
AFV200
AFV300
AST 090-140
GLT & PNP
GLT & PNP
Cooling capacity (N)
kW
310
310
466
Cooling capacity (SN)
kW
242
242
363
Absorbed power (N)
kW
8
8
12
Absorbed power (SN)
kW
7,8
7,8
11,7
Water flow (N)
m³/h
58,3
58,3
87,4
Water flow (SN)
m³/h
45,4
45,4
68,1
Pressure drop (N)
kPa
77
77
86
Pressure drop (SN)
kPa
47
47
52
-
4
4
6
No. of Coils / Fans Power supply
V/Ph/Hz
Sound pressure level (N)
dB(A)
Sound pressure level (SN)
H
61,0
61,0
AFV200 H
D
62,8
dB(A)
54,0
54,0
55,8
mm
2.100
2.100
3.100
Width (W)
mm
2.188
2.190
2.190
Height (H)
mm
1.989
2.360
2.360
kg
1.071
1.260
1.835
Water inlet-outlet 15-10 °C, external air temperature 0 °C, 30% ethylene glycol. Sound pressure level in hemispherical field at 10m from coil side, 1.6 m from ground, full load operation at nominal conditions, tollerance ± 2 dB.
W
D
400 ± 10% / 3-PE / 50
Depth (D)
Installed weight
AFW100
W
AFV300 H
D
W
AFV200 & AFV300 can be mounted directly to the back of the chiller, AFW100 requires a small service area between itself and the chiller.
Tailor made Free-Cooling
Select your efficiency
AquaFree allows the user to define the desired efficiency, simply combining multiple modules to achieve the optimum freecooling level. Any combination of AFV200 and AFV300 modules allows the freecooling section to be increased one “V” coil at a time from a minimum of two coils upwards.
The size and number of AquaFree modules applied allows the efficiency level to be progressively increased from Basic (N) to Efficient (E) and even High efficiency (HE) levels.
Total Freecooling Temp. (°C)
As an example, a GLT150N chiller, operating at water 15/10 °C with 30% glycol and a single AFV300 module (Basic “N” configuration), achieves a TFT (total freecooling temperature), the temperature at which the unit achieves 100% freecooling) of -0,2 °C). Alternatively, the application of two AFV200 modules (Efficient “E” configuration) achieves a TFT of +3,1 °C. By applying an AFV300 module and an AFV200 module (High efficiency “HE” configuration), a TFT of +5,0 °C can be achieved.
+5
High efficiency (HE)
Efficient (E) - Suggested 0
Cooling capacity (kW) Basic (N)
+5
The integral microprocessor allows AquaFree to operate independently.
Each AquaFree module features its own independent electrical panel.
The 3-way valve, installed on-board as standard, optimises the freecooling level.
Unique design allows interconnection of multiple AquaFree modules.
Cooling your industry, optimising your process. | MTA
33
NEPTUNE TECH
R410A
Water-cooled water chillers, heat pumps and condenserless units featuring hermetic scroll compressors. Cooling capacity 300 - 710 kW. Heating capacity 278 - 657 kW. Cooling capacity evaporating units 287 - 674 kW.
Benefits
Standard Features
• Up to 6 compressors offer high efficiency and reliability; • High energy efficiency levels, especially at partial loads; • Extremely compact, even passes through a domestic door; • Operates with water outlet temperatures from 0 °C to 25 °C; • Unloading function allowing operation even in extreme conditions; • Self Adapting Control (SAC) with dynamic set point, for increased precision with low thermal inertias; • Robust design with high quality components from renowned suppliers, fruit of MTA’s industrial background; • Eurovent certified performance; • Reduced noise levels, thanks also to the availability of two differing acoustic versions; • Flexibility of use, sized for operation with either tower or well water; • Energy efficient total heat recovery and desuperheater options; • Easy installation and access to all components; • Allows both inlet and outlet water control, with a PID control logic; • Generous ambient limits (-10 °C to +45 °C); • Easy to use intuitive controller with dual icon display.
• 3 to 6 hermetic scroll compressors, positioned in parallel in one or two circuits; • Brazed stainless steel plate evaporators and condensers; • Shut-off valve and solenoid valve on the liquid line; • Extensive inspections and tests performed on all units; • Factory charged with non-freezing oil and refrigerant (except ME); • IP54 electrical protection rating; • Environmentally friendly refrigerant R410A with zero ozone depletion potential; • All the scroll compressors are equipped with cranckcase heaters as standard; • All the units are delivered with a phase monitor which provides protection against phase loss and phase reversal.
Main Options • Noise reducing compressor housing; • Modulating condensing pressure control valves; • Antivibration dampers; • Soft starter; • Desuperheater (20% heat recovery); • Total heat recovery (100% heat recovery only chiller); • Shell & tube evaporator (on request); • Antifreeze heater for exchangers; • Remote user interface; • RS485 MODBUS interface for connection to supervisor systems; • xWEB300D remote supervision, allowing local or remote monitoring via web server or GPRS; • Matching cooling towers or dry coolers available on request; • Remote condensers for integration with ME units available on request.
34
MTA | Product Guide | Industrial Process Cooling
Versions • NET - Cooling only / Heat pump (with inversion on the water side); • NET Silent - Low noise; • NET / ME - Condenserless unit combinable with remote condenser.
NET - NET/ME models
075
090
100
110
120
135
150
165
180
NET
Tower water Cooling capacity (1)
kW
300
354
397
429
472
533
596
655
710
Total absorbed power (1)
kW
58
68
78
86
92
105
119
128
138
Cooling capacity (2)
kW
237
280
313
338
373
420
469
517
560
Total absorbed power (2)
kW
56
65
75
82
88
101
114
121
131
5,35
5,43
5,22
5,21
5,36
5,32
5,36
5,49
5,54
ESEER
-
Heat Pump
NET
Well water Cooling capacity (3)
kW
305
359
403
435
479
541
605
669
724
Total absorbed power (3)
kW
54
64
73
81
85
98
110
117
126
Cooling capacity (4)
kW
251
297
332
360
396
446
498
551
598
Total absorbed power (4)
kW
48
57
65
72
75
87
98
104
111
Heating capacity (5)
kW
278
328
370
400
437
495
555
607
657
Total absorbed power (5)
kW
68
79
91
99
105
121
136
146
156
Cooling capacity (6)
kW
287
338
380
415
449
509
571
622
674
Total absorbed power (6)
kW
61
72
81
88
96
109
122
133
144
Cooling capacity (7)
kW
224
264
297
324
352
398
445
487
527
Total absorbed power (7)
kW
60
70
80
87
94
107
121
131
141
NET / ME
Condenserless unit
Power supply
V/Ph/Hz
400 ± 10% / 3-PE / 50
Circuits / Compressors
N°
1/3
1/3
2/4
2/4
2/4
2/5
2/6
2/6
2/6
Sound power - basic (8)
dB(A)
86,1
87,8
87,3
88,3
89
89,1
89,1
90
90,8
Sound power - silent (8)
dB(A)
79,1
80,8
80,4
81,3
82
82,1
82,1
83
83,8
Sound power - basic (9)
dB(A)
58,1
59,8
59,3
60,3
61,0
61,1
61,1
62,0
62,8
Sound power - silent (9)
dB(A)
51,1
52,8
52,4
53,3
54,0
54,1
54,1
55,0
55,8
mm
2010
2010
2610
2610
2610
3705
3705
3705
3705
Depth Width
mm
800
800
800
800
800
800
800
800
800
Height
mm
1830
1830
1830
1830
1830
1830
1830
1830
1830
Kg
993
1161
1332
1440
1549
1729
1867
2061
2211
Installed weight
Data declared according to UNI EN 14511:2013. (1) Evaporator water inlet/outlet temperature 20-15 °C, condenser water inlet/outlet temperature 30-35 °C. (2) Evaporator water inlet/outlet temperature 12-7 °C, condenser water inlet/outlet temperature 30-35 °C. (3) Evaporator water inlet/outlet temperature 20-15 °C, condenser water inlet/outlet temperature 15-30 °C. (4) Evaporator water inlet/outlet temperature 12-7 °C, condenser water inlet/outlet temperature 15-30 °C. (5) Condenser water inlet/outlet temperature 40-45 °C; evaporator water inlet/outlet temperature 12-7 °C. (6) Evaporator water inlet/outlet temperature 20-15 °C; condensing temperature 45 °C; (7) Evaporator water inlet/outlet temperature 12-7 °C; condensing temperature 45 °C; (8) Sound power: determined on the basis of measurements taken in accordance with the standard ISO 3744. (9) Sound pressure at 10 m: average value obtained in free field on a reflective surface at a distance of 10 m from the longer side of the machine and at a height of 1.6 m from the unit support base. Values with tolerance ± 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions. The listed noise levels, weights and dimensions refer to base chillers with no options fitted. Microprocessor controller with dual icon-based display.
Optimised performance thanks to multiscroll logic.
Ideal for the cooling of all industrial processes.
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW - N.A. on ME
Easy access to all components.
Cooling your industry, optimising your process. | MTA
35
AQUARIUS PLUS 2
R134a
High efficiency water cooled chillers, heat pumps and evaporating units with screw compressors and R134a refrigerant gas. Cooling capacity 489 - 1982 kW. Heating capacity 427 - 1740 kW. Cooling capacity evaporating units 350 - 1434 kW.
COOLING ONLY
HEAT PUMPS
CONDENSERLESS
LOW WATER TEMPERATURE Benefits
Standard Features
• 20 base models that perfectly match each specific system requirements; • High energy efficiency both at full load and at partial load (Eurovent A Class); • Stepless cooling capacity regulation with self-adaptive control; • High precision and adaptability in cooling capacity regulation; • Compressors minimum partialization step 25%; • Heat exchangers with low water side pressure drops in order to save pumping costs; • Low sound levels, thanks also to the availability of two different acoustic versions; • Easy access to all components; • Fully bundled heat recovery solutions; • Condenser outlet water temperature up to 60 °C.
• Environmentally friendly refrigerant R134a with zero ozone depletion potential; • High efficiency screw compressors with stepless regulation optimized for R134a refrigerant gas; • Automatic circuit breakers for compressors; • Compressor crankcase heaters; • Check valve and shut-off valve on discharge line; • Electronic expansion valves; • Single pass shell & tubes heat exchangers optimized for R134a refrigerant gas; • Electrical panel with numbered wires, forced ventilation and IP54 protection class; • Phase monitor which provides protection against phase loss and phase reversal; • Microprocessor electronic control xDRIVE with high computing capacity and user friendly interface, suitable for connection with supervisor system; • RS485 interface for connection to ModBus supervisor systems; • Ethernet connection featuring pre-programmed HTML supervision pages, allowing local or internet based visualization and modification of the operating parameters.
Main Options • Partial or total heat recovery; • Compressors acoustical enclosure (super silent acoustic configuration); • Shut-off valves on suction line; • Soft starter device available as factory fitted option allows a reduction in start-up current; • Capacitors for compressors; • Condensing control kit (with servo-driven modulating valves or pressure control valves); • Flanges kit on evaporator; • Flanges kit or Victaulic kit on condenser and total heat recovery; • Anti-vibration dampers kit; • Remote control with LCD display VGIP; • xWEB300D supervisor kit; • Cooling tower or dry cooler available on request; • Remote condenser available on request for condenserless version (ME).
Versions • CH - Cooling only version; • HP - Heat pump with hydraulic system reversing and outlet water temperature up to 60 °C; • ME - Condenserless version; • LWT - Low Water Temperature (down to -8 °C);
Acoustic Configurations • Basic acoustic configuration: compressors directly accessible; • Super silent acoustic configuration: optimised for very low noise operation: compressors are housed in a metal compartment insulated with a sound absorbing layer of open-cell expanded polyurethane and a sheet of sound deadening material (noise reduction -6 db(A) in comparison with basic).
36
MTA | Product Guide | Industrial Process Cooling
AQP2 models 1401 1601 CH - (1) Cooling capacity kW 489 545 Total absorbed power kW 82,5 90,8 EER - 5,93 6,00 Energy efficiency class A A ESEER - 5,84 5,84 HP - (2) Heating capacity kW 427 473 Total absorbed power kW 88 97 COP - 4,85 4,88 Energy efficiency class A A Heat recovery (D) Partial recovery heating capacity (3) kW 21 22 (R) Total recovery heating capacity (4) kW 427 473 ME - Condenserless version (5) Cooling capacity kW 350 387 Total absorbed power kW 82 91 EER - 4,26 4,24 Power supply (6) Power V/Ph/Hz Compressor Type Compressors / Cooling circuits n° Cooling capacity regulation Capacity control Refrigerant Sound levels (7) Basic configuration dB(A) 95 96 Super silent configuration dB(A) 90 91 Dimensions and weights (8) Width (W) mm 1460 1460 Depth (D) mm 4344 4344 Height (H) mm 1640 1645 Weight kg 2154 2363 Dimensions and weights (9) Width (W) mm 1460 1460 Depth (D) mm 3924 3876 Height (H) mm 1635 1640 Weight kg 1913 2090
1801 2001 2301 2601 3001 3301 2802 3202 3402 3602 4002 4302 4602 4902 5202 5602 6002 6602 622 104 5,95 A 5,89
686 114 6,02 A 5,89
767 128 6,02 A 5,89
839 139 6,03 A 5,96
923 152 6,08 A 5,99
995 162 6,13 A 6,04
953 161 5,91 A 5,98
1088 1165 1234 1362 1444 1544 1613 1670 1766 1845 1982 179 194 207 225 237 253 264 276 291 303 327 6,06 6,02 5,95 6,05 6,09 6,10 6,10 6,06 6,06 6,08 6,06 A A A A A A A A A A A 5,98 5,97 5,97 5,99 6,05 6,01 6,05 6,05 5,99 6,04 6,00
540 111 4,85 A
593 121 4,89 A
665 136 4,89 A
732 149 4,91 A
799 163 4,91 A
858 174 4,92 A
852 175 4,87 A
953 193 4,93 A
1019 1089 1188 1255 1337 1407 1466 1540 1618 1740 208 223 242 256 272 285 298 312 326 351 4,90 4,89 4,91 4,91 4,92 4,94 4,93 4,93 4,96 4,96 A A A A A A A A A A
23 540
24 593
32 665
33 732
34 799
43 858
42 852
44 953
45 47 47 56 64 66 67 68 69 86 1019 1089 1188 1255 1337 1407 1466 1540 1618 1740
443 104 4,26
488 114 4,29
545 128 4,26
602 140 4,30
656 153 4,29
706 164 4,31
700 164 4,27
783 182 4,30
838 195 4,29
896 209 4,29
978 227 4,31
1032 1100 1159 1207 1267 1332 1434 240 255 267 280 294 307 330 4,29 4,31 4,33 4,32 4,31 4,34 4,34
400 ± 10% / 3 - PE / 50 Screw 1/1
2/2 Stepless
25 ÷ 100
12,5 ÷ 100 R134a
97 91
97 92
97 92
97 92
98 92
98 92
98 93
98 93
99 93
99 93
99 93
99 94
99 94
100 94
100 94
100 95
101 95
101 95
1460 4326 1721 2695
1485 4326 1721 2738
1485 4326 1645 2781
1460 4326 1770 3143
1460 4334 1819 3288
1460 4334 1819 3338
1390 4966 2165 4294
1390 4966 2165 4572
1390 4979 2165 4878
1390 4979 2165 5185
1390 4982 2278 5736
1390 4982 2278 5767
1390 4982 2278 5802
1390 4982 2278 5881
1390 4982 2278 5961
1390 5030 2278 6143
1390 5030 2278 6295
1390 5032 2278 6399
1460 3867 1640 2374
1485 3867 1640 2388
1485 3867 1640 2402
1460 3836 1765 2720
1460 4111 1814 2822
1460 4032 1814 2815
1390 4966 1985 3765
1390 4966 1985 3879
1390 4979 1985 4193
1390 4979 1985 4498
1390 4982 2098 4954
1390 4982 2098 4966
1390 4982 2098 4982
1390 4982 2098 5032
1390 4982 2098 5072
1390 5030 2098 5191
1390 5030 2098 5401
1390 5032 2098 5562
Data declared according to UNI EN 14511:2013. (1) Cooling mode: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; (2) Heating mode: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 40/45 °C; (3) Partial heat recovery: evaporator IN/OUT: 12/7 °C; condenser IN/OUT: 30/35 °C; desuperheater IN/OUT: 40/45 °C; (4) Total heat recovery: evaporator IN/OUT: 12/7 °C; heat recovery IN/OUT: 40/45°C; (5) Condenserless version: evaporator IN/OUT: 12/7 °C; condensing temperature: 45 °C; (6) IP54 protection class; (7) Sound power: determined on the basis of measurements taken in accordance with the standard ISO 3744; the sound levels refer to operation of the unit under full load in nominal conditions; (8) Dimensions and weights are referred to AQP2, without options and water content. (9) Dimensions and weights are referred to AQP2/ME, in the basic configuration, without options and with water content.
xDRIVE microprocessor controller.
Integrated heat recovery.
High energy efficiency.
MTA partecipates in the E.C.C. programme for LCP-HP. Certified products are listed on www.eurovent-certification.com. Eurovent Certification applied to the units: - Air/Water with cooling capacity up to 600 kW - Water/Water up to 1500 kW - N.A. on ME
Electronic expansion valves.
Cooling your industry, optimising your process. | MTA
37
RWD Air-cooled liquid coolers. Cooling capacities 10 - 372 kW.
An environment-friendly solution
Versions
RWD liquid coolers, with finned coils and axial fans, are the ideal solution for the free-cooling of applications in which the process temperature is higher than the ambient temperature for most of the year. Exploiting low ambient air temperatures, RWD cools the fluid free of charge, eliminating energy wastages caused by running refrigerant compressors during winter.
• Acoustic versions: - C (standard); - SC (low noise); - SSC (very low noise).
Free-cooling In new plants customers can select the RWD model which provides the ideal compromise between installation cost and return on investment. In the case of existing plants retrofitting an RWD equipped with a 3-way valve in series with the system chiller is a viable solution. Installation of an RWD not only increases the life of the chiller, but also allows significant energy saving levels ensuring a return on the initial investment in approximately twelve months.
Plug and play From RWD 200 the main components such as 3-way valves, manifolds, and single or double pumps can be installed in the unit. RWD can be installed outdoors thanks to the IP54 protection rating and epoxy surface coating of the frame. Consequently no time is lost in component selection and RWD installation is rendered quick and easy.
38
MTA | Product Guide | Industrial Process Cooling
• Configurations: - Single coil (RWD 010-150); - Packaged twin coil (RWD 200-350). • Airbatic version.
Accessories • Electrical panel; • Microprocessor controller; • Electronic fan speed regulation (special); • Differing head pressure pumps in single or twin configurations (RWD 200-350) (special); • Metal mesh protection filters for coils; • 3-way valves + manifolds (RWD 200-350) (special); • 60 Hz power supply (special); • Manifolds kit; • Horizontal installation kit (RWD 030-150); • Remote control.
RWD models Cooling power (1) Absorbed power Water flow Pressure drop Fans Sound pressure level (3) Power supply (2) Depth Width Height Height with legs Installed weight
Water connections without manifolds Water connections with manifolds
kW kW l/h bar
010 10,3 0,48 1797 0,16
020 20,0 0,96 3470 0,26
030 30,6 2,10 5315 0,33
040 40,6 2,10 7052 0,26
050 49,0 2,10 8522 0,38
075 68,5 4,10 11899 0,60
100 96,8 4,10 16821 0,34
150 133 6,10 23126 0,63
200 195 8,10 33822 0,33
250 248 10,0 43079 0,53
300 304 10,0 52783 0,39
350 372 12,0 64653 0,66
n° dB(A)
1 47,8
2 50,8
1 60,1
1 59,1
1 58,1
2 62,1
2 61,1
3 62,8
4 64,1
5 65,0
5 64,0
6 65,8
230±10%/3/50 847 1682 440 440 763 763 64 124
2145 779 1364 1534 428
2145 779 1364 1534 450
2145 779 1364 1534 463
3042 779 1364 1534 596
4390 1510 1485 1178
5295 1510 1485 1411
5295 1510 2085 1763
6200 1510 2085 2063
G 1 ½” -
G 1 ½” -
G 1 ½” -
G 2” -
G 2” DN 80
G 2” DN 80
G 2 ½” DN 100
G 2 ½” DN 100
V/Ph/Hz mm mm mm mm Kg -
G 1” -
G 1” -
400 ± 10% / 3-PE / 50 3959 4860 779 779 1364 1364 1534 1534 736 891 G 2” -
G 2” -
(1) Values refer to standard units at the following operating conditions: ∆T 10 °C between water inlet temperature and ambient temperature, ∆T 5 °C between water inlet temperature and water temperature at outlet from chiller located at sea level and with 0% glycol. (2) Model RWD 020 is available also in a version for connection to a 400V±10%/3/50Hz power supply. (3) Sound pressure level in hemispherical field at 10 m from condenser side and 1.6 m from ground. Values with tollerance ± 2 dB. The sound levels refer to operation of the unit under full load in nominal conditions.
Reduced costs, reduced environmental impact
Airbatc version
Cooling towers suffer substantial costs due to the treatment of the process water. Because it uses a closed circuit, RWD does not require any form of process fluid treatment and eliminates liquid losses caused by evaporation.
The RWD Airbatic version, thanks to the water sprayed on the cooling coils, offers the following benefits: • The chilled water at the outlet can be at a temperature which is below ambient temperature; • High cooling capacity within compact dimensions; • Low water consumption compared to cooling towers; • Radical energy savings when cooling the condensation water for watercooled chillers; • High cooling power in presence of high ambient temperatures; • High cooling efficiency also in the low noise operating mode..
Microprocessor controller RWD units can be equipped with a microprocessor featuring an intuitive graphic interface. The controller manages the fans independently, starting them in steps in proportion to the fluid inlet temperature.
Integral independent electrical panel.
Internal view of packaged RWD 300-350.
Fans with integrated motors.
Remote control (optional).
Cooling your industry, optimising your process. | MTA
39
CONNECTIVITY AQUAFREE modules Remote control Group control Building Management System Remote supervision Remote assistance Remote Control Display
PC
REMOTE
ETHERNET
Master/Slave
Building Management System
RS
48
5
B
US USB PenDrive AquaFree
xWEB
CLICK AND CHECK xCONNECT, MTA’s world of connectivity solutions, allows connection to User-supplied Building Management Systems (BMS), connection via local LAN or Ethernet networks, connection to MTA’s dedicated xWEB supervisor, the possibility to program or download storical data via USB connection, and much more beyond. Serial connection to the most advanced BMS systems allows MTA units to be integrated into a centralised supervisor through ModBus protocol. The integration with Lonworks, Bacnet, Profibus system is possible through apposite gateways (not included). Local supervision via intranet or internet can also be achieved via Ethernet, with pre-programmed HTML supervision pages which, according to the unit type, are already pre-programmed within the unit itself. Local Ethernet connection allows multiple units to be interconnected within an autonomous system, with one unit acting as Master. The User can manage all units within the system via the Master unit, or via a remote User interface.
40
MTA | Product Guide | Industrial Process Cooling
xWEB function represents one of the most advanced supervision systems currently available, and integrates the latest internet applications. The server reads, files and manages all information arriving from the units to which it is connected. The following functions are offered in Web page format, either locally or remotely, even via GPRS: • Dynamic multiparameter visualization, either graphically or numerically, of all analogue data, the outputs status and the alarm status; • Remote modification of the operating parameters; • Graphic scheduling for command functions; • System personalization, including alarm messaging rules; • Alarm reset procedures and alarm history filing by remote display; • Alarm message transmission via fax, sms and e-mail (only for xWEB with built in GPRS modem). Features offered depend upon unit type and xCONNECT configuration utilised.
THE COMPLETE MTA PRODUCT PROGRAMME ENERDRYER: THE BIOGAS DRYER
LIQUID CHILLERS
A packaged plug & play solution, for the dessication of Biogas. EnerDryer is supplied on a compact galvanized steel frame, requiring no additional installation or programming. The stainless steel gas side features a gas/ gas economizer, water/gas exchanger and separation/condensate discharge system. The cooling water circuit features a pump and storage tank. MTA offers complete design flexibility, including solutions with integrated blowers (biogas 50 - 4700 m³/h).
CYGNUS TECH Air-cooled chillers, heat pumps & condensing units (cooling capacity 4-66 kW) featuring rotary or scroll compressors. Lowest noise levels, standard electronic fan speed regulation, storage tank and pump(s) installed on-board. TAURUS TECH Air-cooled chillers, heat pumps & condensing units (cooling capacity 73-154 kW) featuring scroll compressors. 3 noise levels (down to super silent), low ambient & heat recovery configurations. OCEAN TECH Water-cooled chillers, heat pumps & evaporating units (cooling capacity 4-193 kW) featuring rotary or scroll compressors. Extremely compact with an optional add-on module featuring a pump and storage tank.
ANCILLARY EQUIPMENT Remote condensers to be combined with MTA chillers.
COMPRESSED AIR DRYERS
Refrigeration dryers:
• D E iTECH: New energy saving system Impulse Technology (air flow 18-1620 m³/h). • DE ETM: refrigeration cycling dryers with energy saving liquid thermal mass technology (air flow 1920-13500 m³/h). • DN: Up to 4 scroll compressors for high energy savings (air flow 13500-45600 m³/h). • BD: High capacity dryers for all personal needs (air flow 17400-32400 m³/h). • HPD: 50 barg dryers (air flow 1530-7302 m³/h).
Adsorption dryers: • NA: Compact aluminium heatless dryers (air flow 7-118 m³/h).
Beyond RWD, MTA offers an extensive range of water cooling solutions.
• N C: Heatless dryers featuring unique energy saving microprocessor (air flow 240-1500 m³/h). • NST: Heat regenerated dryers (air flow 116-8903 m³/h).
Evaporative cooling towers to be combined with MTA water-cooled chillers.
Add-on hydraulic modules including tank and single or twin pumps.
External liquid storage tanks for integration within the system hydraulic circuit.
Auxiliary intermediate heat exchangers for specific application needs.
COMPRESSED AIR COMPONENTS Filters and separators for the removal of condensate, oil and impurities from compressed air. Air and water-cooled aftercoolers for air and gas treatment, with a complete choice of applied materials and including high pressure versions. Electronic zero-loss, mechanical zero-loss and timed drains, including high pressure versions. Oil-water separators for simple and economic condensate disposal.
Cooling your industry, optimising your process. | MTA
41
M.T.A. S.p.A. Viale Spagna, 8 ZI 35020 Tribano (PD) Italy www.mta-it.com
The images of the products in the document are for illustrative purposes only and therefore do not have any contractual value.
03-16 5050GPIND001EA
M.T.A. S.p.A. Viale Spagna, 8 ZI 35020 Tribano (PD) Italy
MTA France S.A. Tel: +33 04 7249 8989 www.mtafrance.fr
Tel. +39 049 9588611 Fax +39 049 9588676
MTA Deutschland GmbH Tel: +49 (2157) 12402 - 0 www.mta.de
[email protected] www.mta-it.com Milan branch office Tel. +39 02 95738492
Novair-MTA, S.A. (España) Tel: +34 938 281 790 www.novair-mta.com SC MTA ROMÂNIA Srl Tel: +40 723 022023 www.mta-it.ro
MTA is represented in over 80 countries worldwide. For information concerning your nearest MTA representative please contact M.T.A. S.p.A. The continuous improvement of MTA's products can cause some variations in the information herein even without prior notice. Reproduction in whole or in part is forbidden.
MTA is ISO9001 certified, a sign of its commitment to complete customer satisfaction.
MTA products comply with European safety directives, as recognised by the CE symbol.
MTA USA, LLC Tel: +1 716 693 8651 www.mta-usa.com MTA Australasia Pty Ltd Tel: +61 1300 304 177 www.mta-au.com
MTA participates in the E.C.C. programme for LCP-HP. Certified products are listed on: www.eurovent-certification.com
EAC certification