Preview only show first 10 pages with watermark. For full document please download

Protonode Gateway

   EMBED


Share

Transcript

ProtoNode Gateway Communication Interface Startup Guide 750-361 08/2014 TO: Owners, Operators and/or Maintenance Personnel This operating manual presents information that will help to properly operate and care for the equipment. Study its contents carefully. The unit will provide good service and continued operation if proper operating and maintenance instructions are followed. No attempt should be made to operate the unit until the principles of operation and all of the components are thoroughly understood. It is the responsibility of the owner to provide training and advice in all aspects of safety not only to his or her personnel, but to any contractors' personnel who will be servicing, repairing, or operating the equipment. Cleaver-Brooks equipment is designed and engineered to give long life and excellent service on the job. The electrical and mechanical devices supplied as part of the unit were chosen because of their known ability to perform; however, proper operating techniques and maintenance procedures must be followed at all times. Any "automatic" features included in the design do not relieve the attendant of any responsibility. Such features merely eliminate certain repetitive chores, allowing more time for the proper upkeep of equipment. It is solely the operator’s responsibility to properly operate and maintain the equipment. No amount of written instructions can replace intelligent thinking and reasoning and this manual is not intended to relieve the operating personnel of the responsibility for proper operation. On the other hand, a thorough understanding of this manual is required before attempting to operate, maintain, service, or repair this equipment. Operating controls will normally function for long periods of time and we have found that some operators become lax in their daily or monthly testing, assuming that normal operation will continue indefinitely. Malfunctions of controls lead to uneconomical operation and damage and, in most cases, these conditions can be traced directly to carelessness and deficiencies in testing and maintenance. The operation of this equipment by the owner and any operating personnel must comply with all requirements or regulations of the insurance company and/or other authority having jurisdiction. In the event of any conflict or inconsistency between such requirements and the warnings or instructions contained herein, please contact Cleaver-Brooks before proceeding. ProtoNode Gateway RER (BACnet/N2/Modbus) and LER (LonWorks) for interfacing Cleaver-Brooks products: Falcon Hydronic, Falcon Steam, CB780, CB120, HSC, LCS, PCS, HAWK 1000/4000/5000, HAWK Master Panel, ADAC to Building Energy Management Systems: BACnet MS/TP, BACnet/IP, Modbus/TCP, Modbus RTU, Metasys N2 and LonWorks 08/2014 750-361 ProtoNode Gateway 2 750-361 ProtoNode Gateway CONTENTS 1. INTRODUCTION / PARTS AND COMPONENTS 5 1.1 BTL Mark 5 1.2 LonMark Certification 5 1.3 Device Configuration 6 1.4 Cleaver-Brooks Devices and Point Count Available 7 1.5 Part List 8 2. BACNET/LONWORKS SETUP 9 2.1 Record Identification Data 9 2.2 Configuring Ethernet and Serial Device Communications 9 2.3 “S” Bank DIP Switches: Selecting the Desired Field Protocol and Enabling Auto-Discovery 10 2.4 Set MAC Address for BACnet MS/TP; Set Device Instance for BACnet MS/TP and BACnet/IP; Set Node-ID for Metasys N2 and ModbusTCP on ProtoNode RER 11 2.5 Set Baud Rate for BACnet MS/TP on ProtoNode FPC-N34 (BACnet) 13 3. INTERFACING PROTONODE TO DEVICES 14 3.1 ProtoNode RER and LER Showing Connection Ports 14 3.2 Wiring Connections 15 3.3 Wiring ProtoNode RER to RS-485 Field Protocol (BACnet MS/TP or Metasys N2) 16 3.4 Wiring ProtoNode LER Field Port to a LonWorks Network 17 3.5 Power Wiring 17 4. AUTO-DISCOVERY: SAVING RS-485 DEVICE CONFIGURATIONS 18 5. WEB CONFIGURATOR 18 5.1 Connect the PC to ProtoNode via the Ethernet Port 18 5.2 Connecting to ProtoNode's Web Configurator 19 6. RESTARTING - CLEARING PROFILES 20 7. CHANGE THE PROTONODE IP ADDRESS 21 7.1 Connect the PC to ProtoNode via the Ethernet Port 21 7.2 Accessing the FST Web GUI from the Web Configurator 21 7.3 Set IP Address for BACnet/IP and Modbus TCP 22 8. COMMISSIONING PROTONODE LER ON A LONWORKS NETWORK 23 8.1 Commissioning ProtoNode LER on a LonWorks Network 23 9. CAS BACNET EXPLORER FOR VALIDATING PROTONODE IN THE FIELD 25 9.1 Downloading the CAS Explorer and Requesting an Activation Key 25 9.2 CAS BACnet Setup 26 APPENDIX A - TROUBLESHOOTING 27 APPENDIX B - DATA POINT MAPPINGS FOR CLEAVER-BROOKS APPLICATIONS 31 APPENDIX C - MAC ADDRESS DIP SWITCH SETTINGS 85 APPENDIX D - INTERFACING PROTONODE GATEWAY TO BOILER NETWORKS 89 APPENDIX E - WARRANTY 92 750-361 3 ProtoNode Gateway ProtoNode Specifications Electrical Connections Approvals: ProtoNode RER ProtoNode LER One  6‐pin  Phoenix  connector,  one  RS‐485  +/‐ ground port, power +/‐ frame ground port One 3‐pin RS‐485 Phoenix connector, one RS‐485 +/‐ ground port One Ethernet‐10/100 Ethernet port One  6‐pin  Phoenix  connector,  one  RS‐485  +/‐ ground port, power +/‐ frame ground port One Ethernet 10/100 BaseT port One FTT‐10 LonWorks port    TUV approved to UL 916 EN 60950‐1, EN 50491‐3 and CSA C22‐2 standards    CE & FCC Approved BACnet Marked (BTL) B‐ASC LonMark Certified  Power Requirements Multi‐mode power adapter: 9‐30VDC  Physical Dimensions 11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.) Weight: 0.2 kg (0.4 lbs) Operating Temperature:  ‐40°C to 75°C (‐40°F to167°F)   Surge Suppression EN61000‐4‐2 ESD EN61000‐4‐3 EMC EN61000‐4‐4 EFT Humidity: 5 ‐ 90% RH  (non‐condensing) (Specifications subject to change without notice) For UL compliance, the following instructions must be met when operating the ProtoNode. • • The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range. The interconnecting power connector and power cable shall: Comply with local electrical code Be suited to the expected operating temperature range Meet the current and voltage rating for the ProtoNode/Net • Furthermore, the interconnecting power cable shall: Be of length not exceeding 3.05m (118.3") Be constructed of materials rated VW-1 or FT-1 or better • • If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access. This device must not be connected to a LAN segment with outdoor wiring. For the latest edition of this Startup Guide, go to: http://www.cleaverbrooks.com/protonode 4 750-361 ProtoNode Gateway 1. INTRODUCTION/PARTS AND COMPONENTS ProtoNode is an external, high performance Building Automation multi-protocol gateway that is preconfigured to automatically communicate between any of Cleaver-Brooks' products (hereafter called "device") to various building automation protocols. These protocols include BACnet® MS/TP, BACnet/IP, Metasys® N2 by JCI, Modbus TCP, Modbus RTU, and LonWorks® . It is not necessary to download any configuration files to support the required applications. The ProtoNode has been designed to dynamically support both RS-485 and Ethernet devices connected to the ProtoNode, without having to manually build or download any configurations in the field. The ProtoNode has all of the pretest Profiles/Configurations of all supported devices stored internally. See Section 1.3 for a list of supported devices and their configuration options. 1.1 BTL Mark The BTL Mark on the ProtoNode RER indicates that the product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. Go to http://www.bacnetinternational.net/btl/ for more information about the BACnet Testing Laboratory 1.2 LonMark Certification LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and end users. LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices work together. FieldServer Technologies has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier and ProtoNode for OEM applications and the full featured, configurable gateways. 1  BACnet is a registered trademark of ASHRAE 2  Metasys is a registered trademark of Johnson Controls Inc. LonWorks is a registered trademark of Echelon Corporation 3 750-361 5 ProtoNode Gateway 1.3 Device Configuration There are two ways in which the ProtoNode can be configured to recognize and communicate with connected devices: • Auto-Discovery: Supported RS-485 devices can be automatically detected and identified for addition to the ProtoNode's configuration. • Web Configurator: For Ethernet devices, and for RS-485 devices that are not supported by Auto-Discovery, use the embedded tool which is accessed with a browser, referred to in this manual as the Web Configurator. Select the device(s) from a drop-down list of known profiles and assign a Modbus Node-ID and/ or IP Address for any C-B Ethernet based devices. Then the ProtoNode automatically builds the configuration to support the device(s) with the desired protocol. 6 750-361 ProtoNode Gateway A list of C-B products for use with the ProtoNode, together with their respective means of configuration, is shown in the table below. Table 1: Configuring devices Device Falcon Hydronic Falcon Steam CB780 CB120 HSC LCS PCS HAWK_1000 HAWK_4000* HAWK_5000 HAWK_Master HAWK_ADAC Type of Communication RS-485 RS-485 RS-485 RS-485 RS-485 RS-485 RS-485 Ethernet Ethernet Ethernet Ethernet Ethernet Type of Configuration Auto-Discovery or Web Configurator Auto-Discovery or Web Configurator Web Configurator Web Configurator Auto-Discovery or Web Configurator Web Configurator Web Configurator Web Configurator Web Configurator Web Configurator Web Configurator Web Configurator *Hawk 4000 PLC program must be 985-00479 Rev 3 or higher. For other program numbers contact C-B Service. 1.4 Cleaver-Brooks Devices and Point Count Available When installing the ProtoNode, observe the total combined points (number of value registers) of the devices being connected to the ProtoNode. • The total number of devices attached to ProtoNode RER cannot exceed 10,000 value registers for BACnet MS/TP, BACnet/IP, Modbus/TCP or Metasys N2. • The total number of devices attached to ProtoNode LER cannot exceed 1000 value registers for LonWorks. • A single ProtoNode Gateway is capable of supporting up to 16 connected devices. Contact factory for specific configuration capabilities and limits. Table 2: Device point count Devices Falcon Hydronic Falcon Steam CB780 CB120 HSC LCS PCS HAWK_1000 HAWK_4000 HAWK_5000 HAWK_Master HAWK_ADAC 750-361 Point Count 77 47 93 94 318 59 53 269 283 266 196 265 7 ProtoNode Gateway 1.5 Part List 8 750-361 ProtoNode Gateway 2. BACNET/LONWORKS SETUP 2.1 Record Identification Data Each ProtoNode has a unique part number located on the underside of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Table 3: ProtoNode part numbers Model FieldServer Part Number Cleaver-Brooks Part Number ProtoNode RER FPC-N34-103-122-0676 833-09829-000 ProtoNode LER FPC-N35-103-401-0688 833-09831-000 • RER units have the following 3 ports: RS-485 + Ethernet + RS-485 • LER units have the following 3 ports: LonWorks + Ethernet + RS-485 2.2 Configuring Ethernet and Serial Device Communications 2.2.1 AB Ethernet/IP Host Device Communications • All of the AB EtherNet/IP devices connected to the ProtoNode MUST have IP addresses on the same Subnet as the ProtoNode. • If the Field protocol is BACnet/IP or Modbus TCP, which also use Cat5 cable connections, then the AB EtherNet/IP device cables and the Field network cable must be connected together to the ProtoNode with a Hub/Switch or Router. • Note: If the IP address of the ProtoNode is changed to meet Field network address requirements, remember to set the AB EtherNet/IP devices to use the same IP-subnet address. 2.2.2 RS-485 Serial Device Host Communications • All of the Serial devices connected to ProtoNode MUST have the same Baud Rate, Data Bits, Stop Bits, and Parity settings. • Table 4 specifies the device serial port settings required to communicate with the ProtoNode. The Baud Rate of the C-B device must match the Baud Rate of the ProtoNode's Modbus RTU port. In the Web Configurator, the Baud Rate can be set to 9600, 19200 or 38400 (default). See Section 5.2. Table 4: Modbus RTU COM settings Device Serial Port Setting Protocol Baud Rate* Parity Data Bits Stop Bits Falcon Hydronic, Falcon Steam, HSC, PCS and LCS Modbus RTU 38400 None 8 1 CB780, CB120 Modbus RTU 9600, 19200, or 38400 None 8 1 *All connected Modbus RTU devices must be set to the same Baud rate Set Modbus Node-ID for each of the devices attached to ProtoNode. The Modbus Node-IDs need to be uniquely assigned between 1 and 255. • The Modbus Node-ID that is assigned for each device needs to be documented. • The Modbus Node-ID’s assigned are used for setting the Device Instance for BACnet/IP and BACnet MS/TP (See section 2.4.2) 750-361 9 ProtoNode Gateway • The Metasys N2 and Modbus/TCP Node-ID will be set to the same value as the Node-ID of the Modbus RTU device. 2.3 “S” Bank DIP Switches: Selecting the Desired Field Protocol and Enabling Auto-Discovery 2.3.1 Using S0 – S3 bank of DIP Switches • ProtoNode RER units use the "S" bank of DIP switches (S0 - S2) to select the Field Protocol. See Table 5 for the switch settings to select BACnet MS/TP, BACnet/IP, Modbus/TCP, or Metasys N2. When the "S" bank of switches are all OFF (default setting), BACnet/IP is enabled. The OFF position is when the DIP switches are set closest to the outside of the box. • ProtoNode LER units do not use the "S" bank DIP switches (S0 - S2) to select a Field Protocol. On ProtoNode LER units, these switches are disabled; the Field Protocol is always LonWorks S Bank DIP Switches S0 S1 S2 S 3 Table 5: BACnet MS/TP, BACnet/IP, Modbus/TCP, and Metasys N2 Settings for ProtoNode RER  (BACnet) ProtoNode RER S Bank DIP Switches Profile S0 S1 S2 BACnet IP Off Off Off BACnet MSTP On Off Off Metasys N2 Off On Off Modbus TCP On On Off Table 6: RER and LER S3 settings ProtoNode RER and LER 10 S3 DIP Switch Auto-Discovery Mode S3 Auto-Discovery ON - Build New Configuration On Auto-Discover OFF - Save Current Configuration Off 750-361 ProtoNode Gateway 2.3.2 Enabling Auto-Discovery The S3 DIP switch is used to both enable Auto-Discovery of known devices attached to the ProtoNode, and to save the recently discovered configuration. • See Table 1 for RS-485 devices that are supported by Auto-Discovery. • See Table 5 for the DIP switch setting to enable Auto-Discovery. • If the ProtoNode is being installed for the first time, set S3 to the ON position to enable Auto-Discovery. • The ON position is when the DIP switches are set closest to the inside of the box. 2.4 Set MAC Address for BACnet MS/TP; Set Device Instance for BACnet MS/TP and BACnet/IP; Set Node-ID for Metasys N2 and Modbus/TCP on ProtoNode RER 2.4.1 Setting the MAC Address for BACnet MS/TP for ProtoNode RER (BACnet) Only 1 MAC address is set for the ProtoNode regardless of how many devices are connected. Set the BACnet MS/TP MAC address between 1 to 127 (Master MAC address); this is so that the BMS front end can find the ProtoNode via BACnet auto-discovery. Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS Front Ends that support auto discovery of BACnet MS/TP devices. Note: Never set a BACnet MS/TP MAC Address from 128 to 255. Set DIP switches A0 - A7 to assign MAC Address for BACnet MS/TP for the ProtoNode RER. Please refer to Appendix C for the complete range of MAC Addresses and DIP switch settings. When using Metasys N2 and Modbus/TCP, the A Bank of DIP switches are disabled and not used. They should be set to OFF. MAC Address DIP Switches NOTE: When setting DIP Switches, please ensure that power to the board is OFF. 2.4.2 Setting the Device Instance (Node-ID) for BACnet MS/TP and BACnet/IP on ProtoNode RER (BACnet) The BACnet device instances will be calculated by taking the Node_Offset found in Web Configurator and adding it to the Modbus or EtherNep/IP unique Node-ID (assigned in the Web-Configurator). The BACnet Device Instance can range from 1 to 4,194,303. For example: • Node_Offset default = 50,000 • Device 1 has a Modbus/EtherNet IP Node-ID of 1, Device 2 has a Modbus/EtherNet IP Node-ID of 2, Device 3 has a Modbus Node-ID of 3 • Device 1 - Modbus/EtherNet IP Device Instance = 50,001 • Device 2 - Modbus/EtherNet IP Device Instance = 50,002 750-361 11 ProtoNode Gateway • Device 3 - Modbus/EtherNet IP Device Instance = 50,003 To change the Node_Offset see below. The node offset can be changed from 50,000 to 1 to 4,194,302 via the Web Configurator. 2.4.2.1 Set Node_Off to Assign Specific Device instances for BACnet MS/TP and BACnet/IP If the Device Instances need to be set for addresses other than 50,000 to 50,127, change the Node+-Offset (50,000 is the default for Node+Offset). The BACnet Device Instance can range from 1 to 4,194,303. BACnet/IP/BACnet MS/TP Addressing: The BACnet device instances will be set by taking the Node_Offset found in Web Configurator (see figure below) and adding it to the Modbus/EtherNet IP Node- ID that was assigned to the device. Set the PC's IP address to be on the same subnet as the ProtoNode. (See section 5.1) Open the PC browser; enter the default IP address of ProtoNode 192.168.1.24, which will bring you to the Web Configurator's landing page for the ProtoNode. (See Section 5.2) Change the Node_Offset to meet the required device instance. For example: Required Device Instance = 20,001 • Node_Offset changed to = 20,000. • Device 1 has a Modbus/EtherNet IP Node-ID of 1, Device 2 has a Modbus/EtherNet IP Node-ID of 2, Device 3 has a Modbus/EtherNet IP Node-ID of 3 • Device 1 - Modbus/EtherNet IP Device Instance = 20,001 • Device 2 - Modbus/EtherNet IP Device Instance = 20,002 • Device 3 - Modbus/EtherNet IP Device Instance = 20,003 NOTE: The Modbus/EtherNet IP Node address + Node_Offset = Device Instance setting NOTE: Every Hawk selected selected in the Web-Configurator MUST have a unique Node-ID (1-255) If you have both Hawks and RS-485 devices connected to the ProtoNode, they all must have different NodeID's. 12 750-361 ProtoNode Gateway 2.4.3 Setting the Device Node-ID for Metasys N2 and Modbus/TCP on ProtoNode RER (Metasys N2) The Modbus RTU Node-IDs assigned to the devices attached to the ProtoNode in Section 2.2 will be the Metasys N2 and Modbus TCP Node_IDs for the field protocols. Metasys N2 and Modbus/TCP Node-ID Addressing: Metasys N2 and Modbus/TCP Node-IDs range from 1-255. 2.5 Set Baud Rate for BACnet MS/TP on ProtoNode FPC-N34 (BACnet) 2.5.1 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP DIP Switches B0 - B3 can be used to set the serial baud rate to match the baud rate provided by the Building Management System for BACnet MS/TP. See Figure 9 for baud rate switch settings.DIP Switches B0 - B3 are disabled on ProtoNode FPC-N35 (LonWorks). The baud rate on ProtoNode for Metasys N2 is set for 9600. DIP Switches B0 - B3 are disabled for Metasys N2 on ProtoNode FPC-N34. Table 7: Baud Rate DIP Switch Selection Baud Rate DIP Switches 750-361 Baud B0 B1 B2 B3 9600 On On On Off 19200 Off Off Off On 38400 On On Off On 57600 Off Off On On 76800 On Off On On 13 ProtoNode Gateway 3. INTERFACING PROTONODE TO DEVICES 3.1 ProtoNode RER and LER Showing Connection Ports RER LER 14 750-361 ProtoNode Gateway 3.2 Wiring Connections 3.2.1 ProtoNode 6 pin Phoenix connector - pin outs to Modbus RTU products The 6 pin Phoenix connector is the same for ProtoNode RER (BACnet) and ProtoNode LER (LonWorks). Pins 1 through 3 are for Modbus RS-485 connections to the devices and pins 4 through 6 are for power. Device Pins ProtoNode Pin # Pin assignment Pin RS-485 + Pin 1 RS-485 + Pin RS-485 - Pin 2 RS-485 - Pin GND Pin 3 RS-485 GND Power In (+) Pin 4 V+ Power In (-) Pin 5 V- Frame Ground Pin 6 FRAME GND 3.2.2 Biasing the Modbus RS-485 network • An RS-485 network with more than one device needs to have biasing to ensure proper communication. The biasing needs to be done on one device. • The ProtoNode has a 510 Ohm resistor switch that is used to set the biasing. The ProtoNode's default position for the Biasing switch is OFF from the factory. • It is recommended that the biasing be left in the OFF position, unless there is a problem with communicating with more than one device, then try setting the biasing to ON. • The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of the board of the ProtoNode. RER LER RS-485 Bias Switch 750-361 15 ProtoNode Gateway 3.2.3 End of Line Termination Switch for the Modbus RS-485 port • On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each end. • If the ProtoNode is placed at one of the ends of the trunk, turn the blue RS-485 End-of-Line Terminating switch to the ON position. • On short cabling runs the EOL switch may remain in the default OFF setting. • Always leave the single red jumper in the A position. RER LER Modbus RS‐485  EOL Switch Leave in ‘A’ Position 3.3 Wiring ProtoNode RER to RS-485 Field Protocol (BACnet MS/TP or Metasys N2) Connect the BACnet MS/TP or Metasys N2 network for the Building Management System to the 3pin RS-485 connector on ProtoNode FPC-N34 as shown below. BMS RS-485 Wiring ProtoNode Pin # Pin Assignment RS-485 + Pin 1 RS-485 + RS-485 - Pin 2 RS-485 - - Pin 3 RS-485 GND See Section 7 for information on connecting ProtoNode RER to a BACnet/ IP network. If the ProtoNode is the last device on the BACnet MS/TP or Metasys N2 trunk, then the End-Of-Line Terminator needs to be enabled (see below). It is disabled by default. End‐of‐Line Switch 16 750-361 ProtoNode Gateway 3.4 Wiring ProtoNode LER Field Port to a LonWorks Network Connect ProtoNode to the field network with the LonWorks terminal using a twisted pair nonshielded cable. LonWorks has no polarity. 3.5 Power Wiring Ensure that the power supply used complies with the specifications provided. Ensure that the cable is grounded using the "Frame-GND" terminal. ProtoNode accepts either 9-30VDC or 12-24 VAC. Make sure that the S3 DIP switch is in the ON position to enable the ProtoNode "Auto Discovery" mode for RS-485 devices connected to the ProtoNode. See Section 4 before powering up. Table 8: Power Requirement for ProtoNode at 9V through 30 VDC or 12-24 VAC Current Draw Type ProtoNode Family 12VDC/VAC 24VDC/VAC 30VDC RER (Typical) 170mA 100mA 80mA RER (Maximum) 240mA 140mA 100mA LER (Typical) 210mA 100mA 90mA LER (Maximum) 250mA 130mA 100mA Note: These values are 'nominal' and a safety margin should be added to the power supply of the host system. A safety margin of 25% is recommended. Table 9: Power Connections 750-361 Power to ProtoNode ProtoNode Pin # Pin Assignment Power In (+) Pin 4 V+ Power In (-) Pin 5 V- Frame Ground Pin 6 FRAME GND 17 ProtoNode Gateway 4. AUTO-DISCOVERY: SAVING RS-485 DEVICE CONFIGURATIONS [There are some RS-485 devices that cannot be recognized by Auto-Discovery; see Section 1.2 for a list of devices. Devices that cannot be configured by Auto-Discovery are set up by using the Web Configurator; see Section 5]. The S3 DIP Switch for Enabling Auto-Discovery should have been set in section 2.3 before applying power to the ProtoNode. Do not Enable Auto-Discovery when the unit is powered. If the ProtoNode has both RS-485 devices that can be Auto-discovered and Ethernet devices connected to it, perform Auto-Discovery FIRST before selecting profiles in the Web-Configurator. • When power is applied to a ProtoNode that is set to Enable Auto-Discovery, it will take 3 minutes to complete the discovery of all of the RS-485 devices attached to the ProtoNode. • Once the ProtoNode has discovered all of the RS-485 devices, set the S3 DIP switch to the OFF position to save the current configuration. Leaving S3 in the ON position will result in repetition of Auto Discovery on every power cycle or reboot of the ProtoNode. Table 10: S3 DIP Switch Auto-Discovery Mode S3 Auto-Discovery ON - Build New Configuration On Auto-Discover OFF - Save Current Configuration Off 5. WEB CONFIGURATOR 5.1 Connect the PC to ProtoNode via the Ethernet Port Ethernet port • Connect a standard CAT5 Ethernet cable (straight through or cross-over) between the PC and ProtoNode. • The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network. 1. Go to > > 2. Right-click on Local Area Connection > Properties 3. Highlight and go to 4. Select ‘Use the following IP address:’ 18 750-361 ProtoNode Gateway 5. Click twice.. 5.2 Connecting to ProtoNode's Web Configurator After setting your PC to be on the same subnet as the ProtoNode (Section 5.1), open a web browser on your PC and enter the IP address of the ProtoNode; the default address is 192.168.1.24. If the IP address of the ProtoNode has been changed by previous configuration, you will need to get the assigned IP address from the network administrator. 5.3 Selecting profiles for devices that will be connected to the ProtoNode When you open the Web Configurator, you will see the Active Profiles section on the lower left side of the screen. All Modbus RTU and Ethernet/IP devices can be manually configured with the ProtoNode Web configurator. • The Active Profiles section lists the currently active device profiles, including previous Web Configurator additions and any devices identified by Auto-Discovery configuration methods. This list will be empty for new installations, or after clearing all configurations. • To add an active profile to support a device, click the ADD button under Active Profiles. This will present a dropdown box underneath the Current Profile column that lists all the available profiles. See below. For RER units, profiles for supported devices will be offered in the drop-down box for the Field protocol option selected by the S bank of DIP switches. For LER units, profiles for supported devices will be offered in the drop-down box for the Field protocol LonWorks. • For every device that is added, you need to specify the unique Node-ID assigned to the particular device. This specification must match the device's network settings. • All Modbus RTU devices must be configured before adding Ethernet IP devices to the configuration. Otherwise the ProtoNode's virtual ID's can be conflicted requiring the Modbus network to be readdressed. 750-361 19 ProtoNode Gateway • Once the Profile and Modbus Node Address for the device have been selected, then press the ADD button to add the Profile to be configured. • Continue this process until all the devices have been added. • Completed additions will be listed under Active Profiles as shown above. 6. RESTARTING - CLEARING PROFILES • After setting your PC to be on the same subnet as the ProtoNode (section 5.1), open a web browser on your PC and enter the IP address of the ProtoNode; the default address is 192.168.1.24. • If the IP address of the ProtoNode has been changed by previous configuration, you will need to get the assigned IP address from the network administrator. • The Web Configurator will be displayed as your landing page. • At the bottom-left of the page, click the "Clear Profiles and Restart" button. • Once restart is complete, all the past profiles that were discovered and or added via the Web configurator will be delete. The unit is now ready to be reinstalled. 20 750-361 ProtoNode Gateway 7. CHANGE THE PROTONODE IP ADDRESS 7.1 Connect the PC to ProtoNode via the Ethernet Port Ethernet port • Connect a standard CAT5 Ethernet cable (straight through or cross-over) between the PC and ProtoNode. • The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network. • If the IP address of the ProtoNode has been changed by previous configuration, you will need to get the assigned IP address from the network administrator. 1. Go to > > 2. Right-click on Local Area Connection > Properties 3. Highlight and go to 4. Select ‘Use the following IP address:’ 5. Click twice.. 7.2 Accessing the FST Web GUI from the Web Configurator • After setting your PC to be on the same subnet as the ProtoNode (section 5.1), open a web browser on your PC and enter the IP address of the ProtoNode; the default address is 192.168.1.24. • If the IP address of the ProtoNode has been changed by previous configuration, you will need to get the assigned IP address from the network administrator. • The Web Configurator will be displayed as your landing page (see below). • Below the Active Profiles heading you should see profiles listed for connected devices. If no profiles are present, then the wiring, baud rate, and DIP switch settings must be checked, because there is a problem with device communications. All the active profiles must show the correct Node-ID's before proceeding. • To access the FST Web GUI, click on the "Diagnostics & Debugging" button in the bottom right side of the page. 750-361 21 ProtoNode Gateway 7.3 Set IP Address for BACnet/IP and Modbus TCP • From the Web Configurator landing page, click on the "Diagnostics & Debugging" button in the bottom right side of the page to access the FST Web GUI. • The FST Web GUI page will be presented. • From the FST Web GUI's landing page, click on "Setup" to expand the navigation tree and then select "Network Settings" to access the IP Settings menu. • Enter the new IP address for the ProtoNode's Ethernet port in the "N1 IP address" field. 22 750-361 ProtoNode Gateway • If necessary, change the Subnet Mask setting in the "N1 Netmask" field. • If necessary, change the IP Gateway setting in the "Default Gateway" field. • Note: If the ProtoNode is connected to a router, the IP Gateway of the ProtoNode should be set to the IP address of the router that it is connected to. • Click the "System Restart" button at the bottom of the page to apply changes and restart the ProtoNode. • Unplug Ethernet cable from PC and connect the ProtoNode to the network hub or router. • Record the IP address assigned to the ProtoNode for future reference. 8. COMMISSIONING PROTONODE LER ON A LONWORKS NETWORK Commissioning may only be performed by the LonWorks administrator. 8.1 Commissioning ProtoNode LER on a LonWorks Network The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoNode LER at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool. • If an XIF file is required, see steps below to generate XIF. LonWorks Service Pin 8.1.1 To Upload XIF file from ProtoNode LER using FieldServer GUI Web Server: • Connect a standard cat5 Ethernet cable between the PC and ProtoNode • The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network. • For Windows XP: 1. Go to > > 2. Right-click on Local Area Connection > Properties 3. Highlight 750-361 and go to 23 ProtoNode Gateway • For Windows 7: 1. Go to > > > > 2. Right-click on Local Area Connection > Properties 3. Highlight • > For Windows XP and Windows 7, select: ‘Use the following IP address’ 4. Click twice.. 5. Open a web browser and go to the following address: [IP address of ProtoCessor]/fserver.xif Example: 192.168.1.24/fserver.xif 6. If the web browser prompts you to save file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file on your PC as fserver.xif. 24 750-361 ProtoNode Gateway 9. CAS BACNET EXPLORER FOR VALIDATING PROTONODE IN THE FIELD A complimentary 2 week fully functional copy of CAS BACnet Explorer is available (through Chipkin Automation) that can be used to validate BACnet MS/TP and/or BACnet/IP communications of ProtoNode in the field without having to have the BMS Integrator on site. A Serial or USB to RS-485 converter is needed to test BACnet MS/TP. 9.1 Downloading the CAS Explorer and Requesting an Activation Key To request the complementary BACnet CAS key, go to http://app.chipkin.com/activation/twoweek/ and fill in all the information. Enter Vendor Code "Cleaver12". • Once completed, the key will be sent to the email address that was submitted. From this email, the long key will need to be copied and pasted into the CAS key activation page.In the CAS Activation form, enter the email address and paste the CAS key that was sent. Once completed, select Activation. 750-361 25 ProtoNode Gateway 9.2 CAS BACnet Setup To set CAS Explorer up for the first time on BACnet MS/TP and BACnet/IP: 9.2.1 CAS BACnet MS/TP Setup Using the Serial or USB to RS-485 converter, connect it to your PC and the 3 Pin BACnet MS/TP connector on ProtoNode FPC-N34. In CAS Explorer, do the following: • Click on Settings • Check the BACnet MSTP box and uncheck the BACnet/IP and BACnet Ethernet boxes • Set the BACnet MSTP MAC address to 0 • Set the BACnet MSTP Baud Rate to 38400 • Click Ok • On the bottom right-hand corner, make sure that the BACnet MSTP box is green • Click on discover • Check all 4 boxes • Click Send 9.2.2 CAS BACnet/IP Setup See Section 7.1 to set the IP address and subnet of the PC that will be running the CAS Explorer. Connect a straight through or cross Ethernet cable from the PC to ProtoNode. In CAS Explorer, do the following: • Click on settings • Check the BACnet/IP box and uncheck the BACnet MSTP and BACnet Ethernet boxes • In the "Select a Network Device" box, select the network card of the PC by clicking on it • Click Ok • On the bottom right-hand corner, make sure that the BACnet/IP box is green • Click on discover • Check all 4 boxes • Click Send 26 750-361 ProtoNode Gateway APPENDIX A — TROUBLESHOOTING A.1. Check Wiring and Settings No COMS on Modbus RTU side - If Tx/Rx are not flashing rapidly then there is a COM issue on the Modbus side and you need to check the following things: • Observe LEDs on ProtoNode. (Section A.4) • Check baud rate, parity, data bits, stop bits • Check Modbus device address • Verify wiring • Verify all the Modbus RTU devices that were discovered in FST Web Configurator. (See Section 7.2) Field COM problems: • Observe LEDs on ProtoNode. (Section A.4) • Check dipswitch settings (verify correct baud rate and device instance) • Verify IP address setting • Verify wiring If the problem still exists, a Diagnostic Capture needs to be taken and sent to FieldServer. A.2. Taking a Diagnostic Capture using FieldServer Utilities Once the diagnostic capture is complete, email it to [email protected]. The diagnostic capture will allow us to rapidly diagnose the problem. Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip at http://www.protocessor.com/tech-support/utilities-and-design-documents.php Extract the executable file and complete the installation. • Disable any wireless Ethernet adapters on the PC/Laptop • Disable firewall and virus protection software if possible • Connect a standard CAT5 Ethernet cable between the PC and ProtoNode • Double click on the FS Toolbox Utility 750-361 Ethernet Port 27 ProtoNode Gateway Step 1: Take a Log • Click on the Diagnose button of the desired device Diagnose • Select ‘Full Diagnostic’ • If desired, the default capture period can be changed. • Click on Start Diagnostic 28 750-361 ProtoNode Gateway • Wait for Capture period to finish. Diagnostic Test Complete window will appear. Step 2: Send Log • Once the Diagnostic test is complete, a .zip file will be saved on the PC. • Choose open to launch explorer and have it point directly at the correct folder. Send the Diagnostic zip file to [email protected] 750-361 29 ProtoNode Gateway A.3. Setting the Network Number for BACnet/IP when more than one ProtoNode is on the same Subnet On the main Web Configurator screen, update the Network Number in the Network_Nr and hit Submit. Please note that the default value is 50. A.4. LED Diagnostics for Modbus RTU Communications Between ProtoNode and Devices Please see the diagram below for ProtoNode RER and LER LED Locations. Tag 30 Description RTC Unused RUN The RUN LED will start flashing 20 seconds after power indicating normal operation. ERR The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on ProtoNode. If this occurs, immediately report the related "system error" shown in the error screen of the GUI interface to FieldServer Technologies for evaluation. RX The RX LED will flash when a message is received on the host port. TX The TX LED will flash when a message is sent on the host port. PWR This is the power light and should show steady green at all times when ProtoNode is powered. 750-361 ProtoNode Gateway APPENDIX B — DATA POINT MAPPINGS for CLEAVER-BROOKS APPLICATIONS B.1. FALCON HYDRONIC Table 11: FALCON HYDRONIC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks PumpA BACnet  Object  Type BI BACnet  Object  ID 1 N2  Data  Type DI N2  Point  Address 1 30003 0 nvoXXXPumpA SNVT_switch     PumpB BI 2 DI 2 30003 1 nvoXXXPumpB SNVT_switch     PumpC BI 3 DI 3 30003 2 nvoXXXPumpC SNVT_switch     Blower_Mtr BI 4 DI 4 30003 3 nvoXXXBlower_Mtr SNVT_switch     Ext_Ignition BI 5 DI 5 30003 4 nvoXXXExt_Ignition SNVT_switch     SNVT_switch     Point Name Modbus  Register (Bit) Lon Name Lon SNVT Pilot‐MainDBI_Valve BI 6 DI 6 30003 5 nvoXXXPltMnDBIVlv Main_Valve BI 7 DI 7 30003 6 nvoXXXMainValve SNVT_switch     Alarm BI 8 DI 8 30003 7 nvoXXXAlarm SNVT_switch     Interlock BI 9 DI 9 30003 8 nvoXXXInterlock SNVT_switch     PreIgn_Interlock BI 10 DI 10 30003 9 nvoXXXPreIgnIntrlk SNVT_switch     Load_Control_In BI 11 DI 11 30003 10 nvoXXXLoadCtrlIn SNVT_switch     Low_Fire_Switch BI 12 DI 12 30003 11 nvoXXXLoFireSwitch SNVT_switch     High_Fire_Switch BI 13 DI 13 30003 12 nvoXXXHiFireSwitch SNVT_switch     Stat_Demand BI 14 DI 14 30003 13 nvoXXXStatDem SNVT_switch     TimeOfDay BI 15 DI 15 30003 14 nvoXXXTimeOfDay SNVT_switch     Safety_Relay BI 16 DI 16 30003 15 nvoXXXSafetyRelay SNVT_switch     Int_Air_Switch BI 17 DI 17 30004 0 nvoXXXIntAirSwitch SNVT_switch     Low_Water BI 18 DI 18 30004 1 nvoXXXLoWater SNVT_switch     Aux_Low_Water BI 19 DI 19 30004 2 nvoXXXAuxLoWater SNVT_switch     High_Limit BI 20 DI 20 30004 3 nvoXXXHiLimit SNVT_switch     High_Gas_Press BI 21 DI 21 30004 4 nvoXXXHiGasPress SNVT_switch     Low_Gas_Press BI 22 DI 22 30004 5 nvoXXXLoGasPress SNVT_switch     Natural_Gas BI 23 DI 23 30004 6 nvoXXXNaturalGas SNVT_switch     Propane_Gas BI 24 DI 24 30004 7 nvoXXXPropaneGas SNVT_switch     DEMAND SOURCE AI 1 AI 1 30007 nvoXXXDemSrc SNVT_count_f    SNVT_temp_p     OUTLET WATER TEMP DEG F AI 2 AI 2 30008 nvoXXXOutletWtrTmp FIRING_RATE AI 3 AI 3 30009 nvoXXXFiringRate SNVT_count_f    FAN_SPEED AI 4 AI 4 30010 nvoXXXFanSpeed SNVT_count_f    FLAME_SIGNAL AI 5 AI 5 30011 nvoXXXFlameSignal SNVT_count_f    INLET WATER TEMP DEG F AI 6 AI 6 30012 nvoXXXInletWtrTemp SNVT_temp_p     DHW WATER TEMP DEG F AI 7 AI 7 30013 nvoXXXDHW_WtrTemp SNVT_temp_p     HEADER or ODT DEG F AI 8 AI 8 30014 nvoXXXHeaderOrOdt SNVT_temp_p     STACK TEMP DEG F AI 9 AI 9 30015 nvoXXXStackTemp SNVT_temp_p     CH SETPOINT DEG F AI 11 AI 11 30017 nvoXXXCH_Setpoint SNVT_temp_p     DHW SETPOINT DEG F AI 12 AI 12 30018 nvoXXXDHW_Setpoint SNVT_temp_p     ANALOG_INPUT AI 14 AI 14 30022 nvoXXXAnalogInput SNVT_count_f    BURN_CTL_STATUS AI 15 AI 15 30033 nvoXXXBrnCtlStatus SNVT_count_f    BURN_CTL_STATE AI 16 AI 16 30034 nvoXXXBrnCtlState SNVT_count_f    LOCKOUT_CODE AI 17 AI 17 30035 nvoXXXLockoutCode SNVT_count_f    SNVT_count_f    HOLD_CODE AI 18 AI 18 30041 nvoXXXHoldCode CH STATUS AI 20 AI 20 30063 nvoXXXCH_Status SNVT_count_f    CH SETPOINT SOURCE AI 21 AI 21 30066 nvoXXXCH_SPSrc SNVT_count_f    CH HEAT DEMAND AI 22 AI 22 30067 nvoXXXCH_HeatDem SNVT_count_f    CH BURNER DEMAND AI 23 AI 23 30068 nvoXXXCH_BurnrDem SNVT_count_f    CH REQUESTED RATE AI 24 AI 24 30069 nvoXXXCH_ReqRate SNVT_count_f    750-361 31 ProtoNode Gateway Table 11: FALCON HYDRONIC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks * * * * * * CH FROST HEAT DEMAND AI 25 AI 25 30070 nvoXXXCH_FrstHtDem SNVT_count_f    CH FROST BURNER DEMAND AI 26 AI 26 30071 nvoXXXCHFrstBrnDem SNVT_count_f    DHW STATUS AI 29 AI 29 30081 nvoXXXDHW_Status SNVT_count_f    DHW SETPOINT SOURCE AI 30 AI 30 30082 nvoXXXDHW_SP_Src SNVT_count_f    DHW HEAT DEMAND AI 32 AI 32 30084 nvoXXXDHW_HeatDem SNVT_count_f    DHW BURNER DEMAND AI 33 AI 33 30085 nvoXXXDHW_BrnrDem SNVT_count_f    DHW REQUESTED RATE AI 34 AI 34 30086 nvoXXXDHW_ReqRate SNVT_count_f    CH PUMP STATUS AI 39 AI 39 30097 nvoXXXCH_PmpStatus SNVT_count_f    DHW PUMP STATUS AI 43 AI 43 30101 nvoXXXDHWPmpStatus SNVT_count_f    SYSTEM PUMP STATUS AI 48 AI 48 30106 nvoXXXSysPmpStatus SNVT_count_f    BOILER PUMP STATUS AI 51 AI 51 30109 nvoXXXBlrPmpStatus SNVT_count_f    AUXILIARY1 PUMP STATUS AI 54 AI 54 30112 nvoXXXAux1PmpStatu SNVT_count_f    AUXILIARY2 PUMP STATUS AI 55 AI 55 30114 nvoXXXAux2PmpStatu SNVT_count_f    BURNER_ENABLE AI 57 AI 57 30204 nvoXXXBrnrEnable SNVT_count_f    LEAD/LAG SETPOINT DEG F AI 60 AI 60 30547 nvoXXXLead_LagSP SNVT_temp_p     LEAD/LAG_ENABLE AI 61 AI 61 30556 nvoXXXLead_LagEnbl SNVT_count_f    CYCLE_COUNT AI 58 AI 58 30129‐30 nvoXXXCycCount SNVT_count_f    BURNER RUN_TIME AI 59 AI 59 30131‐32 nvoXXXBrnrRunTime SNVT_time_hour  BOILER BURNER ENABLE AV 1 AO 1 40204 nviXXXBrnrEnable SNVT_count_f    BOILER LEAD/LAG ENABLE AV 11 AO 11 40556 nviXXXLead_LagEnbl SNVT_count_f    BOILER CH SETPOINT DEG F AV 21 AO 21 40212 nviXXXCH_Setpoint SNVT_temp_p     BOILER LEAD/LAG SETPOINT DEG F AV 31 AO 31 40547 nviXXXLead_LagSP SNVT_temp_p     OUTLET WATER TEMP DEG C AI 62 AI 62 30008 INLET WATER TEMP DEG C AI 66 AI 66 30012 DHW WATER TEMP DEG C AI 67 AI 67 30013 HEADER or ODT DEG C AI 68 AI 68 30014 STACK TEMP  DEG C AI 69 AI 69 30015 CH SETPOINT  DEG C AI 71 AI 71 30017 DHW SETPOINT  DEG C AI 72 AI 72 30018 LEAD/LAG SETPOINT DEG C AI 73 AI 73 30547 BOILER CH SETPOINT DEG C AV 41 AO 41 40212 BOILER LEAD/LAG SETPOINT DEG C AV 51 AO 51 40547 * Write points 32 750-361 ProtoNode Gateway B.2. FALCON STEAM Table 12: FALCON STEAM Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks PumpA BACnet  Object Type BI BACnet  Object ID 1 N2 Data  Type DI N2 Point  Address 1 Modbus  Register 30003 0 nvoXXXPumpA SNVT_switch PumpB BI 2 DI 2 30003 1 nvoXXXPumpB SNVT_switch Point Name * * * * (Bit) Lon Name Lon SNVT PumpC BI 3 DI 3 30003 2 nvoXXXPumpC SNVT_switch Blower_Mtr BI 4 DI 4 30003 3 nvoXXXBlower_Mtr SNVT_switch Ext_Ignition BI 5 DI 5 30003 4 nvoXXXExt_Ignition SNVT_switch Pilot_Valve BI 6 DI 6 30003 5 nvoXXXPilotValve SNVT_switch Main_Valve BI 7 DI 7 30003 6 nvoXXXMainValve SNVT_switch Alarm BI 8 DI 8 30003 7 nvoXXXAlarm SNVT_switch Interlock BI 9 DI 9 30003 8 nvoXXXInterlock SNVT_switch PreIgn_Interlock BI 10 DI 10 30003 9 nvoXXXPreIgnIntrlk SNVT_switch SNVT_switch Load_Control_In BI 11 DI 11 30003 10 nvoXXXLoadCtrlIn Low_Fire_Switch BI 12 DI 12 30003 11 nvoXXXLoFireSwitch SNVT_switch High_Fire_Switch BI 13 DI 13 30003 12 nvoXXXHiFireSwitch SNVT_switch Stat_Demand BI 14 DI 14 30003 13 nvoXXXStatDem SNVT_switch TimeOfDay BI 15 DI 15 30003 14 nvoXXXTimeOfDay SNVT_switch Safety_Relay BI 16 DI 16 30003 15 nvoXXXSafetyRelay SNVT_switch Int_Air_Switch BI 17 DI 17 30004 0 nvoXXXIntAirSwitch SNVT_switch Low_Water BI 18 DI 18 30004 1 nvoXXXLoWater SNVT_switch Aux_Low_Water BI 19 DI 19 30004 2 nvoXXXAuxLoWater SNVT_switch High_Limit BI 20 DI 20 30004 3 nvoXXXHiLimit SNVT_switch High_Gas_Press BI 21 DI 21 30004 4 nvoXXXHiGasPress SNVT_switch Low_Gas_Press BI 22 DI 22 30004 5 nvoXXXLoGasPress SNVT_switch High_Water BI 23 DI 23 30004 6 nvoXXXHigh_Water SNVT_switch Feed_Water BI 24 DI 24 30004 7 nvoXXXFeed_Water SNVT_switch DEMAND SOURCE AI 1 AI 1 30007 nvoXXXDemSrc SNVT_count_f FIRING_RATE AI 2 AI 2 30009 nvoXXXFiringRate SNVT_count_f FAN_SPEED AI 3 AI 3 30010 nvoXXXFanSpeed SNVT_count_f FLAME_SIGNAL AI 4 AI 4 30011 nvoXXXFlameSignal SNVT_count_f STEAM_PRESSURE AI 5 AI 5 30021 nvoXXXSteamPress SNVT_count_f ANALOG_INPUT AI 6 AI 6 30022 nvoXXXAna_Input SNVT_count_f ACTIVE_STEAM_SP AI 7 AI 7 30023 nvoXXXActSteamSP SNVT_count_f BURN_CTL_STATUS AI 8 AI 8 30033 nvoXXXBrnCtlStats SNVT_count_f BURN_CTL_STATE AI 9 AI 9 30034 nvoXXXBrnCtlState SNVT_count_f LOCKOUT_CODE AI 10 AI 10 30035 nvoXXXLockoutCode SNVT_count_f HOLD_CODE AI 11 AI 11 30041 nvoXXXHoldCode SNVT_count_f CYCLE_COUNT AI 12 AI 12 30129‐30 nvoXXXCycleCount SNVT_count_f RUN_TIME AI 13 AI 13 30131‐32 nvoXXXRunTime SNVT_count_f BURNER_ENABLE AI 16 AI 16 30204 nvoXXXBrnrEnbl SNVT_count_f STEAM_PRESSURE_SETPOINT AI 14 AI 14 30221 nvoXXXStmPressSP SNVT_count_f LEAD/LAG_STEAM_PRESS_SETPOINT AI 15 AI 15 30739 nvoXXXLdLgStmPrSP SNVT_count_f LEAD/LAG_HEADER_STEAM_PRESS AI 17 AI 17 30807 nvoXXXLdLgHdStmPr SNVT_count_f VESSEL WATER TEMP (Deg C) AI 18 AI 18 30008 nvoXXXVesWtrTmp SNVT_count_f VESSEL WATER TEMP (Deg F) AI 19 AI 19 30008 BURNER ENABLE AV 1 AO 1 40204 nvi1BrnrEnbl SNVT_count_f STEAM_PRESSURE_SETPOINT AV 21 AO 21 40221 nvi1StmPressSP SNVT_count_f LEAD/LAG_ENABLE AV 11 AO 11 40556 nvo/nviXXXLead_LagEnbl SNVT_count_f LEAD/LAG_SETPOINT AV 31 AO 31 40739 nvo/nviXXXLead_LagSP SNVT_count_f *Write points 750-361 33 ProtoNode Gateway B.3. CB780 Table 13: CB780 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BC_Initiate BACnet  Object  Type BI 1 N2  Data  Type DI 40013 0 nvoXXXBCInitiate SNVT_switch BC_Standby BI 2 DI 2 40013 1 nvoXXXBCStandby SNVT_switch BC_Purge BI 3 DI 3 40013 2 nvoXXXBCPurge SNVT_switch BC_Pilot_Ignition BI 4 DI 4 40013 3 nvoXXXBCPlt_Igntn SNVT_switch BC_Main_Ignition BI 5 DI 5 40013 4 nvoXXXBCMainIgntn SNVT_switch BC_Run_Mode BI 6 DI 6 40013 5 nvoXXXBCRunMode SNVT_switch BC_Postpurge BI 7 DI 7 40013 6 nvoXXXBCPostpurge SNVT_switch BC_Preignition BI 8 DI 8 40013 7 nvoXXXBCPreignitn SNVT_switch BC_Alarm_Out BI 9 DI 9 40013 13 nvoXXXBCAlarmOut SNVT_switch BC_Lockout BI 10 DI 10 40013 15 nvoXXXBCLockout SNVT_switch BC_Fault_Code AI 1 AI 1 40001 nvoXXXBCFltCode SNVT_count_f BC_Fault_String_Code AI 2 AI 2 40002 nvoXXXBCFltStrnCod SNVT_count_f BC_Sequence_State AI 3 AI 3 40003 nvoXXXBCSeqState SNVT_count_f BC_State_String_Code_L1 AI 4 AI 4 40004 nvoXXXBCStStrnCdL1 SNVT_count_f SNVT_count_f Point Name See Tables 23-25 34 BACnet  Object ID N2  Point  Address 1 Modbus  Register (Bit) Lon Name Lon SNVT BC_State_String_Code_L2 AI 5 AI 5 40005 nvoXXXBCStStrnCdL2 BC_Sequence_Time AI 6 AI 6 40006 nvoXXXBCSeqTime SNVT_count_f BC_Flame_Signal_Strength AI 7 AI 7 40011 nvoXXXBCFlmSigStre SNVT_count_f BC_State_Bits AI 8 AI 8 40013 nvoXXXBCStateBits SNVT_count_f BC_Flt_Hist_Code_Rec1 AI 9 AI 9 40017 nvoXXXBCFtHtCodRc1 SNVT_count_f BC_Flt_Hist_String_Rec1 AI 10 AI 10 40018 nvoXXXBCFtHtStrRc1 SNVT_count_f BC_Flt_Hist_State_Rec1 AI 11 AI 11 40019 nvoXXXBCFtHtStRc1 SNVT_count_f BC_Flt_Hist_Line1_Rec1 AI 12 AI 12 40020 nvoXXXBCFtHtLn1Rc1 SNVT_count_f BC_Flt_Hist_Line2_Rec1 AI 13 AI 13 40021 nvoXXXBCFtHtLn2Rc1 SNVT_count_f BC_Flt_Hist_Time_Rec1 AI 14 AI 14 40022 nvoXXXBCFtHtTimRc1 SNVT_count_f BC_Flt_Hist_Code_Rec2 AI 15 AI 15 40027 nvoXXXBCFtHtCodRc2 SNVT_count_f BC_Flt_Hist_String_Rec2 AI 16 AI 16 40028 nvoXXXBCFtHtStrRc2 SNVT_count_f BC_Flt_Hist_State_Rec2 AI 17 AI 17 40029 nvoXXXBCFtHtStRc2 SNVT_count_f BC_Flt_Hist_Line1_Rec2 AI 18 AI 18 40030 nvoXXXBCFtHtLn1Rc2 SNVT_count_f BC_Flt_Hist_Line2_Rec2 AI 19 AI 19 40031 nvoXXXBCFtHtLn2Rc2 SNVT_count_f BC_Flt_Hist_Time_Rec2 AI 20 AI 20 40032 nvoXXXBCFtHtTimRc2 SNVT_count_f BC_Flt_Hist_Code_Rec3 AI 21 AI 21 40037 nvoXXXBCFtHtCodRc3 SNVT_count_f BC_Flt_Hist_String_Rec3 AI 22 AI 22 40038 nvoXXXBCFtHtStrRc3 SNVT_count_f BC_Flt_Hist_State_Rec3 AI 23 AI 23 40039 nvoXXXBCFtHtStRc3 SNVT_count_f BC_Flt_Hist_Line1_Rec3 AI 24 AI 24 40040 nvoXXXBCFtHtLn1Rc3 SNVT_count_f BC_Flt_Hist_Line2_Rec3 AI 25 AI 25 40041 nvoXXXBCFtHtLn2Rc3 SNVT_count_f BC_Flt_Hist_Time_Rec3 AI 26 AI 26 40042 nvoXXXBCFtHtTimRc3 SNVT_count_f BC_Flt_Hist_Code_Rec4 AI 27 AI 27 40047 nvoXXXBCFtHtCodRc4 SNVT_count_f BC_Flt_Hist_String_Rec4 AI 28 AI 28 40048 nvoXXXBCFtHtStrRc4 SNVT_count_f BC_Flt_Hist_State_Rec4 AI 29 AI 29 40049 nvoXXXBCFtHtStRc4 SNVT_count_f BC_Flt_Hist_Line1_Rec4 AI 30 AI 30 40050 nvoXXXBCFtHtLn1Rc4 SNVT_count_f BC_Flt_Hist_Line2_Rec4 AI 31 AI 31 40051 nvoXXXBCFtHtLn2Rc4 SNVT_count_f BC_Flt_Hist_Time_Rec4 AI 32 AI 32 40052 nvoXXXBCFtHtTimRc4 SNVT_count_f BC_Flt_Hist_Code_Rec5 AI 33 AI 33 40057 nvoXXXBCFtHtCodRc5 SNVT_count_f BC_Flt_Hist_String_Rec5 AI 34 AI 34 40058 nvoXXXBCFtHtStrRc5 SNVT_count_f BC_Flt_Hist_State_Rec5 AI 35 AI 35 40059 nvoXXXBCFtHtStRc5 SNVT_count_f BC_Flt_Hist_Line1_Rec5 AI 36 AI 36 40060 nvoXXXBCFtHtLn1Rc5 SNVT_count_f BC_Flt_Hist_Line2_Rec5 AI 37 AI 37 40061 nvoXXXBCFtHtLn2Rc5 SNVT_count_f 750-361 ProtoNode Gateway Table 13: CB780 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * BC_Flt_Hist_Time_Rec5 AI 38 AI 38 40062 nvoXXXBCFtHtTimRc5 SNVT_count_f BC_Flt_Hist_Code_Rec6 AI 39 AI 39 40067 nvoXXXBCFtHtCodRc6 SNVT_count_f BC_Flt_Hist_String_Rec6 AI 40 AI 40 40068 nvoXXXBCFtHtStrRc6 SNVT_count_f BC_Flt_Hist_State_Rec6 AI 41 AI 41 40069 nvoXXXBCFtHtStRc6 SNVT_count_f BC_Flt_Hist_Line1_Rec6 AI 42 AI 42 40070 nvoXXXBCFtHtLn1Rc6 SNVT_count_f BC_Flt_Hist_Line2_Rec6 AI 43 AI 43 40071 nvoXXXBCFtHtLn2Rc6 SNVT_count_f BC_Flt_Hist_Time_Rec6 AI 44 AI 44 40072 nvoXXXBCFtHtTimRc6 SNVT_count_f BC_Rem_Comd_Stat AI 45 AI 45 40085 nvoXXXBCRemCmdStat SNVT_count_f BC_Vlv_Prov_Mode AI 46 AI 46 40104 nvoXXXBCVlvProvMod SNVT_count_f BC_Vlv_Prov_Time AI 47 AI 47 40106 nvoXXXBCVlvProvTim SNVT_count_f BC_Rem_Command AI 48 AI 48 40128 nvoXXXBCRemCommand SNVT_count_f BC_Total_Cycles AI 50 AI 50 40007 nvoXXXBCTotCycles SNVT_count_f BC_Total_Hours AI 51 AI 51 40009 nvoXXXBCTotalHours SNVT_time_hour BC_Flt_Hist_Cyc_Rec1 AI 52 AI 52 40023 nvoXXXBCFtHtCycRc1 SNVT_count_f BC_Flt_Hist_Hrs_Rec1 AI 53 AI 53 40025 nvoXXXBCFtHtHrsRc1 SNVT_count_f BC_Flt_Hist_Cyc_Rec2 AI 54 AI 54 40033 nvoXXXBCFtHtCycRc2 SNVT_count_f BC_Flt_Hist_Hrs_Rec2 AI 55 AI 55 40035 nvoXXXBCFtHtHrsRc2 SNVT_count_f BC_Flt_Hist_Cyc_Rec3 AI 56 AI 56 40043 nvoXXXBCFtHtCycRc3 SNVT_count_f BC_Flt_Hist_Hrs_Rec3 AI 57 AI 57 40045 nvoXXXBCFtHtHrsRc3 SNVT_count_f BC_Flt_Hist_Cyc_Rec4 AI 58 AI 58 40053 nvoXXXBCFtHtCycRc4 SNVT_count_f BC_Flt_Hist_Hrs_Rec4 AI 59 AI 59 40055 nvoXXXBCFtHtHrsRc4 SNVT_count_f BC_Flt_Hist_Cyc_Rec5 AI 60 AI 60 40063 nvoXXXBCFtHtCycRc5 SNVT_count_f BC_Flt_Hist_Hrs_Rec5 AI 61 AI 61 40065 nvoXXXBCFtHtHrsRc5 SNVT_count_f BC_Flt_Hist_Cyc_Rec6 AI 62 AI 62 40073 nvoXXXBCFtHtCycRc6 SNVT_count_f BC_Flt_Hist_Hrs_Rec6 AI 63 AI 63 40075 nvoXXXBCFtHtHrsRc6 SNVT_count_f BC_Rem_Command AV 1 AO 1 40128 nviXXXBCRemCommand SNVT_count_f ExpAnn_First_Out_Code AI 49 AI 49 40014 nvoXXXExpAn1stOtCd SNVT_count_f EA_Valve_POC BI 11 DI 11 40015 4 nvoXXXEAValvePOC SNVT_switch EA_Burner_Switch BI 12 DI 12 40015 5 nvoXXXEABrnrSwitch SNVT_switch EA_Oper_Control BI 13 DI 13 40015 6 nvoXXXEAOperCtrl SNVT_switch EA_Aux_Limit_1 BI 14 DI 14 40015 7 nvoXXXEAAuxLim1 SNVT_switch EA_Aux_Limit_2 BI 15 DI 15 40015 8 nvoXXXEAAuxLim2 SNVT_switch EA_LWCO BI 16 DI 16 40015 9 nvoXXXEALWCO SNVT_switch EA_High_Limit BI 17 DI 17 40015 10 nvoXXXEAHiLim SNVT_switch EA_Aux_Limit_3 BI 18 DI 18 40015 11 nvoXXXEAAuxLim3 SNVT_switch EA_Oil_Select BI 19 DI 19 40015 12 nvoXXXEAOilSelect SNVT_switch SNVT_switch EA_High_Oil_Press BI 20 DI 20 40015 13 nvoXXXEAHiOilPress EA_Low_Oil_Press BI 21 DI 21 40015 14 nvoXXXEALoOilPress SNVT_switch EA_High_Oil_Temp BI 22 DI 22 40015 15 nvoXXXEAHiOilTmp SNVT_switch EA_Low_Oil_Temp BI 23 DI 23 40015 16 nvoXXXEALowOilTmp SNVT_switch EA_Gas_Select BI 24 DI 24 40015 17 nvoXXXEAGasSelect SNVT_switch EA_High_Gas_Press BI 25 DI 25 40015 18 nvoXXXEAHiGasPress SNVT_switch EA_Low_Gas_Press BI 26 DI 26 40015 19 nvoXXXEALoGasPress SNVT_switch EA_Air_Flow_Switch BI 27 DI 27 40015 20 nvoXXXEAAirFloSw SNVT_switch EA_Aux_Limit_4 BI 28 DI 28 40015 21 nvoXXXEAAuxLim4 SNVT_switch EA_Aux_Limit_5 BI 29 DI 29 40015 22 nvoXXXEAAuxLim5 SNVT_switch *Write point 750-361 35 ProtoNode Gateway B.4. CB120 Table 14: CB120 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Point Name Safety_Relay Main_Valve_In BACnet  Object  Type BI BACnet  Object  ID 1 N2  Data  Type DI N2  Point  Address 1 BI 2 DI 2 Modbus  Register (Bit) Lon Name Lon SNVT 40007 0 nvoXXXSafetyRelay SNVT_switch 40007 1 nvoXXXMainVlvIn SNVT_switch Delayed_Valve_In BI 3 DI 3 40007 2 nvoXXXDelayVlvIn SNVT_switch Pilot_Valve_In BI 4 DI 4 40007 3 nvoXXXPilotVlvIn SNVT_switch Ignition_In BI 5 DI 5 40007 4 nvoXXXIgnitionIn SNVT_switch Blower_In BI 6 DI 6 40007 5 nvoXXXBlowerIn SNVT_switch Op_Cntrl BI 7 DI 7 40007 6 nvoXXXOpCntrl SNVT_switch SNVT_switch Run_Intlck BI 8 DI 8 40007 7 nvoXXXRunIntlck LAG1 BI 9 DI 9 40007 8 nvoXXXLAG1 SNVT_switch LAG2 BI 10 DI 10 40007 11 nvoXXXLAG2 SNVT_switch Fuel_Vlv_POC BI 11 DI 11 40007 12 nvoXXXFuelVlvPOC SNVT_switch High_Fire_Intlck BI 12 DI 12 40007 13 nvoXXXHiFireIntlck SNVT_switch Low_Fire_Start BI 13 DI 13 40007 14 nvoXXXLoFireStart SNVT_switch Ref_AC_Line BI 14 DI 14 40007 15 nvoXXXRefACLine SNVT_switch Ignition_Out BI 15 DI 15 40008 1 nvoXXXIgnitionOut SNVT_switch Pilot_Valve_Out BI 16 DI 16 40008 2 nvoXXXPilotVlvOut SNVT_switch Blower_Out BI 17 DI 17 40008 3 nvoXXXBLoerOut SNVT_switch Main_Valve_Out BI 18 DI 18 40008 4 nvoXXXMainVlvOut SNVT_switch Delayed_Valve_Out BI 19 DI 19 40008 5 nvoXXXDelayVlvOut SNVT_switch Internal_Safety_Out BI 20 DI 20 40008 6 nvoXXXIntSafetyOut SNVT_switch LowFireOut BI 21 DI 21 40008 8 nvoXXXLoFireOut SNVT_switch HighFireOut BI 22 DI 22 40008 9 nvoXXXHiFireOut SNVT_switch Rel_to_ModOut BI 23 DI 23 40008 10 nvoXXXReltoModOut SNVT_switch Alarm_Out BI 24 DI 24 40008 11 nvoXXXAlmOut SNVT_switch Status AI 1 AI 1 40001 nvoXXXStatus SNVT_count_f Msgn AI 2 AI 2 40002 nvoXXXMsgn SNVT_count_f Gstat AI 3 AI 3 40003 nvoXXXGstat SNVT_count_f Timer AI 4 AI 4 40004 nvoXXXTimer SNVT_count_f Flame AI 5 AI 5 40005 nvoXXXFlame SNVT_count_f Logstat AI 6 AI 6 40006 nvoXXXLogstat SNVT_count_f Lockout_Count AI 7 AI 7 40015 nvoXXXLockoutCount SNVT_count_f Sysmins AI 8 AI 8 40009‐10 nvoXXXSysmins SNVT_time_min Bnrmins AI 9 AI 9 40011‐12 nvoXXXBnrmins SNVT_time_min Cycles AI 10 AI 10 40013‐14 nvoXXXCycles SNVT_count_f SNVT_count_f LOCKOUT1_MSG AI 11 AI 11 40016 nvoXXXLkot1Msg LOCKOUT1_MODULE AI 12 AI 12 40017 nvoXXXLkot1Mod SNVT_count_f LOCKOUT2_MSG AI 13 AI 13 40022 nvoXXXLkot2Msg SNVT_count_f LOCKOUT2_MODULE AI 14 AI 14 40023 nvoXXXLkot2Mod SNVT_count_f LOCKOUT3_MSG AI 15 AI 15 40028 nvoXXXLkot3Msg SNVT_count_f LOCKOUT3_MODULE AI 16 AI 16 40029 nvoXXXLkot3Mod SNVT_count_f LOCKOUT4_MSG AI 17 AI 17 40034 nvoXXXLkot4Msg SNVT_count_f LOCKOUT4_MODULE AI 18 AI 18 40035 nvoXXXLkot4Mod SNVT_count_f LOCKOUT5_MSG AI 19 AI 19 40040 nvoXXXLkot5Msg SNVT_count_f LOCKOUT5_MODULE AI 20 AI 20 40041 nvoXXXLkot5Mod SNVT_count_f LOCKOUT6_MSG AI 21 AI 21 40046 nvoXXXLkot6Msg SNVT_count_f LOCKOUT6_MODULE AI 22 AI 22 40047 nvoXXXLkot6Mod SNVT_count_f 36 750-361 ProtoNode Gateway Table 14: CB120 Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) LOCKOUT7_MSG AI 23 AI 23 40052 nvoXXXLkot7Msg SNVT_count_f LOCKOUT7_MODULE AI 24 AI 24 40053 nvoXXXLkot7Mod SNVT_count_f LOCKOUT8_MSG AI 25 AI 25 40058 nvoXXXLkot8Msg SNVT_count_f LOCKOUT8_MODULE AI 26 AI 26 40059 nvoXXXLkot8Mod SNVT_count_f LOCKOUT9_MSG AI 27 AI 27 40064 nvoXXXLkot9Msg SNVT_count_f LOCKOUT9_MODULE AI 28 AI 28 40065 nvoXXXLkot9Mod SNVT_count_f LOCKOUT10_MSG AI 29 AI 29 40070 nvoXXXLkot10Msg SNVT_count_f LOCKOUT10_MODULE AI 30 AI 30 40071 nvoXXXLkot10Mod SNVT_count_f LOCKOUT1_BNRHRS AI 31 AI 31 40018‐19 nvoXXXLkot1BnrHrs SNVT_time_hour LOCKOUT1_BNRCYCS AI 32 AI 32 40020‐21 nvoXXXLkot1BnrCyc SNVT_count_f LOCKOUT2_BNRHRS AI 33 AI 33 40024‐25 nvoXXXLkot2BnrHrs SNVT_time_hour LOCKOUT2_BNRCYCS AI 34 AI 34 40026‐27 nvoXXXLkot2BnrCyc SNVT_count_f LOCKOUT3_BNRHRS AI 35 AI 35 40030‐31 nvoXXXLkot3BnrHrs SNVT_time_hour LOCKOUT3_BNRCYCS AI 36 AI 36 40032‐34 nvoXXXLkot3BnrCyc SNVT_count_f LOCKOUT4_BNRHRS AI 37 AI 37 40036‐37 nvoXXXLkot4BnrHrs SNVT_time_hour LOCKOUT4_BNRCYCS AI 38 AI 38 40038‐39 nvoXXXLkot4BnrCyc SNVT_count_f LOCKOUT5_BNRHRS AI 39 AI 39 40042‐43 nvoXXXLkot5BnrHrs SNVT_time_hour LOCKOUT5_BNRCYCS AI 40 AI 40 40044‐45 nvoXXXLkot5BnrCyc SNVT_count_f LOCKOUT6_BNRHRS AI 41 AI 41 40048‐49 nvoXXXLkot6BnrHrs SNVT_time_hour LOCKOUT6_BNRCYCS AI 42 AI 42 40050‐51 nvoXXXLkot6BnrCyc SNVT_count_f LOCKOUT7_BNRHRS AI 43 AI 43 40054‐55 nvoXXXLkot7BnrHrs SNVT_time_hour LOCKOUT7_BNRCYCS AI 44 AI 44 40056‐57 nvoXXXLkot7BnrCyc SNVT_count_f LOCKOUT8_BNRHRS AI 45 AI 45 40060‐61 nvoXXXLkot8BnrHrs SNVT_time_hour LOCKOUT8_BNRCYCS AI 46 AI 46 40062‐63 nvoXXXLkot8BnrCyc SNVT_count_f LOCKOUT9_BNRHRS AI 47 AI 47 40066‐67 nvoXXXLkot9BnrHrs SNVT_time_hour SNVT_count_f LOCKOUT9_BNRCYCS AI 48 AI 48 40068‐69 nvoXXXLkot9BnrCyc LOCKOUT10_BNRHRS AI 49 AI 49 40072‐73 nvoXXXLkot10BnrHrs SNVT_time_hour LOCKOUT10_BNRCYCS AI 50 AI 50 40074‐75 nvoXXXLkot10BnrCyc SNVT_count_f Op_Control BI 25 DI 25 40901 0 nvoXXXOpControl SNVT_switch Aux_1 BI 26 DI 26 40901 1 nvoXXXAux1 SNVT_switch Aux_2 BI 27 DI 27 40901 2 nvoXXXAux2 SNVT_switch Aux_3 BI 28 DI 28 40901 3 nvoXXXAux3 SNVT_switch High_water BI 29 DI 29 40901 4 nvoXXXHiwater SNVT_switch Low_Water BI 30 DI 30 40901 5 nvoXXXLoWater SNVT_switch High_Oil_Temp BI 31 DI 31 40901 6 nvoXXXHiOilTemp SNVT_switch Low_Oil_Temp BI 32 DI 32 40901 7 nvoXXXLoOilTemp SNVT_switch Low_Oil_Press BI 33 DI 33 40902 0 nvoXXXLoOilPress SNVT_switch Low_Atom_Media BI 34 DI 34 40902 1 nvoXXXLoAtomMedia SNVT_switch Low_Gas_Press BI 35 DI 35 40902 2 nvoXXXLoGasPress SNVT_switch High_Gas_Press BI 36 DI 36 40902 3 nvoXXXHiGasPress SNVT_switch Aux_Gas BI 37 DI 37 40902 4 nvoXXXAuxGas SNVT_switch High_Press BI 38 DI 38 40902 5 nvoXXXHiPress SNVT_switch High_Temp BI 39 DI 39 40902 6 nvoXXXHiTemp SNVT_switch Aux_4 BI 40 DI 40 40902 7 nvoXXXAux4 SNVT_switch Aux_5 BI 41 DI 41 40903 0 nvoXXXAux5 SNVT_switch Aux_6 BI 42 DI 42 40903 1 nvoXXXAux6 SNVT_switch Aux_7 BI 43 DI 43 40903 2 nvoXXXAux7 SNVT_switch Air_Flow BI 44 DI 44 40903 3 nvoXXXAirFLo SNVT_switch 750-361 37 ProtoNode Gateway B.5. HSC Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet  Object Type AI BACnet  Object ID 1 N2 Data  Type AI N2 Point  Address 1 Modbus  Register 30021 TBD TBD C Boiler 1 Alarm Word AI 2 AI 2 30022 TBD TBD C Boiler 1 Hours Word 1 AI 3 AI 3 30023 TBD TBD C Boiler 1 Hours Word 2 AI 4 AI 4 30024 TBD TBD C Boiler 1 Cycles Word 1 AI 5 AI 5 30025 TBD TBD C Boiler 1 Cycles Word 2 AI 6 AI 6 30026 TBD TBD C Boiler 1 Status Bits AI 7 AI 7 30027 TBD TBD C Boiler 1 Inlet Temp AI 8 AI 8 30028 TBD TBD C Boiler 1 Fire Delay AI 9 AI 9 30029 TBD TBD C Boiler 1 Outlet Temp AI 10 AI 10 30030 TBD TBD Point Name C Boiler 1 State Lon Name Lon SNVT C Boiler 2 State AI 11 AI 11 30031 TBD TBD C Boiler 2 Alarm Word AI 12 AI 12 30032 TBD TBD C Boiler 2 Hours Word 1 AI 13 AI 13 30033 TBD TBD C Boiler 2 Hours Word 2 AI 14 AI 14 30034 TBD TBD C Boiler 2 Cycles Word 1 AI 15 AI 15 30035 TBD TBD C Boiler 2 Cycles Word 2 AI 16 AI 16 30036 TBD TBD C Boiler 2 Status Bits AI 17 AI 17 30037 TBD TBD C Boiler 2 Inlet Temp AI 18 AI 18 30038 TBD TBD C Boiler 2 Fire Delay AI 19 AI 19 30039 TBD TBD C Boiler 2 Outlet Temp AI 20 AI 20 30040 TBD TBD C Boiler 3 State AI 21 AI 21 30041 TBD TBD C Boiler 3 Alarm Word AI 22 AI 22 30042 TBD TBD C Boiler 3 Hours Word 1 AI 23 AI 23 30043 TBD TBD C Boiler 3 Hours Word 2 AI 24 AI 24 30044 TBD TBD C Boiler 3 Cycles Word 1 AI 25 AI 25 30045 TBD TBD C Boiler 3 Cycles Word 2 AI 26 AI 26 30046 TBD TBD C Boiler 3 Status Bits AI 27 AI 27 30047 TBD TBD C Boiler 3 Inlet Temp AI 28 AI 28 30048 TBD TBD C Boiler 3 Fire Delay AI 29 AI 29 30049 TBD TBD C Boiler 3 Outlet Temp AI 30 AI 30 30050 TBD TBD C Boiler 4 State AI 31 AI 31 30051 TBD TBD C Boiler 4 Alarm Word AI 32 AI 32 30052 TBD TBD C Boiler 4 Hours Word 1 AI 33 AI 33 30053 TBD TBD C Boiler 4 Hours Word 2 AI 34 AI 34 30054 TBD TBD C Boiler 4 Cycles Word 1 AI 35 AI 35 30055 TBD TBD C Boiler 4 Cycles Word 2 AI 36 AI 36 30056 TBD TBD C Boiler 4 Status Bits AI 37 AI 37 30057 TBD TBD C Boiler 4 Inlet Temp AI 38 AI 38 30058 TBD TBD C Boiler 4 Fire Delay AI 39 AI 39 30059 TBD TBD C Boiler 4 Outlet Temp AI 40 AI 40 30060 TBD TBD C Boiler 5 State AI 41 AI 41 30061 TBD TBD C Boiler 5 Alarm Word AI 42 AI 42 30062 TBD TBD C Boiler 5 Hours Word 1 AI 43 AI 43 30063 TBD TBD C Boiler 5 Hours Word 2 AI 44 AI 44 30064 TBD TBD C Boiler 5 Cycles Word 1 AI 45 AI 45 30065 TBD TBD C Boiler 5 Cycles Word 2 AI 46 AI 46 30066 TBD TBD C Boiler 5 Status Bits AI 47 AI 47 30067 TBD TBD 38 750-361 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) C Boiler 5 Inlet Temp AI 48 AI 48 30068 C Boiler 5 Fire Delay AI C Boiler 5 Outlet Temp AI TBD TBD 49 AI 49 30069 TBD TBD 50 AI 50 30070 TBD TBD C Boiler 6 State AI 51 AI 51 30071 TBD TBD C Boiler 6 Alarm Word AI 52 AI 52 30072 TBD TBD C Boiler 6 Hours Word 1 AI 53 AI 53 30073 TBD TBD C Boiler 6 Hours Word 2 AI 54 AI 54 30074 TBD TBD C Boiler 6 Cycles Word 1 AI 55 AI 55 30075 TBD TBD C Boiler 6 Cycles Word 2 AI 56 AI 56 30076 TBD TBD C Boiler 6 Status Bits AI 57 AI 57 30077 TBD TBD C Boiler 6 Inlet Temp AI 58 AI 58 30078 TBD TBD C Boiler 6 Fire Delay AI 59 AI 59 30079 TBD TBD C Boiler 6 Outlet Temp AI 60 AI 60 30080 TBD TBD C Boiler 7 State AI 61 AI 61 30081 TBD TBD C Boiler 7 Alarm Word AI 62 AI 62 30082 TBD TBD C Boiler 7 Hours Word 1 AI 63 AI 63 30083 TBD TBD C Boiler 7 Hours Word 2 AI 64 AI 64 30084 TBD TBD C Boiler 7 Cycles Word 1 AI 65 AI 65 30085 TBD TBD C Boiler 7 Cycles Word 2 AI 66 AI 66 30086 TBD TBD C Boiler 7 Status Bits AI 67 AI 67 30087 TBD TBD C Boiler 7 Inlet Temp AI 68 AI 68 30088 TBD TBD C Boiler 7 Fire Delay AI 69 AI 69 30089 TBD TBD C Boiler 7 Outlet Temp AI 70 AI 70 30090 TBD TBD C Boiler 8 State AI 71 AI 71 30091 TBD TBD C Boiler 8 Alarm Word AI 72 AI 72 30092 TBD TBD C Boiler 8 Hours Word 1 AI 73 AI 73 30093 TBD TBD C Boiler 8 Hours Word 2 AI 74 AI 74 30094 TBD TBD C Boiler 8 Cycles Word 1 AI 75 AI 75 30095 TBD TBD C Boiler 8 Cycles Word 2 AI 76 AI 76 30096 TBD TBD C Boiler 8 Status Bits AI 77 AI 77 30097 TBD TBD C Boiler 8 Inlet Temp AI 78 AI 78 30098 TBD TBD C Boiler 8 Fire Delay AI 79 AI 79 30099 TBD TBD C Boiler 8 Outlet Temp AI 80 AI 80 30100 TBD TBD C Boiler 9 State AI 81 AI 81 30101 TBD TBD C Boiler 9 Alarm Word AI 82 AI 82 30102 TBD TBD C Boiler 9 Hours Word 1 AI 83 AI 83 30103 TBD TBD C Boiler 9 Hours Word 2 AI 84 AI 84 30104 TBD TBD C Boiler 9 Cycles Word 1 AI 85 AI 85 30105 TBD TBD C Boiler 9 Cycles Word 2 AI 86 AI 86 30106 TBD TBD C Boiler 9 Status Bits AI 87 AI 87 30107 TBD TBD C Boiler 9 Inlet Temp AI 88 AI 88 30108 TBD TBD C Boiler 9 Fire Delay AI 89 AI 89 30109 TBD TBD C Boiler 9 Outlet Temp AI 90 AI 90 30110 TBD TBD C Boiler 10 State AI 91 AI 91 30111 TBD TBD C Boiler 10 Alarm Word AI 92 AI 92 30112 TBD TBD C Boiler 10 Hours Word 1 AI 93 AI 93 30113 TBD TBD C Boiler 10 Hours Word 2 AI 94 AI 94 30114 TBD TBD C Boiler 10 Cycles Word 1 AI 95 AI 95 30115 TBD TBD C Boiler 10 Cycles Word 2 AI 96 AI 96 30116 TBD TBD C Boiler 10 Status Bits AI 97 AI 97 30117 TBD TBD 750-361 39 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) C Boiler 10 Inlet Temp AI 98 AI 98 30118 TBD TBD C Boiler 10 Fire Delay C Boiler 10 Outlet Temp AI 99 AI 100 AI 99 AI 100 30119 TBD TBD 30120 TBD NC Boiler A State AI 101 AI TBD 101 30121 TBD NC Boiler A Alarm Word AI 102 TBD AI 102 30122 TBD NC Boiler A Hours Word 1 AI TBD 103 AI 103 30123 TBD NC Boiler A Hours Word 2 TBD AI 104 AI 104 30124 TBD TBD NC Boiler A Cycles Word 1 AI 105 AI 105 30125 TBD TBD NC Boiler A Cycles Word 2 AI 106 AI 106 30126 TBD TBD NC Boiler A Status Bits AI 107 AI 107 30127 TBD TBD NC Boiler A Inlet Temp AI 108 AI 108 30128 TBD TBD NC Boiler A Fire Delay AI 109 AI 109 30129 TBD TBD NC Boiler A Outlet Temp AI 110 AI 110 30130 TBD TBD NC Boiler B State AI 111 AI 111 30131 TBD TBD NC Boiler B Alarm Word AI 112 AI 112 30132 TBD TBD NC Boiler B Hours Word 1 AI 113 AI 113 30133 TBD TBD NC Boiler B Hours Word 2 AI 114 AI 114 30134 TBD TBD NC Boiler B Cycles Word 1 AI 115 AI 115 30135 TBD TBD NC Boiler B Cycles Word 2 AI 116 AI 116 30136 TBD TBD NC Boiler B Status Bits AI 117 AI 117 30137 TBD TBD NC Boiler B Inlet Temp AI 118 AI 118 30138 TBD TBD NC Boiler B Fire Delay AI 119 AI 119 30139 TBD TBD NC Boiler B Outlet Temp AI 120 AI 120 30140 TBD TBD NC Boiler C State AI 121 AI 121 30141 TBD TBD NC Boiler C Alarm Word AI 122 AI 122 30142 TBD TBD NC Boiler C Hours Word 1 AI 123 AI 123 30143 TBD TBD NC Boiler C Hours Word 2 AI 124 AI 124 30144 TBD TBD NC Boiler C Cycles Word 1 AI 125 AI 125 30145 TBD TBD NC Boiler C Cycles Word 2 AI 126 AI 126 30146 TBD TBD NC Boiler C Status Bits AI 127 AI 127 30147 TBD TBD NC Boiler C Inlet Temp AI 128 AI 128 30148 TBD TBD NC Boiler C Fire Delay AI 129 AI 129 30149 TBD TBD NC Boiler C Outlet Temp AI 130 AI 130 30150 TBD TBD NC Boiler D State AI 131 AI 131 30151 TBD TBD NC Boiler D Alarm Word AI 132 AI 132 30152 TBD TBD NC Boiler D Hours Word 1 AI 133 AI 133 30153 TBD TBD NC Boiler D Hours Word 2 AI 134 AI 134 30154 TBD TBD NC Boiler D Cycles Word 1 AI 135 AI 135 30155 TBD TBD NC Boiler D Cycles Word 2 AI 136 AI 136 30156 TBD TBD NC Boiler D Status Bits AI 137 AI 137 30157 TBD TBD NC Boiler D Inlet Temp AI 138 AI 138 30158 TBD TBD NC Boiler D Fire Delay AI 139 AI 139 30159 TBD TBD NC Boiler D Outlet Temp AI 140 AI 140 30160 TBD TBD NC Boiler E State AI 141 AI 141 30161 TBD TBD NC Boiler E Alarm Word AI 142 AI 142 30162 TBD TBD NC Boiler E Hours Word 1 AI 143 AI 143 30163 TBD TBD NC Boiler E Hours Word 2 AI 144 AI 144 30164 TBD TBD NC Boiler E Cycles Word 1 AI 145 AI 145 30165 TBD TBD NC Boiler E Cycles Word 2 AI 146 AI 146 30166 TBD TBD NC Boiler E Status Bits AI 147 AI 147 30167 TBD TBD 40 750-361 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) NC Boiler E Inlet Temp AI 148 AI 148 30168 TBD TBD NC Boiler E Fire Delay AI 149 AI 149 NC Boiler E Outlet Temp AI 150 AI 150 30169 TBD TBD 30170 TBD NC Boiler F State AI 151 AI TBD 151 30171 TBD NC Boiler F Alarm Word AI 152 TBD AI 152 30172 TBD NC Boiler F Hours Word 1 AI TBD 153 AI 153 30173 TBD NC Boiler F Hours Word 2 TBD AI 154 AI 154 30174 TBD TBD NC Boiler F Cycles Word 1 AI 155 AI 155 30175 TBD TBD NC Boiler F Cycles Word 2 AI 156 AI 156 30176 TBD TBD NC Boiler F Status Bits AI 157 AI 157 30177 TBD TBD NC Boiler F Inlet Temp AI 158 AI 158 30178 TBD TBD NC Boiler F Fire Delay AI 159 AI 159 30179 TBD TBD NC Boiler F Outlet Temp AI 160 AI 160 30180 TBD TBD NC Boiler G State AI 161 AI 161 30181 TBD TBD NC Boiler G Alarm Word AI 162 AI 162 30182 TBD TBD NC Boiler G Hours Word 1 AI 163 AI 163 30183 TBD TBD NC Boiler G Hours Word 2 AI 164 AI 164 30184 TBD TBD NC Boiler G Cycles Word 1 AI 165 AI 165 30185 TBD TBD NC Boiler G Cycles Word 2 AI 166 AI 166 30186 TBD TBD NC Boiler G Status Bits AI 167 AI 167 30187 TBD TBD NC Boiler G Inlet Temp AI 168 AI 168 30188 TBD TBD NC Boiler G Fire Delay AI 169 AI 169 30189 TBD TBD TBD NC Boiler G Outlet Temp AI 170 AI 170 30190 TBD NC Boiler H State AI 171 AI 171 30191 TBD TBD NC Boiler H Alarm Word AI 172 AI 172 30192 TBD TBD NC Boiler H Hours Word 1 AI 173 AI 173 30193 TBD TBD NC Boiler H Hours Word 2 AI 174 AI 174 30194 TBD TBD NC Boiler H Cycles Word 1 AI 175 AI 175 30195 TBD TBD NC Boiler H Cycles Word 2 AI 176 AI 176 30196 TBD TBD NC Boiler H Status Bits AI 177 AI 177 30197 TBD TBD NC Boiler H Inlet Temp AI 178 AI 178 30198 TBD TBD NC Boiler H Fire Delay AI 179 AI 179 30199 TBD TBD NC Boiler H Outlet Temp AI 180 AI 180 30200 TBD TBD NC Boiler I State AI 181 AI 181 30201 TBD TBD NC Boiler I Alarm Word AI 182 AI 182 30202 TBD TBD NC Boiler I Hours Word 1 AI 183 AI 183 30203 TBD TBD NC Boiler I Hours Word 2 AI 184 AI 184 30204 TBD TBD NC Boiler I Cycles Word 1 AI 185 AI 185 30205 TBD TBD NC Boiler I Cycles Word 2 AI 186 AI 186 30206 TBD TBD NC Boiler I Status Bits AI 187 AI 187 30207 TBD TBD NC Boiler I Inlet Temp AI 188 AI 188 30208 TBD TBD NC Boiler I Fire Delay AI 189 AI 189 30209 TBD TBD NC Boiler I Outlet Temp AI 190 AI 190 30210 TBD TBD NC Boiler J State AI 191 AI 191 30211 TBD TBD NC Boiler J Alarm Word AI 192 AI 192 30212 TBD TBD NC Boiler J Hours Word 1 AI 193 AI 193 30213 TBD TBD NC Boiler J Hours Word 2 AI 194 AI 194 30214 TBD TBD NC Boiler J Cycles Word 1 AI 195 AI 195 30215 TBD TBD NC Boiler J Cycles Word 2 AI 196 AI 196 30216 TBD TBD NC Boiler J Status Bits AI 197 AI 197 30217 TBD TBD 750-361 41 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) NC Boiler J Inlet Temp AI 198 AI 198 30218 TBD TBD NC Boiler J Fire Delay AI 199 AI 199 30219 TBD TBD NC Boiler J Outlet Temp AI 200 AI 200 30220 TBD TBD Rem System Pump Module Input Word AI 201 AI 201 30221 TBD TBD Rem System Pump Module Output Word AI 202 AI 202 30222 TBD TBD Number of Remote System Pumps AI 203 AI 203 30223 TBD TBD Pump Module Analog In 1 Scaled Value AI 247 AI 247 30224 TBD TBD Pump Module Analog In 2 Scaled Value AI 248 AI 248 30226 TBD TBD System Pump Speed Requested AI 249 AI 249 30228 TBD TBD Pump PID Process Variable AI 250 AI 250 30230 TBD TBD Pump PID Setpoint AI 251 AI 251 30232 TBD TBD Rem System Pump Lead Pump Number AI 204 AI 204 30234 TBD TBD Rem System Pump Lag1 Pump Number AI 205 AI 205 30235 TBD TBD Rem System Pump Lag2 Pump Number AI 206 AI 206 30236 TBD TBD Rem System Pump Lag3 Pump Number AI 207 AI 207 30237 TBD TBD Alarm Word 1 Value AI 208 AI 208 30300 TBD TBD Alarm Word 2 Value AI 209 AI 209 30301 TBD TBD Digital Input Word Value AI 210 AI 210 30302 TBD TBD Digital Output Word 1 Value AI 211 AI 211 30303 TBD TBD Digital Output Word 2 Value AI 212 AI 212 30304 TBD TBD Number of Cond Boilers Running AI 213 AI 213 30305 TBD TBD Number of Cond Boilers Requested AI 214 AI 214 30306 TBD TBD Number of Non‐Cond Boilers Running AI 215 AI 215 30307 TBD TBD Number of Non‐Cond Boilers Requested AI 216 AI 216 30308 TBD TBD Number of Cond Boilers in System AI 217 AI 217 30309 TBD TBD Number of Non‐Cond Boilers in System AI 218 AI 218 30310 TBD TBD Cond Lead Boiler Number AI 219 AI 219 30311 TBD TBD Cond Lag1 Boiler Number AI 220 AI 220 30312 TBD TBD Cond Lag2 Boiler Number AI 221 AI 221 30313 TBD TBD Cond Lag3 Boiler Number AI 222 AI 222 30314 TBD TBD Cond Lag4 Boiler Number AI 223 AI 223 30315 TBD TBD Cond Lag5 Boiler Number AI 224 AI 224 30316 TBD TBD Cond Lag6 Boiler Number AI 225 AI 225 30317 TBD TBD Cond Lag7 Boiler Number AI 226 AI 226 30318 TBD TBD Cond Lag8 Boiler Number AI 227 AI 227 30319 TBD TBD Cond Lag9 Boiler Number AI 228 AI 228 30320 TBD TBD Non‐Cond Lead Boiler Number AI 229 AI 229 30321 TBD TBD Non‐Cond Lag1 Boiler Number AI 230 AI 230 30322 TBD TBD Non‐Cond Lag2 Boiler Number AI 231 AI 231 30323 TBD TBD Non‐Cond Lag3 Boiler Number AI 232 AI 232 30324 TBD TBD Non‐Cond Lag4 Boiler Number AI 233 AI 233 30325 TBD TBD Non‐Cond Lag5 Boiler Number AI 234 AI 234 30326 TBD TBD Non‐Cond Lag6 Boiler Number AI 235 AI 235 30327 TBD TBD Non‐Cond Lag7 Boiler Number AI 236 AI 236 30328 TBD TBD Non‐Cond Lag8 Boiler Number AI 237 AI 237 30329 TBD TBD Non‐Cond Lag9 Boiler Number AI 238 AI 238 30330 TBD TBD Damper Mod 1 Input (Prove) Data AI 239 AI 239 30340 TBD TBD Damper Mod 1 Output (Reqired) Data AI 240 AI 240 30341 TBD TBD Damper Mod 2 Input (Prove) Data AI 241 AI 241 30342 TBD TBD Damper Mod 2 Output (Reqired) Data AI 242 AI 242 30343 TBD TBD 42 750-361 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * Damper Mod 3 Input (Prove) Data AI 243 AI 243 30344 TBD TBD Damper Mod 3 Output (Reqired) Data AI 244 AI 244 30345 TBD TBD Damper Mod 4 Input (Prove) Data AI 245 AI 245 30346 TBD TBD Damper Mod 4 Output (Reqired) Data AI 246 AI 246 30347 TBD TBD Cond Boiler Header Temp AI 252 AI 252 40280 TBD TBD Main Supply Header Temp AI 253 AI 253 40282 TBD TBD System Return Temp AI 254 AI 254 40284 TBD TBD OA Temp or Remote Analog SP Value AI 255 AI 255 40286 TBD TBD DHW Setpoint AI 256 AI 256 40300 TBD TBD Cold Building Setpoint AI 257 ADF 1 40304 TBD TBD Remote Analog Input Setpoint Value AI 258 ADF 2 40306 TBD TBD Remote Modbus Setpoint Value AV 1 AO 1 40308 TBD TBD Remote Modbus Outdoor Air Temp AV 2 AO 2 40310 TBD TBD Remote Modbus System Enable AV 3 AO 3 40312 TBD TBD Modbus Heartbeat AV 4 AO 4 40314 TBD TBD Deadband Cond/Non‐Cond Mode Sw Temp AI 259 ADF 3 40318 TBD TBD OA Temp Low Value for Reset Curve AI 260 ADF 4 40320 TBD TBD OA Temp High Value for Reset Curve AI 261 ADF 5 40322 TBD TBD Loop Setpoint at Cold (low) OAT AI 262 ADF 6 40324 TBD TBD Loop Setpoint at Warm (high) OAT AI 263 ADF 7 40326 TBD TBD Min Inlet Temp for Non‐Cond Boilers AI 264 ADF 8 40328 TBD TBD Non‐Cond Reset Shift AI 265 ADF 9 40336 TBD TBD NC/Cond Switch Temp AI 266 ADF 10 40338 TBD TBD Read only NC Header SP (active) AI 267 ADF 11 40340 TBD TBD Read only Cond Header SP (active) AI 268 ADF 12 40342 TBD TBD System Mode AI 312 ADF 13 40344 TBD TBD Cond Boiler Status AI 313 ADF 14 40345 TBD TBD Non‐Cond Boiler Status AI 314 ADF 15 40346 TBD TBD Firing rate for Cond boiler group AI 269 ADF 16 40348 TBD TBD Firing rate for non‐Cond boiler group AI 270 ADF 17 40350 TBD TBD Warm Weather Shutdown Temp AI 271 ADF 18 40352 TBD TBD Cond Boiler 1 Run Hours AI 272 ADF 19 40390 TBD TBD Cond Boiler 2 Run Hours AI 273 ADF 20 40392 TBD TBD Cond Boiler 3 Run Hours AI 274 ADF 21 40394 TBD TBD Cond Boiler 4 Run Hours AI 275 ADF 22 40396 TBD TBD Cond Boiler 5 Run Hours AI 276 ADF 23 40398 TBD TBD Cond Boiler 6 Run Hours AI 277 ADF 24 40400 TBD TBD Cond Boiler 7 Run Hours AI 278 ADF 25 40402 TBD TBD Cond Boiler 8 Run Hours AI 279 ADF 26 40404 TBD TBD Cond Boiler 9 Run Hours AI 280 ADF 27 40406 TBD TBD Cond Boiler 10 Run Hours AI 281 ADF 28 40408 TBD TBD Non‐Cond Boiler A Run Hours AI 282 ADF 29 40410 TBD TBD Non‐Cond Boiler B Run Hours AI 283 ADF 30 40412 TBD TBD Non‐Cond Boiler C Run Hours AI 284 ADF 31 40414 TBD TBD Non‐Cond Boiler D Run Hours AI 285 ADF 32 40416 TBD TBD Non‐Cond Boiler E Run Hours AI 286 ADF 33 40418 TBD TBD Non‐Cond Boiler F Run Hours AI 287 ADF 34 40420 TBD TBD Non‐Cond Boiler G Run Hours AI 288 ADF 35 40422 TBD TBD Non‐Cond Boiler H Run Hours AI 289 ADF 36 40424 TBD TBD Non‐Cond Boiler I Run Hours AI 290 ADF 37 40426 TBD TBD 750-361 43 ProtoNode Gateway Table 15: HSC Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Non‐Cond Boiler J Run Hours AI 291 ADF 38 40428 TBD TBD Cond Boiler 1 Run Cycles AI 292 ADF 39 40430 TBD TBD Cond Boiler 2 Run Cycles AI 293 ADF 40 40432 TBD TBD Cond Boiler 3 Run Cycles AI 294 ADF 41 40434 TBD TBD Cond Boiler 4 Run Cycles AI 295 ADF 42 40436 TBD TBD Cond Boiler 5 Run Cycles AI 296 ADF 43 40438 TBD TBD Cond Boiler 6 Run Cycles AI 297 ADF 44 40440 TBD TBD Cond Boiler 7 Run Cycles AI 298 ADF 45 40442 TBD TBD Cond Boiler 8 Run Cycles AI 299 ADF 46 40444 TBD TBD TBD Cond Boiler 9 Run Cycles AI 300 ADF 47 40446 TBD Cond Boiler 10 Run Cycles AI 301 ADF 48 40448 TBD TBD Non‐Cond Boiler A Run Cycles AI 302 ADF 49 40450 TBD TBD Non‐Cond Boiler B Run Cycles AI 303 ADF 50 40452 TBD TBD Non‐Cond Boiler C Run Cycles AI 304 ADF 51 40454 TBD TBD Non‐Cond Boiler D Run Cycles AI 305 ADF 52 40456 TBD TBD Non‐Cond Boiler E Run Cycles AI 306 ADF 53 40458 TBD TBD Non‐Cond Boiler F Run Cycles AI 307 ADF 54 40460 TBD TBD Non‐Cond Boiler G Run Cycles AI 308 ADF 55 40462 TBD TBD Non‐Cond Boiler H Run Cycles AI 309 ADF 56 40464 TBD TBD Non‐Cond Boiler I Run Cycles AI 310 ADF 57 40466 TBD TBD Non‐Cond Boiler J Run Cycles AI 311 ADF 58 40468 TBD TBD *Write points 44 750-361 ProtoNode Gateway B.6. LCS Table 16: LCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Tank 1 Level BACnet Object  Type AI BACnet  Object ID 101 N2 Data  Type AI N2 Point  Address 1 Modbus  Register 40050 Tank 2 Level AI 102 AI 2 40051 Point Name Lon Name Lon SNVT TBD TBD TBD TBD Primary Valve Position AI 103 AI 3 40052 TBD TBD Secondary Valve Position AI 104 AI 4 40053 TBD TBD Digital Inputs AI 105 AI 5 40054 TBD TBD Digital Outputs AI 106 AI 6 40055 TBD TBD Alarm Word AI 107 AI 7 40056 TBD TBD Tank 1 Level Setpoint AI 108 AI 8 40057 TBD TBD Tank 2 Level Setpoint AI 109 AI 9 40058 TBD TBD Common Alarm BI 230 DI 30 10001 TBD TBD Tank 1 LWCO Alarm BI 231 DI 31 10002 TBD TBD Tank 1 LLW Alarm BI 232 DI 32 10003 TBD TBD Tank 1 LW Alarm BI 233 DI 33 10004 TBD TBD Tank 1 HW Alarm BI 234 DI 34 10005 TBD TBD Tank 1 HHW Alarm BI 235 DI 35 10006 TBD TBD Tank 2 LWCO Alarm BI 236 DI 36 10007 TBD TBD Tank 2 LLW Alarm BI 237 DI 37 10008 TBD TBD Tank 2 LW Alarm BI 238 DI 38 10009 TBD TBD Tank 2 HW Alarm BI 239 DI 39 10010 TBD TBD Tank 2 HHW Alarm BI 240 DI 40 10011 TBD TBD Analog In Failure BI 241 DI 41 10012 TBD TBD Spare Alarm Bit 40056_12 BI 242 DI 42 10013 TBD TBD Spare Alarm Bit 40056_13 BI 243 DI 43 10014 TBD TBD Spare Alarm Bit 40056_14 BI 244 DI 44 10015 TBD TBD Spare Alarm Bit 40056_15 BI 245 DI 45 10016 TBD TBD Tank 1 LWCO Contacts BI 246 DI 46 10017 TBD TBD Tank 1 LLW Contacts BI 247 DI 47 10018 TBD TBD Tank 1 LW Contacts BI 248 DI 48 10019 TBD TBD Tank 1 HW Contacts BI 249 DI 49 10020 TBD TBD Tank 1 HHW Contacts BI 250 DI 50 10021 TBD TBD Tank 2 LWCO Contacts BI 251 DI 51 10022 TBD TBD Tank 2 LLW Contacts BI 252 DI 52 10023 TBD TBD Tank 2 LW Contacts BI 253 DI 53 10024 TBD TBD Tank 2 HW Contacts BI 254 DI 54 10025 TBD TBD Tank 2 HHW Contacts BI 255 DI 55 10026 TBD TBD Digital Input 1 Status BI 256 DI 56 10027 TBD TBD Digital Input 2 Status BI 257 DI 57 10028 TBD TBD Digital Input 3 Status BI 258 DI 58 10029 TBD TBD Digital Input 4 Status BI 259 DI 59 10030 TBD TBD Digital Input 5 Status BI 260 DI 60 10031 TBD TBD Digital Input 6 Status BI 261 DI 61 10032 TBD TBD Digital Input 7 Status BI 262 DI 62 10033 TBD TBD Digital Input 8 Status BI 263 DI 63 10034 TBD TBD Digital Input 9 Status BI 264 DI 64 10035 TBD TBD Digital Input 10 Status BI 265 DI 65 10036 TBD TBD Digital Input 11 Status BI 266 DI 66 10037 TBD TBD Digital Input 12 Status BI 267 DI 67 10038 TBD TBD 750-361 45 ProtoNode Gateway Table 16: LCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Digital Output 1 Status BI 268 DI 68 10039 TBD TBD Digital Output 2 Status BI 269 DI 69 10040 TBD TBD Digital Output 3 Status BI 270 DI 70 10041 TBD TBD Digital Output 4 Status BI 271 DI 71 10042 TBD TBD Digital Output 5 Status BI 272 DI 72 10043 TBD TBD Digital Output 6 Status BI 273 DI 73 10044 TBD TBD Digital Output 7 Status BI 274 DI 74 10045 TBD TBD Digital Output 8 Status BI 275 DI 75 10046 TBD TBD Digital Output 9 Status BI 276 DI 76 10047 TBD TBD Digital Output 10 Status BI 277 DI 77 10048 TBD TBD Digital Output 11 Status BI 278 DI 78 10049 TBD TBD Digital Output 12 Status BI 279 DI 79 10050 TBD TBD 46 750-361 ProtoNode Gateway B.7. PCS Table 17: PCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Header Pressure/Tank Level   BACnet  Object Type AI BACnet  Object ID 1 N2 Data  Type AI N2 Point  Address 1 Modbus  Register 40050 VSD Speed PID Loop Setpoint  AI 2 AI 2 40051 Reserved                     AI 3 AI 3 VSD Speed PID Loop Output    AI 4 AI 4 Digital Input Word           AI 5 AI Digital Output Word          AI 6 Alarm Word 1                 AI Alarm Word 2                 Point Name Lon Name Lon SNVT TBD TBD TBD TBD 40052 TBD TBD 40053 TBD TBD 5 40054 TBD TBD AI 6 40055 TBD TBD 7 AI 7 40056 TBD TBD AI 8 AI 8 40057 TBD TBD Lead Pump                    AI 9 AI 9 40058 TBD TBD Lag 1 Pump                   AI 10 AI 10 40059 TBD TBD Lag 2 Pump                   AI 11 AI 11 40060 TBD TBD Standby Pump                 AI 12 AI 12 40061 TBD TBD Pump 1 Hours (10 000s)       AI 13 AI 13 40062 TBD TBD Pump 1 Hours (1s)            AI 14 AI 14 40063 TBD TBD Pump 2 Hours (10 000s)       AI 15 AI 15 40064 TBD TBD Pump 2 Hours (1s)            AI 16 AI 16 40065 TBD TBD Pump 3 Hours (10 000s)       AI 17 AI 17 40066 TBD TBD Pump 3 Hours (1s)            AI 18 AI 18 40067 TBD TBD Pump 4 Hours (10 000s)       AI 19 AI 19 40068 TBD TBD Pump 4 Hours (1s)            AI 20 AI 20 40069 TBD TBD VSD Speed Output Signal      AI 21 AI 21 40070 TBD TBD Pump 1 Fault                 BI 1 DI 1 10001 TBD TBD Pump 2 Fault                 BI 2 DI 2 10002 TBD TBD Pump 3 Fault                 BI 3 DI 3 10003 TBD TBD Pump 4 Fault                 BI 4 DI 4 10004 TBD TBD Header Pressure Low Alm      BI 5 DI 5 10005 TBD TBD Header Pressure High Alm     BI 6 DI 6 10006 TBD TBD Analog Signal Failure        BI 7 DI 7 10007 TBD TBD Datalog SD Card Full         BI 8 DI 8 10008 TBD TBD Pump 1 in Manual Mode        BI 9 DI 9 10009 TBD TBD Pump 2 in Manual Mode        BI 10 DI 10 10010 TBD TBD Pump 3 in Manual Mode        BI 11 DI 11 10011 TBD TBD Pump 4 in Manual Mode        BI 12 DI 12 10012 TBD TBD Source Tank LWCO             BI 13 DI 13 10013 TBD TBD Low Battery                  BI 14 DI 14 10014 TBD TBD External Alm                 BI 15 DI 15 10015 TBD TBD Level Low Alm                BI 16 DI 16 10016 TBD TBD Level High Alm               BI 17 DI 17 10017 TBD TBD Alarm Word Bit 1             BI 18 DI 18 10018 TBD TBD Alarm Word Bit 2             BI 19 DI 19 10019 TBD TBD Alarm Word Bit 3             BI 20 DI 20 10020 TBD TBD Alarm Word Bit 4             BI 21 DI 21 10021 TBD TBD Alarm Word Bit 5             BI 22 DI 22 10022 TBD TBD Alarm Word Bit 6             BI 23 DI 23 10023 TBD TBD Alarm Word Bit 7             BI 24 DI 24 10024 TBD TBD Alarm Word Bit 8             BI 25 DI 25 10025 TBD TBD Alarm Word Bit 9             BI 26 DI 26 10026 TBD TBD 750-361 47 ProtoNode Gateway Table 17: PCS Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Alarm Word Bit 10            BI 27 DI 27 10027 TBD TBD Alarm Word Bit 11            BI 28 DI 28 10028 TBD TBD Alarm Word Bit 12            BI 29 DI 29 10029 TBD TBD Alarm Word Bit 13            BI 30 DI 30 10030 TBD TBD Alarm Word Bit 14            BI 31 DI 31 10031 TBD TBD Alarm Word Bit 15  BI 32 DI 32 10032 TBD TBD 48 750-361 ProtoNode Gateway B.8. HAWK 1000 Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet  Object  Type BI BACnet  Object  ID 1 Modbus Comm Error BI 2 Lo Water BI Burner Control Alm Boiler Limits Open N2 Data  Type N2 Point  Address Modbus  Register Lon Name Lon SNVT DI 1 10001 TBD TBD DI 2 10002 TBD TBD 3 DI 3 10003 TBD TBD BI 4 DI 4 10004 TBD TBD BI 5 DI 5 10005 TBD TBD Hi Stack Temp Alm BI 6 DI 6 10006 TBD TBD Hi Stack Temp Shutdown BI 7 DI 7 10007 TBD TBD External Interlock BI 8 DI 8 10008 TBD TBD I/O module fault BI 9 DI 9 10009 TBD TBD Steam Sensor Fail BI 10 DI 10 10010 TBD TBD Air Actuator Out Of Pos Alm BI 11 DI 11 10011 TBD TBD Point Name Drive Fault NG Actuator Out Of Pos Alm BI 12 DI 12 10012 TBD TBD F/A Ratio Controller Fault BI 13 DI 13 10013 TBD TBD No Fuel Selected BI 14 DI 14 10014 TBD TBD Lo ControlLogix Battery BI 15 DI 15 10015 TBD TBD Non Recycle Limit Relay Fail BI 16 DI 16 10016 TBD TBD Recyle Limit Relay Fail BI 17 DI 17 10017 TBD TBD Remote Modulation Signal Fail BI 18 DI 18 10018 TBD TBD Header Pressure Sensor Fail BI 19 DI 19 10019 TBD TBD Temperature Channel 0‐5 Failure BI 20 DI 20 10020 TBD TBD Lo O2 Alm BI 21 DI 21 10021 TBD TBD Hi Limit Alm BI 22 DI 22 10022 TBD TBD ALWCO BI 23 DI 23 10023 TBD TBD Lo Gas Pressure/Lo Oil Temp BI 24 DI 24 10024 TBD TBD Hi Gas Pressure/Hi Oil Temp BI 25 DI 25 10025 TBD TBD Lo Oil Pressure BI 26 DI 26 10026 TBD TBD Hi Oil Pressure BI 27 DI 27 10027 TBD TBD Oil Drawer Switch Not Made BI 28 DI 28 10028 TBD TBD Lo Atomizing Air Pressure BI 29 DI 29 10029 TBD TBD Lo Combustion Air Pressure BI 30 DI 30 10030 TBD TBD AUX Alm 1 BI 31 DI 31 10031 TBD TBD AUX Alm 2 BI 32 DI 32 10032 TBD TBD Blower On BI 33 DI 33 10033 TBD TBD Purge Input BI 34 DI 34 10034 TBD TBD Release To Modulate Input BI 35 DI 35 10035 TBD TBD TBD Lo Fire Switch BI 36 DI 36 10036 TBD Hi Fire Switch BI 37 DI 37 10037 TBD TBD Ready to start/Limits Closed BI 38 DI 38 10038 TBD TBD External Start Interlock BI 39 DI 39 10039 TBD TBD ALFCO BI 40 DI 40 10040 TBD TBD Pilot BI 41 DI 41 10041 TBD TBD Main Fuel Valve Open BI 42 DI 42 10042 TBD TBD Fuel 1 Selected BI 43 DI 43 10043 TBD TBD Fuel 2 Selected BI 44 DI 44 10044 TBD TBD Heart Beat To BMS BI 45 DI 45 10045 TBD TBD LWCO Shutdown BI 46 DI 46 10046 TBD TBD 750-361 49 ProtoNode Gateway Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Remote Enable Input BI 47 DI 47 10047 TBD TBD Burner Switch BI 48 DI 48 10048 TBD TBD Recycle Limit Relay BI 49 DI 49 10049 TBD TBD External Device Start BI 50 DI 50 10050 TBD TBD Non Recycle Limit Relay BI 51 DI 51 10051 TBD TBD Drive to Lo Fire (FARC) BI 52 DI 52 10052 TBD TBD Start Slave Blr (2 Blr LL) BI 53 DI 53 10053 TBD TBD Load Demand Output BI 54 DI 54 10054 TBD TBD Alm Output BI 55 DI 55 10055 TBD TBD Boiler Ready (LL) BI 56 DI 56 10056 TBD TBD Boiler Load Demand BI 57 DI 57 10057 TBD TBD Firing Rate Remote/Llag BI 58 DI 58 10058 TBD TBD Firing Rate Manual BI 59 DI 59 10059 TBD TBD Firing Rate Auto BI 60 DI 60 10060 TBD TBD Hot Stand By BI 61 DI 61 10061 TBD TBD Warm Up BI 62 DI 62 10062 TBD TBD Fuel 3 Selected BI 63 DI 63 10063 TBD TBD Aux Alm 3 BI 64 DI 64 10064 TBD TBD Steam or Hot Water 1 = Steam BI 65 DI 65 10065 TBD TBD Level Master Present BI 66 DI 66 10066 TBD TBD Variable Speed Drive Present BI 67 DI 67 10067 TBD TBD Economizer Present BI 68 DI 68 10068 TBD TBD Combustion Air Temp Present BI 69 DI 69 10069 TBD TBD Economizer Inlet FW Sensor Present BI 70 DI 70 10070 TBD TBD O2 Analyzer Present BI 71 DI 71 10071 TBD TBD Feedwater or Return Temp Present BI 72 DI 72 10072 TBD TBD Outdoor Reset Selected BI 73 DI 73 10073 TBD TBD Parallel Posing Selected BI 74 DI 74 10074 TBD TBD Two Boiler Lead Lag Master Select BI 75 DI 75 10075 TBD TBD Two Boiler Lead Lag Slave Select BI 76 DI 76 10076 TBD TBD Master Panel Select BI 77 DI 77 10077 TBD TBD Hot Stand By Select BI 78 DI 78 10078 TBD TBD Dual Setpoint Select BI 79 DI 79 10079 TBD TBD Slot 8 Ch 0 Analog Input Selected BI 80 DI 80 10080 TBD TBD Slot 8 Ch 1 Analog Input Selected BI 81 DI 81 10081 TBD TBD Slot 8 Ch 2 Analog Input Selected BI 82 DI 82 10082 TBD TBD Slot 8 Ch 3 Analog Input Selected BI 83 DI 83 10083 TBD TBD Honeywell or Fireye 1 = Fireye BI 84 DI 84 10084 TBD TBD Hi Water Alm BI 85 DI 85 10085 TBD TBD Oil Actuator Out Of Pos Alm BI 86 DI 86 10086 TBD TBD FGR Actuator Out Of Pos Alm BI 87 DI 87 10087 TBD TBD Air Actuator Feedback Fail Lo Alm BI 88 DI 88 10088 TBD TBD Air Actuator Feedback Fail Hi Alm BI 89 DI 89 10089 TBD TBD NG Actuator Feedback Fail Lo Alm BI 90 DI 90 10090 TBD TBD NG Actuator Feedback Fail Hi Alm BI 91 DI 91 10091 TBD TBD Oil Actuator Feedback Fail Lo Alm BI 92 DI 92 10092 TBD TBD Oil Actuator Feedback Fail Hi Alm BI 93 DI 93 10093 TBD TBD FGR Actuator Feedback Fail Lo Alm BI 94 DI 94 10094 TBD TBD FGR Actuator Feedback Fail Hi Alm BI 95 DI 95 10095 TBD TBD VSD Deviation Alm BI 96 DI 96 10096 TBD TBD 50 750-361 ProtoNode Gateway Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Increase MSG Register Size Bit BI Air/Fuel Deviation Alm BI 2nd Stage CEC Economizer Selected BI Fuel3 Actuator Out Of Pos Alm BI Fuel3 Actuator Feedback Fail Lo Alm BI Fuel3 Actuator Feedback Fail Hi Alm 97 DI 97 10097 TBD TBD 98 DI 98 10098 TBD TBD 99 DI 99 10099 TBD TBD 100 DI 100 10100 TBD TBD 101 DI 101 10101 TBD TBD BI 102 DI 102 10102 TBD TBD Stack Pressure Input Fail BI 103 DI 103 10103 TBD TBD Hi Stack Pressure Alm BI 104 DI 104 10104 TBD TBD Stack Damper Not Open Alm BI 105 DI 105 10105 TBD TBD O2 Calibration Failed BI 106 DI 106 10106 TBD TBD Lo Steam Pressure/Water Temp Alm BI 107 DI 107 10107 TBD TBD Processor Test Fail Alm BI 108 DI 108 10108 TBD TBD O2 Trim Internal Alm BI 109 DI 109 10109 TBD TBD Firetube or Flextube 1 = Flextube BI 110 DI 110 10110 TBD TBD Reserved for Cleaver‐Brooks BI 111 DI 111 10111 TBD TBD VSD Limits Internal Alm BI 112 DI 112 10112 TBD TBD Gas Actuator 2 Out Of Pos Alm BI 113 DI 113 10113 TBD TBD Gas Actuator 2 Feedback Fail Lo Alm BI 114 DI 114 10114 TBD TBD Gas Actuator 2 Feedback Fail Hi Alm BI 115 DI 115 10115 TBD TBD Actuator Modbus Communication Error BI 116 DI 116 10116 TBD TBD Air Actuator Modbus Comm Error Node 1 BI 117 DI 117 10117 TBD TBD Gas Actuator Modbus Comm Error Node 2 BI 118 DI 118 10118 TBD TBD Gas Act 2 Modbus Comm Error Node 3 BI 119 DI 119 10119 TBD TBD Oil Actuator Modbus Comm Error Node 5 BI 120 DI 120 10120 TBD TBD FGR Actuator Modbus Comm Error Node 7 BI 121 DI 121 10121 TBD TBD Reserved BI 122 DI 122 10122 TBD TBD Reserved BI 123 DI 123 10123 TBD TBD 2nd Stg Outlet Wtr Temp Sensor Failed BI 124 DI 124 10124 TBD TBD Wtr Temp Second Stg Out Hi BI 125 DI 125 10125 TBD TBD Air Actuator Man Override Btn Press BI 126 DI 126 10126 TBD TBD Gas Actuator 1 Man Override Btn Press BI 127 DI 127 10127 TBD TBD Gas Actuator 2 Man Override Btn Press BI 128 DI 128 10128 TBD TBD Oil Actuator Man Override Btn Press BI 129 DI 129 10129 TBD TBD FGR Actuator Man Override Btn Press BI 130 DI 130 10130 TBD TBD Fuel 3 Act 1 Man Override Btn Press BI 131 DI 131 10131 TBD TBD Fuel 3 Act 2 Man Override Btn Press BI 132 DI 132 10132 TBD TBD Communication from BMS Failed BI 133 DI 133 10133 TBD TBD Combustion Air Pressure Hi BI 134 DI 134 10134 TBD TBD Wtr FLo Lo BI 135 DI 135 10135 TBD TBD Wtr Level Signal Failed BI 136 DI 136 10136 TBD TBD Remote Setpoint Signal Failed BI 137 DI 137 10137 TBD TBD Lo O2 Shutdown BI 138 DI 138 10138 TBD TBD Air Actuator Fault BI 139 DI 139 10139 TBD TBD Fuel 1 Actuator 1 Fault BI 140 DI 140 10140 TBD TBD Fuel 1 Actuator 2 Fault BI 141 DI 141 10141 TBD TBD Fuel 2 Actuator 1 Fault BI 142 DI 142 10142 TBD TBD Fuel 2 Actuator 2 Fault BI 143 DI 143 10143 TBD TBD FGR Actuator Fault BI 144 DI 144 10144 TBD TBD Fuel 2 Actuator 2 Pos Deviation BI 145 DI 145 10145 TBD TBD Fuel 2 Actuator 2 Feedback Lo BI 146 DI 146 10146 TBD TBD 750-361 51 ProtoNode Gateway Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Fuel 2 Actuator 2 Feedback Hi BI 147 DI 147 10147 TBD TBD Fuel 2 Actuator 2 Man PB Press BI 148 DI 148 10148 TBD TBD VFD Feedback Lo BI 149 DI 149 10149 TBD TBD VFD Feedback Hi BI 150 DI 150 10150 TBD TBD Master PIDE Instruction Fault BI 151 DI 151 10151 TBD TBD FGEN Fault BI 152 DI 152 10152 TBD TBD Outdoor Temp/Retrun Temp Sensor Failed BI 153 DI 153 10153 TBD TBD Combustion Air Temp Sensor Failed BI 154 DI 154 10154 TBD TBD O2 Sensor Fault BI 155 DI 155 10155 TBD TBD AB[9]11 BI 156 DI 156 10156 TBD TBD AB[9]12 BI 157 DI 157 10157 TBD TBD AB[9]13 BI 158 DI 158 10158 TBD TBD AB[9]14 BI 159 DI 159 10159 TBD TBD Hawk 1000 system BI 160 DI 160 10160 TBD TBD Flame Strength Honeywell AI 1 AI 1 30001 TBD TBD Combustion Air Fan Speed AI 2 AI 2 30003 TBD TBD AR[2] AI 3 AI 3 30005 TBD TBD Boiler Efficiency AI 4 AI 4 30007 TBD TBD Firing Rate AI 5 AI 5 30009 TBD TBD O2 Level AI 6 AI 6 30011 TBD TBD SP Steam Pressure/Wtr Temp AI 7 AI 7 30013 TBD TBD Wtr Level AI 8 AI 8 30015 TBD TBD Steam Pressure or Hot Wtr Temp AI 9 AI 9 30017 TBD TBD AR[9] AI 10 AI 10 30019 TBD TBD Stack Temp Before Economizer AI 11 AI 11 30021 TBD TBD Combustion Air Temp AI 12 AI 12 30023 TBD TBD Wtr Temp Shell/Outdoor Temp AI 13 AI 13 30025 TBD TBD FeedWtr Temp/Econ Wtr Out Temp AI 14 AI 14 30027 TBD TBD Stack Temp After Econ/Return HW AI 15 AI 15 30029 TBD TBD Economizer Wtr In Temp AI 16 AI 16 30031 TBD TBD AI Slot8 Ch0 Value 2Stg Econ Temp IN AI 17 AI 17 30033 TBD TBD AI Slot8 Ch1 Value 2Stg Econ Temp OUT AI 18 AI 18 30035 TBD TBD AI Slot8 Ch2 Value (EU) AI 19 AI 19 30037 TBD TBD AI Slot8 Ch3 Value (EU) AI 20 AI 20 30039 TBD TBD Safety Valve Setting or Max Wtr Temp AI 21 AI 21 30041 TBD TBD Header Pressure or Temp 2 Boiler LL AI 22 AI 22 30043 TBD TBD SP 2 Boiler LL AI 23 AI 23 30045 TBD TBD Boiler Off Point AI 24 AI 24 30047 TBD TBD Boiler On Point AI 25 AI 25 30049 TBD TBD Condensate Return Valve Output  Command Makeup Bypass Valve Output Command AI 26 AI 26 30051 TBD TBD AI 27 AI 27 30053 TBD TBD Slot8 Ch0 FLo Total AI 28 AI 28 30055 TBD TBD Slot8 Ch1 FLo Total AI 29 AI 29 30057 TBD TBD Slot8 Ch2 FLo Total AI 30 AI 30 30059 TBD TBD Slot8 Ch3 FLo Total AI 31 AI 31 30061 TBD TBD AR[31] AI 32 AI 32 30063 TBD TBD AR[32] AI 33 AI 33 30065 TBD TBD AR[33] AI 34 AI 34 30067 TBD TBD AR[34] AI 35 AI 35 30069 TBD TBD AR[35] AI 36 AI 36 30071 TBD TBD 52 750-361 ProtoNode Gateway Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * * * * * * * * * * * * * * * * * AR[36] AI 37 AI 37 30073 TBD TBD AR[37] AI 38 AI 38 30075 TBD TBD AR[38] AI 39 AI 39 30077 TBD TBD AR[39] AI 40 AI 40 30079 TBD TBD AR[40] AI 41 AI 41 30081 TBD TBD AR[41] AI 42 AI 42 30083 TBD TBD AR[42] AI 43 AI 43 30085 TBD TBD AR[43] AI 44 AI 44 30087 TBD TBD AR[44] AI 45 AI 45 30089 TBD TBD AR[45] AI 46 AI 46 30091 TBD TBD AR[46] AI 47 AI 47 30093 TBD TBD AR[47] AI 48 AI 48 30095 TBD TBD AR[48] AI 49 AI 49 30097 TBD TBD AR[49] AI 50 AI 50 30099 TBD TBD Burner Control Status Line 1 Honeywell AI 52 AI 52 30102 TBD TBD Burner Control Status Line 2 Honeywell AI 53 AI 53 30103 TBD TBD Burner Control Status Line 1 Fireye AI 54 AI 54 30104 TBD TBD Burner Control Status Line 2 Fireye AI 55 AI 55 30105 TBD TBD Flame Signal Fireye AI 56 AI 56 30106 TBD TBD Fuel 1Type AI 57 AI 57 30107 TBD TBD Fuel 2 Type AI 58 AI 58 30108 TBD TBD Fuel 3 Type AI 59 AI 59 30109 TBD TBD Elapsed Time (First 16 Bits) AI 61 AI 61 30111 TBD TBD Elapsed Time (Second 16 Bits) AI 62 AI 62 30112 TBD TBD Number Of Cycles (First 16 Bits) AI 63 AI 63 30113 TBD TBD Number Of Cycles (Second 16 Bits) AI 64 AI 64 30114 TBD TBD AI[13] AI 65 AI 65 30115 TBD TBD AI[14] AI 66 AI 66 30116 TBD TBD Elapsed Time AI 67 AI 67 30117 TBD TBD Number Of Cycles AI 68 AI 68 30119 TBD TBD Heart Beat From BMS BV 1 DO 1 00001 TBD TBD Remote Start From BMS BV 2 DO 2 00002 TBD TBD AWB[0]2 BV 3 DO 3 00003 TBD TBD AWB[0]3 BV 4 DO 4 00004 TBD TBD AWB[0]4 BV 5 DO 5 00005 TBD TBD AWB[0]5 BV 6 DO 6 00006 TBD TBD AWB[0]6 BV 7 DO 7 00007 TBD TBD AWB[0]7 BV 8 DO 8 00008 TBD TBD AWB[0]8 BV 9 DO 9 00009 TBD TBD AWB[0]9 BV 10 DO 10 00010 TBD TBD AWB[0]10 BV 11 DO 11 00011 TBD TBD AWB[0]11 BV 12 DO 12 00012 TBD TBD AWB[0]12 BV 13 DO 13 00013 TBD TBD AWB[0]13 BV 14 DO 14 00014 TBD TBD AWB[0]14 BV 15 DO 15 00015 TBD TBD AWB[0]15 BV 16 DO 16 00016 TBD TBD AWB[1]0 BV 17 DO 17 00017 TBD TBD AWB[1]1 BV 18 DO 18 00018 TBD TBD AWB[1]2 BV 19 DO 19 00019 TBD TBD AWB[1]3 BV 20 DO 20 00020 TBD TBD 750-361 53 ProtoNode Gateway Table 18: Hawk 1000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * * * * * * * * * * * * * * * * * AWB[1]4 BV 21 DO 21 00021 TBD TBD AWB[1]5 BV 22 DO 22 00022 TBD TBD AWB[1]6 BV 23 DO 23 00023 TBD TBD AWB[1]7 BV 24 DO 24 00024 TBD TBD AWB[1]8 BV 25 DO 25 00025 TBD TBD AWB[1]9 BV 26 DO 26 00026 TBD TBD AWB[1]10 BV 27 DO 27 00027 TBD TBD AWB[1]11 BV 28 DO 28 00028 TBD TBD AWB[1]12 BV 29 DO 29 00029 TBD TBD AWB[1]13 BV 30 DO 30 00030 TBD TBD AWB[1]14 BV 31 DO 31 00031 TBD TBD AWB[1]15 BV 32 DO 32 00032 TBD TBD Rem Op SP Boiler AV 1 AO 1 40001 TBD TBD Rem Firing Rate AV 2 AO 2 40003 TBD TBD Rem Op SP 2 boiler Lead/Lag AV 3 AO 3 40005 TBD TBD AWR[3] AV 4 AO 4 40007 TBD TBD AWR[4] AV 5 AO 5 40009 TBD TBD AWR[5] AV 6 AO 6 40011 TBD TBD AWR[6] AV 7 AO 7 40013 TBD TBD AWR[7] AV 8 AO 8 40015 TBD TBD * AWR[8] AV 9 AO 9 40017 TBD TBD * AWR[9] AV 10 AO 10 40019 TBD TBD *Write points 54 750-361 ProtoNode Gateway B.9. HAWK 4000 Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Point Name Drive Fault Modbus Comm Error BACnet  Object Type BI BACnet  Object ID 1 N2 Data  Type DI N2 Point  Address 1 Modbus  Register 10001 BI 2 DI 2 10002 Lon Name Lon SNVT TBD TBD TBD TBD Lo Water BI 3 DI 3 10003 TBD TBD Burner Control Alm BI 4 DI 4 10004 TBD TBD Boiler Limits Open BI 5 DI 5 10005 TBD TBD Hi Stack Temp Alm BI 6 DI 6 10006 TBD TBD Hi Stack Temp Shutdown BI 7 DI 7 10007 TBD TBD External Interlock BI 8 DI 8 10008 TBD TBD I/O module fault BI 9 DI 9 10009 TBD TBD Steam Sensor Fail BI 10 DI 10 10010 TBD TBD Air Actuator Out Of Pos Alm BI 11 DI 11 10011 TBD TBD NG Actuator Out Of Pos Alm BI 12 DI 12 10012 TBD TBD F/A Ratio Controller Fault BI 13 DI 13 10013 TBD TBD No Fuel Selected BI 14 DI 14 10014 TBD TBD Lo ControlLogix Battery BI 15 DI 15 10015 TBD TBD Non Recycle Limit Relay Fail BI 16 DI 16 10016 TBD TBD Recyle Limit Relay Fail BI 17 DI 17 10017 TBD TBD Rem Modulation Signal Fail BI 18 DI 18 10018 TBD TBD Header Pressure Sensor Fail BI 19 DI 19 10019 TBD TBD Temp Channel 0‐5 Fail BI 20 DI 20 10020 TBD TBD Lo O2 Alm BI 21 DI 21 10021 TBD TBD Hi Limit Alm BI 22 DI 22 10022 TBD TBD ALWCO BI 23 DI 23 10023 TBD TBD Lo Gas Pressure/Lo Oil Temp BI 24 DI 24 10024 TBD TBD Hi Gas Pressure/Hi Oil Temp BI 25 DI 25 10025 TBD TBD Lo Oil Pressure BI 26 DI 26 10026 TBD TBD Hi Oil Pressure BI 27 DI 27 10027 TBD TBD Oil Drawer Switch Not Made BI 28 DI 28 10028 TBD TBD Lo Atomizing Air Pressure BI 29 DI 29 10029 TBD TBD Lo Combustion Air Pressure BI 30 DI 30 10030 TBD TBD AUX Alm 1 BI 31 DI 31 10031 TBD TBD AUX Alm 2 BI 32 DI 32 10032 TBD TBD Blower On BI 33 DI 33 10033 TBD TBD Purge Input BI 34 DI 34 10034 TBD TBD Release To Modulate Input BI 35 DI 35 10035 TBD TBD Lo Fire Switch BI 36 DI 36 10036 TBD TBD Hi Fire Switch BI 37 DI 37 10037 TBD TBD Ready to start/Limits Closed BI 38 DI 38 10038 TBD TBD External Start Interlock BI 39 DI 39 10039 TBD TBD ALFCO BI 40 DI 40 10040 TBD TBD Pilot BI 41 DI 41 10041 TBD TBD Main Fuel Valve Open BI 42 DI 42 10042 TBD TBD Fuel 1 Selected BI 43 DI 43 10043 TBD TBD Fuel  2 Selected BI 44 DI 44 10044 TBD TBD Heart Beat To BMS BI 45 DI 45 10045 TBD TBD LWCO Shutdown BI 46 DI 46 10046 TBD TBD Rem Enable Input BI 47 DI 47 10047 TBD TBD 750-361 55 ProtoNode Gateway Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Burner Switch BI 48 DI 48 10048 TBD TBD Recycle Limit Relay BI 49 DI 49 10049 TBD TBD External Device Start BI 50 DI 50 10050 TBD TBD Non Recycle Limit Relay BI 51 DI 51 10051 TBD TBD Drive to Lo Fire (FARC) BI 52 DI 52 10052 TBD TBD Start Slave Blr (2 Blr LL) BI 53 DI 53 10053 TBD TBD Load Demand Output BI 54 DI 54 10054 TBD TBD Alm Output BI 55 DI 55 10055 TBD TBD Boiler Ready (LL) BI 56 DI 56 10056 TBD TBD Boiler Load Demand BI 57 DI 57 10057 TBD TBD Firing Rate Rem/Llag BI 58 DI 58 10058 TBD TBD Firing Rate Manual BI 59 DI 59 10059 TBD TBD Firing Rate Auto BI 60 DI 60 10060 TBD TBD Hot Stand By BI 61 DI 61 10061 TBD TBD Warm Up BI 62 DI 62 10062 TBD TBD Fuel 3 Selected BI 63 DI 63 10063 TBD TBD Aux Alm 3 BI 64 DI 64 10064 TBD TBD Steam or Hot Water  1 = Steam BI 65 DI 65 10065 TBD TBD Level Master Present BI 66 DI 66 10066 TBD TBD Variable Speed Drive Present BI 67 DI 67 10067 TBD TBD Economizer Present BI 68 DI 68 10068 TBD TBD Combustion Air Temp Present BI 69 DI 69 10069 TBD TBD Economizer Inlet FW Sensor Present BI 70 DI 70 10070 TBD TBD O2 Analyzer Present BI 71 DI 71 10071 TBD TBD Feedwater or Return Temp Present BI 72 DI 72 10072 TBD TBD Outdoor Reset Selected BI 73 DI 73 10073 TBD TBD Parallel Posing Selected BI 74 DI 74 10074 TBD TBD Two Boiler Lead Lag Master Select BI 75 DI 75 10075 TBD TBD Two Boiler Lead Lag Slave Select BI 76 DI 76 10076 TBD TBD Master Panel Select BI 77 DI 77 10077 TBD TBD Hot Stand By Select BI 78 DI 78 10078 TBD TBD Dual Setpoint Select BI 79 DI 79 10079 TBD TBD Slot 8 Ch 0 AI Selected BI 80 DI 80 10080 TBD TBD Slot 8 Ch 1 AI Selected BI 81 DI 81 10081 TBD TBD Slot 8 Ch 2 AI Selected BI 82 DI 82 10082 TBD TBD Slot 8 Ch 3 AI Selected BI 83 DI 83 10083 TBD TBD Honeywell or Fireye 1 = Fireye BI 84 DI 84 10084 TBD TBD Hi Water Alm BI 85 DI 85 10085 TBD TBD Oil Actuator Out Of Pos Alm BI 86 DI 86 10086 TBD TBD FGR Actuator Out Of Pos Alm BI 87 DI 87 10087 TBD TBD Air Actuator Feedback Fail Lo Alm BI 88 DI 88 10088 TBD TBD Air Actuator Feedback Fail Hi Alm BI 89 DI 89 10089 TBD TBD NG Actuator Feedback Fail Lo Alm BI 90 DI 90 10090 TBD TBD NG Actuator Feedback Fail Hi Alm BI 91 DI 91 10091 TBD TBD Oil Actuator Feedback Fail Lo Alm BI 92 DI 92 10092 TBD TBD Oil Actuator Feedback Fail Hi Alm BI 93 DI 93 10093 TBD TBD FGR Actuator Feedback Fail Lo Alm BI 94 DI 94 10094 TBD TBD FGR Actuator Feedback Fail Hi Alm BI 95 DI 95 10095 TBD TBD VSD Deviation Alm BI 96 DI 96 10096 TBD TBD Increase MSG Reg Size Bit (CB Only) BI 97 DI 97 10097 TBD TBD 56 750-361 ProtoNode Gateway Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Air/Fuel Deviation Alm BI 98 DI 2nd Stage CEC Economizer Selected Fuel3 Actuator Out Of Pos Alm BI 99 DI BI 100 DI Fuel3 Actuator Feedback Fail Lo Alm BI 101 DI Fuel3 Actuator Feedback Fail Hi Alm BI 102 Stack Pressure Input Fail BI Hi Stack Pressure Alm Stack Damper Not Open Alm 98 10098 TBD TBD 99 10099 TBD TBD 100 10100 TBD TBD 101 10101 TBD TBD DI 102 10102 TBD TBD 103 DI 103 10103 TBD TBD BI 104 DI 104 10104 TBD TBD BI 105 DI 105 10105 TBD TBD O2 Calibration Failed BI 106 DI 106 10106 TBD TBD Lo Steam Pressure/Water Temp Alm BI 107 DI 107 10107 TBD TBD Processor Test Fail Alm BI 108 DI 108 10108 TBD TBD O2 Trim Internal Alm BI 109 DI 109 10109 TBD TBD Firetube or Flextube 1 = Flextube BI 110 DI 110 10110 TBD TBD Reserved for Cleaver‐Brooks BI 111 DI 111 10111 TBD TBD VSD Limits Internal Alm BI 112 DI 112 10112 TBD TBD Gas Actuator 2 Out Of Pos Alm BI 113 DI 113 10113 TBD TBD Gas Actuator 2 Feedback Fail Lo Alm BI 114 DI 114 10114 TBD TBD Gas Actuator 2 Feedback Fail Hi Alm BI 115 DI 115 10115 TBD TBD Actuator Modbus Communication Error BI 116 DI 116 10116 TBD TBD Air Actuator Modbus Comm Error Node 1 BI 117 DI 117 10117 TBD TBD Gas Actuator Modbus Comm Error Node 2 BI 118 DI 118 10118 TBD TBD Gas Act 2 Modbus Comm Error Node 3 BI 119 DI 119 10119 TBD TBD Oil Actuator Modbus Comm Error Node 5 BI 120 DI 120 10120 TBD TBD FGR Actuator Modbus Comm Error Node 7 BI 121 DI 121 10121 TBD TBD Reserved BI 122 DI 122 10122 TBD TBD Reserved BI 123 DI 123 10123 TBD TBD 2nd Stage Outlet Wtr Temp Sensor Fail BI 124 DI 124 10124 TBD TBD Water Temp Second Stage Out Hi BI 125 DI 125 10125 TBD TBD Air Actuator Man Override Btn Press BI 126 DI 126 10126 TBD TBD Gas Actuator 1 Man Override Btn Press BI 127 DI 127 10127 TBD TBD Gas Actuator 2 Man Override Btn Press BI 128 DI 128 10128 TBD TBD Oil Actuator Man Override Btn Press BI 129 DI 129 10129 TBD TBD FGR Actuator Man Override Btn Press BI 130 DI 130 10130 TBD TBD Fuel 3 Act 1 Man Override Btn Press BI 131 DI 131 10131 TBD TBD Fuel 3 Act 2 Man Override Btn Press BI 132 DI 132 10132 TBD TBD Communication from BMS Failed BI 133 DI 133 10133 TBD TBD Low O2 Shutdown  BI 134 DI 134 10134 TBD TBD AB[8]6 BI 135 DI 135 10135 TBD TBD AB[8]7 BI 136 DI 136 10136 TBD TBD AB[8]8 BI 137 DI 137 10137 TBD TBD AB[8]9 BI 138 DI 138 10138 TBD TBD AB[8]10 BI 139 DI 139 10139 TBD TBD AB[8]11 BI 140 DI 140 10140 TBD TBD AB[8]12 BI 141 DI 141 10141 TBD TBD AB[8]13 BI 142 DI 142 10142 TBD TBD AB[8]14 BI 143 DI 143 10143 TBD TBD AB[8]15 BI 144 DI 144 10144 TBD TBD AB[9]0 BI 145 DI 145 10145 TBD TBD AB[9]1 BI 146 DI 146 10146 TBD TBD AB[9]2 BI 147 DI 147 10147 TBD TBD 750-361 57 ProtoNode Gateway Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) AB[9]3 BI 148 DI 148 10148 TBD TBD AB[9]4 BI 149 DI 149 10149 TBD TBD AB[9]5 BI 150 DI 150 10150 TBD TBD AB[9]6 BI 151 DI 151 10151 TBD TBD AB[9]7 BI 152 DI 152 10152 TBD TBD AB[9]8 BI 153 DI 153 10153 TBD TBD AB[9]9 BI 154 DI 154 10154 TBD TBD AB[9]10 BI 155 DI 155 10155 TBD TBD AB[9]11 BI 156 DI 156 10156 TBD TBD AB[9]12 BI 157 DI 157 10157 TBD TBD AB[9]13 BI 158 DI 158 10158 TBD TBD AB[9]14 BI 159 DI 159 10159 TBD TBD AB[9]15 BI 160 DI 160 10160 TBD TBD Flame Strength Honeywell AI 1 AI 1 30001 TBD TBD Combustion Air Fan Speed AI 2 AI 2 30003 TBD TBD AR[2] AI 3 AI 3 30005 TBD TBD Boiler Efficiency AI 4 AI 4 30007 TBD TBD Firing Rate AI 5 AI 5 30009 TBD TBD O2 Level AI 6 AI 6 30011 TBD TBD SP Steam Pressure/Water Temp AI 7 AI 7 30013 TBD TBD Water Level AI 8 AI 8 30015 TBD TBD TBD Steam Pressure or Hot Water Temp AI 9 AI 9 30017 TBD AR[9] AI 10 AI 10 30019 TBD TBD Stack Temp Before Economizer AI 11 AI 11 30021 TBD TBD Combustion Air Temp AI 12 AI 12 30023 TBD TBD Water Temp Shell/Outdoor Temp AI 13 AI 13 30025 TBD TBD Feedwater Temp/Econ Water Out Temp AI 14 AI 14 30027 TBD TBD Stack Temp After Econ/Return HW AI 15 AI 15 30029 TBD TBD Economizer Water In Temp AI 16 AI 16 30031 TBD TBD AI Slot8Ch0 Value/2Stg Econ Temp IN AI 17 AI 17 30033 TBD TBD AI Slot8Ch1 Value/2Stg Econ Temp OUT AI 18 AI 18 30035 TBD TBD AI Slot8 Ch2 Value (EU) AI 19 AI 19 30037 TBD TBD AI Slot8 Ch3 Value (EU) AI 20 AI 20 30039 TBD TBD Safety Valve Setting or Max Water Temp AI 21 AI 21 30041 TBD TBD Header Pressure or Temp 2 Boiler LL AI 22 AI 22 30043 TBD TBD SP 2 Boiler LL AI 23 AI 23 30045 TBD TBD Boiler Off Point AI 24 AI 24 30047 TBD TBD Boiler On Point AI 25 AI 25 30049 TBD TBD Condensate Return Valve Output  Command Makeup Bypass Valve Output Command AI 26 AI 26 30051 TBD TBD AI 27 AI 27 30053 TBD TBD Slot8 Ch0 FLo Total AI 28 AI 28 30055 TBD TBD Slot8 Ch1 FLo Total AI 29 AI 29 30057 TBD TBD Slot8 Ch2 FLo Total AI 30 AI 30 30059 TBD TBD Slot8 Ch3 FLo Total AI 31 AI 31 30061 TBD TBD AR[31] AI 32 AI 32 30063 TBD TBD AR[32] AI 33 AI 33 30065 TBD TBD AR[33] AI 34 AI 34 30067 TBD TBD AR[34] AI 35 AI 35 30069 TBD TBD AR[35] AI 36 AI 36 30071 TBD TBD AR[36] AI 37 AI 37 30073 TBD TBD 58 750-361 ProtoNode Gateway Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * * * AR[37] AI 38 AI 38 30075 TBD TBD AR[38] AI 39 AI 39 30077 TBD TBD AR[39] AI 40 AI 40 30079 TBD TBD AR[40] AI 41 AI 41 30081 TBD TBD AR[41] AI 42 AI 42 30083 TBD TBD AR[42] AI 43 AI 43 30085 TBD TBD AR[43] AI 44 AI 44 30087 TBD TBD AR[44] AI 45 AI 45 30089 TBD TBD AR[45] AI 46 AI 46 30091 TBD TBD AR[46] AI 47 AI 47 30093 TBD TBD AR[47] AI 48 AI 48 30095 TBD TBD AR[48] AI 49 AI 49 30097 TBD TBD AR[49] AI 50 AI 50 30099 TBD TBD Burner Control Status Line 1 Honeywell AI 52 AI 52 30102 TBD TBD Burner Control Status Line 2 Honeywell AI 53 AI 53 30103 TBD TBD Burner Control Status Line 1 Fireye AI 54 AI 54 30104 TBD TBD Burner Control Status Line 2 Fireye AI 55 AI 55 30105 TBD TBD Flame Signal Fireye AI 56 AI 56 30106 TBD TBD Fuel 1Type AI 57 AI 57 30107 TBD TBD Fuel 2 Type AI 58 AI 58 30108 TBD TBD Fuel 3 Type AI 59 AI 59 30109 TBD TBD Elapsed Time (First 16 Bits) AI 61 AI 61 30111 TBD TBD Elapsed Time (Second 16 Bits) AI 62 AI 62 30112 TBD TBD Number Of Cycles (First 16 Bits) AI 63 AI 63 30113 TBD TBD Number Of Cycles (Second 16 Bits) AI 64 AI 64 30114 TBD TBD AI[13] AI 65 AI 65 30115 TBD TBD AI[14] AI 66 AI 66 30116 TBD TBD AI[15] AI 67 AI 67 30117 TBD TBD AI[16] AI 68 AI 68 30118 TBD TBD AI[17] AI 69 AI 69 30119 TBD TBD AI[18] AI 70 AI 70 30120 TBD TBD AI[19] AI 71 AI 71 30121 TBD TBD AI[20] AI 72 AI 72 30122 TBD TBD AI[21] AI 73 AI 73 30123 TBD TBD AI[22] AI 74 AI 74 30124 TBD TBD AI[23] AI 75 AI 75 30125 TBD TBD AI[24] AI 76 AI 76 30126 TBD TBD AI[25] AI 77 AI 77 30127 TBD TBD AI[26] AI 78 AI 78 30128 TBD TBD AI[27] AI 79 AI 79 30129 TBD TBD AI[28] AI 80 AI 80 30130 TBD TBD AI[29] AI 81 AI 81 30131 TBD TBD Elapsed Time AI 82 AI 82 30132 TBD TBD Number Of Cycles AI 83 AI 83 30134 TBD TBD Heart Beat From BMS BV 1 DO 1 00001 TBD TBD Rem Start From BMS BV 2 DO 2 00002 TBD TBD AWB[0]2 BV 3 DO 3 00003 TBD TBD AWB[0]3 BV 4 DO 4 00004 TBD TBD AWB[0]4 BV 5 DO 5 00005 TBD TBD AWB[0]5 BV 6 DO 6 00006 TBD TBD 750-361 59 ProtoNode Gateway Table 19: Hawk 4000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * AWB[0]6 BV 7 DO 7 00007 TBD TBD AWB[0]7 BV 8 DO 8 00008 TBD TBD AWB[0]8 BV 9 DO 9 00009 TBD TBD AWB[0]9 BV 10 DO 10 00010 TBD TBD AWB[0]10 BV 11 DO 11 00011 TBD TBD AWB[0]11 BV 12 DO 12 00012 TBD TBD AWB[0]12 BV 13 DO 13 00013 TBD TBD AWB[0]13 BV 14 DO 14 00014 TBD TBD AWB[0]14 BV 15 DO 15 00015 TBD TBD AWB[0]15 BV 16 DO 16 00016 TBD TBD AWB[1]0 BV 17 DO 17 00017 TBD TBD AWB[1]1 BV 18 DO 18 00018 TBD TBD AWB[1]2 BV 19 DO 19 00019 TBD TBD AWB[1]3 BV 20 DO 20 00020 TBD TBD AWB[1]4 BV 21 DO 21 00021 TBD TBD AWB[1]5 BV 22 DO 22 00022 TBD TBD AWB[1]6 BV 23 DO 23 00023 TBD TBD AWB[1]7 BV 24 DO 24 00024 TBD TBD AWB[1]8 BV 25 DO 25 00025 TBD TBD AWB[1]9 BV 26 DO 26 00026 TBD TBD AWB[1]10 BV 27 DO 27 00027 TBD TBD AWB[1]11 BV 28 DO 28 00028 TBD TBD AWB[1]12 BV 29 DO 29 00029 TBD TBD AWB[1]13 BV 30 DO 30 00030 TBD TBD AWB[1]14 BV 31 DO 31 00031 TBD TBD AWB[1]15 BV 32 DO 32 00032 TBD TBD Rem Op SP Boiler AV 1 AO 1 40001 TBD TBD Rem Firing Rate AV 2 AO 2 40003 TBD TBD Rem Op SP 2 boiler Lead/Lag AV 3 AO 3 40005 TBD TBD AWR[3] AV 4 AO 4 40007 TBD TBD AWR[4] AV 5 AO 5 40009 TBD TBD AWR[5] AV 6 AO 6 40011 TBD TBD AWR[6] AV 7 AO 7 40013 TBD TBD AWR[7] AV 8 AO 8 40015 TBD TBD AWR[8] AV 9 AO 9 40017 TBD TBD AWR[9] AV 10 AO 10 40019 TBD TBD *Write points 60 750-361 ProtoNode Gateway B.10. HAWK 5000 Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks BACnet  Object Type BI BACnet  Object ID 1 N2 Data  Type DI N2 Point  Address 1 Modbus  Register 10001 TBD TBD FSG Purge Cmd BI 2 DI 2 10002 TBD TBD FSG Release To Modulate Cmd BI 3 DI 3 10003 TBD TBD Actuators At Lo Fire BI 4 DI 4 10004 TBD TBD Actuators At Hi Fire BI 5 DI 5 10005 TBD TBD Ready To Start/ Limits Closed BI 6 DI 6 10006 TBD TBD Ext. Start Interlock Proven BI 7 DI 7 10007 TBD TBD ALFCO BI 8 DI 8 10008 TBD TBD FSG Pilot Terminal Energized BI 9 DI 9 10009 TBD TBD FSG Main Fuel Terminal Energized BI 10 DI 10 10010 TBD TBD Fuel Selector Switch ‐ Fuel 1 Pos BI 11 DI 11 10011 TBD TBD Fuel Selector Switch ‐ Fuel 2 Pos BI 12 DI 12 10012 TBD TBD FSG Burner Control Com Alm BI 13 DI 13 10013 TBD TBD Point Name Comb Air Blower Running Lon Name Lon SNVT Lo Water Cutoff (LWCO) BI 14 DI 14 10014 TBD TBD FSG Lo Fire Cmd BI 15 DI 15 10015 TBD TBD Burner Start Relay Energized BI 16 DI 16 10016 TBD TBD Hi Water Cutoff (HWCO) BI 17 DI 17 10017 TBD TBD Yokagawa O2 Analyzer Ready Status BI 18 DI 18 10018 TBD TBD VSD Bypass Switch ‐ Bypass Pos BI 19 DI 19 10019 TBD TBD Hi Steam Press Switch BI 20 DI 20 10020 TBD TBD Aux Lo Water Cutoff (ALWCO) BI 21 DI 21 10021 TBD TBD Lo Gas Press/Oil Temp Switch (LGP/LOT) BI 22 DI 22 10022 TBD TBD Hi Gas Press/Oil Temp Switch (HGP/HOT) BI 23 DI 23 10023 TBD TBD Lo Oil Press (LOP) BI 24 DI 24 10024 TBD TBD Hi Oil Press (HOP) BI 25 DI 25 10025 TBD TBD Atomizing Media Flo and Press Switches BI 26 DI 26 10026 TBD TBD Lo Water Alm BI 27 DI 27 10027 TBD TBD Comb Air Press Switch BI 28 DI 28 10028 TBD TBD Hi Water Alm BI 29 DI 29 10029 TBD TBD Hi Stack/ Furnace Press Switch BI 30 DI 30 10030 TBD TBD Lo Inst Air Press Switch BI 31 DI 31 10031 TBD TBD Oil Gun Inserted Limit Switch BI 32 DI 32 10032 TBD TBD Recycle Limit Relay BI 33 DI 33 10033 TBD TBD Ext. Device Start Interlock BI 34 DI 34 10034 TBD TBD Non‐Recycle Limit Relay BI 35 DI 35 10035 TBD TBD Proof Of Lo Fire BI 36 DI 36 10036 TBD TBD Proof Of Hi Fire BI 37 DI 37 10037 TBD TBD Load Demand BI 38 DI 38 10038 TBD TBD Alm Bell Relay BI 39 DI 39 10039 TBD TBD Boiler Ready BI 40 DI 40 10040 TBD TBD AB[2].8 BI 41 DI 41 10041 TBD TBD AB[2].9 BI 42 DI 42 10042 TBD TBD AB[2].10 BI 43 DI 43 10043 TBD TBD AB[2].11 BI 44 DI 44 10044 TBD TBD AB[2].12 BI 45 DI 45 10045 TBD TBD AB[2].13 BI 46 DI 46 10046 TBD TBD AB[2].14 BI 47 DI 47 10047 TBD TBD 750-361 61 ProtoNode Gateway Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) AB[2].15 BI 48 DI 48 10048 TBD TBD Bad Ql‐ Steam Press (06:00) BI 49 DI 49 10049 TBD TBD Bad Ql‐ Drum Level (06:01) BI 50 DI 50 10050 TBD TBD Bad Ql‐ Stack Temp (06:02) BI 51 DI 51 10051 TBD TBD Bad Ql‐ Remote Modulation (06:03) BI 52 DI 52 10052 TBD TBD Bad Ql‐ Steam Flo (06:04) BI 53 DI 53 10053 TBD TBD Bad Ql‐ Mud Drm Shell Tmp (06:05) BI 54 DI 54 10054 TBD TBD Bad Ql‐ Act5 (VSD) FB (06:06) BI 55 DI 55 10055 TBD TBD Bad Ql‐ Flue Gas O2 (06:07) BI 56 DI 56 10056 TBD TBD Bad Ql‐ F1 Flo or Usr Def (07:00) BI 57 DI 57 10057 TBD TBD Bad Ql‐ F2 Flo or Usr Def (07:01) BI 58 DI 58 10058 TBD TBD Bad Ql‐ Stack Draft or Usr Def (07:02) BI 59 DI 59 10059 TBD TBD Bad Ql‐ Feedwtr Flo or Usr Def (07:03) BI 60 DI 60 10060 TBD TBD Bad Ql‐ Ecn Out FG Tmp ‐Usr Def (07:04 BI 61 DI 61 10061 TBD TBD Bad Ql‐ Ecn In FW Tmp ‐ Usr Def (07:05 BI 62 DI 62 10062 TBD TBD Bad Ql‐ Ecn Out FW Tmp ‐Usr Def (07:06 BI 63 DI 63 10063 TBD TBD Bad Ql‐ Air Flo or Usr Def (07:07) BI 64 DI 64 10064 TBD TBD Bad Ql‐ Actuator1 (Air) FB (09:00) BI 65 DI 65 10065 TBD TBD Bad Ql‐ Actuator2 (F1) FB (09:01) BI 66 DI 66 10066 TBD TBD Bad Ql‐ Actuator3 (F2) FB (09:02) BI 67 DI 67 10067 TBD TBD Bad Ql‐ Actuator (FGR) FB (09:03) BI 68 DI 68 10068 TBD TBD Bad Ql‐ Actuator8 (2nd Air) FB (09:04) BI 69 DI 69 10069 TBD TBD Bad Ql‐ Actuator9 (2nd F1) FB (09:05) BI 70 DI 70 10070 TBD TBD Bad Ql‐ Reserved (09:06) BI 71 DI 71 10071 TBD TBD Bad Ql‐ Reserved (09:07) BI 72 DI 72 10072 TBD TBD HAlm ‐ Steam Press (Xmtr) BI 73 DI 73 10073 TBD TBD HAlm ‐ Drum Level (xmtr) BI 74 DI 74 10074 TBD TBD HAlm ‐ Stack Temp (Xmtr) BI 75 DI 75 10075 TBD TBD HAlm ‐ Remote Modulation Input BI 76 DI 76 10076 TBD TBD HAlm ‐ Steam Flo (Xmtr) BI 77 DI 77 10077 TBD TBD HAlm ‐ Mud Drum Shell Temp (Xmtr) BI 78 DI 78 10078 TBD TBD HAlm ‐ VSD Speed Feedback (Xmtr) BI 79 DI 79 10079 TBD TBD HAlm ‐ Flue Gas O2 (Xmtr) BI 80 DI 80 10080 TBD TBD HAlm ‐ F1 Flo (Xmtr) BI 81 DI 81 10081 TBD TBD HAlm ‐ F2 Flo (Xmtr) BI 82 DI 82 10082 TBD TBD HAlm ‐ Stack Draft (Xmtr) BI 83 DI 83 10083 TBD TBD HAlm ‐ Feedwater Flo (Xmtr) BI 84 DI 84 10084 TBD TBD HAlm ‐ Econ Outlet FG Temp (Xmtr) BI 85 DI 85 10085 TBD TBD TBD HAlm ‐ Econ Inlet FW Temp (Xmtr) BI 86 DI 86 10086 TBD HAlm ‐ Econ Outlet FW Temp (Xmtr) BI 87 DI 87 10087 TBD TBD HAlm ‐ Air Flo Hi (Xmtr) BI 88 DI 88 10088 TBD TBD HHAlm ‐ Stack Tmp Hi‐Hi SHUTDWN  (Xmtr) HAlm ‐ Hi Water Cutoff (Contact) BI 89 DI 89 10089 TBD TBD BI 90 DI 90 10090 TBD TBD HAlm ‐ Hi Gas Pressure (Contact) BI 91 DI 91 10091 TBD TBD HAlm ‐ Hi Oil Temp (Contact) BI 92 DI 92 10092 TBD TBD HAlm ‐ Hi Oil Pressure (Contact) BI 93 DI 93 10093 TBD TBD HAlm ‐ Hi Water Alm (Contact) BI 94 DI 94 10094 TBD TBD HHAlm ‐ Hi‐Hi Furn Press SHTDWN BI 95 DI 95 10095 TBD TBD Reserved BI 96 DI 96 10096 TBD TBD LAlm ‐ Steam Press (Xmtr) BI 97 DI 97 10097 TBD TBD 62 750-361 ProtoNode Gateway Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) LAlm ‐ Drum Level (Xmtr) BI 98 DI 98 10098 TBD LAlm ‐ Stack Temp (Xmtr) LAlm ‐ Remote Modulation BI 99 BI 100 LAlm ‐ Steam Flo (Xmtr) BI LAlm ‐ Mud Drum Shell Temp (Xmtr) BI LAlm ‐ VSD Speed Feedback TBD DI 99 10099 TBD TBD DI 100 10100 TBD TBD 101 DI 101 10101 TBD TBD 102 DI 102 10102 TBD TBD BI 103 DI 103 10103 TBD TBD LAlm ‐ Flo Gas O2 (Xmtr) BI 104 DI 104 10104 TBD TBD LAlm ‐ F1 Flo (Xmtr) BI 105 DI 105 10105 TBD TBD LAlm ‐ F2 Flo (Xmtr) BI 106 DI 106 10106 TBD TBD LAlm ‐ Stack Draft (Xmtr) BI 107 DI 107 10107 TBD TBD LAlm ‐ Feedwtr Flo (Xmtr) BI 108 DI 108 10108 TBD TBD LAlm ‐ Econ Outlet FG Temp (Xmtr) BI 109 DI 109 10109 TBD TBD LAlm ‐ Econ Inlet Feedwtr Temp (Xmtr) BI 110 DI 110 10110 TBD TBD LAlm ‐ Econ Outlet Feedwtr Temp (Xmtr) BI 111 DI 111 10111 TBD TBD LAlm ‐ Air Flo (Xmtr) BI 112 DI 112 10112 TBD TBD LAlm ‐ Lo wtr Cutoff (Contact) BI 113 DI 113 10113 TBD TBD LAlm ‐ Aux Lo wtr Cutoff (Contact) BI 114 DI 114 10114 TBD TBD TBD LAlm ‐ Lo Gas Press (Contact) BI 115 DI 115 10115 TBD LAlm ‐ Lo Oil Temp (Contact) BI 116 DI 116 10116 TBD TBD LAlm ‐ Lo Oil Press (Contact) BI 117 DI 117 10117 TBD TBD LAlm ‐ Lo wtr Alm (Contact) BI 118 DI 118 10118 TBD TBD LAlm ‐ Lo Comb Air Press (Contact) BI 119 DI 119 10119 TBD TBD LAlm ‐ Lo Inst Air Press (Contact) BI 120 DI 120 10120 TBD TBD LLAlm ‐ Flo Gas O2 Lo‐Lo SHUTDOWN BI 121 DI 121 10121 TBD TBD AB[7].9 BI 122 DI 122 10122 TBD TBD AB[7].10 BI 123 DI 123 10123 TBD TBD AB[7].11 BI 124 DI 124 10124 TBD TBD AB[7].12 BI 125 DI 125 10125 TBD TBD AB[7].13 BI 126 DI 126 10126 TBD TBD AB[7].14 BI 127 DI 127 10127 TBD TBD AB[7].15 BI 128 DI 128 10128 TBD TBD Burner Control Alm (Contact) BI 129 DI 129 10129 TBD TBD Yokagawa O2 Analyzer Not Ready BI 130 DI 130 10130 TBD TBD Lo Atomizing Media (Contact) BI 131 DI 131 10131 TBD TBD Oil Gun Pos Switch Not Made (Contact) BI 132 DI 132 10132 TBD TBD Recycle Limit Relay (RLR) Fault BI 133 DI 133 10133 TBD TBD Non‐Recycle Limit Relay (NRLR) Fault BI 134 DI 134 10134 TBD TBD Actuator1 (Air) Out Of Pos Alm BI 135 DI 135 10135 TBD TBD Actuator2 (F1) Out Of Pos Alm BI 136 DI 136 10136 TBD TBD Actuator3 (F2) Out Of Pos Alm BI 137 DI 137 10137 TBD TBD Actuator (FGR) Out Of Pos Alm BI 138 DI 138 10138 TBD TBD Act1 (Air) Feedback Outside Cal Rng BI 139 DI 139 10139 TBD TBD Act2 (F1) Feedback Outside Cal Rng BI 140 DI 140 10140 TBD TBD Act3 (F2) Feedback Outside Cal Rng BI 141 DI 141 10141 TBD TBD Actu (FGR) Feedback Outside Cal Rng BI 142 DI 142 10142 TBD TBD Ext. Start Interlock Not Closed Alm BI 143 DI 143 10143 TBD TBD Actuator5 (VSD) FB / CVDeviation Alm BI 144 DI 144 10144 TBD TBD A‐B VSD Fault Alm BI 145 DI 145 10145 TBD TBD Modbus Comm Error BI 146 DI 146 10146 TBD TBD I/O Module ## Fault Detected Alm BI 147 DI 147 10147 TBD TBD 750-361 63 ProtoNode Gateway Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Burner Control Fault Alm BI 148 DI 148 10148 TBD TBD Hi Limit Cutoff Alm BI 149 DI 149 10149 TBD TBD CPU Battery Alm BI 150 DI 150 10150 TBD TBD Actuator8 (2nd Air) Out Of Pos Alm BI 151 DI 151 10151 TBD TBD Actuator9 (2nd F1) Out Of Pos Alm BI 152 DI 152 10152 TBD TBD Actuator8 (2nd Air) FB Outside Cal Rng BI 153 DI 153 10153 TBD TBD Actuator9 (2nd F1) FB Outside Cal Rng BI 154 DI 154 10154 TBD TBD Reserved BI 155 DI 155 10155 TBD TBD Reserved BI 156 DI 156 10156 TBD TBD Reserved BI 157 DI 157 10157 TBD TBD No Fuel Selected BI 158 DI 158 10158 TBD TBD EIP Comm Link FAULT ‐ Master Panel BI 159 DI 159 10159 TBD TBD Reserved BI 160 DI 160 10160 TBD TBD HAlm ‐ Usr Def (07:00) BI 161 DI 161 10161 TBD TBD HAlm ‐ Usr Def (07:01) BI 162 DI 162 10162 TBD TBD HAlm ‐ Usr Def (07:02) BI 163 DI 163 10163 TBD TBD HAlm ‐ Usr Def (07:03) BI 164 DI 164 10164 TBD TBD HAlm ‐ Usr Def (07:04) BI 165 DI 165 10165 TBD TBD HAlm ‐ Usr Def (07:05) BI 166 DI 166 10166 TBD TBD HAlm ‐ Usr Def (07:06) BI 167 DI 167 10167 TBD TBD HAlm ‐ Usr Def (07:07) BI 168 DI 168 10168 TBD TBD Input Bad Quality ‐ Usr Def (07:00) BI 169 DI 169 10169 TBD TBD Input Bad Quality ‐ Usr Def (07:01) BI 170 DI 170 10170 TBD TBD Input Bad Quality ‐ Usr Def (07:02) BI 171 DI 171 10171 TBD TBD Input Bad Quality ‐ Usr Def (07:03) BI 172 DI 172 10172 TBD TBD Input Bad Quality ‐ Usr Def (07:04) BI 173 DI 173 10173 TBD TBD Input Bad Quality ‐ Usr Def (07:05) BI 174 DI 174 10174 TBD TBD Input Bad Quality ‐ Usr Def (07:06) BI 175 DI 175 10175 TBD TBD Input Bad Quality ‐ Usr Def (07:07) BI 176 DI 176 10176 TBD TBD LAlm ‐ Usr Def (07:00) BI 177 DI 177 10177 TBD TBD LAlm ‐ Usr Def (07:01) BI 178 DI 178 10178 TBD TBD LAlm ‐ Usr Def (07:02) BI 179 DI 179 10179 TBD TBD LAlm ‐ Usr Def (07:03) BI 180 DI 180 10180 TBD TBD LAlm ‐ Usr Def (07:04) BI 181 DI 181 10181 TBD TBD LAlm ‐ Usr Def (07:05) BI 182 DI 182 10182 TBD TBD LAlm ‐ Usr Def (07:06) BI 183 DI 183 10183 TBD TBD LAlm ‐ Usr Def (07:07) BI 184 DI 184 10184 TBD TBD Reserved BI 185 DI 185 10185 TBD TBD Reserved BI 186 DI 186 10186 TBD TBD Reserved BI 187 DI 187 10187 TBD TBD Reserved BI 188 DI 188 10188 TBD TBD Reserved BI 189 DI 189 10189 TBD TBD Reserved BI 190 DI 190 10190 TBD TBD Reserved BI 191 DI 191 10191 TBD TBD Reserved BI 192 DI 192 10192 TBD TBD Steam Press AI 1 AI 1 30001 TBD TBD Drum Level AI 2 AI 2 30003 TBD TBD Stack Temp AI 3 AI 3 30005 TBD TBD Remote Modulation AI 4 AI 4 30007 TBD TBD Steam Flo AI 5 AI 5 30009 TBD TBD 64 750-361 ProtoNode Gateway Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Mud Drum Shell Temp AI 6 AI 6 30011 TBD TBD VSD Speed Feedback AI 7 AI 7 30013 TBD TBD Flue Gas O2 AI 8 AI 8 30015 TBD TBD F1 Flo or Usr Def AI 9 AI 9 30017 TBD TBD F2 Flo or Usr Def AI 10 AI 10 30019 TBD TBD Stack Draft or Usr Def AI 11 AI 11 30021 TBD TBD Feedwtr Flo or Usr Def AI 12 AI 12 30023 TBD TBD Econ Outlet FG Temp or Usr Def AI 13 AI 13 30025 TBD TBD Econ Inlet FW Temp or Usr Def AI 14 AI 14 30027 TBD TBD Econ Outlet FW Temp or Usr Def AI 15 AI 15 30029 TBD TBD Air Flo or Usr Def AI 16 AI 16 30031 TBD TBD Steam Press SP AI 17 AI 17 30033 TBD TBD Drum Level SP AI 18 AI 18 30035 TBD TBD Flue Gas O2 SP AI 19 AI 19 30037 TBD TBD Boiler Effiiciency AI 20 AI 20 30039 TBD TBD VSD Motor KW AI 21 AI 21 30041 TBD TBD VSD Motor Current AI 22 AI 22 30043 TBD TBD Firing Rate AI 23 AI 23 30045 TBD TBD Drum Level % AI 24 AI 24 30047 TBD TBD Jackshaft Actuator (Pct) AI 25 AI 25 30049 TBD TBD Actuator7 (Feedwtr Valve) (Pct) AI 26 AI 26 30051 TBD TBD Actuator5 (VSD) (Pct) AI 27 AI 27 30053 TBD TBD Actuator6 (Outlet Damper) (Pct) AI 28 AI 28 30055 TBD TBD Actuator1 (Air) CV (POSP_SP) AI 29 AI 29 30057 TBD TBD Actuator2 (F1) CV (POSP_SP) AI 30 AI 30 30059 TBD TBD Actuator3 (F2) CV (POSP_SP) AI 31 AI 31 30061 TBD TBD Actuator4 (FGR) CV (POSP_ SP) AI 32 AI 32 30063 TBD TBD VSD Speed (Hz) AI 33 AI 33 30065 TBD TBD Boiler Number Derrived From IP Address AI 34 AI 34 30067 TBD TBD Reserved AI 35 AI 35 30069 TBD TBD Reserved AI 36 AI 36 30071 TBD TBD Reserved AI 37 AI 37 30073 TBD TBD Reserved AI 38 AI 38 30075 TBD TBD Reserved AI 39 AI 39 30077 TBD TBD Reserved AI 40 AI 40 30079 TBD TBD Elapsed Time AI 41 AI 41 30081 TBD TBD Number Of Cycles AI 42 AI 42 30082 TBD TBD Steam Press (06:00) AI 43 AI 43 30083 TBD TBD Drum Level (06:01) AI 44 AI 44 30084 TBD TBD Stack Temp (06:02) AI 45 AI 45 30085 TBD TBD Remote Modulation (06:03) AI 46 AI 46 30086 TBD TBD Steam Flo (06:04) AI 47 AI 47 30087 TBD TBD Mud Drum Shell Temp (06:05) AI 48 AI 48 30088 TBD TBD Actuator5 (VSD) FB (06:06) AI 49 AI 49 30089 TBD TBD Flue Gas O2 (06:07) AI 50 AI 50 30090 TBD TBD F1 Flo or Usr Def (07:00) AI 51 AI 51 30091 TBD TBD F2 Flo or Usr Def (07:01) AI 52 AI 52 30092 TBD TBD Stack Draft or Usr Def (07:02) AI 53 AI 53 30093 TBD TBD Feedwtr Flo or Usr Def (07:03) AI 54 AI 54 30094 TBD TBD Econ Outlet FG Temp or Usr Def (07:04) AI 55 AI 55 30095 TBD TBD 750-361 65 ProtoNode Gateway Table 20: Hawk 5000 Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Econ Inlet FW Temp or Usr Def (07:05) AI 56 AI 56 30096 TBD TBD Econ Outlet FW Temp or Usr Def (07:06) AI 57 AI 57 30097 TBD TBD Air Flo or Usr Def (07:07) AI 58 AI 58 30098 TBD TBD Alm Tickler State Register AI 59 AI 59 30099 TBD TBD Fuel 1 Type AI 60 AI 60 30100 TBD TBD Fuel 2 Type AI 61 AI 61 30101 TBD TBD Flame Strength ‐ CB120 AI 62 AI 62 30102 TBD TBD Flame Strength ‐ CB780 AI 63 AI 63 30103 TBD TBD Main Flame Flicker AI 64 AI 64 30104 TBD TBD Reserved AI 65 AI 65 30105 TBD TBD Reserved AI 66 AI 66 30106 TBD TBD Burner Control Status Line 00 AI 67 AI 67 30107 TBD TBD Burner Control Diagnostics 05 AI 68 AI 68 30108 TBD TBD Failed I/O Module Number AI 69 AI 69 30109 TBD TBD IP Address 00 AI 70 AI 70 30110 TBD TBD IP Address 01 AI 71 AI 71 30111 TBD TBD IP Address 02 AI 72 AI 72 30112 TBD TBD IP Address 03 AI 73 AI 73 30113 TBD TBD IP Address 04 AI 74 AI 74 30114 TBD TBD 66 750-361 ProtoNode Gateway B.11. HAWK MASTER PANEL Table 21: Hawk Master Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Boiler A Ethernet Comm Error BACnet  Object Type BI BACnet  Object ID 1287 N2 Data  Type DI N2 Point  Address 1 Modbus RTU  Register 11287 Boiler B Ethernet Comm Error BI 1288 DI 2 11288 Boiler C Ethernet Comm Error BI 1289 DI 3 Boiler D Ethernet Comm Error BI 1290 DI 4 Steam/Water  Sensor Fail BI 1291 DI 5 Point Name Lon Name Lon SNVT TBD TBD TBD TBD 11289 TBD TBD 11290 TBD TBD 11291 TBD TBD Low Steam Pressure BI 1292 DI 6 11292 TBD TBD Boiler A Power Failure BI 1293 DI 7 11293 TBD TBD TBD Boiler B Power Failure BI 1294 DI 8 11294 TBD Boiler C Power Failure BI 1295 DI 9 11295 TBD TBD Boiler D Power Failure BI 1296 DI 10 11296 TBD TBD Boiler A Ready BI 1297 DI 11 11297 TBD TBD Boiler B Ready BI 1298 DI 12 11298 TBD TBD Boiler C Ready BI 1299 DI 13 11299 TBD TBD Boiler D Ready BI 1300 DI 14 11300 TBD TBD Power To Boiler A BI 1301 DI 15 11301 TBD TBD Power To Boiler B BI 1302 DI 16 11302 TBD TBD Power To Boiler C BI 1303 DI 17 11303 TBD TBD Power To Boiler D BI 1304 DI 18 11304 TBD TBD Boiler A Start Output BI 1305 DI 19 11305 TBD TBD Boiler B Start Output BI 1306 DI 20 11306 TBD TBD Boiler C Start Output BI 1307 DI 21 11307 TBD TBD Boiler D Start Output BI 1308 DI 22 11308 TBD TBD Unison Modulation BI 1309 DI 23 11309 TBD TBD L/Lag Modulation BI 1310 DI 24 11310 TBD TBD English System BI 1311 DI 25 11311 TBD TBD Metric System BI 1312 DI 26 11312 TBD TBD Auto Rotation On BI 1313 DI 27 11313 TBD TBD AMB[1]11 BI 1314 DI 28 11314 TBD TBD AMB[1]12 BI 1315 DI 29 11315 TBD TBD AMB[1]13 BI 1316 DI 30 11316 TBD TBD AMB[1]14 BI 1317 DI 31 11317 TBD TBD AMB[1]15 BI 1318 DI 32 11318 TBD TBD Boiler E Ethernet Comm Error BI 1319 DI 33 11319 TBD TBD Boiler F Ethernet Comm Error BI 1320 DI 34 11320 TBD TBD Boiler G Ethernet Comm Error BI 1321 DI 35 11321 TBD TBD Boiler H Ethernet Comm Error BI 1322 DI 36 11322 TBD TBD TBD I/O Module Failure BI 1323 DI 37 11323 TBD AMB[2]5 BI 1324 DI 38 11324 TBD TBD Boiler E Power Failure BI 1325 DI 39 11325 TBD TBD Boiler F Power Failure BI 1326 DI 40 11326 TBD TBD Boiler G Power Failure BI 1327 DI 41 11327 TBD TBD Boiler H Power Failure BI 1328 DI 42 11328 TBD TBD Boiler E Ready BI 1329 DI 43 11329 TBD TBD Boiler F Ready BI 1330 DI 44 11330 TBD TBD Boiler G Ready BI 1331 DI 45 11331 TBD TBD Boiler H Ready BI 1332 DI 46 11332 TBD TBD Power To Boiler E BI 1333 DI 47 11333 TBD TBD 750-361 67 ProtoNode Gateway Table 21: Hawk Master Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Power To Boiler F BI 1334 DI 48 11334 TBD TBD Power To Boiler G BI 1335 DI 49 11335 TBD TBD Power To Boiler H BI 1336 DI 50 11336 TBD TBD Boiler E Start Output BI 1337 DI 60 11337 TBD TBD Boiler F Start Output BI 1338 DI 61 11338 TBD TBD Boiler G Start Output BI 1339 DI 62 11339 TBD TBD Boiler H Start Output BI 1340 DI 63 11340 TBD TBD AMB[3]6 BI 1341 DI 64 11341 TBD TBD AMB[3]7 BI 1342 DI 65 11342 TBD TBD AMB[3]8 BI 1343 DI 66 11343 TBD TBD AMB[3]9 BI 1344 DI 67 11344 TBD TBD AMB[3]10 BI 1345 DI 68 11345 TBD TBD AMB[3]11 BI 1346 DI 69 11346 TBD TBD AMB[3]12 BI 1347 DI 70 11347 TBD TBD AMB[3]13 BI 1348 DI 71 11348 TBD TBD AMB[3]14 BI 1349 DI 72 11349 TBD TBD AMB[3]15 BI 1350 DI 73 11350 TBD TBD Number of units AI 613 AI 1 31105 TBD TBD Boiler A Sequence Status AI 614 AI 2 31106 TBD TBD Boiler B Sequence Status AI 615 AI 3 31107 TBD TBD Boiler C Sequence Status AI 616 AI 4 31108 TBD TBD Boiler D Sequence Status AI 617 AI 5 31109 TBD TBD Auto Sequence Rotation Days Set AI 618 AI 6 31110 TBD TBD Blr A Run Time Since Last Rot (Days) AI 619 AI 7 31111 TBD TBD Blr A Run Time Since Last Rot (Hrs) AI 620 AI 8 31112 TBD TBD Blr A Run Time Since Last Rot (Min) AI 621 AI 9 31113 TBD TBD Blr B Run Time Since Last Rot (Days) AI 622 AI 10 31114 TBD TBD Blr B Run Time Since Last Rot (Hrs) AI 623 AI 11 31115 TBD TBD Blr B Run Time Since Last Rot (Min) AI 624 AI 12 31116 TBD TBD Blr C Run Time Since Last Rot (Days) AI 625 AI 13 31117 TBD TBD Blr C Run Time Since Last Rot (Hrs) AI 626 AI 14 31118 TBD TBD Blr C Run Time Since Last Rot (Min) AI 627 AI 15 31119 TBD TBD Blr D Run Time Since Last Rot (Days) AI 628 AI 16 31120 TBD TBD Blr D Run Time Since Last Rot (Hrs) AI 629 AI 17 31121 TBD TBD Blr D Run Time Since Last Rot (Min) AI 630 AI 18 31122 TBD TBD AMI[18] AI 631 AI 19 31123 TBD TBD AMI[19] AI 632 AI 20 31124 TBD TBD AMI[20] AI 633 AI 21 31125 TBD TBD Boiler E Sequence Status AI 634 AI 22 31126 TBD TBD Boiler F Sequence Status AI 635 AI 23 31127 TBD TBD Boiler G Sequence Status AI 636 AI 24 31128 TBD TBD TBD Boiler H Sequence Status AI 637 AI 25 31129 TBD AMI[25] AI 638 AI 26 31130 TBD TBD Blr E Run Time Since Last Rot (Days) AI 639 AI 27 31131 TBD TBD Blr E Run Time Since Last Rot (Hrs) AI 640 AI 28 31132 TBD TBD Blr E Run Time Since Last Rot (Min) AI 641 AI 29 31133 TBD TBD Blr F Run Time Since Last Rot (Days) AI 642 AI 30 31134 TBD TBD Blr F Run Time Since Last Rot (Hrs) AI 643 AI 31 31135 TBD TBD Blr F Run Time Since Last Rot (Min) AI 644 AI 32 31136 TBD TBD Blr G Run Time Since Last Rot (Days) AI 645 AI 33 31137 TBD TBD 68 750-361 ProtoNode Gateway Table 21: Hawk Master Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * Blr G Run Time Since Last Rot (Hrs) AI Blr G Run Time Since Last Rot (Min) AI Blr H Run Time Since Last Rot (Days) AI Blr H Run Time Since Last Rot (Hrs) AI Blr H Run Time Since Last Rot (Min) 646 AI 34 31138 TBD TBD 647 AI 35 31139 TBD TBD 648 AI 36 31140 TBD TBD 649 AI 37 31141 TBD TBD AI 650 AI 38 31142 TBD TBD Blr A Lead Lag Entered Seq AI 651 AI 39 31143 TBD TBD Blr B Lead Lag Entered Seq AI 652 AI 40 31144 TBD TBD Blr C Lead Lag Entered Seq AI 653 AI 41 31145 TBD TBD Blr D Lead Lag Entered Seq AI 654 AI 42 31146 TBD TBD Blr E Lead Lag Entered Seq AI 655 AI 43 31147 TBD TBD Blr F Lead Lag Entered Seq AI 656 AI 44 31148 TBD TBD Blr G Lead Lag Entered Seq AI 657 AI 45 31149 TBD TBD Blr H Lead Lag Entered Seq AI 658 AI 46 31150 TBD TBD Blr A Lead Lag Working Seq AI 659 AI 47 31151 TBD TBD Blr B Lead Lag Working Seq AI 660 AI 48 31152 TBD TBD Blr C Lead Lag Working Seq AI 661 AI 49 31153 TBD TBD Blr D Lead Lag Working Seq AI 662 AI 50 31154 TBD TBD Blr E Lead Lag Working Seq AI 663 AI 51 31155 TBD TBD Blr F Lead Lag Working Seq AI 664 AI 52 31156 TBD TBD Blr G Lead Lag Working Seq AI 665 AI 53 31157 TBD TBD Blr H Lead Lag Working Seq AI 666 AI 54 31158 TBD TBD Max Pressure/Temp AI 401 AI 55 30801 TBD TBD Lead Boiler On Point AI 402 AI 56 30803 TBD TBD Lead Boiler Off Point AI 403 AI 57 30805 TBD TBD Operating Pressure/Temp AI 404 AI 58 30807 TBD TBD Low SP Limit AI 405 AI 59 30809 TBD TBD High SP Limit AI 406 AI 60 30811 TBD TBD Days Till Auto Seq Rotation AI 407 AI 61 30813 TBD TBD Hours Till Auto Seq Rotation AI 408 AI 62 30815 TBD TBD Minutes Till Auto Seq Rotation AI 409 AI 63 30817 TBD TBD Seconds Till Auto Seq Rotation AI 410 AI 64 30819 TBD TBD Control Output Boiler A AI 411 AI 65 30821 TBD TBD Control Output Boiler B AI 412 AI 66 30823 TBD TBD Control Output Boiler C AI 413 AI 67 30825 TBD TBD Control Output Boiler D AI 414 AI 68 30827 TBD TBD Control Output Boiler E AI 415 AI 69 30829 TBD TBD Control Output Boiler F AI 416 AI 70 30831 TBD TBD Control Output Boiler G AI 417 AI 71 30833 TBD TBD Control Output Boiler H AI 418 AI 72 30835 TBD TBD Steam Pressure (Water Temp) SP AI 419 AI 73 30837 TBD TBD AMR[19] AI 420 AI 74 30839 TBD TBD AMR[20] AI 421 AI 75 30841 TBD TBD AMR[21] AI 422 AI 76 30843 TBD TBD AMR[22] AI 423 AI 77 30845 TBD TBD AMR[23] AI 424 AI 78 30847 TBD TBD AMR[24] AI 425 AI 79 30849 TBD TBD AMR[25] AI 426 AI 80 30851 TBD TBD Master Write Bit BV 1 DO 1 00001 TBD TBD Setpoint Value Write AV 51 AO 51 40051 TBD TBD N510[0] AV 1 AO 1 40001 TBD TBD 750-361 69 ProtoNode Gateway Table 21: Hawk Master Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Lag 1 Start Timer Set AV 2 AO 2 40002 TBD TBD Lag 1 Start Point AV 3 AO 3 40003 TBD TBD Lag 1 Stop Point AV 4 AO 4 40004 TBD TBD Lag 1 Stop Timer Set AV 5 AO 5 40005 TBD TBD N510[5] AV 6 AO 6 40006 TBD TBD Lag 2 Start Timer Set AV 7 AO 7 40007 TBD TBD Lag 2 Start Point AV 8 AO 8 40008 TBD TBD Lag 2 Stop Point AV 9 AO 9 40009 TBD TBD Lag 2 Stop Timer Set AV 10 AO 10 40010 TBD TBD N510[10] AV 11 AO 11 40011 TBD TBD Lag 3 Start Timer Set AV 12 AO 12 40012 TBD TBD Lag 3 Start Point AV 13 AO 13 40013 TBD TBD Lag 3 Stop Point AV 14 AO 14 40014 TBD TBD Lag 3 Stop Timer Set AV 15 AO 15 40015 TBD TBD Lead Boiler Selection AV 16 AO 16 40016 TBD TBD Lag 1 Boiler Selection AV 17 AO 17 40017 TBD TBD Lag 2 Boiler Selection AV 18 AO 18 40018 TBD TBD Lag 3 Boiler Selection AV 19 AO 19 40019 TBD TBD Lag 4 Boiler Selection AV 20 AO 20 40020 TBD TBD Lag 5 Boiler Selection AV 21 AO 21 40021 TBD TBD Lag 6 Boiler Selection AV 22 AO 22 40022 TBD TBD Lag 7 Boiler Selection AV 23 AO 23 40023 TBD TBD Lag 4 Start Timer Set AV 24 AO 24 40024 TBD TBD Lag 4 Start Point AV 25 AO 25 40025 TBD TBD Lag 4 Stop Point AV 26 AO 26 40026 TBD TBD Lag 4 Stop Timer Set AV 27 AO 27 40027 TBD TBD Lag 5 Start Timer Set AV 28 AO 28 40028 TBD TBD Lag 5 Start Point AV 29 AO 29 40029 TBD TBD Lag 5 Stop Point AV 30 AO 30 40030 TBD TBD Lag 5 Stop Timer Set AV 31 AO 31 40031 TBD TBD Lag 6 Start Timer Set AV 32 AO 32 40032 TBD TBD Lag 6 Start Point AV 33 AO 33 40033 TBD TBD Lag 6 Stop Point AV 34 AO 34 40034 TBD TBD Lag 6 Stop Timer Set AV 35 AO 35 40035 TBD TBD Lag 7 Start Timer Set AV 36 AO 36 40036 TBD TBD Lag 7 Start Point AV 37 AO 37 40037 TBD TBD Lag 7 Stop Point AV 38 AO 38 40038 TBD TBD Lag 7 Stop Timer Set AV 39 AO 39 40039 TBD TBD N510[39] AV 40 AO 40 40040 TBD TBD N510[40] AV 41 AO 41 40041 TBD TBD N510[41] AV 42 AO 42 40042 TBD TBD N510[42] AV 43 AO 43 40043 TBD TBD N510[43] AV 44 AO 44 40044 TBD TBD N510[44] AV 45 AO 45 40045 TBD TBD N510[45] AV 46 AO 46 40046 TBD TBD N510[46] AV 47 AO 47 40047 TBD TBD N510[47] AV 48 AO 48 40048 TBD TBD N510[48] AV 49 AO 49 40049 TBD TBD N510[49] AV 50 AO 50 40050 TBD TBD *Write points 70 750-361 ProtoNode Gateway B.12. ADAC Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks Point Name Deaerator Lvl BAD QUALITY Deaerator Lvl Hi BACnet  Object Type BI BACnet  Object ID 1 N2 Data  Type DI N2 Point  Address 1 Modbus  Register 11351 BI 2 DI 2 11352 TBD Lon Name Lon SNVT TBD TBD TBD TBD Deaerator Lvl Lo BI 3 DI 3 11353 TBD Deaerator Lvl Lo‐Lo (LWCO) BI 4 DI 4 11354 TBD TBD Feed Pump 1 Flt BI 5 DI 5 11355 TBD TBD Feed Pump 2 Flt BI 6 DI 6 11356 TBD TBD Feed Pump 3 Flt BI 7 DI 7 11357 TBD TBD Feed Pump 4 Flt BI 8 DI 8 11358 TBD TBD Feed Pump 5 Flt BI 9 DI 9 11359 TBD TBD Feed Pump 6 Flt BI 10 DI 10 11360 TBD TBD Feed Pump 1 OVERLOAD BI 11 DI 11 11361 TBD TBD Feed Pump 2 OVERLOAD BI 12 DI 12 11362 TBD TBD Feed Pump 3 OVERLOAD BI 13 DI 13 11363 TBD TBD Feed Pump 4 OVERLOAD BI 14 DI 14 11364 TBD TBD Feed Pump 5 OVERLOAD BI 15 DI 15 11365 TBD TBD Feed Pump 6 OVERLOAD BI 16 DI 16 11366 TBD TBD Spare BI 17 DI 17 11367 TBD TBD Spare BI 18 DI 18 11368 TBD TBD Spare BI 19 DI 19 11369 TBD TBD Deaerator Temp BAD QUALITY BI 20 DI 20 11370 TBD TBD TBD Deaerator Temp Lo BI 21 DI 21 11371 TBD Deaerator Temp Hi BI 22 DI 22 11372 TBD TBD Deaerator Pressure BAD QUALITY BI 23 DI 23 11373 TBD TBD Deaerator Pressure Lo BI 24 DI 24 11374 TBD TBD Deaerator Pressure Hi BI 25 DI 25 11375 TBD TBD Boiler Feed Wtr Header Pressure BQ BI 26 DI 26 11376 TBD TBD Boiler Feed Wtr Header Pressure Lo BI 27 DI 27 11377 TBD TBD Boiler Feed Wtr Header Pressure Hi BI 28 DI 28 11378 TBD TBD DAB1[1]12 BI 29 DI 29 11379 TBD TBD DAB1[1]13 BI 30 DI 30 11380 TBD TBD DAB1[1]14 BI 31 DI 31 11381 TBD TBD DAB1[1]15 BI 32 DI 32 11382 TBD TBD DAB1[2]0 BI 33 DI 33 11383 TBD TBD DAB1[2]1 BI 34 DI 34 11384 TBD TBD DAB1[2]2 BI 35 DI 35 11385 TBD TBD DAB1[2]3 BI 36 DI 36 11386 TBD TBD DAB1[2]4 BI 37 DI 37 11387 TBD TBD DAB1[2]5 BI 38 DI 38 11388 TBD TBD DAB1[2]6 BI 39 DI 39 11389 TBD TBD DAB1[2]7 BI 40 DI 40 11390 TBD TBD DAB1[2]8 BI 41 DI 41 11391 TBD TBD DAB1[2]9 BI 42 DI 42 11392 TBD TBD DAB1[2]10 BI 43 DI 43 11393 TBD TBD DAB1[2]11 BI 44 DI 44 11394 TBD TBD DAB1[2]12 BI 45 DI 45 11395 TBD TBD DAB1[2]13 BI 46 DI 46 11396 TBD TBD DAB1[2]14 BI 47 DI 47 11397 TBD TBD 750-361 71 ProtoNode Gateway Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) DAB1[2]15 BI 48 DI 48 11398 TBD TBD Feed Pump 1 ON BI 49 DI 49 11399 TBD TBD Feed Pump 2 ON BI 50 DI 50 11400 TBD TBD Feed Pump 3 ON BI 51 DI 51 11401 TBD TBD Feed Pump 4 ON BI 52 DI 52 11402 TBD TBD Feed Pump 5 ON BI 53 DI 53 11403 TBD TBD Feed Pump 6 ON BI 54 DI 54 11404 TBD TBD Feed Pump 1 In AUTO BI 55 DI 55 11405 TBD TBD Feed Pump 2 In AUTO BI 56 DI 56 11406 TBD TBD Feed Pump 3 In AUTO BI 57 DI 57 11407 TBD TBD Feed Pump 4 In AUTO BI 58 DI 58 11408 TBD TBD Feed Pump 5 In AUTO BI 59 DI 59 11409 TBD TBD Feed Pump 6 In AUTO BI 60 DI 60 11410 TBD TBD Deaerator No Alarms Relay OK BI 61 DI 61 11411 TBD TBD YelLo Stack Light ON BI 62 DI 62 11412 TBD TBD Green Stack Light ON BI 63 DI 63 11413 TBD TBD Red Stack Light ON BI 64 DI 64 11414 TBD TBD Chemical Feed ON BI 65 DI 65 11415 TBD TBD Deaerator Feed Wtr Valve Open BI 66 DI 66 11416 TBD TBD Feed Pumps ALT MODE ON BI 67 DI 67 11417 TBD TBD DA Lo‐Lo Wtr Cutoff Relay Energized BI 68 DI 68 11418 TBD TBD Deaerator 2nd Feed Wtr Valve Open BI 69 DI 69 11419 TBD TBD Boiler Feed Pump 1 FLo Flt BI 70 DI 70 11420 TBD TBD Boiler Feed Pump 2 FLo Flt BI 71 DI 71 11421 TBD TBD Boiler Feed Pump 3 FLo Flt BI 72 DI 72 11422 TBD TBD Boiler Feed Pump 4 FLo Flt BI 73 DI 73 11423 TBD TBD Boiler Feed Pump 5 FLo Flt BI 74 DI 74 11424 TBD TBD Boiler Feed Pump 6 FLo Flt BI 75 DI 75 11425 TBD TBD PLC Battery Lo  Replace Battery BI 76 DI 76 11426 TBD TBD Feed Pump 1 VSD Speed Feedback  Bad Q Feed Pump 2 VSD Speed Feedback  Bad Q Feed Pump 3 VSD Speed Feedback  Bad Q Feed Pump 4 VSD Speed Feedback  Bad Q Feed Pump 5 VSD Speed Feedback  Bad Q Feed Pump 6 VSD Speed Feedback  Bad Q DAB1[5]2 BI 77 DI 77 11427 TBD TBD BI 78 DI 78 11428 TBD TBD BI 79 DI 79 11429 TBD TBD BI 80 DI 80 11430 TBD TBD BI 81 DI 81 11431 TBD TBD BI 82 DI 82 11432 TBD TBD BI 83 DI 83 11433 TBD TBD DAB1[5]3 BI 84 DI 84 11434 TBD TBD DAB1[5]4 BI 85 DI 85 11435 TBD TBD DAB1[5]5 BI 86 DI 86 11436 TBD TBD DAB1[5]6 BI 87 DI 87 11437 TBD TBD DAB1[5]7 BI 88 DI 88 11438 TBD TBD DAB1[5]8 BI 89 DI 89 11439 TBD TBD DAB1[5]9 BI 90 DI 90 11440 TBD TBD DAB1[5]10 BI 91 DI 91 11441 TBD TBD DAB1[5]11 BI 92 DI 92 11442 TBD TBD DAB1[5]12 BI 93 DI 93 11443 TBD TBD 72 750-361 ProtoNode Gateway Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) DAB1[5]13 BI 94 DI 94 11444 TBD TBD DAB1[5]14 BI 95 DI 95 11445 TBD TBD DAB1[5]15 BI 96 DI 96 11446 TBD TBD Surge Tank Lvl BAD QUALITY BI 97 DI 97 11447 TBD TBD Surge Tank Lvl Hi BI 98 DI 98 11448 TBD TBD Surge Tank Lvl Lo BI 99 DI 99 11449 TBD TBD Surge Tank Temp BAD QUALITY BI 100 DI 100 11450 TBD TBD Surge Tank Temp Lo BI 101 DI 101 11451 TBD TBD Surge Tank Temp Hi BI 102 DI 102 11452 TBD TBD Transfer Pump 1 Flt BI 103 DI 103 11453 TBD TBD Transfer Pump 2 Flt BI 104 DI 104 11454 TBD TBD Transfer Pump 3 Flt BI 105 DI 105 11455 TBD TBD Transfer Pump 1 OVERLOAD BI 106 DI 106 11456 TBD TBD Transfer Pump 2OVERLOAD BI 107 DI 107 11457 TBD TBD Transfer Pump 3OVERLOAD BI 108 DI 108 11458 TBD TBD Surge Tank Lo‐Lo (LWCO) BI 109 DI 109 11459 TBD TBD Surge Tank Header Pressure Hi BI 110 DI 110 11460 TBD TBD Surge Tank Header Pressure Lo BI 111 DI 111 11461 TBD TBD Surge Tank Header Pressure BAD  QUALITY DAB1[7]0 BI 112 DI 112 11462 TBD TBD BI 113 DI 113 11463 TBD TBD DAB1[7]1 BI 114 DI 114 11464 TBD TBD DAB1[7]2 BI 115 DI 115 11465 TBD TBD Surge 2nd Feed Wtr Valve Open BI 116 DI 116 11466 TBD TBD Transfer Pump 1 FLo Flt BI 117 DI 117 11467 TBD TBD Transfer Pump 2 FLo Flt BI 118 DI 118 11468 TBD TBD Transfer Pump 3 FLo Flt BI 119 DI 119 11469 TBD TBD Transfer Pump 1 VSD Speed  Feedback BQ Transfer Pump 2 VSD Speed  Feedback BQ Transfer Pump 3 VSD Speed  Feedback BQ DAB1[7]10 BI 120 DI 120 11470 TBD TBD BI 121 DI 121 11471 TBD TBD BI 122 DI 122 11472 TBD TBD BI 123 DI 123 11473 TBD TBD DAB1[7]11 BI 124 DI 124 11474 TBD TBD DAB1[7]12 BI 125 DI 125 11475 TBD TBD DAB1[7]13 BI 126 DI 126 11476 TBD TBD DAB1[7]14 BI 127 DI 127 11477 TBD TBD DAB1[7]15 BI 128 DI 128 11478 TBD TBD Surge Tank No Alarms Relay OK BI 129 DI 129 11479 TBD TBD YelLo Stack Light ON BI 130 DI 130 11480 TBD TBD Green Stack Light ON BI 131 DI 131 11481 TBD TBD RED Stack Light ON BI 132 DI 132 11482 TBD TBD Surge Tank Feed Wtr Valve Open BI 133 DI 133 11483 TBD TBD ST Lo Lo Wtr Cutoff Relay Energized BI 134 DI 134 11484 TBD TBD Transfer Pump 1 ON BI 135 DI 135 11485 TBD TBD Transfer Pump 2 ON BI 136 DI 136 11486 TBD TBD Transfer Pump 3 ON BI 137 DI 137 11487 TBD TBD Transfer Pump 1 In AUTO BI 138 DI 138 11488 TBD TBD Transfer Pump 2 In AUTO BI 139 DI 139 11489 TBD TBD Transfer Pump 3 In AUTO BI 140 DI 140 11490 TBD TBD 750-361 73 ProtoNode Gateway Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) Transfer Pumps ALT MODE ON BI 141 DI 141 11491 TBD TBD DAB1[8]13 BI 142 DI 142 11492 TBD TBD DAB1[8]14 BI 143 DI 143 11493 TBD TBD DAB1[8]15 BI 144 DI 144 11494 TBD TBD DAB1[9]0 BI 145 DI 145 11495 TBD TBD DAB1[9]1 BI 146 DI 146 11496 TBD TBD DAB1[9]2 BI 147 DI 147 11497 TBD TBD DAB1[9]3 BI 148 DI 148 11498 TBD TBD DAB1[9]4 BI 149 DI 149 11499 TBD TBD DAB1[9]5 BI 150 DI 150 11500 TBD TBD DAB1[9]6 BI 151 DI 151 11501 TBD TBD DAB1[9]7 BI 152 DI 152 11502 TBD TBD DAB1[9]8 BI 153 DI 153 11503 TBD TBD DAB1[9]9 BI 154 DI 154 11504 TBD TBD DAB1[9]10 BI 155 DI 155 11505 TBD TBD DAB1[9]11 BI 156 DI 156 11506 TBD TBD DAB1[9]12 BI 157 DI 157 11507 TBD TBD DAB1[9]13 BI 158 DI 158 11508 TBD TBD DAB1[9]14 BI 159 DI 159 11509 TBD TBD DAB1[9]15 BI 160 DI 160 11510 TBD TBD Feed Pump 1 Run Time AI 1 AI 1 30853 TBD TBD Feed Pump 2 Run Time AI 2 AI 2 30855 TBD TBD Feed Pump 3 Run Time AI 3 AI 3 30857 TBD TBD Feed Pump 4 Run Time AI 4 AI 4 30859 TBD TBD Feed Pump 5 Run Time AI 5 AI 5 30861 TBD TBD Feed Pump 6 Run Time AI 6 AI 6 30863 TBD TBD DAR1[6] AI 7 AI 7 30865 TBD TBD DAR1[7] AI 8 AI 8 30867 TBD TBD DAR1[8] AI 9 AI 9 30869 TBD TBD Stop Lag Feed Pump Limit AI 10 AI 10 30871 TBD TBD Alternate Feed Pumps AI 11 AI 11 30873 TBD TBD Start Chemical Feed Time Delay AI 12 AI 12 30875 TBD TBD Stop Chemical Feed Time Delay AI 13 AI 13 30877 TBD TBD DAR1[14] AI 14 AI 14 30879 TBD TBD Deaerator Temp AI 15 AI 15 30881 TBD TBD Deaerator Tank Pressure AI 16 AI 16 30883 TBD TBD Deaerator Tank Wtr Lvl AI 17 AI 17 30885 TBD TBD Deaerator Feed Wtr (MUV) Signal AI 18 AI 18 30887 TBD TBD Deaerator Steam PRValve Signal AI 19 AI 19 30889 TBD TBD Boiler Feed Wtr Header Pressure AI 20 AI 20 30891 TBD TBD Deaerator 2nd Feed Wtr (MUV)  Signal Start Lag Feed Pump Limit AI 21 AI 21 30893 TBD TBD AI 22 AI 22 30895 TBD TBD DA Lvl ‐ Pump Auto‐Restart Lvl AI 23 AI 23 30897 TBD TBD DAR1[24] AI 24 AI 24 30899 TBD TBD DAR1[25] AI 25 AI 25 30901 TBD TBD DAR1[26] AI 26 AI 26 30903 TBD TBD DAR1[27] AI 27 AI 27 30905 TBD TBD DAR1[28] AI 28 AI 28 30907 TBD TBD DAR1[29] AI 29 AI 29 30909 TBD TBD DAR1[30] AI 30 AI 30 30911 TBD TBD 74 750-361 ProtoNode Gateway Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) DAR1[31] AI 31 AI 31 30913 TBD TBD DAR1[32] AI 32 AI 32 30915 TBD TBD DAR1[33] AI 33 AI 33 30917 TBD TBD DAR1[34] AI 34 AI 34 30919 TBD TBD DAR1[35] AI 35 AI 35 30921 TBD TBD DAR1[36] AI 36 AI 36 30923 TBD TBD DAR1[37] AI 37 AI 37 30925 TBD TBD DAR1[38] AI 38 AI 38 30927 TBD TBD Surge Header Pressure AI 39 AI 39 30929 TBD TBD Surge Tank Temp AI 40 AI 40 30931 TBD TBD Surge Tank Wtr Lvl AI 41 AI 41 30933 TBD TBD Surge Tank Feed Wtr (MUV) Signal AI 42 AI 42 30935 TBD TBD Transfer Pump 1 Run Time AI 43 AI 43 30937 TBD TBD Transfer Pump 2 Run Time AI 44 AI 44 30939 TBD TBD Transfer Pump 3 Run Time AI 45 AI 45 30941 TBD TBD Alternate Transfer Pumps AI 46 AI 46 30943 TBD TBD Stop Transfer Lag Feed Pump Limit AI 47 AI 47 30945 TBD TBD Surge Tank 2nd Feed Wtr (MUV)  Signal Start Lag Feed Pump Limit AI 48 AI 48 30947 TBD TBD AI 49 AI 49 30949 TBD TBD Surge Lvl ‐ Pump Auto‐Restart Lvl AI 50 AI 50 30951 TBD TBD DAR1[51] AI 51 AI 51 30953 TBD TBD DAR1[52] AI 52 AI 52 30955 TBD TBD DAR1[53] AI 53 AI 53 30957 TBD TBD DAR1[54] AI 54 AI 54 30959 TBD TBD DAR1[55] AI 55 AI 55 30961 TBD TBD DAR1[56] AI 56 AI 56 30963 TBD TBD DAR1[57] AI 57 AI 57 30965 TBD TBD DAR1[58] AI 58 AI 58 30967 TBD TBD DAR1[59] AI 59 AI 59 30969 TBD TBD DAR1[60] AI 60 AI 60 30971 TBD TBD DAR1[61] AI 61 AI 61 30973 TBD TBD DAR1[62] AI 62 AI 62 30975 TBD TBD DAR1[63] AI 63 AI 63 30977 TBD TBD DAR1[64] AI 64 AI 64 30979 TBD TBD DAR1[65] AI 65 AI 65 30981 TBD TBD Feed Pump 1 LEAD/LAG Status AI 66 AI 66 30983 TBD TBD Feed Pump 2 LEAD/LAG Status AI 67 AI 67 31159 TBD TBD Feed Pump 3 LEAD/LAG Status AI 68 AI 68 31160 TBD TBD Feed Pump 4 LEAD/LAG Status AI 69 AI 69 31161 TBD TBD Feed Pump 5 LEAD/LAG Status AI 70 AI 70 31162 TBD TBD Feed Pump 6 LEAD/LAG Status AI 71 AI 71 31163 TBD TBD DAI1[6] AI 72 AI 72 31164 TBD TBD DAI1[7] AI 73 AI 73 31165 TBD TBD DAI1[8] AI 74 AI 74 31166 TBD TBD DAI1[9] AI 75 AI 75 31167 TBD TBD DAI1[10] AI 76 AI 76 31168 TBD TBD DAI1[11] AI 77 AI 77 31169 TBD TBD DAI1[12] AI 78 AI 78 31170 TBD TBD DAI1[13] AI 79 AI 79 31171 TBD TBD DAI1[14] AI 80 AI 80 31172 TBD TBD 750-361 75 ProtoNode Gateway Table 22: ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued) DAI1[15] AI 81 AI 81 31173 TBD TBD DAI1[16] AI 82 AI 82 31174 TBD TBD DAI1[17] AI 83 AI 83 31175 TBD TBD DAI1[18] AI 84 AI 84 31176 TBD TBD DAI1[19] AI 85 AI 85 31177 TBD TBD Transfer Pump 1 LEAD/LAG Status AI 86 AI 86 31178 TBD TBD Transfer Pump 2 LEAD/LAG Status AI 87 AI 87 31179 TBD TBD Transfer Pump 3 LEAD/LAG Status AI 88 AI 88 31180 TBD TBD DAI1[23] AI 89 AI 89 31181 TBD TBD DAI1[24] AI 90 AI 90 31182 TBD TBD DAI1[25] AI 91 AI 91 31183 TBD TBD DAI1[26] AI 92 AI 92 31184 TBD TBD DAI1[27] AI 93 AI 93 31185 TBD TBD DAI1[28] AI 94 AI 94 31186 TBD TBD DAI1[29] AI 95 AI 95 31187 TBD TBD DAI1[30] AI 96 AI 96 31188 TBD TBD DAI1[31] AI 97 AI 97 31189 TBD TBD DAI1[32] AI 98 AI 98 31190 TBD TBD DAI1[33] AI 99 AI 99 31191 TBD TBD DAI1[34] AI 100 AI 100 31192 TBD TBD DAI1[35] AI 101 AI 101 31193 TBD TBD DAI1[36] AI 102 AI 102 31194 TBD TBD DAI1[37] AI 103 AI 103 31195 TBD TBD DAI1[38] AI 104 AI 104 31196 TBD TBD DAI1[39] AI 105 AI 105 31197 TBD TBD 76 750-361 ProtoNode Gateway Table 23: CB780 Sequence State Codes String Code cb_sqst Value CB780/784 Sequence State Line 1 LOCKOUT Fault code not zero Line 2 52 Table 25 Uses mm:ss Burner Control State Bits 8000h 0 UNUSED HISTORY 0 0 1 INITIATE 48 0 0000h 2 INITIATE HOLD: AC FREQUENCY/ NOISE 49 8 4001h 3 INITIATE HOLD: AC LINE DROPOUT 49 9 4001h 4 INITIATE HOLD: AC FREQUENCY 49 7 4001h 5 INITIATE HOLD: LOW LINE VOLTAGE 49 60 4001h  0001h 6 STANDBY 103 0 0002h 7 STANDBY HOLD: REM REMOTE CONTROL 104 94 4002h 8 STANDBY HOLD: START SWITCH 104 106 4002h 9 STANDBY HOLD: F/G FLAME DETECTED 104 35 4002h 10 STANDBY HOLD: T20 PREIGNITION LOCK 104 86 4002h 11 STANDBY HOLD: T7 RUNNING INTERLOCK 104 101 4002h 12 STANDBY HOLD: T7 LOCKOUT INTERLOCK 104 54 4002h 13 STANDBY HOLD: AIRFLOW SWITCH 104 13 4002h 14 PURGE HOLD: T19 HIGH FIRE SWITCH 93 40 4004h 15 PURGE DELAY: T19 HIGH FIRE JUMPRD 89 39 4004h 16 PURGE HOLD: TEST RUN/TEST SWITCH 93 98 4004h 17 PURGE DELAY: T18 LOW FIRE JUMPRD 89 56 4004h 4004h 18 PURGE HOLD: F/ G FLAME DETECTED 93 35 19 PURGE 87 0 20 PURGE HOLD: T18 LOW FIRE SWITCH 93 58 4004h 21 PURGE HOLD: T7 RUNNING INTERLOCK 93 101 4004h 22 PURGE HOLD: LOCKOUT INTERLOCK 93 54 4004h  0004h 23 PURGE HOLD: AIRFLOW SWITCH 93 13 4004h 24 PURGE HOLD: START SWITCH 93 106 4004h  25 PILOT IGN 78 0 26 PILOT HOLD: TEST RUN/TEST SWITCH 77 98 4008h 27 PILOT HOLD: START SWITCH 77 106 4008h 28 MAIN IGN 66 0 29 MAIN IG HOLD: MANUAL-OPEN SWITCH 67 72 4010h 30 RUN 95 0 0020h 31 RUN PV HOLD: LOW FIRE SWITCH 96 58 32 PVHOLD IGN 77 46 33 PV HOLD: PV HOLD SWITCH 77 45 4008h 34 RUN/LOWFIRE: TEST RUN/TEST SWITCH 97 98 4020h 35 POSTPURGE 83 0 36 STATE UNKNOWN 31 0 0000h 37 RESET/ALARM TEST 111 0 6000h 38 SAFETY START 102 105 4002h 39 SAFETY1-1 102 2 750-361  0008h 0010h 4020h    4008h 0040h 0008h 77 ProtoNode Gateway     40 SAFETY1-2 102 3 0008h 41 SAFETY1-3 102 4 42 SAFETY1-4 102 5 43 SAFETY1-5 102 6 44 Blank 0 0 45 PREIGNITION 84 0 46 SAFETY 1 102 1 47 PILOT STAB. 79 0 48 MAIN TRIAL 68 0 49 MAIN TRIAL 68 0 0010h 50 STANDBY HOLD: RUN/TEST SWITCH 104 98 4002h 51 STATE 51 31 0 A000h 52 STATE 52 31 0 A000h 53 SAFETY 1: RUN/TEST SWITCH 102 98 4008h 0008h 0008h 0008h A000h   0080h 0008h 0008h  0010h 54 STATE 54 31 0 A000h 55 STANDBY HOLD: PURGE FAN SWITCH 104 92 4002h 56 STATE 56 31 0 A000h 57 PURGE HOLD: PURGE FAN SWITCH 93 92 4004h 58 STANDBY HOLD FLAME DETECTED 104 35 4002h 59 STANDBY HOLD COMB. PRESSURE 104 26 4002h        60 VP START 210 0 61 VP MV2 ON 211 0 62 VP LOW DLY 212 0 63 VP LOW TST 213 0 64 VP MV1 ON 214 0 65 VP HIGH DLY 215 0 66 VP HIGH TST 216 0 67 INITIATE HOLD: AC AC PHASE ERROR 49 10 4001h 68 STANDBY HOLD: PREIGNITION LOCK 104 85 4002h 0100h 0100h 4100h 0100h 0100h 4100h 0100h 69 SETUP NEEDED 217 0 A000h 70 STATE 70 31 0 A000h 71 BURNER OFF: T6 BURNER SWITCH 22 23 4002h 72 STANDBY HOLD: T6 (EA) HOLD MSG 184 30 4002h 73 STANDBY HOLD: (EA) CIRCUIT FAULT 184 25 4002h 74 STANDBY HOLD (EA) 184 Varies 4002h 75 PURGE HOLD (EA) 185 Varies 4004h 76 Unused 0 Varies 000h 77 Unused 0 Varies 000h 78 Unused 0 Varies 000h 79 STANDBY HOLD (EA) 184 Varies 4002h 80 PREIGNITION HOLD (EA) 184 Varies 4002h 81 STANDBY HOLD (EA): VALVE CLOSURE 184 109 4002h 82 STANDBY HOLD (EA) OTHER PII 184 75 4002h 750-361 78 ProtoNode Gateway Table 24: String Code CB780 String Codes String 47 IGNITION ON 48 INITIATE (blank) 49 INITIATE HOLD 1 1 50 JUMPERS CHANGED 2 1-1 51 JUMPERS WRONG 3 1-2 52 LOCKOUT 4 1-3 53 LOCKOUT ILK ON 5 1-4 54 LOCKOUT INTERLOCK 6 1-5 55 LOCKOUT SWITCH 7 AC FREQUENCY 56 LOW FIRE JUMPERED 8 AC FREQUENCY/NOISE 57 LOW FIRE SW OFF 9 AC LINE DROPOUT 58 LOW FIRE SWITCH 10 AC PHASE 59 LOW GAS PRESSURE 11 ACCESSORY FAULT 60 LOW LINE VOLTAGE AIRFLOW SW. ON 61 LOW OIL PRESSURE 13 AIRFLOW SWITCH 62 LOW OIL TEMP 14 ATOMIZING SW 63 LWCO 15 AUX INTERLOCK #4 64 MAIN FLAME FAIL AUX INTERLOCK #5 65 MAIN FLAME IGN. 17 AUX LIMIT #1 66 MAIN IGN 18 AUX LIMIT #2 67 MAIN IGN HOLD 19 AUX LIMIT #3 68 MAIN TRIAL BLOCK INTAKE 69 MAIN VALVE ON BOTH FUELS SELECT 70 MAN‐OPEN SW. OFF 22 BURNER OFF 71 MAN‐OPEN SW. ON 23 BURNER SWITCH 72 MAN‐OPEN SW. 24 CALL SERVICE 73 NO PURGE CARD 25 CIRCUIT FAULT 74 OTHER INTERLOCKS 26 COMB. PRESSURE 75 OTHER PREIGN ILK 27 CONTROL ON 76 PILOT FLAME FAIL DELAYED MV ON 77 PILOT HOLD 29 DEVICE SPECIFIC 78 PILOT IGN 30 EA HOLD MESSAGE 79 PILOT STABILIZE 31 UNKNOWN STATE 80 PILOT VALVE 1 ON 32 FLAME AMP TYPE 81 PILOT VALVE 2 ON 33 FLAME AMP/SHUTR 82 POOR FLAME SENSOR 34 FLAME AMPLIFIER 83 POSTPURGE 35 FLAME DETECTED 84 PREIGNITION 36 FLAME TOO STRONG 85 PREIGNITION ILK 37 FLAME‐OUT TIMER 86 PREIGNITION 38 FUEL SELECT OFF 87 PURGE 39 HIGH FIRE JUMPERED 88 PURGE CARD ERROR HIGH FIRE SWITCH 89 PURGE DELAY 41 HIGH GAS PRESSURE 90 PURGE FAN SW OFF 42 HIGH LIMIT 91 PURGE FAN SW ON 43 HIGH OIL PRESSURE 92 PURGE FAN SWITCH HIGH OIL TEMP 93 PURGE HOLD 45 HOLD SWITCH 94 REMOTE CONTROL 46 IGNITION 95 RUN 0 12 16 20 21 28 40 44 750-361 79 ProtoNode Gateway 96 RUN HOLD 145 HighFire Sw T19 = 1 97 RUN/LOWFIRE 146 PreIgn ILK T20 = 0 98 RUN/TEST SWITCH 147 PreIgn ILK T20 = 1 99 RUNNING ILK 148 Lockout Inp T20 = 0 100 RUNNING ILK ON 149 Lockout Inp T20 = 1 101 RUNNING INTERLOCK 150 Comb Press T20 = 0 102 SAFETY 151 Comb Press T20 = 1 103 STANDBY 152 Valv/Start T21 = 0 104 STANDBY HOLD 153 Valv/Start T21 = 1 105 START 154 Intmitt PV T21 = 0 106 START SWITCH 155 Intmitt PV T21 = 1 107 START SWITCH ON 156 Terminal T6 = 0 108 TEST STATE 157 Terminal T6 = 1 109 VALVE CLOSURE 158 Terminal T7 = 0 110 ALL SWITCHES ON 159 Terminal T7 = 1 111 RESET/ALARM TEST 160 Terminal T8 = 0 112 Run/Test Switch RUN 161 Terminal T8 = 1 113 Run/Test Switch TEST 162 Terminal T9 = 0 114 Operator Control T6 = 0 163 Terminal T9 = 1 115 Operator Control T6 = 1 164 Terminal T10 = 0 116 Interlock T7 = 0 165 Terminal T10 = 1 117 Interlock T7 = 1 166 Terminal T16 = 0 118 Airflow Interlock T7 = 0 167 Terminal T16 = 1 119 Airflow Interlock T7 = 1 168 Terminal T17 = 0 120 Block Intake T7 = 0 169 Terminal T17 = 1 121 Block Intake T7 = 1 170 Terminal T18 = 0 122 Valve T8 = 0 171 Terminal T18 = 1 123 Valve T8 = 1 172 Terminal T19 = 0 124 Intrptd PV T8 = 0 173 Terminal T19 = 1 125 Intrptd PV T8 = 1 174 Terminal T20 = 0 126 Main Valve T9 = 0 175 Terminal T20 = 1 127 Main Valve T9 = 1 176 Terminal T21 = 0 128 Ignition T10 = 0 177 Terminal T21 = 1 129 Ignition T10 = 1 178 Jumper 1 Intact 130 PV Hold T16 = 0 179 Jumper 1 Clipped 131 PVHold T16 = 1 180 Jumper 2 Intact 132 Input A T16 = 0 181 Jumper 2 Clipped 133 Input A T16 = 1 182 Jumper 3 Intact 134 ManOpenSw T17 = 0 183 Jumper 3 Clipped) 135 ManOpenSw T17 = 1 184 STANDBY HOLD (EA) 136 Input B T17 = 0 185 PURGE HOLD (EA) 137 Input B T17 = 1 186 PILOT HOLD (EA) 138 PreIgn ILK T17 = 0 187 MAIN IG HOLD (EA) 139 PreIgn ILK T17 = 1 188 RUN HOLD (EA) 140 LowFire Sw T18 = 0 189 POSTPURGE HOLD (EA) 141 LowFire Sw T18 = 1 190 PREIGNITION HOLD (EA) 142 Purge Fan T18 = 0 191 -SKIPPED- 143 Purge Fan T18 = 1 192 DEMAND T6 = 0 144 HighFire Sw T19 = 0 193 DEMAND T6 = 1 750-361 80 ProtoNode Gateway 194 PILOT VALVE T8 = 0 195 PILOT VALVE T8 = 1 196 INTERMIT PV T8 = 0 197 INTERMIT PV T8 = 1 198 MAIN VALVE1 T9 = 0 199 MAIN VALVE1 T9 = 1 200 VP SWITCH T16 = 0 201 VP SWITCH T16 = 1 202 MAIN VALVE2 T17 = 0 203 MAIN VALVE2 T17 = 1 204 INTERUPTD PV T21 = 0 205 INTERUPTD PV T21 = 1 206 DELAYED MV T21 = 0 207 DELAYED MV T21 = 1 208 START SW T21 = 0 209 START SW T21 = 1 210 VP START 211 VP MV2 ON 212 VP LOW DLY 213 VP LOW TST 214 VP MV1 ON 215 VP HIGH DLY 216 VP HIGH TST 217 VP SETUP NEEDED 218 MAIN VALVE 1 OFF 219 MAIN VALVE 2 OFF 220 MAIN VALVE 1 ON 221 MAIN VALVE 2 ON 222 VPS OFF 223 VPS ON 224 HIGH CYCLE RATE 750-361 81 ProtoNode Gateway Table 25: CB780 Fault Codes Fault Code 0 Blank (no fault) Fault String Code (Table 24) 0 1 FAULT 1: NO PURGE CARD 73 2 FAULT 2: AC FREQUENY/NOISE 8 3 FAULT 3: AC LINE DROPOUT (Reg 40001) Fault Message (NOTE: FAULT n: is not in the Fault and Strings 9 4 FAULT 4: AC FREQUENCY 7 5 FAULT 5: LOW LINE VOLTAGE 60 6 FAULT 6: PURGE CARD ERROR 88 7 FAULT 7: FLAME AMPLIFIER 34 8 FAULT 8: FLAME AMP/SHUTR 33 9 FAULT 9: FLAME DETECTED 35 10 FAULT 10: PREIGNITION ILK 85 11 FAULT 11: RUNNING ILK ON 100 12 FAULT 12: LOCKOUT ILK ON 53 13 FAULT 13: AIRFLOW SW. ON 12 14 FAULT 14: HIGH FIRE SWITCH 40 15 FAULT 15: FLAME DETECTED 35 16 FAULT 16: FLAME‐OUT TIMER 37 17 FAULT 17: MAIN FLAME FAIL 64 18 FAULT 18: FLAME DETECTED 35 19 FAULT 19: MAIN FLAME IGN. 65 20 FAULT 20: LOW FIRE SW OFF 57 21 FAULT 21: RUNNING ILK 99 22 FAULT 22: LOCKOUT ILK 54 23 FAULT 23: AIRFLOW SWITCH 13 24 FAULT 24: CALL SERVICE 24 25 FAULT 25: CALL SERVICE 24 46 FAULT 46: FLAME AMP TYPE 32 47 FAULT 47: JUMPERS CHANGED 50 48 FAULT 48: DELAYED MV ON 28 49 FAULT 49: MAN‐OPEN SW. ON 71 50 FAULT 50: JUMPERS WRONG 51 51 FAULT 51: FLAME TOO STRONG 36 52 FAULT 52: CALL SERVICE 24 53 FAULT 53: LOCKOUT SWITCH 55 54 FAULT 54: COMB. PRESSURE 26 55 FAULT 55: PURGE FAN SW ON 91 56 FAULT 56: BLOCK INTAKE 20 57 FAULT 57: PURGE FAN SW OFF 90 58 FAULT 58: COMB. PRESSURE/ 26 59 FAULT 59: CALL SERVICE 24 60 FAULT 60: CALL SERVICE 24 61 FAULT 61: MV1 OFF 218 62 FAULT 62: MV2 OFF 219 63 FAULT 63: MV1 ON 220 64 FAULT 64: MV2 ON 221 65 FAULT 65: VPS OFF 222 66 FAULT 66: VPS ON 223 67 FAULT 67: AC PHASE 10 68 FAULT 68: PREIGNITION ILK 85 69 FAULT 69: CALL SERVICE 24 70 FAULT 70: CALL SERVICE 24 71-75 FAULT 71-75: DEVICE SPECIFIC 29 76-93 FAULT 76-93: ACCESSORY 11 94-127 FAULT 94-127: CALL SERVICE 24 128 FAULT 128: POOR FLAME 82 129–141 FAULT 129-141: CALL SERVICE 24 142 FAULT 68z: OTHER PREIGN 143 FAULT 68y: VALVE CLOSUREEA 109 144 FAULT 33z: OTHER PREIGN 145 FAULT 33y: VALVE CLOSUREEA 109 26 FAULT 26: MAN‐OPEN SW. OFF 70 27 FAULT 27: START SWITCH ON 28 FAULT 28: PILOT FLAME FAIL 76 29 FAULT 29: LOCKOUT ILK 54 30 FAULT 30: RUNNING ILK 101 31 FAULT 31: LOW FIRE SW OFF 57 146 FAULT 32s: OTHER 74 13 147 FAULT 32r: AUX INTERLOCK 16 148 FAULT 32q: AUX INTERLOCK 15 149 FAULT 32p: AIRFLOW SWITCHEA 13 150 FAULT 32o: LOW GAS 71 32 FAULT 32: AIRFLOW SWITCH 33 FAULT 33: PREIGNITION ILK 85 34 FAULT 34: CONTROL ON 27 35 FAULT 35: CALL SERVICE 24 36 FAULT 36: CALL SERVICE 24 37 FAULT 37: CALL SERVICE 24 75 75 59 151 FAULT 32n: HIGH GAS 41 FAULT 32m: ATOMIZING SWEA 14 38 FAULT 38: CALL SERVICE 24 152 39 FAULT 39: CALL SERVICE 24 153 FAULT 32k: LOW OIL TEMPEA 62 40 FAULT 40: CALL SERVICE 24 154 FAULT 32j: HIGH OIL TEMPEA 44 41 FAULT 41: MAIN VALVE ON 69 155 FAULT 32i: LOW OIL 61 42 FAULT 42: PILOT VALVE 1 ON 80 43 FAULT 43: IGNITION ON 47 156 FAULT 32h: HIGH OIL 43 157 FAULT 32g: BOTH FUELS 21 158 FAULT 32f: FUEL SELECT OFFEA 38 44 FAULT 44: PILOT VALVE 2 ON 81 45 FAULT 45: LOW FIRE SW OFF 57 750-361 82 ProtoNode Gateway 159 FAULT 32e: AUX LIMIT #3EA 19 201 FAULT 23r: AUX INTERLOCK 16 160 FAULT 32d: HIGH LIMITEA 42 202 FAULT 23q: AUX INTERLOCK 15 161 FAULT 32c: LWCOEA 63 203 FAULT 23p: AIRFLOW SWITCHEA 13 162 FAULT 32b: AUX LIMIT #2EA 18 204 FAULT 23o: LOW GAS 59 163 FAULT 32a: AUX LIMIT #1EA 17 205 FAULT 23n: HIGH GAS 41 164 FAULT 30s: OTHER 74 206 FAULT 23m: ATOMIZING SWEA 14 165 FAULT 30r: AUX INTERLOCK 16 207 FAULT 23k: LOW OIL TEMPEA 62 166 FAULT 30q: AUX INTERLOCK 15 208 FAULT 23j: HIGH OIL TEMPEA 44 AIRFLOW SWITCHEA 167 FAULT 30p: 13 209 FAULT 23i LOW OIL 61 168 FAULT 30o: LOW GAS 59 210 FAULT 23h: HIGH OIL 43 169 FAULT 30n: HIGH GAS 41 211 FAULT 23g: BOTH FUELS 21 170 FAULT 30m: ATOMIZING SWEA 14 212 FAULT 23f: FUEL SELECT OFFEA 38 171 FAULT 30k: LOW OIL TEMPEA 62 213 FAULT 23e: AUX LIMIT #3EA 19 172 FAULT 30j: HIGH OIL 44 214 FAULT 23d: HIGH LIMITEA 42 173 FAULT 30i: LOW OIL 61 215 FAULT 23c: LWCOEA 63 174 FAULT 30h: HIGH OIL 43 216 FAULT 23b: AUX LIMIT #2EA 18 175 FAULT 30g: BOTH FUELS 21 217 FAULT 23a: AUX LIMIT #1EA 17 TEMPEA 176 FAULT 30f: FUEL SELECT OFFEA 38 218 FAULT 22s: OTHER 74 177 FAULT 30e: AUX LIMIT #3EA 19 219 FAULT 22r: AUX INTERLOCK 16 178 FAULT 30d: HIGH LIMITEA 42 220 FAULT 22q: AUX INTERLOCK 15 179 FAULT 30c: LWCOEA 63 221 FAULT 22p: AIRFLOW SWITCHEA 13 180 FAULT 30b: AUX LIMIT #2EA 18 222 FAULT 22o: LOW GAS 59 181 FAULT 30a: AUX LIMIT #1EA 17 223 FAULT 22n: HIGH GAS 41 182 FAULT 29s: OTHER 74 224 FAULT 22m: ATOMIZING SWEA 14 183 FAULT 29r: AUX INTERLOCK 16 225 FAULT 22k: LOW OIL TEMPEA 62 184 FAULT 29q: AUX INTERLOCK 15 226 FAULT 22j: HIGH OIL TEMPEA 44 185 FAULT 29p: 13 227 FAULT 22i: LOW OIL 61 186 FAULT 29o: LOW GAS 59 228 FAULT 22h: HIGH OIL 43 187 FAULT 29n: HIGH GAS 41 229 FAULT 22g: BOTH FUELS 21 188 FAULT 29m: ATOMIZING SWEA 14 230 FAULT 22f: FUEL SELECT OFFEA 38 189 FAULT 29k: LOW OIL TEMPEA 62 231 FAULT 22e: AUX LIMIT #3EA 19 190 FAULT 29j: HIGH OIL TEMPEA 44 232 FAULT 22d: HIGH LIMITEA 42 191 FAULT 29i LOW OIL 61 233 FAULT 22c: LWCOEA 63 192 FAULT 29h: HIGH OIL 43 234 FAULT 22b: AUX LIMIT #2EA 18 193 FAULT 29g: BOTH FUELS 21 235 FAULT 22a: AUX LIMIT #1EA 17 194 FAULT 29f: FUEL SELECT OFFEA 38 236 FAULT 21s: OTHER 74 195 FAULT 29e: AUX LIMIT #3EA 19 237 FAULT 21r: AUX INTERLOCK 16 196 FAULT 29d: HIGH LIMITEA 42 238 FAULT 21q: AUX INTERLOCK 15 197 FAULT 29c: LWCOEA 63 239 FAULT 21p: AIRFLOW SWITCHEA 13 198 FAULT 29b: AUX LIMIT #2EA 18 240 FAULT 21o: LOW GAS 199 FAULT 29a: AUX LIMIT #1EA 17 241 FAULT 21n: HIGH GAS 41 200 FAULT 23s: OTHER 74 242 FAULT 21m: ATOMIZING SWEA 14 750-361 AIRFLOW SWITCHEA 59 83 ProtoNode Gateway 243 FAULT 21k: LOW OIL TEMPEA 62 244 FAULT 21j: HIGH OIL TEMPEA 44 245 FAULT 21i: LOW OIL 61 246 FAULT 21h: HIGH OIL 43 247 FAULT 21g: BOTH FUELS 21 248 FAULT 21f: FUEL SELECT OFFEA 38 249 FAULT 21e: AUX LIMIT #3EA 19 250 FAULT 21d: HIGH LIMITEA 42 251 FAULT 21c: 63 252 FAULT 21b: AUX LIMIT #2EA 18 253 FAULT 21a: AUX LIMIT #1EA 17 254 FAULT 10z: OTHER PREIGN 75 255 FAULT 10y: VALVE CLOSUREEA 109 750-361 LWCOEA 84 ProtoNode Gateway APPENDIX C — MAC ADDRESS DIP SWITCH SETTINGS Address A0 A1 A2 A3 A4 A5 A6 A7 45 On Off On On Off On Off Off 46 Off On On On Off On Off Off Off 47 On On On On Off On Off Address A0 A1 A2 A3 A4 A5 A6 A7 48 Off Off Off Off On On Off Off 0 Off Off Off Off Off Off Off Off 49 On Off Off Off On On Off Off 1 On Off Off Off Off Off Off Off 50 Off On Off Off On On Off Off 2 Off On Off Off Off Off Off Off 51 On On Off Off On On Off Off 3 On On Off Off Off Off Off Off 52 Off Off On Off On On Off Off 4 Off Off On Off Off Off Off Off 53 On Off On Off On On Off Off 5 On Off On Off Off Off Off Off 54 Off On On Off On On Off Off 6 Off On On Off Off Off Off Off 55 On On On Off On On Off Off 85 7 On On On Off Off Off Off Off 56 Off Off Off On On On Off Off 8 Off Off Off On Off Off Off Off 57 On Off Off On On On Off Off 9 On Off Off On Off Off Off Off 58 Off On Off On On On Off Off 10 Off On Off On Off Off Off Off 59 On On Off On On On Off Off 11 On On Off On Off Off Off Off 60 Off Off On On On On Off Off 12 Off Off On On Off Off Off Off 61 On Off On On On On Off Off 13 On Off On On Off Off Off Off 62 Off On On On On On Off Off 14 Off On On On Off Off Off Off 63 On On On On On On Off Off 15 On On On On Off Off Off Off 64 Off Off Off Off Off Off On Off 16 Off Off Off Off On Off Off Off 65 On Off Off Off Off Off On Off 17 On Off Off Off On Off Off Off 66 Off On Off Off Off Off On Off 18 Off On Off Off On Off Off Off 67 On On Off Off Off Off On Off 19 On On Off Off On Off Off Off 68 Off Off On Off Off Off On Off 20 Off Off On Off On Off Off Off 69 On Off On Off Off Off On Off 21 On Off On Off On Off Off Off 70 Off On On Off Off Off On Off 22 Off On On Off On Off Off Off 71 On On On Off Off Off On Off 23 On On On Off On Off Off Off 72 Off Off Off On Off Off On Off 24 Off Off Off On On Off Off Off 73 On Off Off On Off Off On Off 25 On Off Off On On Off Off Off 74 Off On Off On Off Off On Off 26 Off On Off On On Off Off Off 75 On On Off On Off Off On Off 27 On On Off On On Off Off Off 76 Off Off On On Off Off On Off 28 Off Off On On On Off Off Off 77 On Off On On Off Off On Off 29 On Off On On On Off Off Off 78 Off On On On Off Off On Off 30 Off On On On On Off Off Off 79 On On On On Off Off On Off 31 On On On On On Off Off Off 80 Off Off Off Off On Off On Off 32 Off Off Off Off Off On Off Off 81 On Off Off Off On Off On Off 33 On Off Off Off Off On Off Off 82 Off On Off Off On Off On Off 34 Off On Off Off Off On Off Off 83 On On Off Off On Off On Off 35 On On Off Off Off On Off Off 84 Off Off On Off On Off On Off 36 Off Off On Off Off On Off Off 85 On Off On Off On Off On Off 37 On Off On Off Off On Off Off 86 Off On On Off On Off On Off 38 Off On On Off Off On Off Off 87 On On On Off On Off On Off 39 On On On Off Off On Off Off 88 Off Off Off On On Off On Off 40 Off Off Off On Off On Off Off 89 On Off Off On On Off On Off 41 On Off Off On Off On Off Off 90 Off On Off On On Off On Off 42 Off On Off On Off On Off Off 91 On On Off On On Off On Off 43 On On Off On Off On Off Off 92 Off Off On On On Off On Off 44 Off Off On On Off On Off Off 93 On Off On On On Off On Off 750-361 ProtoNode Gateway Address A0 A1 A2 A3 A4 A5 A6 A7 Address A0 A1 A2 A3 A4 A5 A6 A7 94 Off On On On On Off On Off 143 On On 95 On On On On On Off On Off 144 Off Off On On Off Off Off On Off Off On Off Off On 96 Off Off Off Off Off On On Off 145 On Off 97 On Off Off Off Off On On Off 146 Off On Off Off On Off Off On Off Off On Off Off 98 Off On Off Off Off On On Off 147 On On On Off Off On Off Off On 99 On On Off Off Off On On Off 148 Off Off On Off On Off Off On 100 Off Off On Off Off On On Off 101 On Off On Off Off On On Off 149 On Off On Off On Off Off On 150 Off On On Off On Off Off On 102 Off On On Off Off On On Off 151 On 103 On On On Off Off On On Off 152 Off On On Off On Off Off On Off Off On On Off Off On 104 Off Off Off On Off On On Off 153 On Off Off On On Off Off On 105 On Off Off On Off On On Off 154 Off On Off On On Off Off On 106 Off On Off On Off On On Off 155 On On Off On On Off Off On 107 On On Off On Off On On Off 156 Off Off On On On Off Off On 108 Off Off On On Off On On Off 157 On Off On On On Off Off On 109 On Off On On Off On On Off 158 Off On On On On Off Off On 110 Off On On On Off On On Off 159 On On On On On Off Off On 111 On On On On Off On On Off 160 Off Off Off Off Off On Off On 112 Off Off Off Off On On On Off 161 On Off Off Off Off On Off On 113 On Off Off Off On On On Off 162 Off On Off Off Off On Off On 114 Off On Off Off On On On Off 163 On On Off Off Off On Off On 115 On On Off Off On On On Off 164 Off Off On Off Off On Off On 116 Off Off On Off On On On Off 165 On Off On Off Off On Off On 117 On Off On Off On On On Off 166 Off On On Off Off On Off On 118 Off On On Off On On On Off 167 On On On Off Off On Off On 119 On On On Off On On On Off 168 Off Off Off On Off On Off On 120 Off Off Off On On On On Off 169 On Off Off On Off On Off On 121 On Off Off On On On On Off 170 Off On Off On Off On Off On 122 Off On Off On On On On Off 171 On On Off On Off On Off On 123 On On Off On On On On Off 172 Off Off On On Off On Off On 124 Off Off On On On On On Off 173 On Off On On Off On Off On 125 On Off On On On On On Off 174 Off On On On Off On Off On 126 Off On On On On On On Off 175 On On On On Off On Off On 127 On On On On On On On Off 176 Off Off Off Off On On Off On 128 Off Off Off Off Off Off Off On 177 On Off Off Off On On Off On 129 On Off Off Off Off Off Off On 178 Off On Off Off On On Off On 130 Off On Off Off Off Off Off On 179 On On Off Off On On Off On 131 On On Off Off Off Off Off On 180 Off Off On Off On On Off On 132 Off Off On Off Off Off Off On 181 On Off On Off On On Off On 133 On Off On Off Off Off Off On 182 Off On On Off On On Off On 134 Off On On Off Off Off Off On 183 On On On Off On On Off On 135 On On On Off Off Off Off On 184 Off Off Off On On On Off On 136 Off Off Off On Off Off Off On 185 On Off Off On On On Off On 137 On Off Off On Off Off Off On 186 Off On Off On On On Off On 138 Off On Off On Off Off Off On 187 On On Off On On On Off On 139 On On Off On Off Off Off On 188 Off Off On On On On Off On 140 Off Off On On Off Off Off On 189 On Off On On On On Off On 141 On Off On On Off Off Off On 190 Off On On On On On Off On 142 Off On On On Off Off Off On 191 On On On On On On Off On 750-361 86 ProtoNode Gateway Address A0 A1 A2 192 Off Off Off Off Off Off 193 On Off Off Off Off Off 194 Off On Off Off Off Off On 87 A3 A4 A5 A6 A7 Address A0 A1 A2 A3 A4 A5 A6 A7 On On On On 241 On Off Off Off On On On On 242 Off On Off Off On On On On On 243 On On Off Off On On On On On 195 On On Off Off Off Off On On 244 Off Off On Off On On On 196 Off Off On Off Off Off On On 245 On Off On Off On On On On 197 On Off On Off Off Off On On 246 Off On On Off On On On On 198 Off On On Off Off Off On On 247 On On On Off On On On On 199 On On On Off Off Off On On 248 Off Off Off On On On On On 200 Off Off Off On Off Off On On 249 On Off Off On On On On On 201 On Off Off On Off Off On On 250 Off On Off On On On On On 202 Off On Off On Off Off On On 251 On On Off On On On On On 203 On On Off On Off Off On On 252 Off Off On On On On On On 204 Off Off On On Off Off On On 253 On Off On On On On On On 205 On Off On On Off Off On On 254 Off On On On On On On On 206 Off On On On Off Off On On 255 On On On On On On On On 207 On On On On Off Off On On 208 Off Off Off Off On Off On On 209 On Off Off Off On Off On On 210 Off On Off Off On Off On On 211 On On Off Off On Off On On 212 Off Off On Off On Off On On 213 On Off On Off On Off On On 214 Off On On Off On Off On On 215 On On On Off On Off On On 216 Off Off Off On On Off On On 217 On Off Off On On Off On On 218 Off On Off On On Off On On 219 On On Off On On Off On On 220 Off Off On On On Off On On 221 On Off On On On Off On On 222 Off On On On On Off On On 223 On On On On On Off On On 224 Off Off Off Off Off On On On 225 On Off Off Off Off On On On 226 Off On Off Off Off On On On 227 On On Off Off Off On On On 228 Off Off On Off Off On On On 229 On Off On Off Off On On On 230 Off On On Off Off On On On 231 On On On Off Off On On On 232 Off Off Off On Off On On On 233 On Off Off On Off On On On 234 Off On Off On Off On On On 235 On On Off On Off On On On 236 Off Off On On Off On On On 237 On Off On On Off On On On 238 Off On On On Off On On On 239 On On On On Off On On On 240 Off Off Off Off On On On On 750-361 ProtoNode Gateway 750-361 88 ProtoNode Gateway APPENDIX D — INTERFACING PROTONODE GATEWAY TO BOILER NETWORKS D.1. Boiler Network Wiring Connections to ProtoNode RER and LER 6 Pin Phoenix connector - pin outs D.2. ClearFire Boiler Modbus Network The diagram below shows a typical application using the ProtoNode Gateway in a ClearFire Lead Lag system NOTE: In the diagram above there are two independent Modbus networks. One is dedicated for Falcon lead lag control; the other is dedicated to the building EMS gateway interface. DO NOT CROSSCONNECT THESE TWO MODBUS NETWORKS. 89 750-361 ProtoNode Gateway D.3 Falcon System Display Modbus Gateway Connection (COM2) Wiring to the ProtoNode • • • • Connect Falcon Display COM 2 port (Modbus A) to Pin 1, labeled Tx/+ on the ProtoNode’s 6 pin Phoenix connector. Connect Falcon Display COM 2 port (Modbus B) to Pin 2, labeled Rx/- on the ProtoNode’s 6 pin Phoenix connector. Ground does not need to be grounded to the ProtoNode. NOTE: the A and B terminal designations on the ProtoNode 6-pin connector do not match the corresponding terminals on the Falcon or CB780E: A+ (Falcon/CB780E) is wired to B+ (ProtoNode) B- (Falcon/CB780E) is wired to A- (ProtoNode) 750-361 90 ProtoNode Gateway D.4 CB780E Modbus connections to ProtoNode D.5. CB120E Modbus connections to ProtoNode D.6. HSC Modbus connections to ProtoNode MJ2 PORT (HSC SYSTEM ADMINISTRATOR) 91 750-361 ProtoNode Gateway APPENDIX E — LIMITED 2 YEAR WARRANTY Cleaver-Brooks warrants this product to be free from defects in workmanship or material under normal use and service for two years after date of shipment. C-B will repair or replace any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by C-B personnel. All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without C-B approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables or to any damage resulting from battery leakage. In all cases C-B's responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty. Except for the express warranty stated above, C-B disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of C-B for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product. 750-361 92