Transcript
Fire Control Panels - conventional PRODUCT CODE TC802, TC804 & TC808
TC800 fire control panels
features •
Fully approved to EN54 part 2 & 4
•
Attractive, modern design
•
Installer friendly
•
One man walk test
•
Two monitored sounder circuits
•
Class change input
•
Single 12V dc battery requirement for 24-hour standby
•
Auxiliary 24V DC output
TC804 FIRE CONTROL PANEL
TC802 FIRE CONTROL PANEL
TC808 FIRE CONTROL PANEL
DESCRIPTION
The TC800 range of conventional fire panels is available in 2, 4 and 8 zones. Aesthetically pleasing with a removable door for easy installation, the control panels provide an excellent value for money proposition for a small, basic conventional fire system.
specifications Electrical Main Power supply
230V AC ±10%, 0.315A fuse
Standby Power supply
1 x 12V / 7Ah, 2A fuse TC802/4
TC808
Sounder Circuit 1
24V / 0.3A, 0.3A fuse (PTC)
24V / 0.5A, 0.5A fuse (PTC)
Sounder Circuit 2
24V / 0.3A, 0.3A fuse (PTC)
24V / 0.5A, 0.5A fuse (PTC)
Fault Relay, volt free changeover contacts 3A @ 120V AC, 3A @ 60V DC Fire Relay, volt free changeover contacts
3A @ 120V AC, 3A @ 60V DC
Auxiliary output
24V DC, 0.3A fuse (PTC)
Environment Working temperature
-5 to 40°C
Storage temperature
-20 to 60°C
Humidity
0 to 95%
Mechanical Size (HxWXD)
270mm x 320mm x 90mm
Weight (excl. batteries)
2.4kg
Cussonia Park, Ridge Rd, Laser Park, Johannesburg PO Box 1752, Randpark Ridge, South Africa, 2156 T: +27(0)11 794 9144 F:+27(0)11 794 9148 E:
[email protected]
www.technoswitch.co.za
E & OE Document No: ps_tc800_1109