Product Specifications DCU DCU--30 350 kW
Data Center on Demand™ 30Rack Solution, 400 Vac input power, 0–11.6 kW per rack
General Specifications Average Annual Power Usage Effectiveness (pPUE) 1.03–1.06 Brand
Data Center on Demand™
Ordering Note
For your customized solution—Call your local CommScope representative
Main Unit Options Input Voltage Range
380–415 Vac
Power Redundancy
Tier 2
Cooling
Evaporative cooling
Cold Weather Package
Not equipped | Temperatures to 10 °C (14 °F) from 10 °C to 40 °C (14 °F to 40 °F)
Vestibule
Not equipped
Door Security
Keyed door locks
Surveillance
Not equipped
Fire Detection
Aspirating smoke detector (ASD)
Fire Suppression
Flooding with fire protection fluid
Air Filtration
MERV 11 filters | MERV 15 filters phase | Salt fog
|
MERV 16 filters
Replacement Parts
Not equipped
|
Recurring maintenance parts kit
|
|
208–240 Vac
Tier 3
| |
|
|
Chilled water cooling
Single width |
|
|
DX cooling |
Temperatures
Double width
Electric door locks with card readers
Closed circuit TV camera with DVR system
Critical parts kit
|
Spot detectors |
Gas
Main Unit Specifications Racks or Cabinets per Unit, maximum
30
Unit Width
5700 mm
Unit Length
17425 mm
Unit Height
3737 mm
|
147 in
Unit Net Weight
42000 kg
|
92594 lb
Cold Aisle Width
1220.0 mm
|
48.0 in
Hot Aisle Width
1162.0 mm
|
45.7 in
Hot Aisle Width Note
Width assumes a rack length of 1000 mm
White Space Width
20140 mm
Output Power Range per Rack
0–11.6 kW
|
224 in |
|
686 in
793 in
Vestibule Specifications Single Width Vestibule Width
2300 mm
Single Width Vestibule Length
17425 mm
|
91 in
Single Width Vestibule Height
3737 mm
|
Single Width Vestibule Net Weight
14760 kg
|
32540 lb
Double Width Vestibule Width
5700 mm
|
224 in
|
686 in 147 in
©2016 CommScope, Inc. All rights reserved. All trademarks identified by ® or ™ are registered trademarks, respectively, of CommScope. All specifications are subject to change without notice. See www.commscope.com for the most current information. Revised: January 16, 2016
page 1 of 2 April 13, 2016
Product Specifications DCU DCU--30 350 kW Double Width Vestibule Length
17425 mm
Double Width Vestibule Height
3737 mm
|
Double Width Vestibule Net Weight
26000.00 kg
|
686 in 147 in |
57320.19 lb
Environmental Specifications Qualification Standard
IEC 60529:2001, IP55
|
NFPA 70
Qualification Standard Note
IEC 60529, IP55 does not apply to the mixing chamber | Achievement of this rating may require a filter with a higher MERV rating
Safety Standard
CE
©2016 CommScope, Inc. All rights reserved. All trademarks identified by ® or ™ are registered trademarks, respectively, of CommScope. All specifications are subject to change without notice. See www.commscope.com for the most current information. Revised: January 16, 2016