Transcript
PUD-P-YMF-C PFD-P-VM-A
Close control CONTENTS 1. Specifications
1 1 2 2
2. Capacity Curves
························································· 2-1 Cooling Capacity ························································· ························································· 2-2 Cooling Input ························································· 2-3 SHF Curves 2-4 Correction by refrigerant piping length ···························· ························································· 2-5 Operation limit
4 4 4 5 6 6
3. Sound Levels ···································································
7 7 8 8
······························································ 1-1 Main Features ······························································ 1-2 List of Possible Combinations of Indoor and Outdoor Units ····· 1-3 Unit Specifications ·························································
3-1 Noise Level ··································································· 3-2 NC Curves ··································································· 3-3 Fan Characteristics Curves ···········································
4. External Dimensions ······················································ 5. Electrical Wiring Diagrams ··········································· 6. Options ·············································································· 7. Refrigerant Circuit Diagram And Thermal Sensor ··· 8. System Design ································································· 8-1 Piping ············································································ 8-2 Control Wiring ································································· 8-3 Types of switch settings and setting methods ················ 8-4 Wiring and Address Setting (System Using MA Remote Controller) ··· 8-5 External input/output specifications ·······························
9 12 15 16 17 17 18 18 20 32
9. Air Conditioning the Computer Room ························· 34 9-1 Main Features of the Floor-Duct Air Conditioners ·········· 9-2 Major Characteristics of Computer Room Air Conditioners ··· 9-3 Step-by-Step Plan for the Implementation of the Air-Conditioning ··· 9-4 Conditions for the Installation of Computer-Room Air Conditioners ··· 9-5 Setting the Air conditioners ············································· 9-6 Automatic Control of the Computer Room ······················
34 34 35 36 37 39
10. Maintenance/Inspection ··············································· 40 10-1 Maintenance/Inspection Schedule ·······························
40
1. Specifications 1-1.Main Features (1) List of Models } Outdoor Unit
PUD-P250YMF-C
10HP(Down flow): PFD-P250VM-A(-H) } Indoor Unit 20HP(Down flow): PFD-P500VM-A(-H) ✻ '-H' in the indoor units indicates that the unit pipes come out of the top of the unit (50/60Hz, fit to order). ✻ PFD-type indoor units cannot be connected to outdoor units other than the ones specified above. ✻ PFD-type indoor units and other types of indoor units cannot coexist in the same refrigerant system. <10HP System> Outdoor Unit
Indoor Unit
PUD-P250YMF-C G-50A
✻3
PFD-P250VM-A
TB7 TB3 ✻2 ✻1
12V DC UP
POWER SUPPLY UNIT MODEL
PAC-SC50KUA
POWER RATING 2.11kg
WEIGHT SERIAL No.
MITSUBISHI ELECTRIC CORPORATION
M-NET
PAC-SC50KUA
When using a PFD-P250VM-A as an indoor unit, connect an outdoor unit PUD-P250YMF-C to each indoor unit and operate with a built-in remote control for the indoor unit. ✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of one refrigerant circuit. ✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units. This system consists of 1 refrigerant circuit. ✻3: Indicates TB7-Type transmission line that allows the unit to communicate with the controller. <20HP System> Outdoor Unit PUD-P250YMF-C G-50A TB7
Indoor Unit PFD-P500VM-A
TB3 ✻2 ✻1
12V DC ✻3 TB7
UP
POWER SUPPLY UNIT MODEL
PAC-SC50KUA
POWER RATING WEIGHT SERIAL No.
2.11kg
MITSUBISHI ELECTRIC CORPORATION
PUD-P250YMF-C TB3
M-NET
PAC-SC50KUA
When using a PFD-P500VM-A as an indoor unit, connect 2 PUD-P250YMF-C outdoor units to each indoor unit and operate with a built-in remote control for the indoor unit. ✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of 2 refrigerant circuits. ✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units. This system consists of 2 refrigerant circuits. ✻3: Indicates TB7-type transmission line that allows the unit to communicate with the controller.
1
1-2. List of Possible Combinations of Indoor and Outdoor Units Units
Indoor Units
Model Name
Down-flow Type
Power Source
380-415V(50Hz) 400,415V(60Hz)
380-415V(50Hz) 400,415V(60Hz)
10HP
20HP
PFD-P250VM-A(-H)
PFD-P500VM-A(-H) 56.0
Unit Horse Power
Air-cooling
Outdoor Units
Series Name
380 /400 /415V
10HP
PUDP250YMF-C
Q
28.0
W
10.9
21.8
A
18.3/17.3/16.3
36.1/34.3/33.0
Power factor
90
91
✻1: Refer to the following pages for detailed specifications of each unit. ✻2: The values in the chart are as follows: Q, Total Capacity [kW]; W, Total Input [kW]; A, Total Electrical Current [A]; Power Factor [%]. They were measured at operation under the following conditions: Indoor Intake Temperature: 27˚CDB/19˚CWB, Outdoor Intake Temperature 35˚CDB with 7.5m of refrigerant piping.
1-3. Unit Specifications (1) Outdoor Unit PUD-P250YMF-C Capacity ✻1 Power source Power input Current Type ✕ Quantity Fan Airflow rate Motor output Type Compressor Motor output Crankcase heater Starting current Refrigerant / Lubricant External finish External dimension High pressure protection Protection Compressor / Fan devices Inverter Refrigerant piping diameter Liquid / Gas ✻2 Noise level Net weight
kW kW A m3/min kW kW kW A
mm
dB(A) kg
28.0 3N ~ 380/400/415V 50/60Hz 8.4 14.0/13.3/12.8 Propeller fan 185 0.38 Hermetic 7.5 0.045 (240V) 12 R407C/MEL32 Steel plate painting with polyester powder
1715(H)✕990(W)✕840(L) 2.94MPa Over current protection / Thermal switch DC bus current protection, thermal switch ø12.7 flare /ø28.58 Flange 56 231 Indoor:12˚CWB ~ 24˚CWB Outdoor:-15˚CDB ~ 43˚CDB (0˚CDB ~ 43˚CDB with outdoorunit at lower position)
Operating temperature range
Note: Cooling capacity indicates the maximum value at operation under the following condition. ✻1 Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB Pipe length 7.5m, Height difference 0m ✻2 It is measured in anechoic room.
2
(2) Indoor Unit PFD-P250VM-A Power source Cooling capacity Power consumption Current External finish Dimensions
✻1
Height Width Depth
Net weight Heat exchanger Type Airflow rate Fan External static pressure Type Motor Output Starting current Air filter
mm mm mm kg
m3/min
120
Pa
3 phases induction motor kW A
3.7 60
5.5 75 PP Honeycomb fabric
Gas Refrigerant pipe dimension
kW kW A
PFD-P500VM-A
3N~380-415V 50Hz / 3N~400-415V 60Hz 28.0 56.0 2.5 5.0 5.5/5.3/5.1 9.5/9.0/8.7 <5Y 7/1> 1895 1,800 1,200 800 350 480 Cross fin (Aluminum-plate fin and copper tube) Sirocco fan Sirocco fan ✕ 2 160 320
(Flare)
Liquid
(Flare) Drain pipe dimension Noise level (Lo-Mid2-Mid1-Hi) ✻ 2
mm
ø 28.58
ø 28.58 ✕ 2
mm
ø 12.7
ø 12.7 ✕ 2
dB(A)
59
Rp1
Note: ✻1 Cooling capacity indicates the maximum value at operation under the following conditions; Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB ✻2 Measured in an anechoic room.
3
64
2. Capacity Curves 2-1. Cooling Capacity 1.5 Indoor Temperature (˚CWB) 1.4 1.3
Ratio
1.2 24˚CWB
1.1 1
21˚CWB
0.9
19˚CWB
0.8
17˚CWB 15˚CWB
0.7 12˚CWB 0.6 -15
-10
-5
0
5
10
15
20
25
30
35
40
45
Outdoor Temperature (˚CDB)
2-2. Cooling Input 1.3 Indoor Temperature (˚CWB) 24˚CWB 1.2
21˚CWB 19˚CWB 17˚CWB
1.1
15˚CWB
Ratio
12˚CWB 1
0.9
0.8
0.7 -15
-10
-5
0
5
10
15
20
25
30
35
40
45
Outdoor Temperature (˚CDB)
✻ The correction curves indicate the values measured at the point where the compressor was operated at its maximum capacity. ✻ indicates the standard value.
4
2-3. SHF Curves Standard Capacity Ratio 130% 120% 110% 100% 90%
80%
70%
1.0 Indoor Temperature 27˚CDB 0.93 0.9
SHF
0.8
0.7
0.6
0.5
0.4 30
40
50
60
70
80
RH (%)
Standard Capacity Ratio 130% 120% 110% 100% 90%
80%
70%
1.0 Indoor Temperature 24˚CDB 0.9
SHF
0.8
0.7
0.6
0.5
0.4 30
40
50
60 RH (%)
Operation Temparature Range : Indoor : 12˚CWB~24˚CWB Outdoor : -5˚CDB~43˚CDB (RH : 30~80%) Standard Point " " : Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB/-
5
70
80
2-4. Correction by refrigerant piping length To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity correction factor based on the refrigerant piping equivalent length in the table below.
Cooling capacity correction factor
1.0
0.9
0.8
0.7 0
20
40
80 100 120 60 Piping equivalent length (m)
140
• How to obtain piping equivalent length
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m
Indoor temperature (˚CWB)
2-5. Operation limit 30 25 20 15 12 10 -15
-10
-5
0
5
10
15
20
25
Outdoor temperature (˚CDB) (Outdoor door temperature :0˚CDB~43˚CDB with outdoor unit at lower position in cooling mode.)
6
30
35
40
45
3. Sound Levels 3-1. Noise Level (1) Outdoor Unit 1m
Measured point 1m
Series PUD-P250YMF-C
Noise Level (dB [Type A]) 56
(2) Indoor Unit 1m
Measured point
1m
Series
7
Noise Level (dB [Type A])
PFD-P250VM-A
59
PFD-P500VM-A
64
3-2. NC Curves static PUD-P250YMF-C (External pressure 0Pa)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa
80
70
NC70
60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise
0 63
125
250
500
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
PFD-P250VM-A
(External static pressure 120Pa)
(External static pressure 120Pa)
PFD-P500VM-A
80
80 High speed
NC70
60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise
0 63
125
250
500
1000
2000
4000
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa
High speed
70
NC70
60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise
0
8000
63
OCTAVE BAND CENTER FREQUENCIES (Hz)
125
250
500
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
3-3. Fan Characteristics Curves PFD-P250VM-A
PFD-P500VM-A : 50/60Hz, standard : 50/60Hz, with middle-high efficient filter box
700
: 50/60Hz, standard
Fan rotation speed
1000
1100rpm
900
Output 3.7kW 600
1000rpm
Total static pressure (Pa)
Total static pressure (Pa)
800 500
400 900rpm
(Output 2.2kW) 300 Internal resistance (middle-high efficient filter )
800rpm
200 Internal resistance
100
1100rpm 600 Output 5.5kW 500 400 1000rpm 300 200
900rpm Internal resistance
100 0 140
Fan rotation speed 1200rp
Output 7.5kW
700
800rpm Standard
0 144
150
160
170
176
260
180
Air volume (m3/min)
270
280
288
300
320
Air volume (m3/min)
8
330
340
352
360
Crosss section Y-Y
Rear view
251
Cross section X-X
778
60
75
Left side view
ø27 Knockout hole Knockout hole Left piping hole
160
Y
40
75 ø40 Knockout hole
Knockout hole Front piping hole 813 590
Plane view
990
560(bolt hole)
55
215
31
79
165
Front view
910
Service panel
1490 Knockout hole
X
80
215
X
Refrig. service valve (liquid) ø12.7
Knockout hole
4X2-14X20 Oval hole
Refrig. service valve(gas)
ø27 Knockout hole
ø40 Knockout hole
Air inlet
Right side view
Air outlet
Air inlet
PUD-P250YMF-C
Knockout hole
100
Conn. pipe ø28.58
25
Note1 Knockout hole Bottom piping hole
237 198
50
234
73 80
Y
194
5
121 100 48
70
40
15 880(bolt hole) 15
12
149
840 78
9 99
< Accessory > • Refrigerant (gas) conn. pipe ··········· 1 pc. (The connecting pipe is fixed with the unit) • Packing for conn. pipe ·················· 1 pc. (Attached near the ball valve) • Wiring mounting board • Conduit mounting plate (Painted the same color as the unit body) ø40································· 1 pc. ø33································· 1 pc. ø27································· 1 pc. • Tapping screw 4 ✕ 10 ················ 6 pcs. Note.1 Please leave a space under the outdoor unit for the piping When, you connect the piping from the bottom. (Please be careful not to close the hole of the bottom plate by the basement)
4. External Dimensions Unit : mm
1715
5
Control box
MA Remote controller
Lamp Power Supply : White Operating : Green Check : Yellow Failure : Red
Lifting bolts (supplied with the unit)
1200
Air outlet
A
Air inlet
Hole for the control wiring
400 200 1895 5 800
50
210
75
Service space
473
1050
340
420 Refrig. piping (liquid) ø 12.7< flare >
Refrig. piping (gas) < flange >
Hole for liquid-pipe-connecting<ø27>
8-ø18 Bolt hole
600 or more 70
15
· Lifting bolts · Refrigerant (gas) conn. pipe (ø 28.58 < brazed >) · Packing for flange · Insulation cover for flange · Flare nut (liquid) · Hexagonal allen key (for front panel opening/closing)
······4pcs. ······1pc. ······1pc. ······1pc. ······1pc. ······1pc.
Drain pipe end connecting
Hole for gas-pipe-connecting<ø48>
235
245
395
< Accessories >
Base measurement
1160 70
Discharge air outlet
180
15
292
192
Note 1
Drain water outlet height Hole for power-supply line<ø60>
Note1. For right-hand-side piping, the minimum space of 200mm on the right side must be increased to a minimum of 500mm. Note2. If a minimum space of 880mm is secured, the panel can fully be opened.
Discharge air outlet height Hole for transmission line<ø60>
90 620 90
100
Air Inlet(Air Filter)
120
11
319 413
Indoor Unit
11
Hole for the power supply
110
15 770 15
200 or more
210
10
260
200 or more
PFD-P250VM-A Unit : mm
205
Control box
MA Remote controller
Power Supply : White Operating : Green Check : Yellow Failure1 : Red Failure2 : Red
Lamp
5
A
1800
Air outlet
Air inlet
5
400
800
Lifting bolts (supplied with the unit)
50
50 50
110
Service space
Indoor unit
205
186
1760 1650
Discharge air outlet
370
NO.2
NO.1
15 70
8-ø 18 Bolt hole
Hole for gas-pipe-connecting<ø 48>
395 245 235
· Lifting bolts · Refrigerant (gas) conn. pipe (ø 28.58 < brazed >) · Packing for flange · Insulation cover for flange · Flare nut (liquid)
< Accessories > ······4pcs. ······2pcs. ······2pcs. ······2pcs. ······2pcs.
Hole for liquid-pipe-connecting<ø 27> Hole for gas-pipe-connecting<ø 48> Hole for liquid-pipe-connecting<ø 27> Drain pipe end connecting
Base measurement
Refrig. piping (liquid) ø 12.7 NO.1
Refrig. piping (gas)
370 270
Discharge air outlet
Refrig. piping (liquid) ø 12.7 NO.2
Refrig. piping (gas)
15 70
218 340
Note 1
600 or more
Drain water outlet height Hole for power-supply line<ø 60>
Note1. For right-hand-side piping, the minimum space of 200mm on the right side must be increased to a minimum of 500mm. Note2. If a minimum space of 880mm is secured, the panel can fully be opened.
Discharge air outlet height Hole for transmission line<ø 60>
420
Hole for the control wiring
120
340
Air inlet(Air Filter) 75 15
200 1895
11
110
Hole for the power supply
100
11
319 413
90 620 770 90
11 15
200 or more
110 50 50 50
200 or more
PFD-P500VM-A Unit : mm
5. Electrical Wiring Diagrams PUD-P250YMF-C
MC1
Inverter Controller Box
Red
Terminal Block TB1A L1 Red
L1
Power source 3N380/400/415V 50/60Hz
L2
L2
White
Noise Filter
NF L1
Terminal Block
L1
L2
Red
L2
L1
TB1B L1 Red L2
White
L3
Black
L3
L3
Black
L3
Black
N
Blue
N
N
Blue
N
Blue
White ACCT -W
Black
ACCT -U
Diode stack
N
L3
R1
DS
White
N
PE
L2
- +
L3
IPM
R5
ZNR4 C1
-
52C DCL
- -
U
+ C2
R2
+ C3
R3
V
W
P Gate amp board (G/A board)
N
Green/ Yellow
PE
Connect to Indoor and remote controller
Motor
U V W (Compressor)
BOX BODY TB3 M1
F3 250VAC 1A F
BOX BODY
CNE (2P)
CNDC1 (4P)
1 2
1 2 3 4
CNDR1 (9P)
CN15V1 (14P)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 1011121314
M2 CNTR1
FB2
FB1
S TB7
CH1 Crank case heater (Compressor) SV1
123
12
CNS2 (3P)
CNS1 (2P)
3 2 CN32 1 (3P) 3 2 CN33 1 (3P) 6 5 4 CN34 3 (6P) 2 1
SV2
1 2
3
CN20 (3P)
1
2
7
1 2 5 4 3 3 4 CNRS2 5 (7P) 6 7
CNVCC41 (2P) 2
1 CNVCC4 2 (2P)
1 2 CNVCC3 3 (6P) 4 5 6
1 2 3 CNVCC2 4 (6P) 5 6
1 2 CNRS3 3 (7P) 4 5 6
3
CNTR (3P)
F1 250VAC 2A F
X01
X10
X02
SV3
1 2 3 4 5 6 7 8 9
CNVDC (4P)
Gray White
Orange Yellow
Black Purple
Brown Red
Black
Red
1 2 3 4
1 2 3 4 5 6 7 8 9 1011121314
CNDR2 (9P)
CN15V2 (14P)
F01 250VAC 2A F
Power circuit board (INV board)
1 CNACCT 2 (4P) 3 4
2 X01
52C
3
CN52C (3P)
CNTH X02 (2P) 1
X05 1 2 3 4 4:Compressor ON/OFF 5
12V
CNAC2 2 1 (5P)
1
1 2 3 CNX10 (3P)
CN51 (5P) 6 5 4 CN36 3 (6P) 2 1
Blue
M2
White
Green
BOX BODY
T01
Brown Orange
BOX BODY M1
5:Trouble
2 3 12 CNFAN (3P)
CNR (3P) 1 2 3
CNL2 (2P)
CN30V (2P)
12
12
L2
R6
MF1 THHS R7 BOX BODY
X06
Control circuit board (MAIN board)
L1 L2 L3
63H High pressure switch
CN38 (3P) 1 2 3
CNPOW (5P)
X10
1 23 4 5
F03 250VAC 6.3A F F02 250VAC 6.3A F F01 250VAC 6.3A F
detection circuit 6 5 CNFC1 4 (6P) 3 2 1
Refer to the service handbook about the switch operations.
6 5 4 CNFC2 3 (6P) 2 1
FB3 1
CNFAN 23 (5P) 4
1 2 3 4
5
CN04 FB4
12
1234
CN03 (3P)
CN02 (8P)
CN01 CNH (2P) (3P)
123
12345678
12
TH6
TH5 TH8 TH7 TH2
TH1
TH10 TH9
LD
1 2 3
Black White Red
Black White Red
12
CNL (3P)
CNLV1 (5P)
CNLV2 (5P)
1 2 3
12345
1234 5
SLEV
LEV1
Fan control board (Fancon board)
Fan motor (Heat exchanger) N
Black White Red
CN09 CN06 CN05 (4P) (2P) (2P)
U V W MF N
3 2 1
3 2 1
63HS
63LS
Name Symbol DC reactor (Power factor improvement) DCL ACCT-U,W Current Sensor ZNR4 Varistor 52C MF1 SV1,SV2 SV3
Magnetic contactor (Inverter main circuit) Fan motor (Radiator panel) Solenoid valve (Discharge--suction bypass) Solenoid valve (Heat exchanger capacity control)
Symbol LEV1
Name Electronic expansion valve (Sub-cool coil bypass)
Symbol TH2 TH5 TH6
SLEV
Electronic expansion valve(Oil return)
63HS 63LS L2 IPM TH1
High pressure sensor Low pressure sensor Choke coil(Transmission) Intelligent power module Thermistor Discharge pipe temp. detect
12
TH7 TH8 TH9
Name Thermistor Saturation evapo. temp. detect Pipe temp. detect OA temp. detect liquid outlet temp. detect at Sub--cool coil bypass outlet temp. detect at Sub--cool coil High pressure liquid. temp.
Symbol TH10 THHS X1~10
Name Compressor shell temp. Radiator panel temp. detect Aux. relay
FB1~4
Ferrite core Earth terminal
13
LEV
TH23
TH22
TH21
TH24
6 5 4 3 2 1
EF
0 12
Address (odd)
SWA SWC SW14
CN82
89A
8 7 6 5 4 3 2 1
345
67
B CD
9 0 1
X11
SW4 SW3 SW2
CN24 CN25
12
9 0 1
Z3
21
SW12 SW11 (2st digit) (1st digit)
21
21
21
21
33P2
33P1
3 21
CN23 CN22 CN20 CN21 CN29 CN31
CN81
CN42
SW1 CN62
A.B 1 2 3 4 5 6
1 2 3 4 5 6 7 8
1 2 3 4
2 3
4 5 6
7 8
12
2 3
4 5 6
7 8
CN3T
65 4 321 3
CN60
ZNR
1 13 T 13
CNT CND
F
X01
13
13
Z1
1 35 7
FAN2
CN32
CN2M
CN3A
I.B
MF
1 3 5 (CN54)
CN70
X06 X05 X04
CN52
1 2345
CNP CNV
X03
CN51
12345
51F
1 2 3
1 2 3 2 1
Z3
ZNR2 F1
(250V 5A F)
52F
FAN over current detection
52F
Z1
51F
Inside the control box
F4(250V 1A F)
1 2 3 4 5
1 2 3 4 5
IFB
CN54
CN53
DSA1
ZNR1
L
PE
SW8 Switch(normal/local)
Power supply (No fuse breaker 20A) 3N~ 380/400/415V(50Hz) 400/415V(60Hz)
TB22
C 1 2 3 4 5
Name Fan motor Indoor controller board Address board Surge absorber board External input/output board Power source terminal bed Transmission terminal bed Transmission terminal bed Terminal bed for distant location on/off TB22 Terminal bed for distant location display TB23 Terminal bed for distant location on/off F Fuse<6A> F1 Fuse<5A> ZNR,ZNR1,ZNR2 Varistor T Transformer LEV Electronic linear expan.valve 52F Contactor(fan I/D) 51F Over current relay (fan I/D) 33P1,33P2 Float switch TH21 Thermistor (inlet temp. detection) TH22 Thermistor (piping temp. detection/liquid) TH23 Thermistor (piping temp. detection/gas) TH24 Thermistor (outlet temp. detection) Switch (for mode selection) SW1(A.B) Switch (for capacity code) SW2(I.B) Switch (for mode selection) SW3(I.B) Switch (for model selection) SW4(I.B) SW8 Switch (normal/local) SW11(A.B) Switch (1st digit address set) SW12(A.B) Switch (2nd digit address set) SW14(A.B) Switch (connection No.set) SWC Switch (outlet/inlet temp.control) X11 Auxiliary relay(check) Z1 Auxiliary relay(fan) Z3 Auxiliary relay(fan failure detection) L1 LED display (failure) L2 LED display (status) L3 LED display (check) L4 LED display (power supply) RC MA Remote controller F4 Fuse<1A>
Symbol MF I.B A.B S.B IFB TB2 TB5 TB15 TB21
Note: 1. The dotted lines show field wiring. 2. Always use odd numbers for the indoor unit address. 3. Connect the transmission line from indoor unit to outdoor unit whose address equals he address of the connected indoor unit + 50. 4. Conventions: ,terminal bed; , connector; , board-insertion connector or fastening connector of control board.
Power supply Status output Failure output
Distant location on/off L
TB2
LED display(power supply)
LED display(check)
LED display(status)
LED display(failure)
BC TB21 B1 B2
L1 L2 L3 N
L4
L3
L2
L1
Power supply DC12 ~ 24V Distant location on/off
3
1 2 3
2
1
2 1 6 5
Indoor unit Control wiring DC24 to 30V
RC
AC TB23 A1 A2
2
CN1 1 1
S.B
X11
B1 A1
SHIELD TB5 S
TB15
1 2
PFD-P250VM-A
LEV2
6 5 4 3 2 1
EF
SW1
0 12
CN81
CN42
9 0 1
CN62
SWA SWC SW14
CN82
345
TH23-2
8 7 6 5 4 3 2 1
A.B2 1 2 3 4 5 6
1 2 3 4 5 6 7 8
1 2 3 4
9 0 1
CN25
CN24
9 0 1
SW12 SW11 (2st digit) (1st digit)
33P2-1
33P1-1
Address (even)
Z3
21
21
21
21
21
33P2-2
33P1-2
3 21
CN23 CN22 CN20 CN21 CN29 CN31
SW4 SW3 SW2
12
Address (odd)
Z3
21
3 21
2 1 21
21
21
CN22 CN20 CN21 CN29 CN31
CN23
12
X12
SW12 SW11 (2st digit) (1st digit)
2 3
TH22-2
6 5 4 3 2 1
SWA SWC SW14
9 0 1
CN62
CN81
CN25
CN24
SW4 SW3 SW2
12
12
2 3
TH21-2
TH24-2
LEV1
TH23-1
TH22-1
TH21-1
0 12
89A
TH24-1
EF
SW1
B CD
CN82
67
8 7 6 5 4 3 2 1
A.B1 1 2 3 4 5 6
7 8
89A
14
4 5 6
67
345
7 8
1 2 3 4 5 6 7 8
4 5 6
7 8
CN42
2 3
4 5 6
1 2 3 4
2 3
B CD
4 5 6
7 8
X11
654321 3
CN60
654321 3
CN60
1 T
CN3T
T
1
CN3T
ZNR
13
13
13
CNP
X03
X01
X03
13
CNP
CN51
12345
ZNR
13
CNT CND
F
13
CNT CND
F
X01
CN51
12345
Z2
MF
1 35 7
CN70
X06 X05 X04
CN52
CNV 13
CN70 1 35 7
Z1
12345
13
CNV
X06 X05 X04
CN52
1 2345
1 2 3
1 2 3 2 1
Z3
5A F) F1
ZNR2 (250V
51F
51F
1 2 3
1 2 3 2 1
52F
1 3 5 (CN54)
FAN2
CN32
CN2M
CN3A
I.B2
FAN over current detection
52F
Z1 Z2
1 3 5 (CN54)
FAN2
CN32
CN2M
CN3A
I.B1
Inside the control box
F4 (250V 1A F) DSA1
ZNR1
1 2 3 4 5
1 2 3 4 5
X11
X12
L1 L2 L3 N
IFB
B2 A2
SHIELD S
AC TB23 A1 A2 CN53 BC TB21 B1 B2 C 1 CN54 TB22 2 3 4 5
S.B CN1 1 1 2 3
B1 A1
SHIELD S
3
4
1 2 3
2
1
2 1 6 5
TB15
2
1
L
L
L2
TB5-2
L
L
PE
TB2
L5
L4
L3
L1
TB5-1
PE
L1 L2 L3 L4 L5 RC
Auxiliary relay(check) Auxiliary relay(fan) Auxiliary relay(fan failure detection) Lamp display (No1.failure) Lamp display (No2.failure) Lamp display (status) Lamp display (check) Lamp display (power supply) MA Remote controller
Fuse<6A> Fuse<5A> Fuse<1A> Varistor Transformer Electronic linear expan.valve Contactor(fan I/D) Over current relay (fan I/D) Float switch Thermistor (inlet temp. detection) Thermistor (piping temp. detection/liquid) Thermistor (piping temp. detection/gas) Thermistor (outlet temp. detection) Switch (for mode selection) Switch (for capacity code) Switch (for mode selection) Switch (for model selection) Switch (normal/local) Switch (1st digit address set) Switch (2nd digit address set) Switch (connection No.set) Switch (outlet/inlet temp.control)
F F1 F4 ZNR,ZNR1,ZNR2 T LEV1,2 52F 51F 33P1-1,-2, 33P2-1,-2 TH21-1,TH21-2 TH22-1,TH22-2 TH23-1,TH23-2 TH24-1,TH24-2 SW1(A.B) SW2(I.B) SW3(I.B) SW4(I.B) SW8 SW11(A.B) SW12(A.B) SW14(A.B) SWC X11~X12 Z1~Z2 Z3
TB22 TB23
Terminal bed for distant location on/off Terminal bed for distant location display Terminal bed for distant location on/off
TB21
Name
Fan motor Indoor controller board Address board Surge absorber board External input/output board Power source terminal bed Transmission terminal bed Transmission terminal bed
Symbol
MF I.B1,I.B2 A.B1,A.B2 S.B IFB TB2 TB5-1,-2 TB15
Note: 1. The dotted lines show field wiring. 2. Always use odd numbers for the indoor unit address. 3. Connect the transmission line from indoor unit to outdoor unit whose address equals he address of the connected indoor unit + 50. 4. Conventions: ,terminal bed; , connector; , board-insertion connector or fastening connector of control board.
Lamp display (No2.failure)
No2.Indoor unit Control wiring DC24 to 30V
Power supply DC12 ~ 24V Distant location on/off Distant location on/off Power supply DC30V,AC100/200V No1.Status output No1.Failure output No2.Status output No2.Failure output
Switch(normal/local)
SW8
Power supply (No fuse breaker 30A) 3N~ 380/400/415V(50Hz) 400/415V(60Hz)
Lamp display (power supply)
Lamp display (check)
Lamp display (No1.failure) Lamp display (status)
No1.Indoor unit Control wiring DC24 to 30V
RC
PFD-P500VM-A
6. Options
Description Square duct flange (Standard filter)✻1
Square duct flange (High-efficiency filter)
High-efficiency filter 65% ✻2
High-efficiency filter 90% ✻2
Model
Applicable capacity
PAC-TS75DFB
P250
PAC-TS76DFB
P500
PAC-TS70TB
P250
PAC-TS72TB
P500
PAC-TS60AF
P250
PAC-TS62AF
P500
PAC-TS65AF
P250
PAC-TS67AF
P500
✻1 Used to connect Intake Duct . Use the filter supplied with the unit. ✻2 Requires square duct flange (High-Efficiency Filter).
15
TH6
HEX1
16
TH5
CV2
HEX2
SV3
SCC
CP3
63H
CV1
ST5
ST3
SV2
SV1
CP
LEV1
TH8
TH2
Drier TH9
TH10
Comp
TH1
O/S
63HS
CJ1
ST4
TH7
MA
SLEV
63LS
CJ2
SA
Indoor units
BV1
ST2 BV2
ST1
7. Refrigerant Circuit Diagram And Thermal Sensor
PUD-P250YMF-C
8. System Design 8-1.Piping
Outdoor Unit
A A
Sample Unit Connection
L
H
L
Indoor
Maximum Pipe Length (L)
Net length: under 120m, Total Length: under 150m
Maximum Height Difference Between Indoor and outdoor units (H)
Under 50m (Under 40m if the outdoor unit is installed below the indoor unit. Under 15m if the outdoor temperature is under 10˚C.)
■ Selecting Refrigerant Pipes
Gas pipe: Liquid pipe:
■ Adding the Refrigerant The outdoor unit is shipped with 8.5 kg of refrigerant. It does not include enough refrigerant for extra piping system. Use additional refrigerant for each refrigerant piping system (2 refrigerant circuits). Record the length of the pipe and the amount of the added refrigerant on the outdoor unit for services in the future. ■ Calculating the amount of refrigerant to be added
ø 28.58 ✕ 2 ø 12.7 ✕ 2
Size of the liquid pipe Total length of the pipe with a diameter of ø 12.7 ✕ 0.12
+ 2.0kg
(m) ✕ 0.12 (kg/m)
(i.e.) When using a 120m pipe with a diameter of ø 12.7 120m ✕ 0.12kg/m + 2.0kg = 16.4 kg
· The amount of refrigerant needed for additional piping depends on the diameter and the length of the added liquid pipes. · Calculate the amount to be added as shown on the right, and add the refrigerant in that amount. · Round up the figure under 0.1kg. (e.g. 11.06kg would be 11.1kg).
Caution Charge Liquid Refrigerant Filling the equipment with gas refrigerant will result in a power loss due to transformation of refrigerant in the tank.
17
8-2.Control Wiring (1) Specifications of control wiring and maximum length of wiring Transmission line is a type of control line. When the source of noise is located adjacent to the unit, the use of shield cable as well as moving the unit as far away from the noise source are recommended. 1 Transmission line (M-NET transmission line) System component
For multiple-refrigerant system
Length of transmission line
n/a
Facility type (noise level measurement)
All types of facilities
Cable type
Shield cable CVVS · CPEVS
No. of cable
2-core cable
Diameter
Over 1.25mm2
Wiring specifications
Maximum length: 200m Maximum length of centralized control transmission line and Indoor/Outdoor transmission line via indoor/outdoor units: 500m maximum
Total length of indoor/outdoor transmission line
2 Remote control wiring MA remote controller ✻ 1 Cable type
VCTF · VCTFK · CVV · CVS · VVR · VVF · VCT
No. of cable
2-core cable
Diameter
0.3~1.25mm2 (0.75~1.25mm2)
Wiring specifications
Total Length
✻2 ✻3
Maximum length: 200 m
✻ 1: “MA remote controller” includes MA remote controller, Simple MA controller, and wireless remote controller. ✻ 2: Cables with a diameter of 0.75mm2 or smaller recommended for easier handling. ✻ 3: When connecting to simple remote controller terminal, use a cable with a diameter within the range shown in the parenthesis.
8-3.Types of switch settings and setting methods Whether a particular system requires switch settings depends on its components. Refer to the section “7-4 Wiring and Address Setting” before conducting electrical work. Keep the power turned off while setting the switches. If settings are changed while being powered, the changed settings will not register, and the unit may malfunction. Unit
Symbol
Outdoor unit Indoor unit
Main/sub controllers
✻ 10HP has only the main controller
18
✻
Turn off the power to
OC
Outdoor unit
IC
Indoor and outdoor units
(1) Address setting This system requires address setting. The range of address varies depending on the type of unit. Refer to “7-4 Wiring and Address Setting” for details. Unit
Indoor unit
Symbol
Address setting range
Setting method
Factory setting
IC
01~50 ✻2
Assign a number to all indoor units, starting with 1 and using sequential numbers. Use odd numbers for the top controller and even numbers for the bottom controller of the indoor units. Use odd numbers starting with 01 for 10HP system.
00
OC
51~100 ✻2 ✻3
Add 50 to the address assigned to the indoor unit to which the outdoor or heat-source unit is connected.
00
Main/sub controllers ✻1
Outdoor Unit
✻ 1: 10HP only has the main controller. ✻ 2: Avoid using the same address as the ones used by the indoor/outdoor units in another refrigerant system; choose a different one in the range specified above. ✻ 3: When setting the address to 100, set the switch to 50.
(2) Setting the outdoor unit power-source switch connector (Factory setting: CN41 Connected) System component
Multiple-refrigerant system
Power supply switch unit Replace the power source switch connector CN41 with CN40 on only one of the outdoor units Use CN41 as it is.
(3) Choosing the temperature detection spot by indoor unit (Factory Setting: SWC “Standard”) When using the suction temperature sensor, set SWC to “Option.”
(4) Setting the MA “Sub” controller When using two remote controllers or running two indoor units as a group, one of the controllers must be set to “Sub” controller. ✻ No more than two remote controllers can be connected to a group. (Factory setting: “Main”) Set the controller according to the following procedure. Refer also to the instructions manual supplied with the MA remote controller. Remove the cover on the remote controller Screwdriver
Insert a flat-head screwdriver in the groove shown in the picture, and move the screwdriver in the direction shown in the arrow.
ON
Set Dip Switch No.1 on the remote controller to “OFF” (Main to Sub)
1
2
3
4
Dip switches
19
Remote controller body
8-4.Wiring and Address Setting (1) System Using MA Remote Controller 1 System with one indoor unit (10HP system) Control Wiring Diagram
L1
Use CN41 as is.
IC
OC
51 TB7 A B S
TB3 A BE
01
✻There is one indoor controller board inside indoor unit.
TB5-1 ABS
TB15 1 2
A1 B2 MA
Remarks
Maximum Allowable Length Maximum Length (above 1.25mm2) L1 200m
1. Use power supply connector (CN41) on the outdoor unit as is. 2. It is not necessary to ground the S terminal of centralized control transmission terminal board (TB7) on the outdoor unit.
20
Wiring and Address Setting Connect A, B terminals of indoor/outdoor transmission line terminal board (TB3) on the outdoor unit and A, B terminals of the Indoor/outdoor transmission terminal board (TB5). (Non-polar 2 wire) ✻ Only use shield line. [Grounding the shield line] Connect the earth terminal of the OC and S terminal of the IC terminal board (TB5).
Steps
Set the address as follows. Address Setting Range
Unit or Controller
Setting Procedures
IC
01 ~ 50
Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05).
OC
51 ~ 100
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
Main Controller
MA
n/a
Sub Controller
MA Sub controller
1
Indoor Unit
2
Outdoor Unit
3
MA remote controller
Main Unit
Remarks
Factory Setting
00
00
Main Use dipswitch to set the controller as sub controller.
21
(1) System Using MA Remote Controller 2 Unit with One Indoor Unit (20HP Systems) Control Wiring Diagram
L1 Replace CN41 with CN40. IC
OC
51 TB7 A B S
✻There are 2 indoor controller boards inside indoor unit.
01
TB3 A BE
TB5-1 ABS
Conect
TB15 1 2
L31
A1 B2 MA
Use CN41 as is.
NO
OC
52 TB7 A B S
02 TB5-2 ABS
TB3 A BE
NO
L2
Remarks
Maximum Allowable Length Maximum Length (above 1.25mm2) L1, L2 200m Maximum length via outdoor unit (over 1.25mm2) L1 + L3 + L2 500m
1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal).
22
Wiring and Address Setting Connect A, B terminals of indoor/outdoor transmission line terminal board (TB3) on the outdoor unit and A, B terminals of the Indoor/outdoor transmission terminal board (TB5). (Non-polar 2 wire) ✻Only use shield line. [Grounding the shield line] Connect the earth terminal of the OC and S terminal of the IC terminal board (TB5).
Connect A terminals of centralized control transmission line terminal board on each of the outdoor units with each other. Do the same with B terminals. Replace CN41 (power supply switch connector) with CN40 on only one OC. ✻Only use shield line. [Grounding the shield line] Connect S terminals of the TB7 of each of the outdoor units with each other. Connect the S terminal of TB7 on the outdoor unit whose CN41 was replaced with CN40 to the earth terminal of the electric box.
Steps
Set the address as follows.
Main Unit 1
Address Setting Range
Unit or Controller
IC
01 ~ 49
Indoor Unit
Setting Procedures
Remarks
Factory Setting
Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). 00
Sub Unit
IC
02 ~ 50
OC
51 ~ 100
Main Controller
MA
n/a
Sub Controller
MA Sub controller
2
Outdoor Unit
3
MA remote controller
Add 1 to the address assigned to the main unit in the same room.
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
00
Main Use dipswitch to set the controller as sub controller.
23
(1) System Using MA Remote Controller 3 When connecting 2 MA remote controller to one indoor unit (20HP Systems) Control Wiring Diagram
L1 Replace CN41 with CN40 IC
OC
51 TB7 A B S
TB3 A BE
TB5-1 ABS
Connect
TB15 1 2 m1
L31
m2
A1 B2 MA(Sub)
Use CN41 as is
A1 B2 MA(Main)
OC
52 TB7 A B S
✻There are 2 indoor controller boards inside indoor unit.
01
A1 B2 MA
02 TB5-2 ABS
TB3 A BE
NO
NO NO
L2
Remarks
Maximum Allowable Length Same as (2). Same as (2). Maximum allowable length (0.3 ~ 1.25mm2) m1 + m2 200m
1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal). 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers.
24
Wiring and Address Setting Same as (2).
Same as (2).
[When using 2 remote controllers] When using two remote controllers, connect terminals 1 and 2 of TB15 on the indoor unit to terminal board of MA controller(option). ✻ Set the connected MA remote controller (option) as sub controller (Refer to manual that came with MA remote controller.)
Steps
Set the address as follows.
Main Unit 1
Address Setting Range
Unit or Controller
IC
01 ~ 49
Indoor Unit
Setting Procedures
Remarks
Factory Setting
Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). 00
Sub Unit
IC
02 ~ 50
OC
51 ~ 100
Main Controller
MA
n/a
Sub Controller
MA Sub controller
2
Outdoor Unit
3
MA remote controller
Add 1 to the address assigned to the main unit in the same room.
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
00
Main Use dipswitch to set the controller as sub controller.
25
(1) System Using MA Remote Controller 4 When grouping 2 indoor units (20HP systems) with MA remote controller Control Wiring Diagram ✻There are two indoor controller board inside each indoor unit. L1
L1
Replace CN41 with CN40.
Replace CN41 with CN40. IC
OC
51 TB7 A B S
53
01
TB3 A BE
TB5-1 ABS
Connect
TB7 A B S
TB5-1 ABS
Connect
TB15 1 2
TB15 1 2 m2
Use CN41 as is.
A1 B2 MA(Sub)
L31
L31
A1 B2 MA(Main)
Use CN41 as is.
OC
OC
52
54
02 TB5-2 ABS
TB3 A BE
NO
03
TB3 A BE
m1
TB7 A B S
IC
OC
TB7 A B S
TB5-2 ABS
TB3 A BE
NO
L2
04
L2
m3
Remarks
Maximum Allowable Length Same as (2). Same as (2). Maximum allowable length (0.3 ~ 1.25mm2) m1 + m2 + m3 200m
1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal). 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers.
26
Wiring and Address Setting Same as (2).
Same as (2).
✻ When grouping units that use different refrigerants, set MA remote controller of one of the indoor units as sub controller. [When grouping indoor units] When grouping indoor units, connect 1 and 2 terminals of both IC terminal boards (TB15) with each other (nonpolar 2 line). ✻ Set MA remote controller of one of the indoor units as sub controller.
Steps
Set the address as follows.
Main Unit 1
Address Setting Range
Unit or Controller
IC
01 ~ 49
Indoor Unit
Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05).
IC
02 ~ 50
Add 1 to the address assigned to the main unit in the same room.
OC
51 ~ 100
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
Main Controller
MA
n/a
Sub Controller
MA Sub controller
Sub Unit
2
Outdoor Unit
3
MA remote controller
Remarks
Factory Setting
00
00
Main Use dipswitch to set the controller as sub controller.
27
(1) System Using MA Remote Controller 5 When grouping multiple indoor units (combination of 10HP, 20HP systems) Control Wiring Diagram ✻There is one indoor controller board inside indoor unit. L1
Use CN41 as is
IC
OC 51
✻There are two indoor controller boards inside indoor unit.
IC
53
01
TB7 TB3 ABS ABE
L1
Replace CN41 with CN40. OC
03
TB5-1 ABS
TB7 TB3 ABS ABE
TB5-1 ABS
TB15 1 2
Connect
TB15 1 2
m1 A1 B2 MA(Main)
L31
m2 A1 B2 MA(Sub)
Use CN41 as is. OC 54
04 TB5-2 ABS
TB7 TB3 ABS ABE
NO
L2
m3
Remarks
Maximum Allowable Length Same as (2). Same as (2). Total Length (0.3 ~ 1.25mm2) m1 + m2 + m3 + m4 + m5 200m
1. Use odd numbers to set 10HP indoor unit address. 2. When setting unit address for 20HP indoor unit, use odd numbers for the top controllers and even numbers for the bottom controllers (main controller+1). 3. Replace CN41 (power supply switch connector) with CN40 on only one 20HP outdoor unit. 4. Ground the S terminal of TB7 (centralized control transmission terminal board) of only one of the 20HP outdoor units. 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers
28
Control Wiring Diagram ✻There is one indoor controller board inside indoor unit.
✻There are two indoor controller board inside indoor unit.
L1
Use CN41 as is
Replace CN41 with CN40.
IC
OC 55
IC
OC 57
05
TB7 TB3 ABS ABE
L1
07
TB5-1 ABS
TB7 TB3 ABS ABE
TB5-1 ABS
TB15 1 2
Connect
TB15 1 2
NO
NO
L31
A1B2 MA
A1B2 MA
Use CN41 as is. OC 58
08 TB5-2 ABS
TB7 TB3 ABS ABE
NO
Steps
m4
1
m5
Address Setting Range
Unit or Controller
Indoor Unit
L2
Main Unit (10HP, 20HP)
Sub Unit (20HP)
IC
01 ~ 49
Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05).
IC
02 ~ 50
Add 1 to the address assigned to the main unit in the same room.
OC
51 ~ 100
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
Main Controller
MA
n/a
Sub Controller
MA Sub controller
2
Outdoor Unit
3
MA remote controller
Remarks
Factory Setting
00
00
Main Use dipswitch to set the controller as sub controller.
29
(2) System with MA remote controller and G-50A 1 System with multiple indoor units (10HP, 20HP) Control Wiring Diagram L31
✻There is one indoor controller board inside indoor unit.
✻There are two indoor controller boards inside indoor unit.
L1
Use CN41 as is.
IC
OC
51 TB7 A B S
53
TB5-1 ABS
TB7 A B S
TB3 A BE
TB5-1 ABS
TB15 1 2 m1
L35
L32
m1
A B S
03
NO
TB15 1 2
Power Supply
IC
OC
01
TB3 A BE
L2
Use CN41 as is.
A1 B2 MA
Use CN41 as is.
A1 B2 MA
OC
L33
54 G-50A A B S
TB7 A B S
DC power supply line (DC12V)
04 TB5-2 ABS
TB3 A BE
Option
NO L3
L36
Remarks
Maximum Allowable Length
1. Be sure to use odd numbers to set the address for indoor units (10HP). 2. To set the indoor unit address for 20HP, use odd numbers for the top controllers and use even numbers for the bottom controllers (Main controller plus 1). 3. Use the power supply switch connector (CN41) on the outdoor unit as is. 4. It is not necessary to ground the S terminal of transmission line terminal board for centralized controller on the outdoor unit. 5 No more than two main/sub remote controllers can be connected to the indoor unit in the same group. When more than two remote controllers are present in the system, disconnect MA remote controller from TB15 in the indoor unit. 6. Put both types of the addresses for P500-type indoor units in the same group when setting groups for indoor units with a remote controller.
L1, L2, L3, L4, L5, L6 200m L31 + L32 + L33 + L35 + L36 + L37 + L38 + L6 500m L1 + L31 + L35 + L36 + L37 + L38 + L6 500m Total Length (0.3 ~ 1.25mm2) m1 200m
30
Control Wiring Diagram L37
✻There is one indoor controller board inside indoor unit. L4
Use CN41 as is.
L5
Use CN41 as is. IC
OC
55 TB7 A B S
✻There are two indoor controller boards inside indoor unit.
57
05
TB3 A BE
IC
OC
TB5-1 ABS
TB7 A B S
07
TB3 A BE
TB5-1 ABS
NO
TB15 1 2 m1
TB15 1 2
L38
m1 A1 B2 MA
Use CN41 as is.
A1 B2 MA
OC
58 TB7 A B S
08
Steps
NO
1
Address Setting Range
Unit or Controller
Indoor Unit
Main Unit (10HP, 20HP)
Sub Unit (20HP)
IC
01 ~ 49
Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05).
IC
02 ~ 50
Add 1 to the address assigned to the main unit in the same room.
OC
51 ~ 100
Add 50 to the address assigned to the indoor unit within the same refrigerant system.
Main Controller
MA
n/a
Sub Controller
MA Sub controller
2
Outdoor Unit
3
MA remote controller
TB5-2 ABS
TB3 A BE
L6
Remarks
Factory Setting
00
00
Main Use dipswitch to set the controller as sub controller.
31
8-5.External input/output specifications (1) Input/output specifications Input
Output
Function
Usage
Signals
Start/stop
Turning ON/OFF the indoor unit
Usage
Function
Signal
No. 2 Operation Status ✻
Obtaining signals indicating Relay a-contact operation status of indoor units output in each refrigerant circuit. DC 30V or AC 100V/200V Obtaining signals indicating error status of indoor units in Standard Current : each refrigerant circuit. 1A Obtaining signals indicating Minimum Current : operation status of indoor units 1mA in each refrigerant circuit.
over 200ms
No. 2 Error Status ✻
Obtaining signals indicating error status of indoor units in each refrigerant circuit.
✻1 Use minute-current contact (DC12V 1mA)
✻ 20HP only
Pulse (a-contact with voltage/without voltage) ✻1
No.1 Operation Status
Power Source: DC12~24V Electrical Current: Approximately 10mA (DC12V)
No. 1 Error Status
(2) Wiring
External input/output board
Input with voltage (polarized)
TB23 AC
External power source SW12
Stop/Start
A1
Short Circuit Input without voltage
CN53 1
TB21 BC
Common SW11
Stop/Start
A2
Short Circuit Relay Contact Point Output
B1
2
B2
3 XA
TB22 COM
Power Source for Display No.1 Operation Status
L1
No.1 Error Status
L2
✻ No.2 Operation Status
L3
✻ No.2 Error Status
L4
XA
1
XB
XC
3
XD
4
XE
5
5 CN54 1
XB
2
4
XC XD XE
2 3 4 5
✻ 20HP only
Connection to terminal board
Connection with connectors
Maximum : 100 m
External powe source
DC12~24V Electrical current input (per contact) Approximately 10mA (DC12V)
SW11
Remote start/stop ✻ Each pressing pf the SW (Pulse input) switches between ON and OFF.
Remote start/stop switch Each pressing of the SW (Pulse input) switches between ON and OFF.
Minute-current contact: DC12V 1mA
SW12
Power supply for displays
DC30V 1A AC220-240V 1A
L1
No.1 Operation Status Indicator Lamp
L2
No.1 Error Status Indicator Lamp
L3
No.2 Operation Status Indicator Lamp
L4
No.2 Error Status Indicator Lamp
XA~XE
Relay (Permissible Electrical Current: 10mA~1A)
● Setting on the Indoor Unit Confirm the following setting when using external input. 1 No.1, No.2 Controller board Dip SW 3-8: ON (Factory Setting: ON; External input will not be available when OFF.) 2 No.1, No.2 address board Dip SW 1-10: OFF (Factory Setting: OFF; External input will not be available when ON.) 3 Normal/Local switch inside the unit controller box is set to “Normal.” (Factory Setting: Normal; External input will not be available when it is set to “Local.”)
32
(3) Wiring Method 1 Check the indoor unit setting (Refer to 7-5.(2) Wiring ) 2 When using the external output function, connect each signal line to External output Terminal (TB22) on the unit, depending on the usage. 3 When using external input function, peal the outer layer of the signal line off, and connect it to external input terminal (TB21 or TB23) on the unit, depending on the usage. Wiring On Site
TB23 ✻1
AC A1 A2
✻1
CN53
TB21
BC B1 B2
Fix the wire on the lowvoltage (below DC30V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻2
To CN51 of No.1 board Wiring inside the unit
CN54
TB22
COM 1
To CN51 of No.2 board
2 3 4 5
Fix the wire on the highvoltage (AC220-240V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻3
✻1 20HP indoor unit is shipped with B1 and B2 terminals of TB21 and A1 and A2 terminals of TB23 short-circuited respectively. When connecting wire to those terminals, do not eliminate this feature. If it is eliminated, the units in one of the 2 refrigerant circuits may not operate. ✻2 Do not bundle with high-voltage (AC220-240V) wire, since noise interference from such wire may cause the unit to malfunction. ✻3 Do not bundle with minute-voltage (DC30V or below) wire, since noise interference from such wire may cause the unit to malfunction.
Caution 1) Wiring should be covered by insulation tube with supplementary insulation. 2) Use relays or switches with IEC or equivalent standard. 3) The electric strength between accessible parts and control circuit should have 2750V or more. 4) TB21 is a terminal specifically for No-voltage contact point input. Do not apply voltage to TB21, since it must result in malfunction of indoor unit controller board. 5) TB23 is specifically for contact point input with voltage. Check the polarity before connecting to avoid damage to the unit. 6) Keep the wires on the input side and on the output side away from each other when using AC220240V as a power source for displays. 7) Keep the length of the extension part of external signal line under 100m. 8) 20HP is shipped with B1 and B2 terminals of TB21 and A1 and A2 terminals of TB23 short-circuited respectively. Do not eliminate this feature. If it is eliminated, the units in one of the two refrigerant circuits may not operate.
33
9. Air Conditioning the Computer Room 9-1 Main Features of the Floor-Duct Air Conditioners This system is installed by building a floor over an existing floor and using the space between these two floors as an air-conditioning duct. This system has the following characteristics: 1 The temperature and humidity can efficiently and reliably be controlled, since the air-conditioned air is sent directly to the machine. 2 It provides a comfortable environment for the operator, since the air can be conditioned to best suit the needs of the operator and machines. 3 It is favorable in terms of appearance because the air-conditioning duct is out of sight. 4 The location of the duct is irrelevant when considering adding new machines or rearranging the existing machines, since the entire floor serves as the air duct.
Ceiling
Free-access top floor
Computer
Filter
Caution (1) Unlike plenum ventilation and overhead-duct type conditioners, since the conditioned air is not mixed with the air in the room, the air that comes out of the unit has to meet the predetermined conditions (constant temperature/constant humidity) at the time the air exits the unit. Close attention must be paid to the auto-controlling system. (2) Dust in the duct space (between the free-access top floor and the existing floor) must be thoroughly removed before installing the unit. (3) Since the existing floor is cooled by the unit, it may produce dews on the ceiling of the room down below.
9-2 Major Characteristics of Computer Room Air Conditioners (Constant Temperature · Constant Humidity) A computer-room air conditioner is a device that is used to maintain certain temperature and humidity in the room. Especially, floor-duct conditioners must be able to provide air that meets predetermined requirements. In this unit, the compressor works year around. To respond to the change in temperature, the capacity control compressor regulates the temperature. Since this unit does not ship with a humidifier, humidity is controlled with the use of a humidifier installed in the room.
34
9-3 Step-by-Step Plan for the Implementation of the Air-Conditioning Purpose
Making decisions on the computer system
Basic Conditions
Accommodates possible future expansion (ensuring the acquisition route) Operation schedule Back-up system (in case of breakdowns, power outage, water-supply cut offs etc.) Air conditioning methods (continuous, floor-duct type etc.)
Securing Necessary Rooms
Computer room, CVCF room, MT Disk Storage room Supplementary computer room, system surveillance room Programmer room, operator room Battery room, transformer room
Decision to Install the Air-Conditioning System
Setting the Conditions for the Room
Temperature/humidity Condition
Calculating the Load
Selecting the AirConditioner Model
Selecting the Controllers
Total System
Air-conditioning operation panel (secure individual operation circuit), Auto Controller (temperature and humidity indicator/recorder), management, safety, laws, maintenance, earthquake proof, anti-vibration (floor load, anti-vibration device), noise control, etc.
35
9-4 Conditions for the Installation of Computer-Room Air Conditioners (1) Outdoor Temperature and Humidity Generally the values set for general air conditioners are used, although the value higher than the maximum outdoor temperature and humidity may be set for devices like computer-room air conditioners that must keep the air temperature and humidity under predetermined levels.
(2) Indoor Temperature and Humidity There is a wide range of conditions set by different computer manufacturers, and the conditions need to be set in consultation with the manufacturers. The most basic conditions include keeping dew condensation and static electricity from forming. It is also necessary to keep the room free of dust to ensure a smooth operation of the computer.
(3) Matching the Volume of Air Flow It is possible to use the fan on the computer to cool the room. This controlling method requires a certain volume of cold air in proportion to the amount of heat produced by the device. The inlet panel is located at the bottom of the unit, and the exhaust pipe is located either on the ceiling, front and back, or on the side. Air intake
Air conditioner
Computer Fan Free-access floor Air discharge
(4) Considering a Back-up Air Conditioning System When the system is not allowed to stop at all, a back-up system is necessary. There are several different options for a back-up as the following: 1 Installing two sets of air conditioning systems necessary for the computer. 2 Utilizing regular office air conditioners (for people) 3 Using one of the units as a back-up 1 is used infrequently due to high costs involved. 2 involves many technical problems such as the difference between preset conditions for computer rooms and office rooms. In general, 3 is a preferred method. If 3 is chosen, the unit method (package method) is more economical than the central method.
36
9-5 Setting the Air conditioners (1) Air-Conditioning Load 1 Once the floor plan is made and the conditions for the air-conditioning system are set, air conditioning capacity has to be determined by calculating the load. 2 Unlike the outdoor air, computer load remains constant throughout the year. However, it is possible that there are considerable fluctuations within a day. This is due to the fact that, depending on the time of the day, there are changes in the number of computers that are turned on and that the different computer systems are in operation. 3 If there is a plan to expand the current computer system in the future, it is important to include the load for the units to be added in the future when calculating the thermal load because it is practically impossible to keep the computers off for days on end during the installation of the new units. 4 The following items need to be checked before calculating the unit capacity: · Floor area of the computer room (m2) · Total quantity of heat generated by computers
(2) Sample Selection of Air Conditioners (2-1) Conditions 20.9kW
Computer-generated heat
5
Number of workers
20W/m2
Lighting
Indoor ˚CDB/Indoor WBT : 24˚C/17˚C ˚CDB of the air going into the computer : 18˚C
Temperature and humidity
60Hz
Frequency
(2-2) Building Conditions (W: 4.5m, H: 1.5m) ✕ 2
Windows Inside Measurement Surroundings
Ceiling height 2.2m Upstairs room, downstairs room, heat and air conditioning
1 Coefficient of Overall Heat Transmission U (W/m2 ·K) Outer Walls Inner Walls
Summer 3.6, Winter 3.8 2.05 Downward convection 3.36, upward convection 3.3
Ceiling Floor (free access)
Downward convection 3.05, upward convection 4.56
Floor
Downward convection 2.42, upward convection 3.3
Windows
Summer 5.93, Winter 6.5 Window
2 Internal Load Number of People in the Room 5 Lighting 20W/m2 Calculator 20.9kW Draft 0.2 times/h
3 Volume of Outdoor Air Intake 25m3/h·person
37
(2-3) Calculating the Load and Selecting a Model Calculate the temperature difference by setting the outdoor temperature; then, calculate hourly loads. The chart shows the result of a calculation, supposing that the system reaches its highest load at 12 o'clock. Outdoor temperatures in this example Summer : 32˚CDB relative humidity 60% Winter : -2˚CDB relative humidity 42%
1 Load (in the summer with air-conditioning) < Sensible Heat > SH Computer
20.9 kW
Lighting Number of people in the room Infiltration draft Outer wall (heat transmission) Windows (radiation)
1,800W
1.8 kW
5 persons ✕ 64 (U)
0.32 kW
3
(0.2 times/h) 39.6m ✕ 0.336 ✕ 8
0.11 kW
✕ 3.6 ✕ 8
0.25 kW
✕ 0.65 ✕ 188
1.91 kW
8.5m2 13.5m2
Windows (heat transmission)
13.5 ✕ 5.93 ✕ 8
0.64 kW
Inner wall(heat transmission)
61.6 ✕ 2.05 ✕ 4
0.5 kW
125m3 ✕ 0.336 ✕ 8
0.34 kW
Outside air
Total
26.8 kW
< Latent Heat > LH Infiltration draft Number of people in the room Outside air
39.6 ✕ 834 ✕ 0.0117
0.39 kW
5 persons ✕ 82
0.41 kW
125m3 ✕ 834 ✕ 0.0117
1.22 kW Total
2.0 kW
Total load is 28.8kW
2 Necessary Air Circulation V=
26800 0.336 ✕ (24 -18)
÷ 60 = 221m3/min
3 Model Selection PUY-P250YMF-C ✕ 2, PFD-P500VM-A type Indoor ˚CDB 24˚C / Indoor ˚CWB 17˚C outdoor ˚CDB 32˚C Capacity of the Moment 51.5kW SHF = 0.92 Capacity of Sensible Heat 51.5 ✕ 0.92 = 47.4/kW Standard Air-Flow Volume: 320m3/min can be accommodated with PUY-P250YMF-C ✕ 2 and PFD-P500VM-A.
38
9-6 Automatic Control of the Computer Room Example PFD-P560VM-A automatically controls the cooling temperature with a built-in controller. (suction temperature or discharge temperature control) This unit is designed for high sensible-heat specifications, and it does not include a humidifier or a dehumidifier. Install such components as necessary.
< Outdoor Unit > TB7 No1 TB3
TB7 No2 TB3 ✻2 ✻1 Intake Thermistor
RA < Indoor unit >
Controller Terminal Bed for External Input/Output
Discharge Thermistor
Free-Access Floor
SA Remote Controller
✻1 Bold lines in the diagram indicate refrigerant piping (gas/liquid). This system consists of 2 refrigerant circuits. ✻2 Indicates TB3-type transmission line used to communicate with the indoor unit. This system is made up of 2 circuits.
39
10. Maintenance/Inspection 10-1. Maintenance/Inspection Schedule Having the units inspected by a specialist on a regular basis, in addition to regular maintenance such as changing the filters, will allow the users to use them safely and in good condition for an extended period of time. The chart below indicates standard maintenance schedule.
(1) Approximate Longevity of Various Parts The chart shows an approximate longevity of parts. It is an estimation of the time when old parts may need to be replaced or repairs need to be made. It does not mean that the parts must absolutely be replaced (except for the fan belt). Please note that the figures in the chart do not mean warranty periods.
Fan Belt
Check Replace every after 6 months 40000 hours 6 months 40000 hours 6 months 8000 hours
Air Filter
3 months 5 years
Drain Pan
6 months 8 years
Yes
Drain Hose
6 months 8 years
Linear Expansion Valve
1 year 1 year
Yes Yes Yes
Unit
Parts Fan Motor
Indoor
Bearing
Heat Exchanger Float Switch Indicator Lamp
Outdoor
25000 hours 5 years 6 months 25000 hours 1year 8000 hours
Heat Exchanger Pressure Switch Inverter Cooling Fan
1 year
Fan motor Linear Expansion Valve
Periodically check Yes Yes Yes
Remarks Add lubricant once a year Disposable parts
Yes
6 months 40000 hours 6 months 40000 hours 1 year 25000 hours 5 years 1 year 1 year 25000 hours
Compressor
Daily check
40000 hours
Maintenance schedule changes depending on the local conditions
Yes Yes Yes Yes Yes Yes Yes Yes
(2) Notes ●The above chart shows a maintenance schedule for a unit that is used under the following conditions: A. Less than 6 times per hour of compressor stoppage B. The unit stays on 24 hours a day. ●Shortening the inspection cycle may need to be considered when the following conditions apply: ➀ When used in high temperature/high humidity area or when used in a place where the temperature and/or humidity fluctuate greatly ➁ When plugged into an unstable power source (sudden change in voltage, frequency, wave distortions) (Do not exceed the maximum capacity.) ➂ When the unit is installed in a place where it receives vibrations or major impacts. ➃ When used in a place with poor air quality (containing dust particles, salt, poisonous gas such as sulfuric acid gas and sulfuric hydrogen gas, oil mist). ●Even when the above maintenance schedule is followed, there could be unexpected problems that cannot be predicted. ●Holding of Parts We will hold parts for the units for at least 9 years after the termination of the production of the unit, following the standards set by the ministry of economics and industries.
40
Details of Maintenance/Inspection Unit
Parts
Inspection Cycle
Check points
Assessment
Fan motor
· Check for unusual noise · Measure the insulation resistance
· Free of unusual noise · Insulation resistance over 1MΩ
Replace when insulation resistance is under 1MΩ
Bearing
· Check for unusual noise
· Free of unusual noise
If the noise doesn't stop after lubrication, change the oil. Add lubricant once a year.
· Check for excessive slack · Check for wear and tear · Check for unusual noise
· Resistance (3-4kg/belt) · Adequate amount of slack=5mm · Belt length=no longer than 102% of the original length · Free of wear and tear · Free of unusual noise
Adjust the belt Replace if the belt length exceeds 2% of the original length, worn, or used over 8000 hours
· Check for clogging and tear · Clean the filter
· Clean, free of damage
Clean the filter Replace if extremely dirty or damaged
· Check for clogging of the drainage system · Check for loosened bolts · Check for corrosion
· Clean, free of clogging · Free of loose screws · No major disintegration
Clean if dirty or clogged Tighten bolts Replace if extremely worn
· Make sure the loop of the hose has water to prevent air from traveling through the hose (Fill the hose with water) · Check for clogging of the drainage system
· Clean, free of clogging · Free of wear and tear
Clean if dirty or clogged Replace if extremely worm
· Perform an operation check using the operation data
· Adequately controls the air temperature (Check temperature change on the centralized controller)
Replace if malfunctioning
· Check for clogging, dirt, and damage
· Clean, free of clogging or damage
Clean
· Check the outer appearance · Make sure its free of foreign objects
· Free of frayed or cut wires · Free of foreign objects
Replace if damaged or extremely worn Remove foreign objects
· Make sure the lamp comes on
· Comes on when the output is on
Replace if the light does not come on when the power is on
· Check for unusual noise · Check insulation resistance · Check for loosened terminals
· Free of unusual sound · Insulation resistance over 1MΩ · Free of loosened terminals
Replace if insulation resistance goes below 1MΩ (under the condition that the refrigerant is not liquefied) Tighten loosened bolts
Fan motor
· Check for unusual noise · Measure insulation resistance
· Free of unusual sound · Insulation resistance over 1MΩ
Replace if insulation resistance goes below 1MΩ
Linear expansion valve
· Perform an operation check using the operation data
· Adequately controls the air temperature (Check temperature change on the centralized controller)
Replace if malfunctioning
Heat exchanger
· Check for clogging, dirt, and damage
· Clean, free of clogging or damage
Clean
Pressure switch
· Check for torn wire, fraying, and unplugged connectors · Check insulation resistance
· No frayed or cut wires or unplugged connectors · Insulation resistance over 1MΩ
Replace when cut or shorted, when the insulation resistance goes below 1MΩ, or if there is a history of abnormal operation
· Check for unusual sound · Measure insulation resistance · Look for abnormal history
· Free of unusual sound · Insulation resistance over 1MΩ · No heatsink overheat protection (4230,4330) on the report
Replace when producing unusual sounds, when insulation resistance goes under 1MΩ, or if there is a history of abnormal operation.
Fan belt
Air filter
6 months
3 months
Indoor
Drain pan
Drain hose
6 months
Linear expansion valve 1 year Heat exchanger Float switch
Indicator lamp
6 months 1 year
Compressor 6 months
Outdoor
What to do
1 year Inverter cooling fan
41
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Issued in June 2004 MEE03K204-A Printed in Japan
New publication, effective June 2004 Specifications subject to change without notice