Preview only show first 10 pages with watermark. For full document please download

Pud-p-ymf-c Databook

   EMBED


Share

Transcript

PUD-P-YMF-C PFD-P-VM-A Close control CONTENTS 1. Specifications 1 1 2 2 2. Capacity Curves ························································· 2-1 Cooling Capacity ························································· ························································· 2-2 Cooling Input ························································· 2-3 SHF Curves 2-4 Correction by refrigerant piping length ···························· ························································· 2-5 Operation limit 4 4 4 5 6 6 3. Sound Levels ··································································· 7 7 8 8 ······························································ 1-1 Main Features ······························································ 1-2 List of Possible Combinations of Indoor and Outdoor Units ····· 1-3 Unit Specifications ························································· 3-1 Noise Level ··································································· 3-2 NC Curves ··································································· 3-3 Fan Characteristics Curves ··········································· 4. External Dimensions ······················································ 5. Electrical Wiring Diagrams ··········································· 6. Options ·············································································· 7. Refrigerant Circuit Diagram And Thermal Sensor ··· 8. System Design ································································· 8-1 Piping ············································································ 8-2 Control Wiring ································································· 8-3 Types of switch settings and setting methods ················ 8-4 Wiring and Address Setting (System Using MA Remote Controller) ··· 8-5 External input/output specifications ······························· 9 12 15 16 17 17 18 18 20 32 9. Air Conditioning the Computer Room ························· 34 9-1 Main Features of the Floor-Duct Air Conditioners ·········· 9-2 Major Characteristics of Computer Room Air Conditioners ··· 9-3 Step-by-Step Plan for the Implementation of the Air-Conditioning ··· 9-4 Conditions for the Installation of Computer-Room Air Conditioners ··· 9-5 Setting the Air conditioners ············································· 9-6 Automatic Control of the Computer Room ······················ 34 34 35 36 37 39 10. Maintenance/Inspection ··············································· 40 10-1 Maintenance/Inspection Schedule ······························· 40 1. Specifications 1-1.Main Features (1) List of Models } Outdoor Unit PUD-P250YMF-C 10HP(Down flow): PFD-P250VM-A(-H) } Indoor Unit 20HP(Down flow): PFD-P500VM-A(-H) ✻ '-H' in the indoor units indicates that the unit pipes come out of the top of the unit (50/60Hz, fit to order). ✻ PFD-type indoor units cannot be connected to outdoor units other than the ones specified above. ✻ PFD-type indoor units and other types of indoor units cannot coexist in the same refrigerant system. <10HP System> Outdoor Unit Indoor Unit PUD-P250YMF-C G-50A ✻3 PFD-P250VM-A TB7 TB3 ✻2 ✻1 12V DC UP POWER SUPPLY UNIT MODEL PAC-SC50KUA POWER RATING 2.11kg WEIGHT SERIAL No. MITSUBISHI ELECTRIC CORPORATION M-NET PAC-SC50KUA When using a PFD-P250VM-A as an indoor unit, connect an outdoor unit PUD-P250YMF-C to each indoor unit and operate with a built-in remote control for the indoor unit. ✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of one refrigerant circuit. ✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units. This system consists of 1 refrigerant circuit. ✻3: Indicates TB7-Type transmission line that allows the unit to communicate with the controller. <20HP System> Outdoor Unit PUD-P250YMF-C G-50A TB7 Indoor Unit PFD-P500VM-A TB3 ✻2 ✻1 12V DC ✻3 TB7 UP POWER SUPPLY UNIT MODEL PAC-SC50KUA POWER RATING WEIGHT SERIAL No. 2.11kg MITSUBISHI ELECTRIC CORPORATION PUD-P250YMF-C TB3 M-NET PAC-SC50KUA When using a PFD-P500VM-A as an indoor unit, connect 2 PUD-P250YMF-C outdoor units to each indoor unit and operate with a built-in remote control for the indoor unit. ✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of 2 refrigerant circuits. ✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units. This system consists of 2 refrigerant circuits. ✻3: Indicates TB7-type transmission line that allows the unit to communicate with the controller. 1 1-2. List of Possible Combinations of Indoor and Outdoor Units Units Indoor Units Model Name Down-flow Type Power Source 380-415V(50Hz) 400,415V(60Hz) 380-415V(50Hz) 400,415V(60Hz) 10HP 20HP PFD-P250VM-A(-H) PFD-P500VM-A(-H) 56.0 Unit Horse Power Air-cooling Outdoor Units Series Name 380 /400 /415V 10HP PUDP250YMF-C Q 28.0 W 10.9 21.8 A 18.3/17.3/16.3 36.1/34.3/33.0 Power factor 90 91 ✻1: Refer to the following pages for detailed specifications of each unit. ✻2: The values in the chart are as follows: Q, Total Capacity [kW]; W, Total Input [kW]; A, Total Electrical Current [A]; Power Factor [%]. They were measured at operation under the following conditions: Indoor Intake Temperature: 27˚CDB/19˚CWB, Outdoor Intake Temperature 35˚CDB with 7.5m of refrigerant piping. 1-3. Unit Specifications (1) Outdoor Unit PUD-P250YMF-C Capacity ✻1 Power source Power input Current Type ✕ Quantity Fan Airflow rate Motor output Type Compressor Motor output Crankcase heater Starting current Refrigerant / Lubricant External finish External dimension High pressure protection Protection Compressor / Fan devices Inverter Refrigerant piping diameter Liquid / Gas ✻2 Noise level Net weight kW kW A m3/min kW kW kW A mm dB(A) kg 28.0 3N ~ 380/400/415V 50/60Hz 8.4 14.0/13.3/12.8 Propeller fan 185 0.38 Hermetic 7.5 0.045 (240V) 12 R407C/MEL32 Steel plate painting with polyester powder 1715(H)✕990(W)✕840(L) 2.94MPa Over current protection / Thermal switch DC bus current protection, thermal switch ø12.7 flare /ø28.58 Flange 56 231 Indoor:12˚CWB ~ 24˚CWB Outdoor:-15˚CDB ~ 43˚CDB (0˚CDB ~ 43˚CDB with outdoorunit at lower position) Operating temperature range Note: Cooling capacity indicates the maximum value at operation under the following condition. ✻1 Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB Pipe length 7.5m, Height difference 0m ✻2 It is measured in anechoic room. 2 (2) Indoor Unit PFD-P250VM-A Power source Cooling capacity Power consumption Current External finish Dimensions ✻1 Height Width Depth Net weight Heat exchanger Type Airflow rate Fan External static pressure Type Motor Output Starting current Air filter mm mm mm kg m3/min 120 Pa 3 phases induction motor kW A 3.7 60 5.5 75 PP Honeycomb fabric Gas Refrigerant pipe dimension kW kW A PFD-P500VM-A 3N~380-415V 50Hz / 3N~400-415V 60Hz 28.0 56.0 2.5 5.0 5.5/5.3/5.1 9.5/9.0/8.7 <5Y 7/1> 1895 1,800 1,200 800 350 480 Cross fin (Aluminum-plate fin and copper tube) Sirocco fan Sirocco fan ✕ 2 160 320 (Flare) Liquid (Flare) Drain pipe dimension Noise level (Lo-Mid2-Mid1-Hi) ✻ 2 mm ø 28.58 ø 28.58 ✕ 2 mm ø 12.7 ø 12.7 ✕ 2 dB(A) 59 Rp1 Note: ✻1 Cooling capacity indicates the maximum value at operation under the following conditions; Indoor 27˚CDB/19˚CWB, Outdoor 35˚CDB ✻2 Measured in an anechoic room. 3 64 2. Capacity Curves 2-1. Cooling Capacity 1.5 Indoor Temperature (˚CWB) 1.4 1.3 Ratio 1.2 24˚CWB 1.1 1 21˚CWB 0.9 19˚CWB 0.8 17˚CWB 15˚CWB 0.7 12˚CWB 0.6 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor Temperature (˚CDB) 2-2. Cooling Input 1.3 Indoor Temperature (˚CWB) 24˚CWB 1.2 21˚CWB 19˚CWB 17˚CWB 1.1 15˚CWB Ratio 12˚CWB 1 0.9 0.8 0.7 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor Temperature (˚CDB) ✻ The correction curves indicate the values measured at the point where the compressor was operated at its maximum capacity. ✻ indicates the standard value. 4 2-3. SHF Curves Standard Capacity Ratio 130% 120% 110% 100% 90% 80% 70% 1.0 Indoor Temperature 27˚CDB 0.93 0.9 SHF 0.8 0.7 0.6 0.5 0.4 30 40 50 60 70 80 RH (%) Standard Capacity Ratio 130% 120% 110% 100% 90% 80% 70% 1.0 Indoor Temperature 24˚CDB 0.9 SHF 0.8 0.7 0.6 0.5 0.4 30 40 50 60 RH (%) Operation Temparature Range : Indoor : 12˚CWB~24˚CWB Outdoor : -5˚CDB~43˚CDB (RH : 30~80%) Standard Point " " : Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB/- 5 70 80 2-4. Correction by refrigerant piping length To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity correction factor based on the refrigerant piping equivalent length in the table below. Cooling capacity correction factor 1.0 0.9 0.8 0.7 0 20 40 80 100 120 60 Piping equivalent length (m) 140 • How to obtain piping equivalent length Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m Indoor temperature (˚CWB) 2-5. Operation limit 30 25 20 15 12 10 -15 -10 -5 0 5 10 15 20 25 Outdoor temperature (˚CDB) (Outdoor door temperature :0˚CDB~43˚CDB with outdoor unit at lower position in cooling mode.) 6 30 35 40 45 3. Sound Levels 3-1. Noise Level (1) Outdoor Unit 1m Measured point 1m Series PUD-P250YMF-C Noise Level (dB [Type A]) 56 (2) Indoor Unit 1m Measured point 1m Series 7 Noise Level (dB [Type A]) PFD-P250VM-A 59 PFD-P500VM-A 64 3-2. NC Curves static PUD-P250YMF-C (External pressure 0Pa) OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa 80 70 NC70 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 63 125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) PFD-P250VM-A (External static pressure 120Pa) (External static pressure 120Pa) PFD-P500VM-A 80 80 High speed NC70 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 63 125 250 500 1000 2000 4000 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa High speed 70 NC70 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 8000 63 OCTAVE BAND CENTER FREQUENCIES (Hz) 125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) 3-3. Fan Characteristics Curves PFD-P250VM-A PFD-P500VM-A : 50/60Hz, standard : 50/60Hz, with middle-high efficient filter box 700 : 50/60Hz, standard Fan rotation speed 1000 1100rpm 900 Output 3.7kW 600 1000rpm Total static pressure (Pa) Total static pressure (Pa) 800 500 400 900rpm (Output 2.2kW) 300 Internal resistance (middle-high efficient filter ) 800rpm 200 Internal resistance 100 1100rpm 600 Output 5.5kW 500 400 1000rpm 300 200 900rpm Internal resistance 100 0 140 Fan rotation speed 1200rp Output 7.5kW 700 800rpm Standard 0 144 150 160 170 176 260 180 Air volume (m3/min) 270 280 288 300 320 Air volume (m3/min) 8 330 340 352 360 Crosss section Y-Y Rear view 251 Cross section X-X 778 60 75 Left side view ø27 Knockout hole Knockout hole Left piping hole 160 Y 40 75 ø40 Knockout hole Knockout hole Front piping hole 813 590 Plane view 990 560(bolt hole) 55 215 31 79 165 Front view 910 Service panel 1490 Knockout hole X 80 215 X Refrig. service valve (liquid) ø12.7 Knockout hole 4X2-14X20 Oval hole Refrig. service valve(gas) ø27 Knockout hole ø40 Knockout hole Air inlet Right side view Air outlet Air inlet PUD-P250YMF-C Knockout hole 100 Conn. pipe ø28.58 25 Note1 Knockout hole Bottom piping hole 237 198 50 234 73 80 Y 194 5 121 100 48 70 40 15 880(bolt hole) 15 12 149 840 78 9 99 < Accessory > • Refrigerant (gas) conn. pipe ··········· 1 pc. (The connecting pipe is fixed with the unit) • Packing for conn. pipe ·················· 1 pc. (Attached near the ball valve) • Wiring mounting board • Conduit mounting plate (Painted the same color as the unit body) ø40································· 1 pc. ø33································· 1 pc. ø27································· 1 pc. • Tapping screw 4 ✕ 10 ················ 6 pcs. Note.1 Please leave a space under the outdoor unit for the piping When, you connect the piping from the bottom. (Please be careful not to close the hole of the bottom plate by the basement) 4. External Dimensions Unit : mm 1715 5 Control box MA Remote controller Lamp Power Supply : White Operating : Green Check : Yellow Failure : Red Lifting bolts (supplied with the unit) 1200 Air outlet A Air inlet Hole for the control wiring 400 200 1895 5 800 50 210 75 Service space 473 1050 340 420 Refrig. piping (liquid) ø 12.7< flare > Refrig. piping (gas) < flange > Hole for liquid-pipe-connecting<ø27> 8-ø18 Bolt hole 600 or more 70 15 · Lifting bolts · Refrigerant (gas) conn. pipe (ø 28.58 < brazed >) · Packing for flange · Insulation cover for flange · Flare nut (liquid) · Hexagonal allen key (for front panel opening/closing) ······4pcs. ······1pc. ······1pc. ······1pc. ······1pc. ······1pc. Drain pipe end connecting Hole for gas-pipe-connecting<ø48> 235 245 395 < Accessories > Base measurement 1160 70 Discharge air outlet 180 15 292 192 Note 1 Drain water outlet height Hole for power-supply line<ø60> Note1. For right-hand-side piping, the minimum space of 200mm on the right side must be increased to a minimum of 500mm. Note2. If a minimum space of 880mm is secured, the panel can fully be opened. Discharge air outlet height Hole for transmission line<ø60> 90 620 90 100 Air Inlet(Air Filter) 120 11 319 413 Indoor Unit 11 Hole for the power supply 110 15 770 15 200 or more 210 10 260 200 or more PFD-P250VM-A Unit : mm 205 Control box MA Remote controller Power Supply : White Operating : Green Check : Yellow Failure1 : Red Failure2 : Red Lamp 5 A 1800 Air outlet Air inlet 5 400 800 Lifting bolts (supplied with the unit) 50 50 50 110 Service space Indoor unit 205 186 1760 1650 Discharge air outlet 370 NO.2 NO.1 15 70 8-ø 18 Bolt hole Hole for gas-pipe-connecting<ø 48> 395 245 235 · Lifting bolts · Refrigerant (gas) conn. pipe (ø 28.58 < brazed >) · Packing for flange · Insulation cover for flange · Flare nut (liquid) < Accessories > ······4pcs. ······2pcs. ······2pcs. ······2pcs. ······2pcs. Hole for liquid-pipe-connecting<ø 27> Hole for gas-pipe-connecting<ø 48> Hole for liquid-pipe-connecting<ø 27> Drain pipe end connecting Base measurement Refrig. piping (liquid) ø 12.7 NO.1 Refrig. piping (gas) 370 270 Discharge air outlet Refrig. piping (liquid) ø 12.7 NO.2 Refrig. piping (gas) 15 70 218 340 Note 1 600 or more Drain water outlet height Hole for power-supply line<ø 60> Note1. For right-hand-side piping, the minimum space of 200mm on the right side must be increased to a minimum of 500mm. Note2. If a minimum space of 880mm is secured, the panel can fully be opened. Discharge air outlet height Hole for transmission line<ø 60> 420 Hole for the control wiring 120 340 Air inlet(Air Filter) 75 15 200 1895 11 110 Hole for the power supply 100 11 319 413 90 620 770 90 11 15 200 or more 110 50 50 50 200 or more PFD-P500VM-A Unit : mm 5. Electrical Wiring Diagrams PUD-P250YMF-C MC1 Inverter Controller Box Red Terminal Block TB1A L1 Red L1 Power source 3N380/400/415V 50/60Hz L2 L2 White Noise Filter NF L1 Terminal Block L1 L2 Red L2 L1 TB1B L1 Red L2 White L3 Black L3 L3 Black L3 Black N Blue N N Blue N Blue White ACCT -W Black ACCT -U Diode stack N L3 R1 DS White N PE L2 - + L3 IPM R5 ZNR4 C1 - 52C DCL - - U + C2 R2 + C3 R3 V W P Gate amp board (G/A board) N Green/ Yellow PE Connect to Indoor and remote controller Motor U V W (Compressor) BOX BODY TB3 M1 F3 250VAC 1A F BOX BODY CNE (2P) CNDC1 (4P) 1 2 1 2 3 4 CNDR1 (9P) CN15V1 (14P) 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1011121314 M2 CNTR1 FB2 FB1 S TB7 CH1 Crank case heater (Compressor) SV1 123 12 CNS2 (3P) CNS1 (2P) 3 2 CN32 1 (3P) 3 2 CN33 1 (3P) 6 5 4 CN34 3 (6P) 2 1 SV2 1 2 3 CN20 (3P) 1 2 7 1 2 5 4 3 3 4 CNRS2 5 (7P) 6 7 CNVCC41 (2P) 2 1 CNVCC4 2 (2P) 1 2 CNVCC3 3 (6P) 4 5 6 1 2 3 CNVCC2 4 (6P) 5 6 1 2 CNRS3 3 (7P) 4 5 6 3 CNTR (3P) F1 250VAC 2A F X01 X10 X02 SV3 1 2 3 4 5 6 7 8 9 CNVDC (4P) Gray White Orange Yellow Black Purple Brown Red Black Red 1 2 3 4 1 2 3 4 5 6 7 8 9 1011121314 CNDR2 (9P) CN15V2 (14P) F01 250VAC 2A F Power circuit board (INV board) 1 CNACCT 2 (4P) 3 4 2 X01 52C 3 CN52C (3P) CNTH X02 (2P) 1 X05 1 2 3 4 4:Compressor ON/OFF 5 12V CNAC2 2 1 (5P) 1 1 2 3 CNX10 (3P) CN51 (5P) 6 5 4 CN36 3 (6P) 2 1 Blue M2 White Green BOX BODY T01 Brown Orange BOX BODY M1 5:Trouble 2 3 12 CNFAN (3P) CNR (3P) 1 2 3 CNL2 (2P) CN30V (2P) 12 12 L2 R6 MF1 THHS R7 BOX BODY X06 Control circuit board (MAIN board) L1 L2 L3 63H High pressure switch CN38 (3P) 1 2 3 CNPOW (5P) X10 1 23 4 5 F03 250VAC 6.3A F F02 250VAC 6.3A F F01 250VAC 6.3A F detection circuit 6 5 CNFC1 4 (6P) 3 2 1 Refer to the service handbook about the switch operations. 6 5 4 CNFC2 3 (6P) 2 1 FB3 1 CNFAN 23 (5P) 4 1 2 3 4 5 CN04 FB4 12 1234 CN03 (3P) CN02 (8P) CN01 CNH (2P) (3P) 123 12345678 12 TH6 TH5 TH8 TH7 TH2 TH1 TH10 TH9 LD 1 2 3 Black White Red Black White Red 12 CNL (3P) CNLV1 (5P) CNLV2 (5P) 1 2 3 12345 1234 5 SLEV LEV1 Fan control board (Fancon board) Fan motor (Heat exchanger) N Black White Red CN09 CN06 CN05 (4P) (2P) (2P) U V W MF N 3 2 1 3 2 1 63HS 63LS Name Symbol DC reactor (Power factor improvement) DCL ACCT-U,W Current Sensor ZNR4 Varistor 52C MF1 SV1,SV2 SV3 Magnetic contactor (Inverter main circuit) Fan motor (Radiator panel) Solenoid valve (Discharge--suction bypass) Solenoid valve (Heat exchanger capacity control) Symbol LEV1 Name Electronic expansion valve (Sub-cool coil bypass) Symbol TH2 TH5 TH6 SLEV Electronic expansion valve(Oil return) 63HS 63LS L2 IPM TH1 High pressure sensor Low pressure sensor Choke coil(Transmission) Intelligent power module Thermistor Discharge pipe temp. detect 12 TH7 TH8 TH9 Name Thermistor Saturation evapo. temp. detect Pipe temp. detect OA temp. detect liquid outlet temp. detect at Sub--cool coil bypass outlet temp. detect at Sub--cool coil High pressure liquid. temp. Symbol TH10 THHS X1~10 Name Compressor shell temp. Radiator panel temp. detect Aux. relay FB1~4 Ferrite core Earth terminal 13 LEV TH23 TH22 TH21 TH24 6 5 4 3 2 1 EF 0 12 Address (odd) SWA SWC SW14 CN82 89A 8 7 6 5 4 3 2 1 345 67 B CD 9 0 1 X11 SW4 SW3 SW2 CN24 CN25 12 9 0 1 Z3 21 SW12 SW11 (2st digit) (1st digit) 21 21 21 21 33P2 33P1 3 21 CN23 CN22 CN20 CN21 CN29 CN31 CN81 CN42 SW1 CN62 A.B 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 2 3 4 5 6 7 8 12 2 3 4 5 6 7 8 CN3T 65 4 321 3 CN60 ZNR 1 13 T 13 CNT CND F X01 13 13 Z1 1 35 7 FAN2 CN32 CN2M CN3A I.B MF 1 3 5 (CN54) CN70 X06 X05 X04 CN52 1 2345 CNP CNV X03 CN51 12345 51F 1 2 3 1 2 3 2 1 Z3 ZNR2 F1 (250V 5A F) 52F FAN over current detection 52F Z1 51F Inside the control box F4(250V 1A F) 1 2 3 4 5 1 2 3 4 5 IFB CN54 CN53 DSA1 ZNR1 L PE SW8 Switch(normal/local) Power supply (No fuse breaker 20A) 3N~ 380/400/415V(50Hz) 400/415V(60Hz) TB22 C 1 2 3 4 5 Name Fan motor Indoor controller board Address board Surge absorber board External input/output board Power source terminal bed Transmission terminal bed Transmission terminal bed Terminal bed for distant location on/off TB22 Terminal bed for distant location display TB23 Terminal bed for distant location on/off F Fuse<6A> F1 Fuse<5A> ZNR,ZNR1,ZNR2 Varistor T Transformer LEV Electronic linear expan.valve 52F Contactor(fan I/D) 51F Over current relay (fan I/D) 33P1,33P2 Float switch TH21 Thermistor (inlet temp. detection) TH22 Thermistor (piping temp. detection/liquid) TH23 Thermistor (piping temp. detection/gas) TH24 Thermistor (outlet temp. detection) Switch (for mode selection) SW1(A.B) Switch (for capacity code) SW2(I.B) Switch (for mode selection) SW3(I.B) Switch (for model selection) SW4(I.B) SW8 Switch (normal/local) SW11(A.B) Switch (1st digit address set) SW12(A.B) Switch (2nd digit address set) SW14(A.B) Switch (connection No.set) SWC Switch (outlet/inlet temp.control) X11 Auxiliary relay(check) Z1 Auxiliary relay(fan) Z3 Auxiliary relay(fan failure detection) L1 LED display (failure) L2 LED display (status) L3 LED display (check) L4 LED display (power supply) RC MA Remote controller F4 Fuse<1A> Symbol MF I.B A.B S.B IFB TB2 TB5 TB15 TB21 Note: 1. The dotted lines show field wiring. 2. Always use odd numbers for the indoor unit address. 3. Connect the transmission line from indoor unit to outdoor unit whose address equals he address of the connected indoor unit + 50. 4. Conventions: ,terminal bed; , connector; , board-insertion connector or fastening connector of control board. Power supply Status output Failure output Distant location on/off L TB2 LED display(power supply) LED display(check) LED display(status) LED display(failure) BC TB21 B1 B2 L1 L2 L3 N L4 L3 L2 L1 Power supply DC12 ~ 24V Distant location on/off 3 1 2 3 2 1 2 1 6 5 Indoor unit Control wiring DC24 to 30V RC AC TB23 A1 A2 2 CN1 1 1 S.B X11 B1 A1 SHIELD TB5 S TB15 1 2 PFD-P250VM-A LEV2 6 5 4 3 2 1 EF SW1 0 12 CN81 CN42 9 0 1 CN62 SWA SWC SW14 CN82 345 TH23-2 8 7 6 5 4 3 2 1 A.B2 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 9 0 1 CN25 CN24 9 0 1 SW12 SW11 (2st digit) (1st digit) 33P2-1 33P1-1 Address (even) Z3 21 21 21 21 21 33P2-2 33P1-2 3 21 CN23 CN22 CN20 CN21 CN29 CN31 SW4 SW3 SW2 12 Address (odd) Z3 21 3 21 2 1 21 21 21 CN22 CN20 CN21 CN29 CN31 CN23 12 X12 SW12 SW11 (2st digit) (1st digit) 2 3 TH22-2 6 5 4 3 2 1 SWA SWC SW14 9 0 1 CN62 CN81 CN25 CN24 SW4 SW3 SW2 12 12 2 3 TH21-2 TH24-2 LEV1 TH23-1 TH22-1 TH21-1 0 12 89A TH24-1 EF SW1 B CD CN82 67 8 7 6 5 4 3 2 1 A.B1 1 2 3 4 5 6 7 8 89A 14 4 5 6 67 345 7 8 1 2 3 4 5 6 7 8 4 5 6 7 8 CN42 2 3 4 5 6 1 2 3 4 2 3 B CD 4 5 6 7 8 X11 654321 3 CN60 654321 3 CN60 1 T CN3T T 1 CN3T ZNR 13 13 13 CNP X03 X01 X03 13 CNP CN51 12345 ZNR 13 CNT CND F 13 CNT CND F X01 CN51 12345 Z2 MF 1 35 7 CN70 X06 X05 X04 CN52 CNV 13 CN70 1 35 7 Z1 12345 13 CNV X06 X05 X04 CN52 1 2345 1 2 3 1 2 3 2 1 Z3 5A F) F1 ZNR2 (250V 51F 51F 1 2 3 1 2 3 2 1 52F 1 3 5 (CN54) FAN2 CN32 CN2M CN3A I.B2 FAN over current detection 52F Z1 Z2 1 3 5 (CN54) FAN2 CN32 CN2M CN3A I.B1 Inside the control box F4 (250V 1A F) DSA1 ZNR1 1 2 3 4 5 1 2 3 4 5 X11 X12 L1 L2 L3 N IFB B2 A2 SHIELD S AC TB23 A1 A2 CN53 BC TB21 B1 B2 C 1 CN54 TB22 2 3 4 5 S.B CN1 1 1 2 3 B1 A1 SHIELD S 3 4 1 2 3 2 1 2 1 6 5 TB15 2 1 L L L2 TB5-2 L L PE TB2 L5 L4 L3 L1 TB5-1 PE L1 L2 L3 L4 L5 RC Auxiliary relay(check) Auxiliary relay(fan) Auxiliary relay(fan failure detection) Lamp display (No1.failure) Lamp display (No2.failure) Lamp display (status) Lamp display (check) Lamp display (power supply) MA Remote controller Fuse<6A> Fuse<5A> Fuse<1A> Varistor Transformer Electronic linear expan.valve Contactor(fan I/D) Over current relay (fan I/D) Float switch Thermistor (inlet temp. detection) Thermistor (piping temp. detection/liquid) Thermistor (piping temp. detection/gas) Thermistor (outlet temp. detection) Switch (for mode selection) Switch (for capacity code) Switch (for mode selection) Switch (for model selection) Switch (normal/local) Switch (1st digit address set) Switch (2nd digit address set) Switch (connection No.set) Switch (outlet/inlet temp.control) F F1 F4 ZNR,ZNR1,ZNR2 T LEV1,2 52F 51F 33P1-1,-2, 33P2-1,-2 TH21-1,TH21-2 TH22-1,TH22-2 TH23-1,TH23-2 TH24-1,TH24-2 SW1(A.B) SW2(I.B) SW3(I.B) SW4(I.B) SW8 SW11(A.B) SW12(A.B) SW14(A.B) SWC X11~X12 Z1~Z2 Z3 TB22 TB23 Terminal bed for distant location on/off Terminal bed for distant location display Terminal bed for distant location on/off TB21 Name Fan motor Indoor controller board Address board Surge absorber board External input/output board Power source terminal bed Transmission terminal bed Transmission terminal bed Symbol MF I.B1,I.B2 A.B1,A.B2 S.B IFB TB2 TB5-1,-2 TB15 Note: 1. The dotted lines show field wiring. 2. Always use odd numbers for the indoor unit address. 3. Connect the transmission line from indoor unit to outdoor unit whose address equals he address of the connected indoor unit + 50. 4. Conventions: ,terminal bed; , connector; , board-insertion connector or fastening connector of control board. Lamp display (No2.failure) No2.Indoor unit Control wiring DC24 to 30V Power supply DC12 ~ 24V Distant location on/off Distant location on/off Power supply DC30V,AC100/200V No1.Status output No1.Failure output No2.Status output No2.Failure output Switch(normal/local) SW8 Power supply (No fuse breaker 30A) 3N~ 380/400/415V(50Hz) 400/415V(60Hz) Lamp display (power supply) Lamp display (check) Lamp display (No1.failure) Lamp display (status) No1.Indoor unit Control wiring DC24 to 30V RC PFD-P500VM-A 6. Options Description Square duct flange (Standard filter)✻1 Square duct flange (High-efficiency filter) High-efficiency filter 65% ✻2 High-efficiency filter 90% ✻2 Model Applicable capacity PAC-TS75DFB P250 PAC-TS76DFB P500 PAC-TS70TB P250 PAC-TS72TB P500 PAC-TS60AF P250 PAC-TS62AF P500 PAC-TS65AF P250 PAC-TS67AF P500 ✻1 Used to connect Intake Duct . Use the filter supplied with the unit. ✻2 Requires square duct flange (High-Efficiency Filter). 15 TH6 HEX1 16 TH5 CV2 HEX2 SV3 SCC CP3 63H CV1 ST5 ST3 SV2 SV1 CP LEV1 TH8 TH2 Drier TH9 TH10 Comp TH1 O/S 63HS CJ1 ST4 TH7 MA SLEV 63LS CJ2 SA Indoor units BV1 ST2 BV2 ST1 7. Refrigerant Circuit Diagram And Thermal Sensor PUD-P250YMF-C 8. System Design 8-1.Piping Outdoor Unit A A Sample Unit Connection L H L Indoor Maximum Pipe Length (L) Net length: under 120m, Total Length: under 150m Maximum Height Difference Between Indoor and outdoor units (H) Under 50m (Under 40m if the outdoor unit is installed below the indoor unit. Under 15m if the outdoor temperature is under 10˚C.) ■ Selecting Refrigerant Pipes Gas pipe: Liquid pipe: ■ Adding the Refrigerant The outdoor unit is shipped with 8.5 kg of refrigerant. It does not include enough refrigerant for extra piping system. Use additional refrigerant for each refrigerant piping system (2 refrigerant circuits). Record the length of the pipe and the amount of the added refrigerant on the outdoor unit for services in the future. ■ Calculating the amount of refrigerant to be added ø 28.58 ✕ 2 ø 12.7 ✕ 2 Size of the liquid pipe Total length of the pipe with a diameter of ø 12.7 ✕ 0.12 + 2.0kg (m) ✕ 0.12 (kg/m) (i.e.) When using a 120m pipe with a diameter of ø 12.7 120m ✕ 0.12kg/m + 2.0kg = 16.4 kg · The amount of refrigerant needed for additional piping depends on the diameter and the length of the added liquid pipes. · Calculate the amount to be added as shown on the right, and add the refrigerant in that amount. · Round up the figure under 0.1kg. (e.g. 11.06kg would be 11.1kg). Caution Charge Liquid Refrigerant Filling the equipment with gas refrigerant will result in a power loss due to transformation of refrigerant in the tank. 17 8-2.Control Wiring (1) Specifications of control wiring and maximum length of wiring Transmission line is a type of control line. When the source of noise is located adjacent to the unit, the use of shield cable as well as moving the unit as far away from the noise source are recommended. 1 Transmission line (M-NET transmission line) System component For multiple-refrigerant system Length of transmission line n/a Facility type (noise level measurement) All types of facilities Cable type Shield cable CVVS · CPEVS No. of cable 2-core cable Diameter Over 1.25mm2 Wiring specifications Maximum length: 200m Maximum length of centralized control transmission line and Indoor/Outdoor transmission line via indoor/outdoor units: 500m maximum Total length of indoor/outdoor transmission line 2 Remote control wiring MA remote controller ✻ 1 Cable type VCTF · VCTFK · CVV · CVS · VVR · VVF · VCT No. of cable 2-core cable Diameter 0.3~1.25mm2 (0.75~1.25mm2) Wiring specifications Total Length ✻2 ✻3 Maximum length: 200 m ✻ 1: “MA remote controller” includes MA remote controller, Simple MA controller, and wireless remote controller. ✻ 2: Cables with a diameter of 0.75mm2 or smaller recommended for easier handling. ✻ 3: When connecting to simple remote controller terminal, use a cable with a diameter within the range shown in the parenthesis. 8-3.Types of switch settings and setting methods Whether a particular system requires switch settings depends on its components. Refer to the section “7-4 Wiring and Address Setting” before conducting electrical work. Keep the power turned off while setting the switches. If settings are changed while being powered, the changed settings will not register, and the unit may malfunction. Unit Symbol Outdoor unit Indoor unit Main/sub controllers ✻ 10HP has only the main controller 18 ✻ Turn off the power to OC Outdoor unit IC Indoor and outdoor units (1) Address setting This system requires address setting. The range of address varies depending on the type of unit. Refer to “7-4 Wiring and Address Setting” for details. Unit Indoor unit Symbol Address setting range Setting method Factory setting IC 01~50 ✻2 Assign a number to all indoor units, starting with 1 and using sequential numbers. Use odd numbers for the top controller and even numbers for the bottom controller of the indoor units. Use odd numbers starting with 01 for 10HP system. 00 OC 51~100 ✻2 ✻3 Add 50 to the address assigned to the indoor unit to which the outdoor or heat-source unit is connected. 00 Main/sub controllers ✻1 Outdoor Unit ✻ 1: 10HP only has the main controller. ✻ 2: Avoid using the same address as the ones used by the indoor/outdoor units in another refrigerant system; choose a different one in the range specified above. ✻ 3: When setting the address to 100, set the switch to 50. (2) Setting the outdoor unit power-source switch connector (Factory setting: CN41 Connected) System component Multiple-refrigerant system Power supply switch unit Replace the power source switch connector CN41 with CN40 on only one of the outdoor units Use CN41 as it is. (3) Choosing the temperature detection spot by indoor unit (Factory Setting: SWC “Standard”) When using the suction temperature sensor, set SWC to “Option.” (4) Setting the MA “Sub” controller When using two remote controllers or running two indoor units as a group, one of the controllers must be set to “Sub” controller. ✻ No more than two remote controllers can be connected to a group. (Factory setting: “Main”) Set the controller according to the following procedure. Refer also to the instructions manual supplied with the MA remote controller. Remove the cover on the remote controller Screwdriver Insert a flat-head screwdriver in the groove shown in the picture, and move the screwdriver in the direction shown in the arrow. ON Set Dip Switch No.1 on the remote controller to “OFF” (Main to Sub) 1 2 3 4 Dip switches 19 Remote controller body 8-4.Wiring and Address Setting (1) System Using MA Remote Controller 1 System with one indoor unit (10HP system) Control Wiring Diagram L1 Use CN41 as is. IC OC 51 TB7 A B S TB3 A BE 01 ✻There is one indoor controller board inside indoor unit. TB5-1 ABS TB15 1 2 A1 B2 MA Remarks Maximum Allowable Length Maximum Length (above 1.25mm2) L1 200m 1. Use power supply connector (CN41) on the outdoor unit as is. 2. It is not necessary to ground the S terminal of centralized control transmission terminal board (TB7) on the outdoor unit. 20 Wiring and Address Setting Connect A, B terminals of indoor/outdoor transmission line terminal board (TB3) on the outdoor unit and A, B terminals of the Indoor/outdoor transmission terminal board (TB5). (Non-polar 2 wire) ✻ Only use shield line. [Grounding the shield line] Connect the earth terminal of the OC and S terminal of the IC terminal board (TB5). Steps Set the address as follows. Address Setting Range Unit or Controller Setting Procedures IC 01 ~ 50 Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). OC 51 ~ 100 Add 50 to the address assigned to the indoor unit within the same refrigerant system. Main Controller MA n/a Sub Controller MA Sub controller 1 Indoor Unit 2 Outdoor Unit 3 MA remote controller Main Unit Remarks Factory Setting 00 00 Main Use dipswitch to set the controller as sub controller. 21 (1) System Using MA Remote Controller 2 Unit with One Indoor Unit (20HP Systems) Control Wiring Diagram L1 Replace CN41 with CN40. IC OC 51 TB7 A B S ✻There are 2 indoor controller boards inside indoor unit. 01 TB3 A BE TB5-1 ABS Conect TB15 1 2 L31 A1 B2 MA Use CN41 as is. NO OC 52 TB7 A B S 02 TB5-2 ABS TB3 A BE NO L2 Remarks Maximum Allowable Length Maximum Length (above 1.25mm2) L1, L2 200m Maximum length via outdoor unit (over 1.25mm2) L1 + L3 + L2 500m 1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal). 22 Wiring and Address Setting Connect A, B terminals of indoor/outdoor transmission line terminal board (TB3) on the outdoor unit and A, B terminals of the Indoor/outdoor transmission terminal board (TB5). (Non-polar 2 wire) ✻Only use shield line. [Grounding the shield line] Connect the earth terminal of the OC and S terminal of the IC terminal board (TB5). Connect A terminals of centralized control transmission line terminal board on each of the outdoor units with each other. Do the same with B terminals. Replace CN41 (power supply switch connector) with CN40 on only one OC. ✻Only use shield line. [Grounding the shield line] Connect S terminals of the TB7 of each of the outdoor units with each other. Connect the S terminal of TB7 on the outdoor unit whose CN41 was replaced with CN40 to the earth terminal of the electric box. Steps Set the address as follows. Main Unit 1 Address Setting Range Unit or Controller IC 01 ~ 49 Indoor Unit Setting Procedures Remarks Factory Setting Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). 00 Sub Unit IC 02 ~ 50 OC 51 ~ 100 Main Controller MA n/a Sub Controller MA Sub controller 2 Outdoor Unit 3 MA remote controller Add 1 to the address assigned to the main unit in the same room. Add 50 to the address assigned to the indoor unit within the same refrigerant system. 00 Main Use dipswitch to set the controller as sub controller. 23 (1) System Using MA Remote Controller 3 When connecting 2 MA remote controller to one indoor unit (20HP Systems) Control Wiring Diagram L1 Replace CN41 with CN40 IC OC 51 TB7 A B S TB3 A BE TB5-1 ABS Connect TB15 1 2 m1 L31 m2 A1 B2 MA(Sub) Use CN41 as is A1 B2 MA(Main) OC 52 TB7 A B S ✻There are 2 indoor controller boards inside indoor unit. 01 A1 B2 MA 02 TB5-2 ABS TB3 A BE NO NO NO L2 Remarks Maximum Allowable Length Same as (2). Same as (2). Maximum allowable length (0.3 ~ 1.25mm2) m1 + m2 200m 1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal). 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers. 24 Wiring and Address Setting Same as (2). Same as (2). [When using 2 remote controllers] When using two remote controllers, connect terminals 1 and 2 of TB15 on the indoor unit to terminal board of MA controller(option). ✻ Set the connected MA remote controller (option) as sub controller (Refer to manual that came with MA remote controller.) Steps Set the address as follows. Main Unit 1 Address Setting Range Unit or Controller IC 01 ~ 49 Indoor Unit Setting Procedures Remarks Factory Setting Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). 00 Sub Unit IC 02 ~ 50 OC 51 ~ 100 Main Controller MA n/a Sub Controller MA Sub controller 2 Outdoor Unit 3 MA remote controller Add 1 to the address assigned to the main unit in the same room. Add 50 to the address assigned to the indoor unit within the same refrigerant system. 00 Main Use dipswitch to set the controller as sub controller. 25 (1) System Using MA Remote Controller 4 When grouping 2 indoor units (20HP systems) with MA remote controller Control Wiring Diagram ✻There are two indoor controller board inside each indoor unit. L1 L1 Replace CN41 with CN40. Replace CN41 with CN40. IC OC 51 TB7 A B S 53 01 TB3 A BE TB5-1 ABS Connect TB7 A B S TB5-1 ABS Connect TB15 1 2 TB15 1 2 m2 Use CN41 as is. A1 B2 MA(Sub) L31 L31 A1 B2 MA(Main) Use CN41 as is. OC OC 52 54 02 TB5-2 ABS TB3 A BE NO 03 TB3 A BE m1 TB7 A B S IC OC TB7 A B S TB5-2 ABS TB3 A BE NO L2 04 L2 m3 Remarks Maximum Allowable Length Same as (2). Same as (2). Maximum allowable length (0.3 ~ 1.25mm2) m1 + m2 + m3 200m 1. Use sequential numbers to set indoor unit address. 2. Do not connect TB5s' of the indoor units that are connected to different outdoor units with each other. 3. Replace CN41 with CN40 on only one outdoor unit. 4. Ground only one of the outdoor units' S terminal of TB7 (centralized control transmission terminal). 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers. 26 Wiring and Address Setting Same as (2). Same as (2). ✻ When grouping units that use different refrigerants, set MA remote controller of one of the indoor units as sub controller. [When grouping indoor units] When grouping indoor units, connect 1 and 2 terminals of both IC terminal boards (TB15) with each other (nonpolar 2 line). ✻ Set MA remote controller of one of the indoor units as sub controller. Steps Set the address as follows. Main Unit 1 Address Setting Range Unit or Controller IC 01 ~ 49 Indoor Unit Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). IC 02 ~ 50 Add 1 to the address assigned to the main unit in the same room. OC 51 ~ 100 Add 50 to the address assigned to the indoor unit within the same refrigerant system. Main Controller MA n/a Sub Controller MA Sub controller Sub Unit 2 Outdoor Unit 3 MA remote controller Remarks Factory Setting 00 00 Main Use dipswitch to set the controller as sub controller. 27 (1) System Using MA Remote Controller 5 When grouping multiple indoor units (combination of 10HP, 20HP systems) Control Wiring Diagram ✻There is one indoor controller board inside indoor unit. L1 Use CN41 as is IC OC 51 ✻There are two indoor controller boards inside indoor unit. IC 53 01 TB7 TB3 ABS ABE L1 Replace CN41 with CN40. OC 03 TB5-1 ABS TB7 TB3 ABS ABE TB5-1 ABS TB15 1 2 Connect TB15 1 2 m1 A1 B2 MA(Main) L31 m2 A1 B2 MA(Sub) Use CN41 as is. OC 54 04 TB5-2 ABS TB7 TB3 ABS ABE NO L2 m3 Remarks Maximum Allowable Length Same as (2). Same as (2). Total Length (0.3 ~ 1.25mm2) m1 + m2 + m3 + m4 + m5 200m 1. Use odd numbers to set 10HP indoor unit address. 2. When setting unit address for 20HP indoor unit, use odd numbers for the top controllers and even numbers for the bottom controllers (main controller+1). 3. Replace CN41 (power supply switch connector) with CN40 on only one 20HP outdoor unit. 4. Ground the S terminal of TB7 (centralized control transmission terminal board) of only one of the 20HP outdoor units. 5. No more than two main and sub controllers can be connected to the indoor unit in the same group. Disconnect the MA remote control wire from TB15 if using more than 2 remote controllers 28 Control Wiring Diagram ✻There is one indoor controller board inside indoor unit. ✻There are two indoor controller board inside indoor unit. L1 Use CN41 as is Replace CN41 with CN40. IC OC 55 IC OC 57 05 TB7 TB3 ABS ABE L1 07 TB5-1 ABS TB7 TB3 ABS ABE TB5-1 ABS TB15 1 2 Connect TB15 1 2 NO NO L31 A1B2 MA A1B2 MA Use CN41 as is. OC 58 08 TB5-2 ABS TB7 TB3 ABS ABE NO Steps m4 1 m5 Address Setting Range Unit or Controller Indoor Unit L2 Main Unit (10HP, 20HP) Sub Unit (20HP) IC 01 ~ 49 Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). IC 02 ~ 50 Add 1 to the address assigned to the main unit in the same room. OC 51 ~ 100 Add 50 to the address assigned to the indoor unit within the same refrigerant system. Main Controller MA n/a Sub Controller MA Sub controller 2 Outdoor Unit 3 MA remote controller Remarks Factory Setting 00 00 Main Use dipswitch to set the controller as sub controller. 29 (2) System with MA remote controller and G-50A 1 System with multiple indoor units (10HP, 20HP) Control Wiring Diagram L31 ✻There is one indoor controller board inside indoor unit. ✻There are two indoor controller boards inside indoor unit. L1 Use CN41 as is. IC OC 51 TB7 A B S 53 TB5-1 ABS TB7 A B S TB3 A BE TB5-1 ABS TB15 1 2 m1 L35 L32 m1 A B S 03 NO TB15 1 2 Power Supply IC OC 01 TB3 A BE L2 Use CN41 as is. A1 B2 MA Use CN41 as is. A1 B2 MA OC L33 54 G-50A A B S TB7 A B S DC power supply line (DC12V) 04 TB5-2 ABS TB3 A BE Option NO L3 L36 Remarks Maximum Allowable Length 1. Be sure to use odd numbers to set the address for indoor units (10HP). 2. To set the indoor unit address for 20HP, use odd numbers for the top controllers and use even numbers for the bottom controllers (Main controller plus 1). 3. Use the power supply switch connector (CN41) on the outdoor unit as is. 4. It is not necessary to ground the S terminal of transmission line terminal board for centralized controller on the outdoor unit. 5 No more than two main/sub remote controllers can be connected to the indoor unit in the same group. When more than two remote controllers are present in the system, disconnect MA remote controller from TB15 in the indoor unit. 6. Put both types of the addresses for P500-type indoor units in the same group when setting groups for indoor units with a remote controller. L1, L2, L3, L4, L5, L6 200m L31 + L32 + L33 + L35 + L36 + L37 + L38 + L6 500m L1 + L31 + L35 + L36 + L37 + L38 + L6 500m Total Length (0.3 ~ 1.25mm2) m1 200m 30 Control Wiring Diagram L37 ✻There is one indoor controller board inside indoor unit. L4 Use CN41 as is. L5 Use CN41 as is. IC OC 55 TB7 A B S ✻There are two indoor controller boards inside indoor unit. 57 05 TB3 A BE IC OC TB5-1 ABS TB7 A B S 07 TB3 A BE TB5-1 ABS NO TB15 1 2 m1 TB15 1 2 L38 m1 A1 B2 MA Use CN41 as is. A1 B2 MA OC 58 TB7 A B S 08 Steps NO 1 Address Setting Range Unit or Controller Indoor Unit Main Unit (10HP, 20HP) Sub Unit (20HP) IC 01 ~ 49 Setting Procedures Set the address for the controller at the top of the indoor unit. Start with "01" then use sequential odd numbers (i.e.01, 03, 05). IC 02 ~ 50 Add 1 to the address assigned to the main unit in the same room. OC 51 ~ 100 Add 50 to the address assigned to the indoor unit within the same refrigerant system. Main Controller MA n/a Sub Controller MA Sub controller 2 Outdoor Unit 3 MA remote controller TB5-2 ABS TB3 A BE L6 Remarks Factory Setting 00 00 Main Use dipswitch to set the controller as sub controller. 31 8-5.External input/output specifications (1) Input/output specifications Input Output Function Usage Signals Start/stop Turning ON/OFF the indoor unit Usage Function Signal No. 2 Operation Status ✻ Obtaining signals indicating Relay a-contact operation status of indoor units output in each refrigerant circuit. DC 30V or AC 100V/200V Obtaining signals indicating error status of indoor units in Standard Current : each refrigerant circuit. 1A Obtaining signals indicating Minimum Current : operation status of indoor units 1mA in each refrigerant circuit. over 200ms No. 2 Error Status ✻ Obtaining signals indicating error status of indoor units in each refrigerant circuit. ✻1 Use minute-current contact (DC12V 1mA) ✻ 20HP only Pulse (a-contact with voltage/without voltage) ✻1 No.1 Operation Status Power Source: DC12~24V Electrical Current: Approximately 10mA (DC12V) No. 1 Error Status (2) Wiring External input/output board Input with voltage (polarized) TB23 AC External power source SW12 Stop/Start A1 Short Circuit Input without voltage CN53 1 TB21 BC Common SW11 Stop/Start A2 Short Circuit Relay Contact Point Output B1 2 B2 3 XA TB22 COM Power Source for Display No.1 Operation Status L1 No.1 Error Status L2 ✻ No.2 Operation Status L3 ✻ No.2 Error Status L4 XA 1 XB XC 3 XD 4 XE 5 5 CN54 1 XB 2 4 XC XD XE 2 3 4 5 ✻ 20HP only Connection to terminal board Connection with connectors Maximum : 100 m External powe source DC12~24V Electrical current input (per contact) Approximately 10mA (DC12V) SW11 Remote start/stop ✻ Each pressing pf the SW (Pulse input) switches between ON and OFF. Remote start/stop switch Each pressing of the SW (Pulse input) switches between ON and OFF. Minute-current contact: DC12V 1mA SW12 Power supply for displays DC30V 1A AC220-240V 1A L1 No.1 Operation Status Indicator Lamp L2 No.1 Error Status Indicator Lamp L3 No.2 Operation Status Indicator Lamp L4 No.2 Error Status Indicator Lamp XA~XE Relay (Permissible Electrical Current: 10mA~1A) ● Setting on the Indoor Unit Confirm the following setting when using external input. 1 No.1, No.2 Controller board Dip SW 3-8: ON (Factory Setting: ON; External input will not be available when OFF.) 2 No.1, No.2 address board Dip SW 1-10: OFF (Factory Setting: OFF; External input will not be available when ON.) 3 Normal/Local switch inside the unit controller box is set to “Normal.” (Factory Setting: Normal; External input will not be available when it is set to “Local.”) 32 (3) Wiring Method 1 Check the indoor unit setting (Refer to 7-5.(2) Wiring ) 2 When using the external output function, connect each signal line to External output Terminal (TB22) on the unit, depending on the usage. 3 When using external input function, peal the outer layer of the signal line off, and connect it to external input terminal (TB21 or TB23) on the unit, depending on the usage. Wiring On Site TB23 ✻1 AC A1 A2 ✻1 CN53 TB21 BC B1 B2 Fix the wire on the lowvoltage (below DC30V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻2 To CN51 of No.1 board Wiring inside the unit CN54 TB22 COM 1 To CN51 of No.2 board 2 3 4 5 Fix the wire on the highvoltage (AC220-240V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻3 ✻1 20HP indoor unit is shipped with B1 and B2 terminals of TB21 and A1 and A2 terminals of TB23 short-circuited respectively. When connecting wire to those terminals, do not eliminate this feature. If it is eliminated, the units in one of the 2 refrigerant circuits may not operate. ✻2 Do not bundle with high-voltage (AC220-240V) wire, since noise interference from such wire may cause the unit to malfunction. ✻3 Do not bundle with minute-voltage (DC30V or below) wire, since noise interference from such wire may cause the unit to malfunction. Caution 1) Wiring should be covered by insulation tube with supplementary insulation. 2) Use relays or switches with IEC or equivalent standard. 3) The electric strength between accessible parts and control circuit should have 2750V or more. 4) TB21 is a terminal specifically for No-voltage contact point input. Do not apply voltage to TB21, since it must result in malfunction of indoor unit controller board. 5) TB23 is specifically for contact point input with voltage. Check the polarity before connecting to avoid damage to the unit. 6) Keep the wires on the input side and on the output side away from each other when using AC220240V as a power source for displays. 7) Keep the length of the extension part of external signal line under 100m. 8) 20HP is shipped with B1 and B2 terminals of TB21 and A1 and A2 terminals of TB23 short-circuited respectively. Do not eliminate this feature. If it is eliminated, the units in one of the two refrigerant circuits may not operate. 33 9. Air Conditioning the Computer Room 9-1 Main Features of the Floor-Duct Air Conditioners This system is installed by building a floor over an existing floor and using the space between these two floors as an air-conditioning duct. This system has the following characteristics: 1 The temperature and humidity can efficiently and reliably be controlled, since the air-conditioned air is sent directly to the machine. 2 It provides a comfortable environment for the operator, since the air can be conditioned to best suit the needs of the operator and machines. 3 It is favorable in terms of appearance because the air-conditioning duct is out of sight. 4 The location of the duct is irrelevant when considering adding new machines or rearranging the existing machines, since the entire floor serves as the air duct. Ceiling Free-access top floor Computer Filter Caution (1) Unlike plenum ventilation and overhead-duct type conditioners, since the conditioned air is not mixed with the air in the room, the air that comes out of the unit has to meet the predetermined conditions (constant temperature/constant humidity) at the time the air exits the unit. Close attention must be paid to the auto-controlling system. (2) Dust in the duct space (between the free-access top floor and the existing floor) must be thoroughly removed before installing the unit. (3) Since the existing floor is cooled by the unit, it may produce dews on the ceiling of the room down below. 9-2 Major Characteristics of Computer Room Air Conditioners (Constant Temperature · Constant Humidity) A computer-room air conditioner is a device that is used to maintain certain temperature and humidity in the room. Especially, floor-duct conditioners must be able to provide air that meets predetermined requirements. In this unit, the compressor works year around. To respond to the change in temperature, the capacity control compressor regulates the temperature. Since this unit does not ship with a humidifier, humidity is controlled with the use of a humidifier installed in the room. 34 9-3 Step-by-Step Plan for the Implementation of the Air-Conditioning Purpose Making decisions on the computer system Basic Conditions Accommodates possible future expansion (ensuring the acquisition route) Operation schedule Back-up system (in case of breakdowns, power outage, water-supply cut offs etc.) Air conditioning methods (continuous, floor-duct type etc.) Securing Necessary Rooms Computer room, CVCF room, MT Disk Storage room Supplementary computer room, system surveillance room Programmer room, operator room Battery room, transformer room Decision to Install the Air-Conditioning System Setting the Conditions for the Room Temperature/humidity Condition Calculating the Load Selecting the AirConditioner Model Selecting the Controllers Total System Air-conditioning operation panel (secure individual operation circuit), Auto Controller (temperature and humidity indicator/recorder), management, safety, laws, maintenance, earthquake proof, anti-vibration (floor load, anti-vibration device), noise control, etc. 35 9-4 Conditions for the Installation of Computer-Room Air Conditioners (1) Outdoor Temperature and Humidity Generally the values set for general air conditioners are used, although the value higher than the maximum outdoor temperature and humidity may be set for devices like computer-room air conditioners that must keep the air temperature and humidity under predetermined levels. (2) Indoor Temperature and Humidity There is a wide range of conditions set by different computer manufacturers, and the conditions need to be set in consultation with the manufacturers. The most basic conditions include keeping dew condensation and static electricity from forming. It is also necessary to keep the room free of dust to ensure a smooth operation of the computer. (3) Matching the Volume of Air Flow It is possible to use the fan on the computer to cool the room. This controlling method requires a certain volume of cold air in proportion to the amount of heat produced by the device. The inlet panel is located at the bottom of the unit, and the exhaust pipe is located either on the ceiling, front and back, or on the side. Air intake Air conditioner Computer Fan Free-access floor Air discharge (4) Considering a Back-up Air Conditioning System When the system is not allowed to stop at all, a back-up system is necessary. There are several different options for a back-up as the following: 1 Installing two sets of air conditioning systems necessary for the computer. 2 Utilizing regular office air conditioners (for people) 3 Using one of the units as a back-up 1 is used infrequently due to high costs involved. 2 involves many technical problems such as the difference between preset conditions for computer rooms and office rooms. In general, 3 is a preferred method. If 3 is chosen, the unit method (package method) is more economical than the central method. 36 9-5 Setting the Air conditioners (1) Air-Conditioning Load 1 Once the floor plan is made and the conditions for the air-conditioning system are set, air conditioning capacity has to be determined by calculating the load. 2 Unlike the outdoor air, computer load remains constant throughout the year. However, it is possible that there are considerable fluctuations within a day. This is due to the fact that, depending on the time of the day, there are changes in the number of computers that are turned on and that the different computer systems are in operation. 3 If there is a plan to expand the current computer system in the future, it is important to include the load for the units to be added in the future when calculating the thermal load because it is practically impossible to keep the computers off for days on end during the installation of the new units. 4 The following items need to be checked before calculating the unit capacity: · Floor area of the computer room (m2) · Total quantity of heat generated by computers (2) Sample Selection of Air Conditioners (2-1) Conditions 20.9kW Computer-generated heat 5 Number of workers 20W/m2 Lighting Indoor ˚CDB/Indoor WBT : 24˚C/17˚C ˚CDB of the air going into the computer : 18˚C Temperature and humidity 60Hz Frequency (2-2) Building Conditions (W: 4.5m, H: 1.5m) ✕ 2 Windows Inside Measurement Surroundings Ceiling height 2.2m Upstairs room, downstairs room, heat and air conditioning 1 Coefficient of Overall Heat Transmission U (W/m2 ·K) Outer Walls Inner Walls Summer 3.6, Winter 3.8 2.05 Downward convection 3.36, upward convection 3.3 Ceiling Floor (free access) Downward convection 3.05, upward convection 4.56 Floor Downward convection 2.42, upward convection 3.3 Windows Summer 5.93, Winter 6.5 Window 2 Internal Load Number of People in the Room 5 Lighting 20W/m2 Calculator 20.9kW Draft 0.2 times/h 3 Volume of Outdoor Air Intake 25m3/h·person 37 (2-3) Calculating the Load and Selecting a Model Calculate the temperature difference by setting the outdoor temperature; then, calculate hourly loads. The chart shows the result of a calculation, supposing that the system reaches its highest load at 12 o'clock. Outdoor temperatures in this example Summer : 32˚CDB relative humidity 60% Winter : -2˚CDB relative humidity 42% 1 Load (in the summer with air-conditioning) < Sensible Heat > SH Computer 20.9 kW Lighting Number of people in the room Infiltration draft Outer wall (heat transmission) Windows (radiation) 1,800W 1.8 kW 5 persons ✕ 64 (U) 0.32 kW 3 (0.2 times/h) 39.6m ✕ 0.336 ✕ 8 0.11 kW ✕ 3.6 ✕ 8 0.25 kW ✕ 0.65 ✕ 188 1.91 kW 8.5m2 13.5m2 Windows (heat transmission) 13.5 ✕ 5.93 ✕ 8 0.64 kW Inner wall(heat transmission) 61.6 ✕ 2.05 ✕ 4 0.5 kW 125m3 ✕ 0.336 ✕ 8 0.34 kW Outside air Total 26.8 kW < Latent Heat > LH Infiltration draft Number of people in the room Outside air 39.6 ✕ 834 ✕ 0.0117 0.39 kW 5 persons ✕ 82 0.41 kW 125m3 ✕ 834 ✕ 0.0117 1.22 kW Total 2.0 kW Total load is 28.8kW 2 Necessary Air Circulation V= 26800 0.336 ✕ (24 -18) ÷ 60 = 221m3/min 3 Model Selection PUY-P250YMF-C ✕ 2, PFD-P500VM-A type Indoor ˚CDB 24˚C / Indoor ˚CWB 17˚C outdoor ˚CDB 32˚C Capacity of the Moment 51.5kW SHF = 0.92 Capacity of Sensible Heat 51.5 ✕ 0.92 = 47.4/kW Standard Air-Flow Volume: 320m3/min can be accommodated with PUY-P250YMF-C ✕ 2 and PFD-P500VM-A. 38 9-6 Automatic Control of the Computer Room Example PFD-P560VM-A automatically controls the cooling temperature with a built-in controller. (suction temperature or discharge temperature control) This unit is designed for high sensible-heat specifications, and it does not include a humidifier or a dehumidifier. Install such components as necessary. < Outdoor Unit > TB7 No1 TB3 TB7 No2 TB3 ✻2 ✻1 Intake Thermistor RA < Indoor unit > Controller Terminal Bed for External Input/Output Discharge Thermistor Free-Access Floor SA Remote Controller ✻1 Bold lines in the diagram indicate refrigerant piping (gas/liquid). This system consists of 2 refrigerant circuits. ✻2 Indicates TB3-type transmission line used to communicate with the indoor unit. This system is made up of 2 circuits. 39 10. Maintenance/Inspection 10-1. Maintenance/Inspection Schedule Having the units inspected by a specialist on a regular basis, in addition to regular maintenance such as changing the filters, will allow the users to use them safely and in good condition for an extended period of time. The chart below indicates standard maintenance schedule. (1) Approximate Longevity of Various Parts The chart shows an approximate longevity of parts. It is an estimation of the time when old parts may need to be replaced or repairs need to be made. It does not mean that the parts must absolutely be replaced (except for the fan belt). Please note that the figures in the chart do not mean warranty periods. Fan Belt Check Replace every after 6 months 40000 hours 6 months 40000 hours 6 months 8000 hours Air Filter 3 months 5 years Drain Pan 6 months 8 years Yes Drain Hose 6 months 8 years Linear Expansion Valve 1 year 1 year Yes Yes Yes Unit Parts Fan Motor Indoor Bearing Heat Exchanger Float Switch Indicator Lamp Outdoor 25000 hours 5 years 6 months 25000 hours 1year 8000 hours Heat Exchanger Pressure Switch Inverter Cooling Fan 1 year Fan motor Linear Expansion Valve Periodically check Yes Yes Yes Remarks Add lubricant once a year Disposable parts Yes 6 months 40000 hours 6 months 40000 hours 1 year 25000 hours 5 years 1 year 1 year 25000 hours Compressor Daily check 40000 hours Maintenance schedule changes depending on the local conditions Yes Yes Yes Yes Yes Yes Yes Yes (2) Notes ●The above chart shows a maintenance schedule for a unit that is used under the following conditions: A. Less than 6 times per hour of compressor stoppage B. The unit stays on 24 hours a day. ●Shortening the inspection cycle may need to be considered when the following conditions apply: ➀ When used in high temperature/high humidity area or when used in a place where the temperature and/or humidity fluctuate greatly ➁ When plugged into an unstable power source (sudden change in voltage, frequency, wave distortions) (Do not exceed the maximum capacity.) ➂ When the unit is installed in a place where it receives vibrations or major impacts. ➃ When used in a place with poor air quality (containing dust particles, salt, poisonous gas such as sulfuric acid gas and sulfuric hydrogen gas, oil mist). ●Even when the above maintenance schedule is followed, there could be unexpected problems that cannot be predicted. ●Holding of Parts We will hold parts for the units for at least 9 years after the termination of the production of the unit, following the standards set by the ministry of economics and industries. 40 Details of Maintenance/Inspection Unit Parts Inspection Cycle Check points Assessment Fan motor · Check for unusual noise · Measure the insulation resistance · Free of unusual noise · Insulation resistance over 1MΩ Replace when insulation resistance is under 1MΩ Bearing · Check for unusual noise · Free of unusual noise If the noise doesn't stop after lubrication, change the oil. Add lubricant once a year. · Check for excessive slack · Check for wear and tear · Check for unusual noise · Resistance (3-4kg/belt) · Adequate amount of slack=5mm · Belt length=no longer than 102% of the original length · Free of wear and tear · Free of unusual noise Adjust the belt Replace if the belt length exceeds 2% of the original length, worn, or used over 8000 hours · Check for clogging and tear · Clean the filter · Clean, free of damage Clean the filter Replace if extremely dirty or damaged · Check for clogging of the drainage system · Check for loosened bolts · Check for corrosion · Clean, free of clogging · Free of loose screws · No major disintegration Clean if dirty or clogged Tighten bolts Replace if extremely worn · Make sure the loop of the hose has water to prevent air from traveling through the hose (Fill the hose with water) · Check for clogging of the drainage system · Clean, free of clogging · Free of wear and tear Clean if dirty or clogged Replace if extremely worm · Perform an operation check using the operation data · Adequately controls the air temperature (Check temperature change on the centralized controller) Replace if malfunctioning · Check for clogging, dirt, and damage · Clean, free of clogging or damage Clean · Check the outer appearance · Make sure its free of foreign objects · Free of frayed or cut wires · Free of foreign objects Replace if damaged or extremely worn Remove foreign objects · Make sure the lamp comes on · Comes on when the output is on Replace if the light does not come on when the power is on · Check for unusual noise · Check insulation resistance · Check for loosened terminals · Free of unusual sound · Insulation resistance over 1MΩ · Free of loosened terminals Replace if insulation resistance goes below 1MΩ (under the condition that the refrigerant is not liquefied) Tighten loosened bolts Fan motor · Check for unusual noise · Measure insulation resistance · Free of unusual sound · Insulation resistance over 1MΩ Replace if insulation resistance goes below 1MΩ Linear expansion valve · Perform an operation check using the operation data · Adequately controls the air temperature (Check temperature change on the centralized controller) Replace if malfunctioning Heat exchanger · Check for clogging, dirt, and damage · Clean, free of clogging or damage Clean Pressure switch · Check for torn wire, fraying, and unplugged connectors · Check insulation resistance · No frayed or cut wires or unplugged connectors · Insulation resistance over 1MΩ Replace when cut or shorted, when the insulation resistance goes below 1MΩ, or if there is a history of abnormal operation · Check for unusual sound · Measure insulation resistance · Look for abnormal history · Free of unusual sound · Insulation resistance over 1MΩ · No heatsink overheat protection (4230,4330) on the report Replace when producing unusual sounds, when insulation resistance goes under 1MΩ, or if there is a history of abnormal operation. Fan belt Air filter 6 months 3 months Indoor Drain pan Drain hose 6 months Linear expansion valve 1 year Heat exchanger Float switch Indicator lamp 6 months 1 year Compressor 6 months Outdoor What to do 1 year Inverter cooling fan 41 HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Issued in June 2004 MEE03K204-A Printed in Japan New publication, effective June 2004 Specifications subject to change without notice