PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 1 of 11
PART 1 - GENERAL 1.1
SECTION INCLUDES .1 Pipe and pipe fittings, and valves, for sanitary sewer and domestic water piping systems. .2 Specialties: Floor drains, clean outs, water hammer arresters, thermostatic mixing valves. .3 Fixtures: Water closets, urinals, lavatories, and sinks.
1.2
SUBMITTALS .1 Submit shop drawings to requirements of Section 01 00 00 and Section 23 05 00. .2 Include product description, model, dimensions, component sizes, rough-in requirements, service sizes, finishes, connections to other equipment and piping, performance data, power requirements, and certified pump curves. .3 Submissions for valves shall clearly indicate make, model, location, type, size and pressure rating .4 Submit manufacturer's installation instructions under provisions of Section 01 00 00.
1.3
OPERATION AND MAINTENANCE .1 Submit operation and maintenance data under provisions of Section 01 78 00 and Section 23 05 00. .2 Include fixture trim exploded view and replacement parts lists. .3 Include operation, maintenance, and inspection data, replacement part numbers and availability, and service depot location and telephone number.
1.4
WARRANTY .1 Extended warranties shall be as detailed in Equipment Schedule and Specifications. .2 Provide manufacturers extended warranty to Section 01 70 00 and CCDC 2 General Conditions. .3 Provide copy of original warranty for equipment which has warranty period longer than one year.
1.5
WELDING .1 Welding materials and labour must conform to ASME Code and the Provincial Board of Labour Regulations. .2 Use welders fully qualified and licensed by Provincial Authorities.
1.6
QUALITY ASSURANCE .1 Domestic water, drainage and vent piping shall meet the requirements of the National Building Code and the Provincial and Municipal Codes. .2 Contractor to supply shop drawings for all grooved end components. Do piping system work including hangers in accordance with ANSI B31.1-1983. Install all grooved end components as per manufacturer's latest recommendations. All grooved joint couplings, fittings, valves and specialties shall be the products of a single manufacturer. Grooving tools shall be of the same manufacturer as the grooved components.
1.7
PLUMBING GENERAL REQUIREMENTS .1 Provide materials, equipment and labour to install plumbing as required by Provincial and Local Codes and as specified herein. .2 Provide water and drainage connections to equipment furnished in other sections of this specification and by the Owner. .3 Provide and include charges for connections to Municipal and Utility Company services.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 2 of 11
1.8
PLUMBING VALVES, GENERAL REQUIREMENTS .1 Provide valves of same manufacturer throughout where possible. .2 Provide valves with manufacturer's name and pressure rating clearly marked on outside of body. .3 Provide valves suitable to connect to adjoining piping as specified for pipe joints. Use pipe size valves. .4 Thread pipe sizes 50 mm (2") and smaller. .5 Flange pipe sizes 63 mm (2-1/2") and larger. .6 Solder or screw to solder adaptors for copper tubing. .7 Use grooved body valves with mechanical grooved jointed piping. .8 Provide butterfly valve with tapped lug body when used for isolating service. .9 With the Victaulic Vic-Press system, valves may be supplied with Vic-Press connections.
1.9
PLUMBING FIXTURES, GENERAL REQUIREMENTS .1 Provide new fixtures, CSA approved, free from flaws and blemishes with finished surfaces clear, smooth and bright. .2 Provide CSA approved plumbing fittings. Visible parts of fixture brass and accessories shall be heavily chrome plated. .3 Fixtures shall be product of one manufacturer. Fittings of same type shall be product of one manufacturer. .4 Protect fixtures against use and damage during construction. .5 Check millwork shop drawings. Confirm location and size of fixtures and openings before rough-in and installation.
PART 2 - PRODUCTS 2.1
SANITARY SEWER AND VENT PIPING, UNBURIED (EXCLUDING RETURN AIR PLENUMS) .1 Cast iron pipe and fittings; hub-and spigot, neoprene gaskets; or hubless with neoprene gaskets and stainless steel clamp-and-shield assemblies. .2 Type "M" or "DWV" copper with cast brass, or bronze or wrought copper fittings; 95/5 solder joints or grooved mechanical. .3 CSA rated PVC pipe and fittings; solvent weld joints or grooved mechanical.
2.2
SANITARY SEWER AND VENT PIPING, UNBURIED IN RETURN AIR PLENUMS) .1 Cast iron pipe and fittings; hub-and spigot, neoprene gaskets, or lead and oakum joints; or hubless with neoprene gaskets and stainless steel clamp-and-shield assemblies. .2 Type "M" or "DWV" copper with cast brass, or bronze or wrought copper fittings; 95/5 solder joints or grooved mechanical. .3
Plastic PVC-XFR-15/50 pipe and fittings; solvent weld joints or grooved mechanical.
2.3
WATER PIPING, UNBURIED .1 Type L hard copper; with cast brass or wrought copper fittings; 95/5 solder joints. .2 Cross Linked Polyethylene (PEX) pipe.
2.4
FLANGES, UNIONS, AND COUPLINGS .1 Pipe Size 50 mm and Under, 1034 kPa (150 PSI): Malleable iron, bronze to iron ground joint unions for threaded ferrous piping air tested for gas service; soldered bronze unions for copper pipe.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
.2 .3
.4
SECTION 22 42 00 Page 3 of 11
Pipe Size over 50 mm, 1034 kPa (150 PSI): Forged steel slip-on flanges for ferrous piping; bronze flanges for copper piping. Gaskets shall be 2 mm (1/16") thick reformed synthetic rubber. Gaskets for gas service shall be synthetic rubber. All grooved products to be of one manufacturer. Coupling gaskets to be Grade "E" EPDM for water service -34 deg.C to 110 deg.C (-30 deg.F to 230 deg.F) and oil free compressed air. For oil saturated compressed air use Grade "T" gasket. All grooved fittings and couplings to be manufactured from ductile iron conforming to ASTM A536; wrought steel conforming to ASTM A234; or factory fabricated from steel pipe conforming to ASTM A53. .1 Couplings shall consist of two ductile iron housing segments, pressure responsive elastomer gasket, and zinc-electroplated steel bolts and nuts. .1 Steel Pipe to 300 mm (12"): .1 Rigid Type: Housings shall be cast with offsetting angle-pattern bolt pads to provide rigidity and system support and hanging in accordance with ANSI B31.1 and B31.9. .1 50 mm to 150 mm (2" to 6"): Installation ready, for direct stab installation without field disassembly, with grade EHP gasket suitable for operating temperatures to 121 deg.C (250 deg.F). Victaulic Style 107. .2 Victaulic Zero-Flex Style 07. .2 Flexible Type: For use in locations where vibration attenuation and stress relief are required. Three flexible couplings may be used in lieu of a flexible connector. The couplings shall be placed in close proximity to the source of the vibration. Victaulic Style 75 or 77. .2 Copper-tube 50 mm to 200 mm (2" to 8"): Copper-tube dimensions, with housings shall be cast with offsetting angle-pattern bolt pads to provide rigidity, with FlushSeal gasket. Victaulic Style 606. .1 50 mm to 100 mm (2" to 4"): Installation ready, for direct stab installation without field disassembly, with grade EHP gasket suitable for operating temperatures to 121 deg.C (250 deg.F). Victaulic Style 607. Dielectric Connections: Union with galvanized or plated steel threaded end, Copper solder end, water impervious isolation barrier.
2.5
VALVE OPERATORS .1 Provide suitable handwheels for gate, globe or angle, and drain valves, and inside hose bibbs. .2 Provide one plug cock wrench for every ten plug cocks sized 50 mm (2") and smaller, minimum of one. .3 For butterfly valves provide lever lock handle with toothed plate for shut-off service and infinitely adjustable handle with lock nut and memory stop for throttling service. .4 Where indicated on drawings, provide chain operated sheaves. Extend chains to about 1500 mm (5') above floor and hook to clips arranged to clear walking aisles. .5 For ball valves provide quarter turn removable lever handles.
2.6
GATE VALVES .1 Bronze, non-rising stem, inside screw, single wedge or disc, solder or threaded ends. .2 Iron, bronze trim, rising stem, OS&Y, single wedge, flanged or grooved ends.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 4 of 11
2.7
GLOBE VALVES .1 Bronze, rising stem, inside screw, renewable composition disc, solder or screwed ends, with back seating capacity. .2 Iron, bronze trim, rising stem, OS&Y, renewable composition disc, flanged ends.
2.8
BALL VALVES .1 Brass body and trim, stainless steel ball, teflon seats and stuffing box ring, lever handle, solder or threaded ends with union. .2 Ball orifice to be full diameter. .3 Balance plates with locking device for throttling service
2.9
PLUG COCKS .1 Cocks Up to 50 mm: Iron body, bronze tapered plug and washers, air tested, nonlubricated, teflon packing, threaded ends. .2 Cocks Over 50 mm: Cast iron steel body and plug, pressure lubricated type, teflon packing, flanged ends.
2.10
BUTTERFLY VALVES .1 Iron body, bronze disc, resilient replaceable seat, water or lug ends, 10 position lever handle or infinite lever handle with memory stop. .2 Grooved end valves shall be 2068 kPa (300 psi) bubble tight shutoff on dead end service. Valve stem shall be offset from the disc centreline to provide full 360 degree circumferential seating. Victaulic MasterSeal (sizes to 300 mm) or AGS-Vic300 (350 mm to 600 mm).
2.11
SWING CHECK VALVES .1 Bronze, bronze swing disc, solder or screwed ends. .2 Iron body, bronze trim, swing disc, renewable disc and seat, flanged ends or grooved ends. .3 Grooved end check valves shall be 2068 kPa (300 psi) minimum working pressure, in sizes through 300 mm (12"), non-slamming spring loaded disk. Victaulic Series 716. .1 For sizes 350 mm to 600 mm (14" to 24"): Valves shall be rated to 1575 kPa (230 psi), with dual stainless steel disc. Victaulic Series W715.
2.12
SPRING LOADED CHECK VALVES .1 Iron body, bronze trim, spring loaded, renewable composition disc, screwed, wafer or flanged ends.
2.13
RELIEF VALVES .1 Valves: Bronze body, teflon seat, steel stem and springs, automatic, direct pressure actuated, capacities ASME certified and labelled.
2.14
CLEAN OUTS .1 Cleanout: Adjustable floor cleanout with lacquered cast iron body and anchor flange, secondary O ring test seal, 4" diameter cleanout opening and combined scoriated satin finished nickel bronze cover and plug top assembly with stainless steel vandal-proof allan key screws and primary gasket seal. Provide membrane clamp for all membrane floors. Specification based on Mifab Model C1100. .2 Cleanout Plugs: heavy cast iron male ferrule with brass screws and threaded brass or bronze plug. Sealing-caulked lead seat or neoprene gasket.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 5 of 11
2.15
ACCESS COVERS .1 Wall Access: face or wall type, polished nickel bronze with chrome plated cap, round cover with flush head securing screws, bevelled edge frame complete with anchoring lugs. .2 Floor Access: round cast iron body and frame with adjustable secured nickel bronze top and: .1 Plugs: bolted bronze with neoprene gasket. .2 Cover for Unfinished Concrete Floors: round, nickel bronze, gasket, vandal-proof screws. .3 Cover for Terrazzo Finish: Polished nickel bronze with recessed cover for filling with terrazzo, vandal-proof locking screws. .4 Cover for Tile and Linoleum Floors: polished nickle bronze with recessed cover for linoleum or tile infill, complete with vandal-proof locking screws. .5 Cover for Carpeted Floors; polished nickel bronze with deep flange cover for carpet infill, complete with carpet retainer vandal-proof locking screws. .3 Provide bolted cover plates on all vertical rainwater leaders.
2.16
WATER HAMMER ARRESTORS .1 Fit water supply to each fixture or group of fixtures with water hammer arrestors. .2 Stainless steel or copper construction, bellows or piston type: to PDI-WH201. .3 Air chamber same size as supply line of 19 mm minimum, and minimum 450 mm long. .4 Where permitted by authority having jurisdiction, air chambers same size as supply line or 20 mm (3/4") minimum, and minimum 450 mm (18") long may be utilized in lieu of water hammer arrestors.
2.17
WATER CLOSET WC-1 (Public WR) .1 Bowl: Acorn Meridian Model 2141-W-2-FM-ULF-FVBO-ADA-FG-FVT-HS-OFWCMC siphon jet toilet. Fixture to be heavy gauge type 304 stainless steel. Exposed surfaces shall be polished to a satin finish. Housing to include side access panels and punching for hinged seat with cover. Toilet shall meet ASME A112.19.3-2008 and CSA B45.4-2008 requirements and will flush with a minimum of 25 PSI flow pressure when used in conjunction with a minimum of 1.6 gpf. Toilet trap shall have a minimum 3-1/2” seal that shall pass a 2-1/8” diameter ball and be fully closed. Unit to be complete with: wall supply selection, on-floor fixture mounting, wall outlet waste, front mount installation, 1.6 GPF flush valve by others, 18” ADA integral seat height, 14 gauge, flush valve thruwall connection, hinged seat with cover, and mounting carrier. .2 Flush Valve: Sloan Crown Model 152-1.6 SWB ES-S. Concealed, Sensor Activated Water Closet Flushometer, enclosed behind a 305mm x 305mm (12” x 12”) wall box with stainless steel access panel, for wall hung back spud bowls. Quiet, Concealed, Piston Type, Rough Brass Closet Flushometer with the following features: Fixed Volume Piston with Dual Filtered O-ring Bypass, OPTIMA EL-1500-L Self-Adaptive Infrared Sensor with Indicator Light, User friendly three second Flush Delay, Courtesy Flush Override with Waterproof Piezo Electric Button, Wall Plate with Stainless Steel Access Panel and Vandal Resistant Screws, 1” I.P.S. Wheel Handle bak-chek Angle Stop, Adjustable Tailpiece, High Back Pressure Vacuum Breaker Flush Connection and Spud Coupling for 1-1/2” Concealed Back Spud, Sweat Solder Adapter, Main Seat filters water supplied to the Solenoid Operator, Type 316 Stainless Steel Non-Hold-Open Relief Valve Assembly, High Copper, Low Zinc Brass Castings for Dezincification Resistance, Valve designed to accept Low and Ultra-Low Consumption Pistons only to ensure Water Conservation, Non-Hold-Open Integral Solenoid Operator, Fixed Metering Bypass and No External Volume Adjustment to Ensure Water Conservation, Main Seat, Stop Seat, and Vacuum Breaker molded from PERMEX Rubber Compound for Chloramine Resistance, Valve
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 6 of 11
Body, Tailpiece, and Control Stop shall be in conformance with ASTM alloy Classification for Semi-Red Brass. Valve shall be in compliance with the applicable sections of ASSE 1037. Installation conforms to ADA requirements. 2.18
WATER CLOSET WC-2 (Staff WR) .1 Bowl/Flush Valve: Sloan, Model WETS 2020.1001-1.28 (1.28 gpf/4.8 Lpf). Quiet, exposed, diaphragm type, chrome plated HET closet Flushometer and HET vitreous china ADA compliant fixture with the following features: Flushometer: PERMEX Synthetic Rubber Diaphragm with Dual Filtered Fixed Bypass, ADA compliant metal oscillating Non-Hold-Open Handle with Triple Seal Handle Packing, 1” I.P.S. Screwdriver Bak-Check Angle Stop, Free spinning Vandal Resistant Stop Cap, Adjustable Tailpiece, High Back Pressure Vacuum Breaker Flush Connection with Onepiece Bottom Hex Coupling Nut, Spud Coupling and Flange for 1-1/2” Top Spud, Sweat Solder Adapter w/Cover Tube and Cast Wall Flange w/Set Screw, High copper, low zinc brass castings for dezincification resistance, Non-Hold-Open Handle, Fixed Metering Bypass and no external volume adjustment to ensure water conservation, Flush accuracy controlled by CID technology, Diaphragm, Handle Packing, Stop Seat, and Vacuum Breaker molded from PERMEX rubber compound for chloramine resistance, Valve Body, Cover, Tailpiece, and Control Stop shall be in conformance with ASTM Alloy Classification for Semi-Red Brass. Valve shall be in compliance to the applicable sections of ASSE 1037. Fixture: ADA compliant, Vitreous chine, Floor Mounted, 1-1/2” I.P.S. top spud inlet, 2-1/8” trapway diameter, Integral flushing rim, Elongated bowl, Siphon jet flush, Closet bolts and caps included, 100% factory flush tested, toilet seat not included, water closet shall be in compliance to the applicable sections of ASME A112.19.2/CSA B45.1. .2 Seat: Bemis Model 1950SS. Open front with cover, elongated, heavy-duty, injection molded solid plastic toilet seat. Features four molded-in bumpers, color-matched TopTite hinges with non-corrosive 300 Series stainless steel self-sustaining hinges. This seat complies with American National Standard Z124.5 Toilet (Water Closet) Seats as a class Commercial Heavy Duty.
2.19
LAVATORY L-1 (Public WR) .1 Basin and Trim: Acorn Meridian Model 3702-1-SO-DMJ-IB-OF-PDM-SES, stainless steel curved front two-person washbasin, off-floor fixture mounting (wall requires adequate backing to support washbasin), wall outlet waste. Unit with 850mm (34”) rim height to conform with ANSI, UFAS, and ADA Accessibility Standards. Washbasin to include: two individual integral bowl round basins (15-3/4” diameter x 5” deep) with basin overflow, metering liquid soap dispenser, and scalloped enclosure style. Basins, countertop, backsplash, and apron, and trap enclosure to be constructed of heavy gauge, type 304 stainless steel with satin finish. Operation: Hands-Free Sensor operation with infra-red sensor operated, solenoid water valve, mixing valve, and a transformer. Sensor to operate with a 30 second metered flow or cycle once an object is detected before turning off the solenoid valve.
2.20
LAVATORY L-2 (Staff WR) .1 Basin: Sloan Model SS-3001, oval under mount lavatory, white vitreous china, front overflow, ADA compliant when mounted with lavatory mounted at 580mm (34”) from finished floor. Overall Size: 495mm x 419mm (19.5” x 16.5”). .2 Trim: Delta Model 500-DST, single handle deck mount lavatory faucet. 102mm (4”) center-set, 127mm (5”) long spout, lever and knob handle, control mechanism is the diamond embedded ceramic disc cartridge, control handle shall return to neutral position when valve is turned off, 3/8” O.D. straight, staggered pex supply tubes, 889mm (35”)
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
.3 .4
SECTION 22 42 00 Page 7 of 11
and 914mm (36”) long, brass drain w/plastic tailpiece, maximum 1.6 gpm flow rate at 60 PSI, lever handle have red/blue button, included cartridge limit switch to allow a maximum hot water mix of 50%. Lavatory Supplies and Riser Tubes: Cambridge Brass Model 47T2512SD chrome plated angle supplies with lockshield stem, screwdriver stop, 9.5mm O.D. X 305mm long flexible braided stainless steel riser and stainless steel escutcheon plate. Tailpiece and Trap: P3906 offset grid drain assembly, complete with open grid strainer. P4001 chrome plated cast brass adjustable P-trap complete with cleanout and escutcheon. Mount trap tight to wall. Insulate trap and supplies with Truebro Lavguard assembly for supplies, tailpiece and trap assembly-white.
2.21
SINKS SK-1 (Single Compartment Soft Room) .1 Bowl: Kindred Commercial, model LBS7314P-1/3, single compartment sink with faucet ledge. 18 gauge, type 304, 18-10 stainless steel. Self-rimming. Exposed surfaces are satin finished. Undercoated to reduce condensation and resonance. Includes factory applied rim seal, cut out template, Universal Installation System hardware and 89mm (3-1/2”) crumb cup waste assembly, location center. Compartment size: 44cm x 60cm x 36cm (17-1/2” x 23-1/2” x 14”). Overall size: 57cm x 65cm (22-6/16” x 25-5/8”). Faucet hole drilling: 3 hole, 1-1/2”, 4” centers, 8” centerset. .2 Trim: Delta Model 100-DST single handle deck mount kitchen faucet. 221mm (811/16”) long spout swings 180 degrees, lever handle shall return to neutral position when faucet is turned off, control mechanism shall be the diamond coated ceramic cartridge, 3/8” O.D. straight, staggered PEX supply tubes 889mm (35”) and 914mm (36”) long, standard 10mm (3/8”) compression gasket fittings, mounts on standard 35mm (1-3/8”) +\- 3mm (1/8”) diameter holes on 203mm (8”) centers. .3 Sink Supplies and Riser Tubes: Cambridge Brass Model 47T2512SD chrome plated angle supplies with lockshield stem, screwdriver stop, 9.5mm O.D. X 305mm long flexible braided stainless steel riser and stainless steel escutcheon plate. .4 Trap: Crane P4005 cast-brass adjustable swivel pattern P-trap with cleanout.
2.22
SINKS SK-2 (Single Compartment Staff Room) .1 Bowl: Kindred Commercial, Model LBS4610P-1/3, single compartment sink with faucet ledge. 18 gauge, type 304, 18-10 stainless steel. Self rimming. Exposed surfaces are satin finished. Undercoated to reduce condensation and resonance. Includes factory applied rim seal, cut out template, Universal Installation System hardware and 89mm (3-1/2”) crumb cup waste assembly, location center. Compartment size: 36cm x 41cm x 25cm (14” x 16” x 10”). Overall size: 47cm x 46cm (18-9/16” x 18-1/8”). Faucet hole drilling: 3 hole, 1-1/2” diameter, 4” centers, 8” centerset. .2 Trim: Delta Model 100-DST single handle deck mount kitchen faucet. 221mm (811/16”) long spout swings 180 degrees, lever handle shall return to neutral position when faucet is turned off, control mechanism shall be the diamond coated ceramic cartridge, 3/8” O.D. straight, staggered PEX supply tubes 889mm (35”) and 914mm (36”) long, standard 10mm (3/8”) compression gasket fittings, mounts on standard 35mm (1-3/8”) +\- 3mm (1/8”) diameter holes on 203mm (8”) centers. .3 Sink Supplies and Riser Tubes: Cambridge Brass Model 47T2512SD chrome plated angle supplies with lockshield stem, screwdriver stop, 9.5mm O.D. X 305mm long flexible braided stainless steel riser and stainless steel escutcheon plate. .4 Trap: Crane P4005 cast-brass adjustable swivel pattern P-trap with cleanout.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
SECTION 22 42 00 Page 8 of 11
2.23
SINKS SK-3 (Double Compartment Staff Room with Pantry Faucet) .1 Bowl: Kindred Commercial, Model LBD6410PCB-1/4. Double compartment sink with faucet ledge. 18 gauge, type 304, 18-10 stainless steel. Self rimming. Exposed surfaces are satin finished. Undercoated to reduce condensation and resonance. Complete with factory applied rim seal, Universal Installation Sytem hardware, cutout template and 89mm (3-1/2”) waste assembly, location center back. Compartment size: 41cm x 36cm x 25cm (16” x 14” x 10”). Overall size: 52cm x 79cm (20-9/16” x 31-1/4”). Faucet hole drilling: 4 hole, 1-1/2” diameter, 4” centers, 8” centerset, plus 1 hole 4” to the right. .2 Trim: Delta Model 100-DST single handle deck mount kitchen faucet. 221mm (811/16”) long spout swings 180 degrees, lever handle shall return to neutral position when faucet is turned off, control mechanism shall be the diamond coated ceramic cartridge, 3/8” O.D. straight, staggered pex supply tubes 889mm (35”) and 914mm (36”) long, standard 10mm (3/8”) compression gasket fittings, mounts on standard 35mm (1-3/8”) +\- 3mm (1/8”) diameter holes on 203mm (8”) centers. .3 Pantry Faucet: Delta Model 27C643. Cast Brass single pantry faucet, single hole mount, polished chrome plate finish, pout and rim, Cer-Tek ceramic structure, metal hold-down package, spout #6 gooseneck pout 4.5” radius standard rigid/swivel field installation vandal resistant .090” wall thickness (R2), Outlet #4 standard 5.7 L/Min (1.5 GPM) Flow control aerator, Handle #3 76mm (3”) lever blade handle ADA Compliant metal color indexed vandal resistant screw. .4 Sink Supplies and Riser Tubes: Cambridge Brass Model 47T2512SD chrome plated angle supplies with lockshield stem, screwdriver stop, 9.5mm O.D. X 305mm long flexible braided stainless steel riser and stainless steel escutcheon plate. .5 Trap: Crane P4005 cast-brass adjustable swivel pattern P-trap with cleanout.
2.24
SINKS SK-4 (Double Compartment Staff Room) .1 Bowl: Kindred Commercial, Model LBD6410PCB-1/3. Double compartment sink with faucet ledge. 18 gauge, type 304, 18-10 stainless steel. Self rimming. Exposed surfaces are satin finished. Undercoated to reduce condensation and resonance. Complete with factory applied rim seal, Universal Installation System hardware, cut out template and 89mm (3-1/2”) waste assembly, location center back. Compartment size: 41cm x 36cm x 25cm (16” x 14” x 10”). Overall size: 52cm x 79cm (20-9/16” x 31-1/4”). Faucet hole drilling: 3 hole, 1-1/2” diameter, 4” centers, 8” centerset. .2 Trim: Delta Model 100-DST single handle deck mount kitchen faucet. 221mm (811/16”) long spout swings 180 degrees, lever handle shall return to neutral position when faucet is turned off, control mechanism shall be the diamond coated ceramic cartridge, 3/8” O.D. straight, staggered PEX supply tubes 889mm (35”) and 914mm (36”) long, standard 10mm (3/8”) compression gasket fittings, mounts on standard 35mm (1-3/8”) +\- 3mm (1/8”) diameter holes on 203mm (8”) centers. 3 Sink Supplies and Riser Tubes: Cambridge Brass Model 47T2512SD chrome plated angle supplies with lockshield stem, screwdriver stop, 9.5mm O.D. X 305mm long flexible braided stainless steel riser and stainless steel escutcheon plate. .4 Trap: Crane P4005 cast-brass adjustable swivel pattern P-trap with cleanout.
PART 3 - EXECUTION 3.1
GENERAL INSTALLATION .1 Ream pipes and tubes. Clean off scale and dirt, inside and outside, before assembly. Remove welding slag or other foreign material from piping. .2 Install equipment in accordance with manufacturer's instructions.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
.3 .4 .5 .6 .7 .8 .9 .10 .11 .12 .13
.14 .15 .16
.17 .18
.19 .20
SECTION 22 42 00 Page 9 of 11
Install piping to conserve building space and not interfere with use of space. Route piping in orderly manner and maintain gradient. Group whenever practical at common elevations. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment. Provide clearance for installation of insulation and access to valves, air vents, drains and fittings. Install unions downstream of valves, at branch connections to mains, and at equipment or apparatus connections. Unions are not required in installations using grooved mechanical joint couplings. (The couplings shall serve as unions and disconnect points.) Provide non-conducting dielectric connections wherever jointing dissimilar metals. Install brass male adapters each side of valves in copper piped system. Sweat solder adapters to pipe. Extend clean outs to finish floor or wall surface. Lubricate threaded clean out plugs with mixture of graphite and linseed oil. Ensure clearance at clean out for rodding of drainage system. Prior to building turnover remove cleanout plugs, re-lubricate and re-install using only enough force to ensure permanent leakproof joint. Install water hammer arrestors complete with accessible isolation valve on supply to each fixture or group of fixtures in a single room. Screw joint steel piping up to and including 38 mm (1-1/2"). Weld piping 63 mm (2-1/2") and larger, including branch connections. Screw or weld 50 mm (2") piping. Make screwed joints with full cut standard taper pipe threads with approved non-toxic joint compound applied to male threads only. Use main sized saddle type branch connections or directly connecting branch lines to mains in steel piping if main is at least one pipe size larger than the branch for up to 150 mm (6") mains and if main is at least two pipe sizes larger than branch for 200 mm (8") and larger mains. Do not project branch pipes inside the main pipe. Make joints for cast iron bell and spigot pipe with neoprene gasketing system, or PC4 caulking compound. Make joints for plain end pipe with gasket and clamp type mechanical fastener. Clamp cast iron water pipe at fittings with 20 mm (3/4") rods and properly anchor and support. Use grooved mechanical couplings and mechanical fasteners in accessible locations, risers, pipe chases, and in other locations as approved by the Engineer. Use flexible couplings at pumps, coils and all vibration isolated equipment in lieu of flexible connectors, all other couplings to be rigid. Grooved joints shall be installed in accordance with the manufacturer's latest published installation instructions. The grooved coupling manufacturer's factory trained representative shall provide on-site training for Contractor's field personnel in the use of grooving tools and installation of grooved joint products. The representative shall periodically visit the job site and review Contractor is following best recommended practices in grooved product installation. (A distributor's representative is not considered qualified to conduct the training or job site visits). Provide non-conducting type connections wherever jointing dissimilar metals in systems. Brass adaptors and valves are acceptable. Pressfit piping and fittings to be installed in strict accordance with manufacturer's recommendations.
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
.21
.22 .23 .24 .25 .26
SECTION 22 42 00 Page 10 of 11
Use of PVC plastic pipe allowed where approved by the authority having jurisdiction. PVC pipe run in plenum spaces shall have flame and smoke rating for that purpose. PVC pipe to be complete with ULC labelled fire stopping wherever penetrating fire separations. Install vacuum breakers on plumbing lines where contamination of domestic water may occur; generally necessary on flush valves. Where floor drains are located over occupied areas, provide waterproof installation. Install trap primers where required by Codes and/or where indicated on drawings. Install pressure reducing valves to limit maximum static pressure at plumbing fixtures to 550 kPa (80 psi). Install isolation and drain valves at the base of all risers.
3.2
ROUTES AND GRADES .1 Route piping in orderly manner and maintain proper grades. Install to conserve headroom and interfere as little as possible with use of space. Run exposed piping parallel to walls. Group piping wherever practical at common elevations. Install concealed pipes close to the building structure to keep furrings to a minimum. .2 Slope water piping 25 mm in 12 m (1" in 40') and arrange to drain at low points. .3 On closed systems, equip low points with 20 mm (3/4") drain valves and hose nipples. Provide, at high points, collecting chambers and high capacity float operated automatic air vents. .4 Make reductions in water pipes with eccentric reducing fittings installed to provide drainage and venting. .5 Grade horizontal drainage and vent piping 22 mm per meter (1/4" per foot) minimum unless otherwise indicated on drawings.
3.3
PLUMBING FIXTURE INSTALLATION .1 Install each fixture with its own trap, easily removable for servicing and cleaning. At completion thoroughly clean plumbing fixtures and equipment. .2 Provide chrome plated rigid or flexible supplies to fixtures with screwdriver stops, reducers and escutcheons. .3 Install wall mounted lavatories, urinals and water closets with approved wall carriers, model to suit installation. .4 Mount fixtures the following heights above finished floor; unless noted otherwise on Architectural drawings: Water Closet: Standard 355 mm (14") to top of bowl rim Handicapped 410 mm (16.5") to top of bowl rim Urinal: Standard 558 mm (22") to top of bowl rim Handicapped 430 mm (17") to top of bowl rim Lavatory: Standard 813 mm (32") to top of basin rim Handicapped 850 mm (34") to top of basin rim
PROPOSED TENANT IMPROVEMENTS MINISTRY OF SOCIAL SERVICES 2045 BROAD STREET REGINA, SASKATCHEWAN PLUMBING
3.4
SECTION 22 42 00 Page 11 of 11
PLUMBING FIXTURE ROUGH-IN SCHEDULE .1 Rough-in fixture piping connections in accordance with the following table of minimum sizes or as required for particular fixtures: Hot Water Cold Water Waste Vent Lavatories 12 mm 12 mm 38 mm 32 mm (½") (½") (1-1/2") (1-1/4") Sink
12 mm (½")
12 mm (½")
38 mm (1-1/2")
32 mm (1-1/4")
Water Closet ----(flush valve)
38 mm (1-1/2")
102 mm (4")
51 mm (2")
Floor Drains -----
-----
75 mm (3")
38 mm (1-1/2")
3.5
VALVE INSTALLATION AND APPLICATION .1 Install valves with stems upright or horizontal, not inverted. .2 Install gate, ball and butterfly valves for isolating service, to isolate equipment, part of systems or vertical risers. .3 Install globe, ball or angle valves for throttling service and control device or meter bypass. .4 Use plug cocks for gas service. .5 Use plug cocks in water systems for throttling service. Use non-lubricated plug cocks only when shut-off or isolation valves are also provided. .6 Provide drain valves at main shut-off valves, low points of piping and apparatus. .7 Provide thermometer wells and thermometers at locations shown on drawings.
3.6
DISINFECTION OF DOMESTIC WATER PIPING SYSTEM .1 Prior to starting work, verify system is complete, flushed and clean. Ensure PH of water to be treated is between 7.4 and 7.6 by adding alkali (caustic soda or soda ash) or acid (hydrochloric). .2 Inject disinfectant, free chlorine in liquid, powder, tablet or gas form, throughout system to obtain 50 to 80 mg/l residual. .3 Bleed water from outlets to ensure distribution and test for disinfectant residual at minimum 15 percent of outlets. Maintain disinfectant in system for 24 hours. If final disinfectant residual tests less than 25 mg/L, repeat treatment. .4 Flush disinfectant from system until residual equal to that of incoming water or 1.0 mg/L. Take samples no sooner than 24 hours after flushing, from 10 percent of outlets and from water entry, and analyze.