Programming -

   EMBED


Share

Transcript

Relay Control Relay Control -- Introduction Two-position control, using a digital (relay) output, is used to turn something on and off. We use a differential and an offset to tell an output when to open and close based on the control variable and setpoint. www.tcsbasys.com PH: 800.288.9383 P1 Relay Control -- Definitions • Differential – amount of change in the control variable from when the output turns on to when it turns off • Offset – a value that creates a deadband for a stage – the first stage typically has an offset of 0 Offsets and Differentials, 2 Setpoints "COOLING" or "HIGH ALARM" Differential Output turns ON Output turns OFF Offset Cool Setpoint Offset Heat Setpoint Differential Output turns OFF Output turns ON "HEATING" or "LOW ALARM" Offsets, Differentials and Deadband, 1 Setpoint "COOLING" or "HIGH ALARM" Output turns ON Differential Output turns OFF Offset Deadband Setpoint Deadband Used on the SZ1025b and SZ1143b Offset Differential Output turns OFF Output turns ON "HEATING" or "LOW ALARM" www.tcsbasys.com PH: 800.288.9383 P2 Proportional Control Proportional Control -- Introduction Analog outputs are called modulating outputs. These outputs vary based on how far the input is away from setpoint. Modulating outputs provide tighter control than two position outputs. Proportional Control -- Definitions • Proportional Control – generates an output that is related to the distance between the active setpoint and the input • Proportional Band/Throttling Range – number of degrees (or percent of span) that the input must change to drive the output from 0 to 100% (either 0 to 20 mA or 4 to 20 mA) www.tcsbasys.com PH: 800.288.9383 P3 Proportional Control -- Definitions • Setpoint Offset – a value that creates a deadband before modulation starts • Aquastat – allows the action to reverse when a digital input is made (SZ1017a, SZ1018, SZ1143b, SZ1051) or an analog input exceeds a certain value (SZ1025a, SZ1018, SZ1062, SZ1064) Proportional Control -- Definitions • Direct Acting – the output increases as the input increases • Reverse Acting – the output decreases as the input increases Direct Acting - Output 12mA @ Setpoint Input Setp oin t + 1/ 2 P } Setp oin t Setpoint - 1/ 2 P 4m A 1 2m A P 20 m A Output www.tcsbasys.com PH: 800.288.9383 P4 Reverse Acting - Output 12mA @ Setpoint Input Setpo int + 1 / 2 P } Setp oin t Setpo in t - 1/ 2 P 1 2m A 4m A P 20m A Output Direct Acting - Output 4 or 20mA @ Setpoint Cooling Heating Input Input Setpoint + P Setpoint } Setpoint + 1/ 2P Setpoint 4m A 12m A P } Setpoint - 1/ 2P Setpoint - P 20m A 4m A 12m A P 20m A Output Output Reverse Acting - Output 4 or 20mA @ Setpoint Cooling Heating Input Input Se tp o in t + P Setp o in t } Setp o in t + 1 / 2 P Setp o in t 4m A 12m A P 20m A Output www.tcsbasys.com } Setp o in t - 1/ 2 P Se tp o in t - P 4m A 12m A P 20m A Output PH: 800.288.9383 P5 Keypad Programming Thermostat Keypad Layout Occupied Heating Cooling fan switch service status Fan Service Program/ Data WARMER system switch COOLER program setup clock setup SZ1060 Series Keypad Layout www.tcsbasys.com PH: 800.288.9383 P6 Comparison of Thermostat Keypads Occupied Heating Cooling fan switch service status Fan Service Program/ Data WARMER system switch COOLER program setup clock setup Typical Superstat™ Keypad SZ1060 Series Keypad SL1001a & SZ1140 Series Keypad Layout SCROLL NEXT UP DOWN Conventional Thermostats • Menu-by-Menu Example – Follow Along Using Demo Panel – Slides Printed in Handout – Catalog Page 183 • All Thermostats Basically the Same • Complete Sequences in Product Manuals • All Sequences in Product Catalog • www.tcsbasys.com www.tcsbasys.com PH: 800.288.9383 P7 SZ-QD Trainer Demo Panel (SZ1031) MON 01- 01- 97 72F 12:00 AM program setup ENTER ACCESS CODE 000 program setup 248 always works!!! Use down arrow to get to 248 more quickly. SZ-QD Trainer Demo Panel (SZ1031) -SET ADDRESS: 000 continued Use your badge number as the address for your stat. program setup SET BAUD RATE: 9.6K program setup TEMPS SHOWN IN: FAHRENHEIT program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued USER ACCESS TO SYSTEM MODE?YES program setup SET SYSTEM MODE: AUTO program setup www.tcsbasys.com PH: 800.288.9383 P8 SZ-QD Trainer Demo Panel (SZ1031) -- continued USER ACCESS TO FAN MODE? YES program setup SET OCCUPIED FAN MODE: ON program setup SET UNOCCUPIED FAN MODE: AUTO program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued This Screen is Repeated for Occupied Periods B, C, and D This Screen is Repeated for Occupied Periods B, C, and D SZ-QD Trainer Demo Panel (SZ1031) -- continued UNOCCUPIED COOL SETPOINT: 80F pro gram setup LIMIT SETPOINT ADJUST +/-: 5F pro gram setup SET OVERRIDE TIME: 180 MINUTES program setup www.tcsbasys.com PH: 800.288.9383 P9 Model Specific Features – SZ1035 ENABLE 3 HEAT & 3 COOL? YES program setup ENABLE STAGE 3 & 4 AS? HEAT program setup Additional Model Specific Features -- continued ENABLE SECOND STAGE HEAT? YES program setup ENABLE SECOND STAGE COOL? YES program setup ENABLE THIRD ST STA AG GE EA AS S:: C CO OO OL L program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued HEAT STAGE 1 OFFSET: 0F program setup HEAT STAGE 1 DIFF: 2F 1F program setup HEAT STAGE 2 OFFSET: 2F 1F program setup HEAT STAGE 2 DIFF: 2F 1F program setup www.tcsbasys.com PH: 800.288.9383 P10 SZ-QD Trainer Demo Panel (SZ1031) -- continued COOL STAGE 1 O 0F OF FFSE FSET T:: 0F program setup COOL STAGE 1 DIFF: 2F 1F program setup COOL STAGE 2 OFFSET: 1F 2F program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued COOL STAGE 2 DIFF: 2F 1F program setup COOL STAGE 3 OFFSET: 2F program setup COOL STAGE 3 DIFF: 1F program setup SZ-QD Trainer Demo Panel (SZ1031) -- www.tcsbasys.com continued PH: 800.288.9383 P11 SZ-QD Trainer Demo Panel (SZ1031) -- continued SZ-QD Trainer Demo Panel (SZ1031) -- continued COOLING LOCKOUT TEMP: 60F program setup HEATING LOCKOUT TEMP: 70F program setup DI1 USED FOR: FAN PROVING program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued DI2 USED FOR: SERVICE pro gram s e tup SET DI2 SETPOINT SHIFT: 02F s e tu p program DI3 USED FOR: FILTER SERVICE s e t u p program www.tcsbasys.com PH: 800.288.9383 P12 SZ-QD Trainer Demo Panel (SZ1031) -- continued DELAY ON POWERUP 60 SECONDS program s e tu p ENABLE SMART RECOVERY? YES s e tu p program REQUIRE CODE FOR PROGRAMMING?YES program setup SZ-QD Trainer Demo Panel (SZ1031) -- continued REQUIRE CODE FOR CLOCK/ SCHED? YES program setup SET ACCESS CODE: 000 NOTE: This is a secondary access code. program setup MON 01- 01- 97 12:00 AM 72F Setting the Clock & Schedule (SZ1031) 248 always works!!! Use down arrow to get to 248 more quickly. www.tcsbasys.com PH: 800.288.9383 P13 Setting the Clock & Schedule (SZ1031) -- continued This Screen is Repeated for Occupied Periods C and D Setting the Clock & Schedule (SZ1031) -- continued These Screens are Repeated for Wed., Thurs., Fri., Sat., Sun., Plus Holiday #1 & #2. This Screen is Repeated for Occupied Periods C and D Setting the Clock & Schedule (SZ1031)-- continued Total Possible Holidays 2 x 12 x 99 = 2,376 scheds. www.tcsbasys.com instances days days . PH: 800.288.9383 P14 Setting the Clock & Schedule (SZ1031)-- continued Where to Get Help or Answers • • • • Instructions Sent with Product TCS Basys Controls Catalog Training & Reference Manual www.tcsbasys.com • Call TCS Directly – 800-288-9383 Software Programming www.tcsbasys.com PH: 800.288.9383 P15 PC Based Software -- Revelation Professional • Menu Driven Programming • Use for Network Setup & Testing, Commissioning, & Load Balancing • “Read” Before Making Changes • “Write” Before Going to NEXT Menu • “Write” vs. “Write Half / Write Page” • “Load All” & “Save All” Options *** NOT SUPPORTED AS OF JAN 2009 *** Superstat™ – conventional heat/cool… Rev Pro Manual pg C-9 Superstat™ – conventional heat/cool… Rev Pro Manual pg C-9 www.tcsbasys.com PH: 800.288.9383 P16 Superstat™ – conventional heat/cool… Rev Pro Manual pg C-9 PC Based Software -- Insight Similar to Revelation Professional… • Tab Driven Interface • Uses Same Datasheets as Ubiquity • Use for Network Setup & Testing, Commissioning, & Load Balancing • Shows Current Values (no “read” required) • “Write Page” Before Going to New Tab *** NEW SOLUTION AS OF JAN 2009 *** Superstat™ – heat pump… www.tcsbasys.com PH: 800.288.9383 P17 Superstat™ – heat pump… Superstat™ – heat pump… Superstat™ – heat pump… www.tcsbasys.com PH: 800.288.9383 P18 Superstat™ – heat pump… Superstat™ – heat pump… Internet Style Software – Ubiquity Similar to Revelation Professional… • Single Page for All Programming Info • Shows Current Values (no “read” required) • Writes All Values on “Submit” • “Read Controller” Option (if needed) www.tcsbasys.com PH: 800.288.9383 P19 Single Page Programming Screen General Info, Alarms, & Assigned Assets Schedule www.tcsbasys.com PH: 800.288.9383 P20 Controller Summary & Ubiquity Functions System and Setpoints & Digital Inputs Digital Outputs www.tcsbasys.com PH: 800.288.9383 P21 Additional Functions, Comments & Buttons Superstat™ – heat pump…SZ1033 Superstat™ with 1 analog output…SZ1017a www.tcsbasys.com PH: 800.288.9383 P22 Superstat™ with 1 analog output…SZ1041 Superstat™ with 2 analog outputs…SZ1051 Superstat™ with 2 analog outputs…SZ1053 www.tcsbasys.com PH: 800.288.9383 P23 General Purpose Controller…SZ1143b General Purpose Controller…SZ1143b - cont’d General Purpose Monitor…SZ1145 www.tcsbasys.com PH: 800.288.9383 P24 General Purpose Monitor…SZ1145 - cont’d General Purpose Monitor…SZ1145 - cont’d VAV Box Controller…SZ1025b www.tcsbasys.com PH: 800.288.9383 P25 VAV Box Controller…SZ1025b - cont’d VAV Box Controller…SZ1025b - cont’d 2 Channel, 365-Day Time Clock…SL1001a www.tcsbasys.com PH: 800.288.9383 P26 2 Ch., 365-Day Time Clock…SL1001a - cont’d Where to Get Help or Answers • • • • Instructions Sent with Product TCS Basys Controls Catalog Training & Reference Manual www.tcsbasys.com • Call TCS Directly – 800-288-9383 www.tcsbasys.com PH: 800.288.9383 P27