Transcript
R15 Protection Relay Test Solutions IEC61850 Test Solutions Amplifier for Power Simulation Application
PONOVO POWER CO., LTD. 2F,4Cell, Tower C, In.Do Mansion, No.48A Zhichun Road, Haidian District Beijing, PR China (100098) Tel.+86 (10) 8275 5151(reception) Tel. +86 (10) 8275 5151ext.8887 Fax. +86 (10) 8275 5151-8103
[email protected] www.relaytest.com
Revised on 06/2013. Contents subject to change
Professional Solution Provider For The Power World
PONOVO POWER CO., LTD.
About us
Contents
About us Throughout the last decade, PONOVO POWER CO., LTD (previously known as Power Advanced Co., LTD) has been focusing on providing professional solutions to over 5000 clients in the fields of intelligent testing and power quality control.
Contents Products Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03 6-Phase Relay Testing System
2001: Foundation of PONOVO POWER CO., LTD 2001: Launch of PWA, the relay test system with in-built output monitoring and recording function 2002: Launch of PW466A, the relay test system with 6 currents and 6 voltages 2003: Launch of PH01, the testing system for Traveling Wave Fault Locater 2004: Launch of PWS, the relay test system for subway used protective relays 2005: Launch of PWF, the relay test system for digital substation with IEC61850 protocol 2005: Launch of e40, the software for automatic test and management 2006: Launch of the relay test system for serial compensation system used relays 2007: Launch of PM605A, the universal calibrator and test system 2008: Launch of T200A, the single phase universal tester which can provide 120s output time at 250A 2008: Launch of MR1200, the portable disturbance recorder with in-built oscilloscope function 2008: Launch of PowerTest relay test software 2009: Launch of the relay test system for 500KV DC converting station test application 2009: Launch of L336i, the compact relay test system with 6 currents and 4 voltages and has a weight of 8.8kg 2009: Launch of PCT100i, the CT/PT tester with a weight of 11kg 2009: Launch of HB-6000, the online DGA (dissolved gas analyzer) system for transformer 2009: Launch of PF3000, the test system for automatic test of power filters 2009: Launch of T1000/T2000, the primary injection kit which can provide 120s output time at 1000A 2009: Launch of TD4000A, which can continuously supply 4000A DC current for testing DC type CT 2010: Launch of PCT200i, new generation of CT\PT Tester 2010: Launch of PNS series handheld digital signal analyzer for intelligent substation maintenance 2010: Launch of new generation PNF801 portable Fiber Digital relay tester with 8 fiber optical ports 2010: Launch of SSCS, the solid state composite switch for improving the performance of capacitor bank control 2010: Launch of LVRT (Low voltage ride through) 2011: Launch of APF (Active Power Filter) 2011: Launch of STATCOM (Static compensator)
01
- PW460 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05 - PW636i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06 - PW336i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 07 - PW466i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08 - L336i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 09 - POM2-6143 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3-Phase Relay Testing System - POM2-3243 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - S40A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PowerTest Relay Test Software - Software Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..13 - PowerTest Relay Test Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Single Phase Relay Tester - T200A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Primary Injection - T1000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
IEC61850 Test Solution - NF801 Intelligent Relay Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 - NS601 Handheld Digital Signal Analyzer . . . . . . . . . . . . . . . . . . 20
CT/PT Testing System - PCT200 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DC Converting Station Test solution - TD series DC Current Tester. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power Filter Characteristic Tester - FT3000 Power Filter Characteristic Tester . . . . . . . . . . . . . . . . . . . 23 Amplifier for Real Time Dynamic Simulation . . . . . . . . . . . . . . . . . 25
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
02
Products introduction
Products introduction
Products introduction L336i Universal Test System 6×15A,4×150V v 8 binary inputs and 4 binary outputs v Can be upgraded to support the test of IEC61850 v complied relay Weight: 8.8kg v Size: 256×110×395mm v
PCT 200 Series CT/PT Test System T1000 Primary Injection and Test Equipment
Test standard: IEC60044-1/6 and ANSI/IEEE C57.13 v All kinds of CT v One test can get all CT parameters v Fast test for excitation check v Also can do the PT test v PCT series: PCT 200Ai PCT 200i v Weight: 12 kg v
1×1000Aac/7000VA v 1×250Vac/250VA v 1×300Vdc/600W v In-built ammeter function v 120s continuous output time at 1000A v Weight : 30kg v
PW460 Universal Test System v 6×15A,4×300V
8 binary inputs and 8 binary outputs, 4 counter v inputs, 12 low level outputs Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v DC measuring inputs v In-built output monitoring and recording function v Can be upgraded to support the test of IEC61850 v complied relay
POM2-6143 Universal Test System
TD series DC Current Tester
v 6×15A,4×300V
v TD series testing equipment consists of control
v 8 binary inputs and 8 binary outputs, 12 low level
outputs v Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v DC measuring inputs v Support IEC61850 testing
PW636i Universal Test System
unit and DC high current output unit. It outputs 02000A/0-4000A DC with the accuracy of 0.1% high accuracy DC current used in HVDC convertor station and testing DC current transformer characteristics.
T200A Universal Tester 1×250Aac, 1×20A ac/dc, 1×200mA ac/dc v 1×500Vac, 1×120V ac/dc, 1×300Vdc v Auxiliary DC (0-240V) v 2 binary inputs and 1 binary outputs v v In-built voltmeter and ammeter v Long output time: 120s at 250A
v 6×32A,4×300V v 8 binary inputs and 8 binary outputs, 4 counter
inputs, 12 low level outputs Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v DC measuring inputs v In-built output monitoring and recording function v Can be upgraded to support the test of IEC61850 v complied relay
FT 3000 Power Filter Characteristic Tester Precisely v
POM2-3243 Universal Test System 3×20A,4×300V v 8 binary inputs and 8 binary outputs, 12 low level v outputs Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v DC measuring inputs v Support IEC61850 testing v
PW336i Universal Test System 6×15A,4×150V v 8 binary inputs and 4 binary outputs v Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v In-built output monitoring and recording function v Can be upgraded to support the test of IEC61850 v
and automatically complete power filter amplitude frequency and phase frequency characteristic measurement Automatically measure power filter by parameters of v reactor, capacitor and resistor v Compensate and measure capacitor group unbalanced current 0.01 mA—10 mA
NF801 Intelligent Relay Tester 8 Fiber Optical Ports v Receiving and sending IEC61850-9-1/2 and v IEC60044-7/8 Measuring received fiber optical power v IEEE 1588 synchronization v GPS Synchronization interface v IRIG-B code interface v v 12 independent Low level output
complied relay
S40A Universal Test System
NS601 Handheld Digital Signal Analyzer
v 3×40A,3×150V
Standard: v IEC61850-9-1 signal Samples v v IEC61850-9-2/LE signal samples v IEC61850 GOOSE signal IEC60044-7/8 optical serial signal v
Auxiliary DC (24V, 110V, 220V) v 4 binary inputs and 1 binary outputs v
PW466i Universal Test System
Local control with LCD display v
6×20A,6 ×150V v 8 binary inputs and 4 binary outputs v Adjustable threshold for binary inputs v Auxiliary DC (0-300V) v In-built output monitoring and recording function v Can be upgraded to support the test of IEC61850 v
Amplifier for Real Time Digital Simulator v PA series amplifiers are specially designed for power
network real time simulation applications,which requires large power output,high accuracy even at high current output for all kinds of load.It can be used together with RTDS to compose a complete power network real time dynamic simulation system.
complied relay
03
04
6-Phase Relay Testing System
6-Phase Relay Testing System
PW460 Universal Test System
PW636i Universal Test System Specifications
Voltage generators Setting range 4-phase ac(L-N) 1-phase ac(L-L) dc (L-N)
4 × 0 ~ 300V 1 × 0 ~ 6 00V 4 × 0 ~ ±300V
Power 4- phase ac(L-N)
4 × 75VA typ., at 300V 4 × 50VA guar., at 300V 3- phase ac(L- N) 3 × 100VA typ., at 300V 3 × 85VA guar., at 300V 1- phase ac(L-L) 1 × 200VA typ., at 600V 1 × 170VA guar., at 600V dc (L-N) 4 × 100 W at ± 300 V Accuracy error < 0.0 8 % rd .+0. 02 % rg .guar. error < 0.0 2 % rd .+0. 01 % rg .typ. 300V Ranges Resolution 10mV for 300Vac Distortion < 0.05 % typ. (< 0.1 % guar.)
Current generators Setting range 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) dc(L-N) dc(6L-N) Power 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) 1-phase AC(L-L) Max compliance Voltage(L-N)(L-L) dc(L-N) dc(6L-N)
6×0~15A 3×0~30A 1×0~90A 6×0~±10A 1×0~±60A
Auxiliary dc supply
6×150VA 3×240VA 1×450VA 1×450VA
at 15A at 30A at 90A at 30A
15Vpk/32Vpk 6×100W at ±10A 1×540W at ±60A
DC voltage measuring input
Voltage range Power Accuracy
0~ 300V Measuring range 88W at 110V, 176W at Accuracy 220V, 120W at 300V error < 0.1 % rg. typ. (<0.5 % rg. guar.) Input impedance
Power supply Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50 / 60Hz 45~65Hz
Binary inputs Group1 Number Input characteristics Sample rate Time resolution Max. measuring time Debounce/Deglitch time Counting function Galvanic isolation
Accuracy error < 0.0 8 % rd . + 0. 02 % rg .guar. error < 0.0 2 % rd . + 0. 01 % rg . t yp. Ranges 15A or 30A Resolution 1mA Distortion < 0.05 % typ. (< 0.1 % guar.)
DC,1~1000Hz dc~10.0 kHz ± 1ppm 0.001 Hz
0~ ± 10V error <0.02% rg . typ. (<0.05% rg . guar.) 100KΩ
DC current measuring input Measuring range Accuracy Input impedance
0~ ± 20mA error <0.02% rg . typ. (<0.05% rg . guar.) 50Ω
In-built monitoring and recording
currents and voltage outputs Monitoring 8 0~400Vdc threshold or Recording analog outputs, binary inputs/outputs status Mode real time monitoring, no external wiring is required potential free Recording length 16s 20kHz
50μs infinite 0~25ms < 3kHz at pulse width>150μs 8 galvaincally isolated
Binary inputs Group2
Low level outputs Setting range 12×0~10Vpk 1mA Max.output current error < 0.025 % typ. (< 0.07 % guar.)at 1~10Vpk Accuracy Resolution 250μV < 0.05 % typ. (< 0.1 % guar.) Distortion(THD+N) Connection 19 pin combination socket (rear side)
Number 4 IEC61850 upgrade Input characteristics 0~+5Vdc or dry contact Interpretation hardware is in-built. Please contact the supplier Sample rate 25kHz for options to activate the IEC61850 software support function Time resolution 40μs Max. measuring time infinite Environmental conditions Debounce/Deglitch time 0~25ms 0 ~+50ºC Operation temperature Max.counting frequency 25kHz -25 ~+70ºC Storage temperature 5~95% non - condensing Relative humidity Pulse width > 3μs IEC-61000-3-2/3 EMC (Emission) Threshold voltage 2V IEC 61000-4-2/3/4/5/6/11 EMC (Immunity) Voltage hysteresis 0.8V IEC 61010-1 Safety Max.input voltage +5V
Binary outputs, semiconductor
General Frequency Sine signal Transient signal Accuracy Resolution
Phase Binary outputs, relay Angle range - 360º~+360º Number 4 (front side) Accuracy Potential free relay contacts,software controlled <0.05º typ.,<0.1º guar.at 50/60Hz Type Break capacity ac Vmax: 300Vac /Imax: 8A /Pmax: 2000VA Resolution ± 0.001º Break capacity dc Vmax: 300Vdc /Imax: 8A /Pmax: 150W
Number Type Break capacity dc Update rate Imax
4 (rear side ) semiconductor Vmax: 300Vdc /Imax: 0.5A /Pmax: 150W 100 μ s 0.5 A
05
Others PC connection External amplifier interface Current booster interface GPS interface Ground Socket (earth) Weight Dimensions (W x H x D)
Ethernet,10M/100M Circular connector Circular connector DB9/TTL 4 mm banana socket; front side 20kg 360mm× 157mm× 367 mm
Voltage generators Setting range 4-phase ac(L-N) 1-phase ac(L-L) dc (L-N)
Accuracy Resolution
4×0~300V 1×0~600V 4×0~±300V
Power 4-phase ac( L- N)
4× 75VA typ., at 300V 4 × 50VA guar., at 300V 3- phase ac(L- N) 3 × 100VA typ., at 300V 3 × 85VA guar., at 300V 1-phase ac( L- L) 1 × 200VA typ., at 600V 1 × 170VA guar., at 600V dc (L-N) 4 × 100 W at ±300 V Accuracy error < 0.0 8 % rd .+ 0. 02 % rg . guar., at 0~ 30 0 V error < 0.0 3 % rd .+ 0. 01 % rg . typ., at 0~ 30 0 V Ranges 300V Resolution 10mV for 300Vac Distortion < 0.05 % typ., (< 0.1 % guar.)
Current generators Setting range 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) dc(6L-N) Power 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) 1-phase DC(6L-N)
6×0~32A 3×0~64A 1×0~180A 1×0~±180A 6×450VA typ. at 32A 6×400VA guar. at 32A 3×800VA typ. at 64A 3×700VA guar. at 64A 1×1200VA typ. at 180A 1×1000VA guar. at 180A 1×1400W typ. at 180A 1×1000W guar. at 180A
Max compliance Voltage(L-N)(L-L) Accuracy
Ranges Resolution Distortion
21Vpk/42Vpk
error < 0.15 % rd .+ 0. 05 % rg . guar., at 0~ 32A error < 0.0 5 % rd .+0. 02 % rg . typ., at 0~ 32A 32 A 1mA < 0.05 % typ. (< 0.1 % guar.)
General Frequency Sine signal Transient signal
Specifications
DC,1~1000Hz dc~10.0 kHz
±1ppm 0.001 Hz
Binary outputs, relay
Number 4 (front side) Type Potential free relay contacts,software controlled Phase Break capacity ac Vmax: 300Vac /Imax: 8A /Pmax: 2000VA - 360º~+360º Angle range Break capacity dc Vmax: 300Vdc /Imax: 8A /Pmax: 150W <0.05ºtyp.,<0.1°guar.at 50/60Hz Accuracy ± 0.001° Resolution
DC voltage measuring inputs
Measuring range Accuracy
Auxiliary dc supply Voltage range Power Accuracy
0~ 300V 88W at 110V, 176W at Input impedance 220V, 90W at 300V error < 0.1 % rg. typ. (<0.5 % rg. guar.)
0~ ± 10V error <0.02% rg . typ. (<0.05% rg . guar.) 100KΩ
DC current measuring inputs
Power supply Nominal input voltage Permissible tolerance Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
Measuring range Accuracy Input impedance
0~ ± 20mA error <0.02% rg . typ. (<0.05% rg . guar.) 50Ω
In-built monitoring and recording
Monitoring currents and voltage outputs Binary inputs Group1 Recording analog outputs, binary inputs/outputs status Number 8 Mode real time monitoring, no external wiring is required Input characteristics 0~400Vdc threshold or Recording length 16s potential free Sample rate 20kHz Low level outputs Time resolution 50μs Setting range 12×0~10Vpk Max. measuring time infinite 1mA Max.output current Debounce/Deglitch time 0~25ms Accuracy error < 0.025 % typ. (< 0.07 % guar.)at 1~10Vpk Counting function < 3kHz at pulse Resolution 250μV width>150μs < 0.05 % typ. (< 0.1 % guar.) Distortion(THD+N) Galvanic isolation 8 galvanically isolated 19 pin combination socket (rear side) Connection
Binary inputs Group2 4 Number 0~+5Vdc or dry contact Input characteristics 25kHz Sample rate 40μs Time resolution infinite Max. measuring time 0~25ms Debounce/Deglitch time 25kHz Max.counting frequency > 3μs Pulse width 2V Threshold voltage 0.8V Voltage hysteresis +5V Max.input voltage
Binary outputs, semiconductor Number Type Break capacity dc Update rate Imax
IEC61850 upgrade Interpretation hardware is in-built. Please contact the supplier for options to activate the IEC61850 software support function
Environmental conditions Operation temperature Storage temperature Relative humidity EMC (Emission) EMC (Immunity) Safety
Others
PC connection 4 (rear side) External amplifier interface semiconductor Current booster interface Vmax: 300Vdc /Imax: GPS interface 0.5A /Pmax: 150W Ground Socket (earth) 100 μs Weight Dimensions (W x H x D) 0.5 A
06
0~+50 º C -25~+70 º C 5~95% non - condensing IEC-61000-3-2/3 IEC 61000-4-2/3/4/5/6/11 IEC 61010-1
Ethernet,10M/100M Circular connector Circular connector DB9/TTL 4 mm banana socket; front side 20kg 360 mm× 157mm× 427 mm
6-Phase Relay Testing System
6-Phase Relay Testing System
PW336i Universal Test System
PW466i Universal Test System
Specifications Voltage generators Setting range 4-phase ac(L-N) 1- phase ac( L-L) dc (L-N)
Voltage generators 4 × 0~150V 1 × 0~300V 4 × 0~±150V
Power 4-phase ac(L-N) 4 × 45VA at 150V 3- phase ac(L-N) 3 × 60VA at 150V 1 × 100VA at 300V 1-phase ac(L-L) 4 × 40 W at ± 150 V dc (L-N) Accuracy error < 0.0 8 % rd .+0. 02 % rg . guar., at 0~ 15 0 V error < 0.04 % rd .+0. 01 % rg . typ., at 0~ 15 0 V Ranges 150V Resolution 5mV for 150Vac Distortion < 0.05 % typ., (< 0.1 % guar.)
Ranges Resolution Distortion
error < 0.05 % rd .+ 0. 02 % rg . typ., at 0~ 15A 15A or 30A 1mA < 0.05 % typ. (< 0.1 % guar.)
Frequency Sine signal Accuracy Resolution
DC,1~2000Hz ± 1ppm 0.001 Hz
Phase Angle range - 360º~+360º Accuracy <0.05º typ.,<0.1º guar.at 50/60Hz Resolution ±0.001º
Auxiliary dc supply Voltage range Power
Accuracy
6×150VA at 15A 3×240VA at 30A 1×450VA at 90A 1×450VA at 30A 15Vpk/32Vpk 6×100W at ±10A 1×480W at ±60A error < 0.1 5 % rd .+ 0. 05 % rg . guar., at 0~ 15A
Break capacity dc
Vmax: 300Vac /Imax: 8A /Pmax: 2000VA Vmax: 300Vdc /Imax: 8A /Pmax: 150W
Monitoring currents and voltage outputs Recording analog outputs, binary inputs/outputs status Mode real time monitoring, no external wiring is required Recording length 16s
Power supply
Setting range 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) dc(L-N) dc(6L-N)
6×0~15A 3×0~30A 1×0~90A 6×0~±10A 1×0~±60A
Break capacity ac
In-built monitoring and recording
General
Current generators
Power 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) 1-phase AC(L-L) Max compliance voltage(L-N)(L-L) dc(L-N) dc(6L-N)
Specifications
0~ 300V 88W at 110V, 176W at 220V, 120W at 300V Accuracy error < 0.1 % rg. typ. (<0.5 % rg. guar.)
Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
Interpretation hardware is in-built. Please contact the supplier for options to activate the IEC61850 software support function
Binary inputs
Environmental conditions
8 Number Input characteristics 0~400Vdc threshold or potential free 50μs Time resolution infinite Max. measuring time Debounce/Deglitch time 0~25ms Counting function < 3kHz at pulse width>150μs
Operation temperature Storage temperature Relative humidity EMC (Emission) EMC (Immunity) Safety
07
6 × 0~150V 1 × 0~300V 6 × 0~±150V
Power 6-phase AC( L- N) 6 × 30VA at 150V 3- phase AC( L- N) 3 × 60VA at 150V 1 × 100VA at 300V 1-phase AC(L-L) 6 × 40 W at ± 150 V dc (L-N) Accuracy error < 0.0 8 % rd .+ 0. 02 % rg . guar., at 0~ 15 0 V error < 0.04 % rd .+0. 01 % rg . typ., at 0~ 15 0 V Ranges 150V Resolution 5mV for 150Vac Distortion < 0.05 % typ., (< 0.1 % guar.)
Current generators
IEC61850 upgrade
0~+50ºC -25~+70ºC 5~95% non - condensing IEC-61000-3-2/3 IEC 61000-4-2/3/4/5/6/11 IEC 61010-1
Setting range 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N) dc(L-N) dc(6L-N) Power 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(6L-N)
Others
PC connection Binary outputs, relay GPS interface Number 4 Ground Socket (earth) Type Potential free relay contacts, Weight software controlled Dimensions (W x H x D)
Binary outputs, relay Accuracy
Setting range 6-phase AC( L-N) 1-phase AC( L-L) dc (L-N)
Ethernet,10M/100M DB9/TTL 4 mm banana socket; front side 20kg 360mm × 157mm× 367 mm
1-phase AC(L-L) Max compliance voltage(L-N)(L-L) dc(L-N) dc(6L-N)
6×0~20A 3×0~40A 1×0~120A 6×0~±20A 1×0~±120A 6×180VA typ., at 20A 6×150VA guar., at 15A 3×320VA typ., at 40A 3×240VA guar., at 30A 1×600VA typ., at 120A 1×450VA guar., at 90A 1×450VA typ., at 30A 15Vpk/32Vpk 6×100W at ±10A 1×480W at ±60A
Ranges Resolution Distortion
error < 0. 15 % rd .+ 0.05 % rg . guar., at 0~ 2 0 A error < 0.0 8 % rd .+ 0. 02 % rg . typ., at 0~ 2 0 A 20A or 40A 1mA < 0.05 % typ. (< 0.1 % guar.)
4 Potential free relay contacts, software controlled
Break capacity ac Break capacity dc
Vmax: 300Vac /Imax: 8A /Pmax: 2000VA Vmax: 300Vdc /Imax: 8A /Pmax: 150W
In-built monitoring and recording
General Frequency Sine signal Transient signal Accuracy Resolution
Number Type
DC,1~2000Hz DC~10.0 KHz ± 1ppm 0.001 Hz
Phase Angle range - 360º~+360º Accuracy <0.05º typ.,<0.1º guar.at 50/60Hz Resolution ±0.001º
Auxiliary dc supply 0~ 300V 88W at 110V, 176W at 220V, 120W at 300V Accuracy error < 0.1 % rg. typ. (<0.5 % rg. guar.) Voltage range Power
Binary inputs 8 Number Input characteristics 0~400Vdc threshold or potential free 100μs Time resolution infinite Max. measuring time Debounce/Deglitch time 0~25ms Counting function < 3kHz at pulse width>150μs
08
Monitoring currents and voltage outputs Recording analog outputs, binary inputs/outputs status Mode real time monitoring, no external wiring is required Recording length 16s
Power supply Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
IEC61850 upgrade Interpretation hardware is in-built. Please contact the supplier for options to activate the IEC61850 software support function
Environmental conditions Operation temperature Storage temperature Relative humidity EMC (Emission) EMC (Immunity) Safety
0~+50ºC -25~+70ºC 5~95% non - condensing IEC-61000-3-2/3 IEC 61000-4-2/3/4/5/6 IEC 61010-1
Others PC connection GPS interface Ground Socket (earth) Weight Dimensions (W x H x D)
Ethernet,10M/100M DB9/TTL 4 mm banana socket; front side 20kg 360mm × 157mm× 367mm
6-Phase Relay Testing System
6-Phase Relay Testing System
POM2-6143 Universal Test System
L336i Universal Test System
Specifications
Specifications
Frequency Sine signal
1Hz~1000Hz <1mHz (20 Hz ~65Hz) <10mHz (65 Hz ~450Hz) <20mHz (450 Hz ~1000Hz) 0.001Hz th nd Can simulate2 -20 harmonic or DC
Accuracy
Resolution Output characteristic
Voltage generators Setting range
Binary outputs, relay
Phase angle Range Accuracy Resolution
0 ~359. 9° ±0.1° 0.1°
AC Current outputs Control
DC current outputs Range Accuracy Resolution Output power Operation indication
Range Accuracy
3×0A~10A ±5mA (0.05A~1A) ±0.5% (1A~10A) 1mA (0.2A~10A) 300W (30A 10V) Overload, distortion, open circuit, over heat
Resolution Output power
Independent control of amplitude, frequency and phase angle 6×15Aor 3×30A ±1mA (<0.5A), ±0.1% (0.5A~20A) ±0.2% (20A~30A) 1mA (0.1A~10A), 10mA (10A~30A) ≥210VA (at 30A, L-N) ≥105VA (at 15A, L-N) ≥420VA (at 30A, L-L)
DC voltage outputs Range Accuracy Resolution Output power Operation indication
Pmax(VA)
4×0V~150V ±10m V (0.05 V~2 V) ±0.5% (2V~150V) 1mV (0.2V~2V);10mV (2V~150V) 40W at 150V Overload, distortion, open circuit, over heat
Synchronization time between current and voltage outputs
210
Time resolution Max. measuring time Debounce/Deglitch time Counting function
≤10μs Output response time Distortion (THD%) Frequency range Frequency- Amplitude chacteristic Output time
Operation indication
<100µs ≤0.5% (0.5A~Imax) 1Hz ~1kHz ≤±0.1%~±0.5% (1Hz~1kHz) continuous (<10A/channel) >70s (<10~20A/channel) >15s (<20~30A/channel) Overload, distortion, open circuit, over heat
Pmax(VA)
Interpretation hardware is in-built. Please contact the supplier for options to activate the IEC61850 software support function
Power Supply
Pmax
Output characteristic
110-240Vac 50/60Hz 6.3A
Others PC connection GPS interface Ground Socket (earth) Dimension ( WXHXD) Weight
I out(A)
Control Fourth voltage (Uz) Independent control of amplitude, frequency and phase angle Can be set as zero sequence voltage, line voltage, or any value Range 4×150V Accuracy ±2mV (0.05V~2V), ±0.1% (2V ~150V) Resolution 1mV (0.2V~10V), 10mV (10V~150V) Output power ≥60VA (at 150V)
IEC61850 upgrade
Input Frequency Max. current
30
AC Voltage outputs
4 Potential free relay contact (auto detection) Vmax:250V(AC)/Imax:0.5A Vmax:250V(DC)/Imax:0.5A
Output response time <100µs ≤0.5% (2V~150V) Distortion (THD%) Frequency range 1Hz ~1kHz Frequency- Amplitude chacteristic ≤±0.1%~±0.5% (1Hz~1kHz) Continuous at rated output condition Output time Overload, distortion, short circuit, over heat Operation indication
Ethernet,10M/100M DB9/TTL 4 mm banana socket; front side 256mm × 110mm× 395 mm 8.8 kg
09
Power
4 (1-4) Potential free relay contacts,software controlled Vmax: 300Vac /Imax: 8A /Pmax: 2000VA Vmax: 300Vdc /Imax: 8A /Pmax: 150W
Binary outputs, semiconductor Number Type Break capacity
4 (5-8) semiconductor Vmax: 300Vdc /Imax: 0.5A /Pmax: 150W 100μs 0.5A
Update rate Imax
Auxiliary dc supply Voltage range Power Accuracy
0~300V 88W at 110V , 110W at 220V , 110W at 300V error <0.1% rg. typ. (<0.5% rg. guar.)
Measuring range Accuracy Input impedance 15
8 0~400Vdc threshold or potential free 50μs infinite 0~25ms < 3kHz at pulse width>150μs
Number Type Break capacity ac Break capacity dc
DC voltage measuring inputs 105
Binary outputs Number Characteristic Break capacity ac Break capacity dc
Pmax
Output characteristic
Binary inputs Number Input characteristics
4-phase ac (L-N) 1-phase ac (L-L) dc (L-N)
0 ~ ±10V error <0.02% rg. typ. (<0.05% rg. guar.) 100KΩ
DC current measuring inputs Measuring range Accuracy error Input impedance
0 ~ ±20mA <0.02% rg. typ. (<0.05% rg. guar.) 50Ω
Low level outputs Setting range Max.output current Accuracy Resolution Distortion(THD+N) Connection
12×0~10Vpk 1mA error < 0.025 % typ. (< 0.07 % guar.) at 1~10Vpk 250μV < 0.05 % typ. (< 0.1 % guar.) 14 pin combination socket
Power supply Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
Environmental conditions Operation temperature Storage temperature Relative humidity EMC (Emission) EMC (Immunity) Safety
0 ~ +50°C -25~+70°C 5~95% non - condensing IEC61000-3-2/3 IEC61000-4-2/3/4/5/6/11 IEC 61010-1
4-phase ac (L-N) 3-phase ac (L-N) 1-phase ac (L-L) dc (L-N) Accuracy error Ranges Resolution Distortion
4×0 ~ 300V 1×0~600V 4×0~300V 4 × 75VA typ., at 300V 4 × 50VA guar., at 300V 3 × 100VA typ., at 300V 3 × 85VA guar., at 300V 1 × 200VA typ., at 600V 1 × 170VA guar., at 600V 4 ×100 W at ±300 V < 0.08 % rd. + 0.02 % rg. guar., at 0~300 V < 0.02 % rd. + 0.01 % rg. typ., at 0~300 V 300V 10mV < 0.05 % typ. (< 0.1 % guar.)
Current generators Setting range 6-phase AC (L-N) 3-phase AC (2L-N) 1-phase AC (3L-3L) 1-phase AC(6L-N) dc (L-N) dc (6L-N)
6×0 ~ 15A 3×0~30A 1×0~30A(10A/Phase) 1×0~90A 6×0~10A 1×0~60A
power 6-phase AC(L-N) 3-phase AC(2L-N) 1-phase AC(3L-3L) dc(L-N) dc(6L-N) Max compliance voltage(L-N)(L-L) Accuracy error Ranges Resolution Distortion
6×105VA at 15A 3×210VA at 30A 1×420VA at 30A 6×100W at 10A 600W at 60A 10Vpk/20Vpk < 0.08 % rd . + 0.02 % rg. guar., at 0 ~ 15A < 0.02 % rd . + 0.01 % rg. typ., at 0 ~ 15A 15A or 30A 1mA < 0.05 % typ. (< 0.1 % guar.)
General Frequency Sine signal Transient signal Accuracy Resolution
1 ~ 1000Hz dc~10.0 kHz ±1ppm 0.001 Hz
Phase Angle range Accuracy Resolution
Others
Binary inputs
PC connection Ethernet,10M/100M Low level outputs interface Circular connector GPS/IRIG-B interface Circular connector IEC61850 Goose and sampled values Optical interface (Optional) Ground Socket (earth) 4mm banana socket 14.5kg without control panel, 16kg with control panel Weight Dimensions 390x287x214mm ( WxDxH )
Number Input characteristics T ime resolution Max. measuring time Debounce/Deglitch time Counting function
10
-360° ~ +360° <0.05° typ., <0.1° guar. at 50/60Hz ±0.001° 8 0-400Vdc or ac (peak) with adjustable threshold or potential free 50μs infinite 0~25ms < 3kHz at pulse width>150 μs
3-Phase Relay Testing System
3-Phase Relay Testing System
POM2-3243 Universal Test System Specifications Voltage generators Setting range 4-phase ac(L-N) 1-phase ac(L-L) dc(L-N)
Binary outputs, relay Number Type Break capacity ac Break capacity dc
Power
4 (1-4) Potential free relay contacts,software controlled Vmax: 300Vac /Imax: 8A /Pmax: 2000VA Vmax: 300Vdc /Imax: 8A /Pmax: 150W 4 (5-8) semiconductor Vmax: 300Vdc /Imax: 0.5A /Pmax: 150W 100μs 0.5A
Number Type Break capacity Update rate Imax
Auxiliary dc supply 0~300V 88W at 110V , 110W at 220V , 110W at 300V error <0.1% rg. typ. (<0.5% rg. guar.)
DC voltage measuring inputs(Optional) Measuring range Accuracy Input impedance
4-phase ac(L-N)
4× 75VA typ., at 300V 4 × 50VA guar., at 300V 3× 100VA typ., at 300V 3× 85VA guar., at 300V 1 × 200VA typ., at 600V 1 × 170VA guar., at600V 4 ×100 W at ±300 V < 0.08 % rd. + 0.02 % rg. guar., at 0~300 V < 0.02 % rd. + 0.01 % rg. typ., at 0~300 V 300V 10mV < 0.05 % typ. (< 0.1 % guar.)
3-phase ac(L-N) 1-phase ac(L-L)
Binary outputs, semiconductor
Voltage range Power Accuracy
4×0 ~ 300V 1×0~600V 4×0~300V
0 ~ ±10V error <0.02% rg. typ. (<0.05% rg. guar.) 100KΩ
dc (L-N) Accuracy error Ranges Resolution Distortion
Current generators Setting range 3-phase AC(L-N) 1-phase AC(3L-N) 1-phase AC(L-L) dc(L-N) dc(3L-N)
3×0 ~ 20A 1×0 ~ 60A 1×0~20A 3×0~10A 1×0~30A
DC current measuring inputs(Optional)
power
Measuring range Accuracy error Input impedance
3-phase AC(L-N) 1-phase AC(L-L) 1-phase AC(3L-N) dc(L-N) dc(3L-N)
3×140VA at 20A 1×280VA at20A 1×280VA at 60A 3×100W at 10A 1×300W at 30A
Max compliance voltage(L-N)(L-L) Accuracy error
10Vpk/20Vpk
Low level outputs(Optional) Setting range Max.output current Accuracy Resolution Distortion(THD+N) Connection
0 ~ ±20mA <0.02% rg. typ. (<0.05% rg. guar.) 50Ω
12×0~10Vpk 1mA error < 0.025 % typ. (< 0.07 % guar.) at 1~10Vpk 250μV < 0.05 % typ. (< 0.1 % guar.) 14 pin combination socket
Power supply Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
Environmental conditions Operation temperature Storage temperature Relative humidity EMC (Emission) EMC (Immunity) Safety
0 ~ +50°C -25~+70°C 5~95% non - condensing IEC61000-3-2/3 IEC61000-4-2/3/4/5/6/11 IEC 61010-1
Others PC connection (Optional) Ethernet,10M/100M Low level outputs interface (Optional) Circular connector GPS/IRIG-B interface Circular connector IEC61850 Goose and sampled values Optical interface (Optional) Ground Socket (earth) 4mm banana socket 13kg without control panel, 14.5kg with control panel Weight Dimensions 390 × 287× 194 mm (W × H × D)
Ranges Resolution Distortion
< 0.08 % rd . + 0.02 % rg. guar., < 0.02 % rd . + 0.01 % rg. typ., 20A 1mA < 0.05 % typ. (< 0.1 % guar.)
S40A Universal Test System Specifications Voltage generators Setting range 3- phase ac(L- N) 1- phase ac( L- L) dc (L-L)
Power 3- phase ac( L- N) 1-phase ac( L-L) dc (L-N) Accuracy Ranges Resolution Distortion
3 × 60VA at 150V 1 × 100 VA at 300V (two generators in series) 4×48W at ± 180 V < 0.16% rd .+ 0. 04 % rg . guar., < 0.0 8 % rd .+ 0. 02 % rg . typ., 150V 10mV 0.1 %
Setting range Model 3-phase AC(L-N) 1-phase AC(L-N) dc (L-N) Low grade 1-phase AC(L-N)
S40A 3×40A 1×120A 1×10A 1× 0...200mA 3VA at 200mA 1 × 0...200mA 4W at 200mA
Frequency Sine signal Transient signal Accuracy Resolution
1 ~ 1000Hz dc~10.0 kHz ±1ppm 0.001 Hz
Phase Angle range Accuracy Resolution
-360° ~ +360° <0.05° typ., <0.1° guar. at 50/60Hz ±0.001°
Power Model 3-phase AC(L-N) 1-phase AC(L-N) dc (L-N) Accuracy
Binary inputs Number Input characteristics T ime resolution Max. measuring time Debounce/Deglitch time Counting function
11
8 0-400Vdc or ac (peak) with adjustable threshold or potential free 50μs infinite 0~25ms < 3kHz at pulse width>150 μs
Harmonics Distortion Resolution
S40A 3×75VA at 5A 3×520VA at 40A 90W at 10A < 0.16 rd .+0. 04 % rg. guar., at 0~30A < 0.0 8 rd .+0. 02 % rg. typ., at 0~30A 2nd 0.1% 5mA (1mA,low grade)
General Frequency Range
0.002% 0.002 Hz
Phase Angle range Accuracy Resolution
0 ... 360º 0.2º 0.1º
Auxiliary dc supply Voltage range Power
0, 24V, 110V , 220V 110W at 220V, 55W at 110V, 12W at 24V
Binary inputs Number Input characteristics Max. measuring time Accuracy Resolution
Current generators
dc(L-N)
General
3×0. . .150V 1×0. . .300V 1×0... ± 300V
Accuracy Resolution
DC 40 to 100Hz
4 0-+/-250Vdc or potential free 999999.999 s 1ms±0.1% 1ms
Binary output,relay Number Type Break capacity ac Break capacity dc
1 Potential free relay contacts, software controlled Vmax: 300Vac /Imax: 1A /Pmax: 125VA Vmax: 300Vdc /Imax: 1A /Pmax: 60W
Power supply Nominal input voltage Permissible input voltage Nominal frequency Permissible frequency
110~240Vac 90~260Vac 50/60Hz 45~65Hz
Environmental conditions Operation temperature 0 ...+50°C Storage temperature -25 ...+70°C Relative humidity 5...95% non - condensing EMC (Emission) IEC-61000-3-2/3 EMC (Immunity) IEC 61000-4-2/3/4/5/6/11 Safety IEC 61010-1
Others PC connection USB Ground Socket (earth) 4 mm banana socket; front side Weight 18kg Dimensions (W x H x D) 360mm × 157mm× 367 mm
12
Software
Software
Powertest introduction l PowerTest software provides comprehensive functions to
manage the test work. l General software package contains the common used
modules which can meet the general relay test requirement. l Advanced software package contains the optional modules
for specific test purpose.
Software Classification Basic package
Protection package
Basic package is included
Distance (Z-Phi)
Check zone settings (Z-Phi) of impedance relay
Distance (R-X)
Check zone settings (R-X) of impedance relay
Time Inversed Current
Check time inversed current relay based on IEC standard
Time Inversed Voltage
Check time inversed Voltage relay based on IEC standard
Directional
Check directional current relay
Differential (6I)
Check IR/ID characteristic of differential relay with 6 current output and harmonic block
Differential (3I)
Check IR/ID characteristic of differential relay with 3 current output and harmonic block
Frequency Relay
Check under frequency relay
Voltage Relay
Check under voltage rela
U,I,T Relay (AC)
Check ac type auxiliary relay and time relayy
U,I,T Relay (DC)
Check dc type auxiliary relay and time relay
Auto-Reclosing
Check Auto-Reclosing function
Advanced package
Basic and Protection packages are included
QuickTest (4V, 3I)
Manually or automatically control over 4 voltage and 3 current sources
RX Characteristic Sweep
Search out the boundary of impedance relay
QuickTest (4V, 6I)
Manually or automatically control over 4 voltage and 6 current sources
Advanced Differential (3I)
Search out the IR/ID curve of differential relay with 6 current output and harmonic block
QuickTest (VL-L, 3I)
Manually or automatically control over L-L voltages, and 3 current sources
Advanced Differential (6I)
Search out the IR/ID curve of differential relay with 3 current output and harmonic block
Manually or automatically control over sequence voltages, including positiv esequence, negative sequence and zero sequence voltages
Synchronizer
Test synchronizer device
QuickTest (Sequence)
Advanced TransPlay (4U, 3I)
Edit and play back COMTRADE format file
QuickTest (Power)
Manually or automatically control over output power
Special
QuickTest (Z, I Const)
Manually or automatically measure Z with current is constant
Power Swing Simulation
Simulate the power swing with pre-set dz/dt
QuickTest (Z, V Const)
Manually or automatically measure Z with voltage is constant
Energy Meter
Check energy meters (PACB108 scanning head is required)
QuickTest (Z, Zs Const)
Manually or automatically measure Z with Zs is constant
Transducer
Check Transducers
Ramp (3I)
Realize the ramping for different quantities in 3 current mode
High Burden Relay
Test high burden relay (Phpc01 accessory is required)
Time
Used to check the tripping time
IEC61850
State Sequence ( 4V,3I )
Edit more complicated state sequences in 3 current mode
QuickTest(IEC)
GOOSE configuration, interpretation and publishing
State Sequence ( 4V,6I )
Edit more complicated state sequences in 6 current mode
State Sequence(IEC)
Edit more complicated state sequence based on IEC61850
Harmonic
Edit harmonic components to the output
New Modules
Can be downloaded from the website after registered
CB Operation
Simulate the whole test scheme
Loss of Excitation
Check loss of excitation relay
TransPlay (4V, 3I)
Play back COMTRADE format file
QuickTest(Harmonic)
Manually or automatically output 2nd to 20th harmonic source
Non-eletricity check
Manual check module to be included in a test plan
Transplay(6V,6I)
Play back COMTRADE format file
0513
14
Software
Software
PONOVO Template Service
PowerTest Relay Test Software Auto-reclosing
Start Page
Auto-reclosing module is the specific module which is
PONOVO provides relay test templates based on relay model from different relay manufactures. With the use of template the relay test work can be simplified greatly. Each relay test template is one independent file which can be
applied to test the reclose function. This module can
opened in PowerTest relay test software. Registered users can
realize that relay automatic reclosing with checking the
download the relay templates from PONOVO website. The
difference between system and unit, checking the
following are some typical relay templates for some popular
synchronization setting, reclose set time checking and
relays from relay manufactures.
automatic evaluating of testing results.
Differential Differential module is suitable for use the 6 output current channels' relay tester, which is applied on transformer, generator and bus bar etc. differential protection equipment test. Because of adopting the 6 currents output, it realizes the two sides three phases
State Sequence
test between relay tester and relay equipment.
In the State-Sequence module, the relay tester can output multiple continuous state sequences. This module can help user to do customized test.
Inverse time overcurrent This module realizes the directional over-current test and non-directional over-current test. This module also include: testing positive sequence, negative sequence
Power swing
and zero sequence instantaneous time over-current,
Power swing module is applied to simulate the power
over-heat protection inverse time over-current or the
system swing and test the generator losing
customized “Current/Time” operation characteristic.
synchronization and normal network splitting equipment.
LZ96 REG100 REL511 REL531 MSOC RAZFE REB670 REC670 REF542 REG216 REL300 REL316 REL350 REL352 REL356 REL511 REL512 REL521 REL531 REL561 REL650 REL670 RET521 RET670 REZ1 SPAC150C SPAC310C TPU2000R
CAG17 CAG37 CDD CDG 11 CTIG CTIGM CTMFM CTMM CTNM CTT CTTM CTU DIFB EAP3100-350 Generic Mho KBCH KCEU 141 241 KVFG LFZP LFZR LGPG MBCH MCGG MFVUM Micromho MVAPM MWTU Optimho P111 P115 P120 P121 P122 P123 P124 P125 P126
P127 P141 P142 P143 P144 P145 P241 P242 P243 P342 P343 P344 P345 P430 P437 P433 P435 P436 P438 P441 P442 P443 P444 P445 P521 P543 P544 P545 P546 P547 P631 P632 P633 P634 P642 P643 P645
P921 P922 P923 P940 P941 P942 P943 PPX PVMM Quadromho SKE SKD VAGM22 VAPM
SEPAM 10 SEPAM 80 SEPAM 2000 SEPAM S42 T20
Sr489 SR745 F650 SR750 GT60 D60 DLPD G30 L90 Ge345
SEL300 SEL351 SEL587 SEL311B SEL487B SEL487E SEL167 SEL411 SEL311C SEL311L SEL321 SEL421 SEL501 SEL587 SEL701 SEL751 SEL751A SEL787
7RW600 7SA6XX 7SA511 7SA513 7SA518 7SA519 7SA522 7SD5 7SD52 7SD63 7SJ61 7SJ63 7SJ80 7SJ600 7SL24 7SS52 7ST6 7UM61 7UM62 7UM512 7UM515 7UM516 7UT6xx 7UT51 7UT512 7UT6127VE61 7VE61 7VE63 ARGUS 1 DCD121A DCD125A
GRB100 GRD110 GRD140 GRD150 GRF100 GRL100 GRL150 GRT100 GRZ100
PCS-902 RCS-915 RCS-931 RCS-993 RCS-902 PCS-9611 PCS-902H PCS-931D PCS-9611C
MRA4 MRDT4 MRI4 MRM MRN
326GD
F_PRO L_PRO T_PRO
VAMP 255 VAMP 265
PCT210 ……
More Templates can be download from our website www.relaytest.com
0515
16
Single Phase Relay Tester
Primary Injection
Model T1000 Primar y Injection and Test Equipment
T200A Universal Tester Specifications
Features
High power AC current output (I1) Range Accuracy Output voltage Power Load time Output Time
0.2A~20A
10~250A ±0.5%
130V~100V 2000VA(20A) 250A 120s
10V~8V 2000VA(250A) 50A 3000s
High precision AC/DC current output (I3) Mode Range Accuracy Power(200mA) Frequency
<50A continuous
High power AC voltage output (U1) Range Accuracy Power Load time <1A : 1~3A :
10~500V ±0.5% 1200VA(400V) continuous Max 60min
Number Input characteristics Time resolution Max. measuring time
10~300V ±0.5% 750W(300V) < 1A >1 A continuous Max 60min
Number Type Break capacity AC Break capacity DC
20~240V ±1% 55W at 110V/110W at 220V continuous at 0.5A
AC/DC current output (I2) Mode AC output Range 0~20A Accuracy ±0.5% Power(20A) 200VA Frequency 20~100Hz Phase angle 0~360° Phase angle accuracy 0.5 ° Distortion 1A~20A <0.5% Transient response Load time 20A : 10A : <10A : Harmonic(2nd,3rd,5th,7th)accuracy
DC output 0~20A ±0.5% 200W — — — —
AC output 0~120V ±0.5% 60VA 20~100Hz 0~360° 0.5 ° <0.5% 500μs
1 Potential free relay contacts Vmax 250V AC / Imax 8A / Pmax 2000VA Vmax 250V DC/ Imax 8A / Pmax 150W
Specifications High power AC current output (I1) Range Output voltage Accuracy Power Load time
High power AC voltage output (U1)
Nominal input voltage Permissible tolerance Nominal frequency Permissible frequency
110/220Vac -20% ~+15% 50/60Hz 45~65Hz
0~600V AC/DC ±1%
Range Accuracy Power Load time
Range Accuracy
0~6A AC/DC ±1%
Certificates EMC (Emission) EMC (Immunity) Safety
DC output 0~120V ±0.5% 80W — — — — 500μs
IEC-61000-3-2/3 IEC 61000-4-2/3/4/5/6/11 IEC 61010-1
Others
17
- 5 ~ +45°C 5 ~95 %, non-condensing 23kg 440 mm×255mm×255 mm USB 4 mm banana socket; front side
10~300V ±0.5% 750W(300V) >1 A Output : < 1A Time : continuous Max 60min
Auxiliary DC voltage output (Aux Udc) Range Accuracy Power Load time
20~240V ± 1% 55W at 110V/110W at 220V continuous at 0.5A
Ammeter Range
Operation temperatur Operation humidity Weight Dimensions (W x H x D) PC connection Ground Socket (earth)
10~250V ±0.5% 750VA(250V) continuous
High power DC voltage output (Udc)
Ammeter
1%
7000VA 120s at 1000A
Range Accuracy Power Load time
Range Accuracy
500μs 60s 240s continuous
2A~50A, 50A~1000A 7V 20V ±0.5%
Power supply
Voltmeter
AC/DC voltage output (U2) Mode Range Accuracy Power(120V) Frequency Phase angle Phase angle accuracy Distortion 5V~120V Transient response
2 30~250V DC, or dry contact ±1ms(0.001~1s) ±0.1%(1~9999.999s) 9999.999s
Binary output
Auxiliary DC voltage output (Aux Udc) Range Accuracy Power Load time
DC output 0~200mA ±0.5% 3W —
Binary inputs
High power DC voltage output (Udc) Range Accuracy Power (300V) Load time Output : Time :
AC output 0~200mA ±0.5% 3VA 20~100Hz
2 minutes continuous output at1 000A Manual and Ramp control CT test functions available Independent Aux DC supply In-built multi-meter funtion Weight : 37kg
Accuracy
0~6A AC direct measurement 0~2000A AC with external CT ±1%
Binary inputs Number Input characteristics Time resolution Max. measuring time
2 ( auto detection ) ±30 ~ ±250Vdc, or potential free ±1ms ( 0.001~1s ) ±0 . 1% ( 1~9999.999s ) 9999.999s
Binary output Number Type Break capacity AC Break capacity DC
1 Potential free relay contacts Vmax 250V AC / Imax 5A / Pmax 1250VA Vmax 250V DC/ Imax 5A / Pmax 150W
Power supply Nominal input voltage frequency
220VAC±15% 45~65Hz
Others Operation temperature Operation humidity Weight Dimensions (W x H x D) PC connection Ground Socket (earth)
-5 ~ +50°C 5 ~95 %, non-condensing 37kg 260 ×330×500 mm USB 4 mm banana socket; front panel
Certificates Voltmeter Range Accuracy
0~600V AC/DC ± 1%
EMC (Emission) EMC (Immunity) Safety
18
IEC-61000-3-2/3 IEC 61000-4-2/3/4/5/6/11 IEC 61010-1
Handeheld Digital Signal Analyzer
Intelligent Relay Tester
NF801 Intelligent Relay Tester
NS601 Handheld Digital Signal Analyzer
Specifications Power Supply Main power Rated voltage Range
100V~240V (AC)
Rated frequency Resolution
250μV
Distortion(THD+N)
<0.1% 10~1000Hz
Transient signal
DC~10.0kHz
Accuracy
Cable type Status indication
RJ45 LED
100Base-FX (100Mbit, fiber-optic, full-duplex) Type 8 Number of ports Interface type LC Fiber-optic type 62.5/125μm(multimode fiber, orange) 1310nm Wave length Transmission distance >1km Status indication LED
30V~250V(DC) or empty comtact
Input characteristic
(automatic identification)
Sample frequency
10kHz
Time resolution
100μs 5
Max measurement time
1.50×10 s 5
±1ms(0.001s~1s) ±1%(1s~1.50×10 s)
Anti-shake time
Rear panel FT3 interface: for IEC60044-7/8 of FT3 communication
0ms~25ms
setting range (software)
Standard Number of ports Interface type Fiber-optic type Wave length Transmission distance
8 pairs input electrical isolation
Threshold impedance parameters (Dry Contact)
5kΩ…13kΩ
4 pairs of binary output (1-4) Empty contacts, regardless of polarity
Status indication
(software control) Vmax:250V(AC)/Imax:0.5A Vmax:250V(DC)/Imax:0.5A
IEC60044-7/8 8 ST 62.5/125μm(multimode fiber, orange) 850nm >1km LED
Low-level Signal Analog Output Signal amplitude
4 pairs of binary output (5-8)
Output channel
Fast contact output, the speed of response is 100us
Set range
Vmax:220V(AC)/Imax:0.5A Vmax:220V(DC)/Imax:0.5A
Max. output current Accuracy
19
Specifications
Category 5 twisted pair
Front panel fiber-optic communication interface: for IEC61850-9-1/2, GOOSE communication
±0.01°
8 pairs of binary inputs(A-H)
AC capacity DC capacity
1
<0.1°,50/60Hz
Binary
Type
10/100Base-TX(10/100Mbit, twisted-pair, automatic cross)
Interface type
0 to 359. 9°
Resolution
AC capacity DC capacity
1A(max)
Interface
Phase
Type
Current
Type
0.001Hz
Range of phase angle
Electrical isolation
40~60Hz
Ethernet communication port: for communication with the PC
0.002%(under frequency,error 1mHz)
Resolution
Timing error
50Hz
Range
Ethernet Communication Interface
Frequency Sinusoidal signal Accuracy
220V (AC)
12 AC:0~7.07Vrms DC:0~10V 1mA
Environment Conditions Altitude: ≤4000m Environment temperature:-10 ℃ ~50℃ Relative humidity: 5%~95% Atmospheric pressure: 86~106 kPa
PNS601 Support the signal detection and numerical analysis specification
Security Standard
IEC61850-9-1 signal samples IEC61850-9-2/LE signal samples IEC61850-8-1 signal (GOOSE) IEC60044-7 / 8 optical serial signal
GB / T 17626.2-1998 EMC testing and measurement techniques Electrostatic discharge immunity test 4 GB / T 17626.4-1998 EMC testing and measurement techniques Electrical fast transient burst immunity test 4 IEC 60255-21-1:1988 Electrical relays Part 21:
Interface parameters
Measuring vibration, shock, bump and seismic tests of relays
1 USB port (OTG) 2 100Mbps Optical Ethernet: 1310nm wavelength, receiving IEC61850-9-2 / 1 samples, GOOSE messages 2 ST Interface: 850nm wavelength, multimode fiber interface (supports 2.5M, 5M, 10M baud rate), receiving the FT3 signal.
and devices, Chapter One: Vibration tests (sinusoidal) Enclosure rating IP5X
Power Supply Battery: 6 18650 4400mAh large capacity lithium battery Charging power adapter: Input: 85V ~ 264V AC-DC Universal Output: DC19V, 4.74A Charging time: 2-3 hours full of need, the new battery charge time greater than 12 hours is recommended, at the first three times. full power working hours> 4 hours Standby time> 400 hours
Type of fiber optic cable 62.5/125um multi-mode fiber or 50/125um multi-mode fiber.
Other parameters Dimensions: 270mm (length) × 280mm (width) × 55mm (H) Display: 7 inch TFT color screen, 800 × 480 dot-matrix, liquid crystal display Keyboard: 64-bit rubber full-function keyboard Expansion slot: SD card slot Weight: 2 kg
Self-protection Built-in charging circuit and over-discharge protection circuit to ensure the reliability of rechargeable battery
0.07~7.07Vrms:Error<0.2% 0.02~0.07Vrms:Error<1%
20
DC current Tesing Equipment
CT/PT Testing System
PCT200 Series CT/PT Test System TD Series DC Current Tester
Specifications
Main Functions TD series testing equipment consists of control unit and DC high
Application Output voltage range
Specifications
Output current range Output power
PCT200i
PCT200Ai
Test M/P/TP type CT and PT
Test M/P/TP type CT and PT
0 ~ 120V
0 ~ 120V
0~5Arms(15A peak)
0~5Arms(15A peak)
0.0001~500VArms(1500VA peak)
0.0001~500VArms(1500VA peak)
35000:1 ~ 45000:5
35000:1 ~ 45000:5
±0.1%
±0.05%
45000V
45000V
current output unit. It outputs 0-4000A 0.1% high accuracy DC current used in HVDC convertor station and testing DC current transformer characteristics.
Easy panel control with LCD display and rotary encoder l l Manual and auto test by software
Ratio test range Ratio test accuracy Max. knee point voltage Burden test range Burden test accuracy Winding resistance test rang Winding resistance test accuracy
CT
Accuracy limiting factor (ALF)
0.05~200Ω ±0.05%±1mΩ Typ.
±0.1%±1mΩ Gur.
±0.1%±1mΩ Gur.
0.05~200Ω ±0.05%±1mΩ Typ.
±0.1%±1mΩ Gur.
Yes
Yes
Yes
Yes
Yes
Yes
Secondary time constant (Ts)
Yes
Yes
Unsaturated inductance (Lu)
Yes
Yes
Saturated inductance (Ls)
Yes
Yes
Excitation characteristic curve
Yes
Yes
10%(5%)error curve
Yes
Yes
Rated symmetrical short circuit current factor (Kssc) Accuracy limiting voltage (Eal)
Yes
Yes
Yes
Yes
Transient dimensioning factor (Ktd)
Yes
Yes
Peak instantaneous error (ε^ )
Yes
Yes
Composite error (εc )
Yes
Yes
±0.05%Typ. ±0.1%Gur.
±0.02% Typ.
±0.05% Gur.
1min Typ. 3min Gur.
1min Typ. 2min Gur.
0.1min
0.01min
Ratio
Yes
Yes
Polarity
Yes
Yes
Excitation characteristic
Yes
Yes
110-240Vac/50-60Hz (norminal) 90-260Vac/45-65Hz (permissible)
110-240Vac/50-60Hz (norminal) 90-260Vac/45-65Hz (permissible)
Main supply Operation temperature Relative humidity Dimensions Weight LCT display Operating system
-10°С~50°С
-10°С~50°С
≤90%,non-condensing
≤90%,non-condensing
470 x200 x 245mm (W×H×L)
470 x200 x 245mm (W×H×L)
14Kg
Specification TD2000A Output Range Port Voltage
TD4000A
0-2000A
0-4000A
5V
5V
DC Current Output Accuracy
0.1%
0.1%
Display Accuracy(rd)
0.2%
0.2%
Display Accuracy(rg)
0.05%
0.05%
Binary Input
2 Nos
2 Nos
Binary Output
1 No
1 No
Power Supply
3X380V ac, 22KVA
Weight
80 Kg
8.4 inch, color display
windows
windows
3X380V ac, 22KVA 110 Kg
14Kg
8.4 inch, color display
21
Multi high current connector for busbar l
0.05~200Ω ±0.05%±1mΩ Typ.
Instrument security factor (FS)
Phase displacement
Others
±0.1%±1mΩ Gur.
Remanence flux (Kr)
Ratio error
PT
0.05~200Ω ±0.05%±1mΩ Typ.
Output DC current wavefrom by USB port l
22
Power Filter Characteristic Tester
Power Filter Characteristic Tester
FT3000 Power Filter Characteristic Tester Main Functions
Other
Precisely and automatically complete power filter amplitude frequency and phase frequency characteristic measurement Automatically measure power filter by parameters of reactor, capacitor and resistor Compensate and measure capacitor group unbalanced current
Operation Off-line operation/External PC operation Conmunication Port USB/100M Ethernet Self Protection Overload/Overheat Report 1000 Reports
Impedance frequency, phase frequency, resistance, inductance and capacitance measurement.
Report LCD Dimension Weight
1000 Reports 8.4" TFT 364 mm×200 mm×475mm (W×H×D) 11.8kg
Unbalanced current measurement
0.01 mA—10 mA
Technical Parameters Signal source technical parameters Max output voltage Max output ccurrent Output frequency Frequency control step
f(5-3000Hz)
60V RMS 5A 5Hz—3000Hz 0.1 Hz
Output
Measurement system technical parameters Voltage Shortcut Key
Accuracyq
Mouse
Frequency Amplitude
Characteristic Graph
Key Board
0.5% 5Hz—3000Hz 0.2V—60V
Current Accuracy 0.5% Frequency 5Hz—3000Hz Amplitude 0.01 A—10 A Impedance measurement range 1Ω— 6KΩ Impedance measurement accuracy 0.5% Phase measurement accuracy 1° Inductance measurement range 2mH—10H 0.5% Inductance measurement accuracy 0.5% Capacitance measurement accuracy Capacitance measurement range 0.05uF-500uF Unbalance current measurement accuracy 0.5% Frequency output 100Hz—3000Hz Amplitude output 0.01 mA—10 mA
USB Port
23
Analog
FT3000 Power Filter Characteristic Tester
Double-tuned power filter
f(5-3000Hz) Output
Analog
0.01mA-10mA Compensation capacitance group
FT3000 Power Filter Characteristic Tester
24
Amplifier
Amplifier
Power Amplifier for Real Time Digital Simulation Panel mount type Optional Accessories Model
Output
Type
Notes
PAC2000B
1×200A RMS, 2400VA/phase
4U
Requires PAP-01 power unit
PAC60Bi
3×60A RMS, 800VA/phase
4U
3 phase 380VAC±10%,47-63Hz
PAC60Ci
6×30A RMS, 450VA/phase
4U
3 phase 380VAC±10%,47-63Hz
3×30A RMS, 450VA/phase ,4×120v RMS ,60VA/phase,
4U
3 phase 380VAC±10%,47-63Hz
4U
3 phase 380VAC±10%,47-63Hz
PA30Bi PA30Bi-H
3×30A RMS 450VA/phase,4×250v RMS 75VA/phase
PAD24
Binary input & output converter Number: 12; type: NC (300V,0.5A)
2U
PAP01
Three phase main power supply for PAC2000
Rack
3 phase 380VAC±10%,47-63Hz
PAP02
Three phase main power supply for PA series amplifiers
Rack
3 phase 380VAC±10%,47-63Hz
PSS01B
3U
220V AC
PSS02B
Circuit Breaker Simulator(two tripping coils, 2.5A)
3U
220V AC
Circuit Breaker Simulator(two tripping coils, 5A)
3U
220V AC
Control unit(limit high current output, protect relay under test, reference base signal for calibrating amplifier source)
2U
220V AC
PAV250Bi
6 x 250v RMS,75VA/phase
4U
3 phase 380VAC±10%,47-63Hz
PSS05B
PAV120Bi
6 x 120v RMS , 60VA/phase
4U
3 phase 380VAC±10%,47-63Hz
PAT01
IEC61850 simulating device (3 fiber outputs, 12 analog signal sampling, ±10V input, 12 analog signal recording, GOOSE interpretation and publishing, support IEC61850-9-1, IEC61850-9-2)
2U
220V AC
PWF-2T
Circuit Breaker Simulator(single tripping coil)
220V AC
Specifications Portable Type 3×PAC60Bi
PAC60Cip
PAC60Bip
PA30Bip
6×30A RMS, 210VA/phase
3×60A RMS,400VA/phase
3×30A RMS , 210VA/phase ; 4×120 v RMS , 60VA/phase
4U
4U
4U
110V or 220V AC
Configuration Example
110V or 220V AC
This customized panel mount type amplifier consists of: 3×PAC60Bi 1×PAT-01 1×PAD24 1×PSS01B 1×PDC1000
110V or 220V AC
1×PAT-01
PONOVO provides the customized amplifier service. 1×PAD24
PA30Bip-H
3×30A RMS , 210VA/phase; 4×250v RMS , 75VA/phase
4U
1×PSS01B
110V or 220V AC
1×PDC1000
PAV250Bip
6 x 250v RMS , 75VA/phase
3U
110V or 220V AC
PAV120Bip
6 x 120 v RMS , 60VA/phase
3U
110V or 220V AC
25
26
Accessories
Accessories
Standard accessories PW336i
PW466i
L336i
POM3243
POM6143
S40A
8
8
8
8
8
8
8
4
SAW0202
Color coded voltage cable with 4 mm safety plugs (2.5mm²×3m)
5
5
5
8
5
5
5
5
SAW0203
Color coded current cable with 4 mm safety plugs 2# (2.5mm²×0.5m)
4
4
4
4
4
4
4
SAW0204
Signal cable with 4 mm safety plugs1# (1mm²×3m)
4
4
4
4
4
4
SAW0205
Signal cable with 4 mm safety plugs2# (1mm²×0.5m)
4
4
4
4
4
SAW0206
Flexible terminal adapters for screw-typeterminals(2.5mm²×0.1m)
20
20
20
20
SAW0207
Flexible jumpers for paralleling current triples or shorting neutrals of binary inputs(2.5mm²×0.1m)
4
4
4
SAW0208
Crocodile clips(Jaws open 20mm)
8
8
SAW0209
U clamps 1# (for 4mm screws)
20
SAW0210
U clamps 2#(for 5mm-7mm screws)
10
SAW0211
SAW0009
SAW0018
Pin clamps
8
Power cord (250V/10A, 2m)
1
Earthing lead (2.5mm²×4m)
SAW0012
PC control cable (LAN)
SAW0011
Data cable (USB)
SAC0105
Transportation case
1
1
SAW0001
Color coded current cable(16mm²×3m)
4
SAW0002
Color coded voltage/current cable(2.5mm ² ×4m)
4
4
SAW0003
Signal cable(2.5mm ² ×4m)
4
4
4
SAW0004
Short Lead (2.5mm²×0.5m)
4
4
20
20
20
20
SAW0005
Crocodile clips(Jaws open 10mm)
4
8
4
4
4
4
4
SAW0006
Crocodile clips(Jaws open 20mm)
8
8
8
8
8
8
SAW0007
U clamps (Jaws open 10.5mm)
20
20
20
20
20
20
20
SAW0008
Pin clamps
8
10
10
10
10
10
10
10 SAW0009
Power cord (250V/10A, 2m)
1
SAW0018
Earthing lead (2.5mm²×4m)
SAW0011
Data cable (USB)
SAC0106
Transportation Case
8
1
1
1
8
1
1
1
8
1
1
1
8
1
1
8
1
1
8
1
1
27
1
1
1
1
1
4
6
4
4
2
8 1
1
1 1
1 1
1
1
2
8
1
1
T200A
PW636i
Color coded current cable with 4 mm safety plugs 1#(2.5mm²×3m)
T 10 00
PW460
SAW0201
Standard accessories
1
28
1
Accessories
Accessories
Optional Accessories Optional Accessories
SAG0102
IRIG-B based synchronization device
SAB0101
PSS01 Circuit Breaker Simulator
SAH0101
Phpc01 Current Booster
SAS0101
PACB108 scanning head
SAW0014
Low level output and counter input cable
SAW0015
Synchronization control cable
It provides GPS synchronization signal in PPS PGPS02
(pulse per second) or PPM (pulse per minute) for synchronized test. Trigger time can be set for endto-end test application.
Circuit breaker simulator(PSS01) Working together with PONOVO relay testing device, PSS01 is to be used to simulate the circuit breaker operation for checking the relay scheme performance. Complicated software settings can be avoided by using this simple accessory.
Scanning Head (PACB108) The passive optical scanning head PACB108 detects the status of an LED, that is either an optical pulse output from an energy meter or the binary status of a protective relay or other similar optical source.
29
30
POM2-3243
PGPS02 GPS based synchronization device
POM2-6143
GPS synchronization (PGPS02)
SAG0101
S40A
electromagnetic current relays.
L336i
high compliance voltage even at small current range, suitable for testing high burden
PW466i
Phpc01 current booster is designed to supply
Phpc-01
PW336i
PW636i
Current Booster (Phpc01)