TECHNICAL SPECIFICATIONS
R6GP Series 6, 7½ and 10 Ton Packaged Gas/Electric Units 11.2 EER Commercial System 80% Steady State Efficiency with Optional Stainless Steel Heat Exchangers These units are designed specifically for retrofit applications and compatibility with most standard footprints. They take less time to install and retrofit, making the contractor's job more profitable. These units offer flexibility in the replacement market.
FEATURES and BENEFITS • Quality Compressor: State of the art scroll compressor is standard equipment. • 7 ½ & 10 Ton Feature Two-Stage Cooling • 6 Ton Features Single Stage Cooling • High Efficient Blower Motor: Meets the requirements of NEMA 12/19/2010 • Hi/Low Pressure Switches: Ensure long compressor life. Featuring manual reset high pressure control. • CopperTube / Aluminum Fin Coils: Both indoor and outdoor coils are designed to optimize heat transfer, minimize size and cost, and increase durability and reliability. • Plastic Mesh Hail Guard: A guard that will never rust and protects the units coil from being damaged. • For Easy Service: Hi/low service ports allow quick access without disrupting operation. • Permanently Lubricated Condenser Fan Motors: A heavy duty PSC motor for long lasting reliability and quiet operation. Requires no maintenance and is completely protected from rain and snow. • 75 VA Transformer: Includes 4 Amp circuit breaker to protect the low voltage circuit. • Liquid Line Filter Driers: Factory installed for convenience. • Crankcase Heater: Protection from liquid flood back and future compressor failures. • Freeze Protection Thermostats: provide reliable compressor operation. • Easy Compressor and Control Access: Designed to make servicing easier for the contractor, access panels are provided to all controls and the compressor from the side of the unit. • 80% Steady State Efficiency: Aluminized steel or stainless steel heat exchanger tubes are available. • Two-Stage Heating: Provides High / Low fire operation • Direct Spark Ignition Control: With 3 amp fuse, flame sensing, and diagnostic LED • Convertible Air Delivery with Kit: Converts to horizontal airflow with side panels including duct flange and bottom close off panels. • Quick-Release Filter Access Panels: Requires no special servicing tools. • Fully Insulated Bottom Pan: Helps ensure quiet operation and prevents condensation. • Removable Top Grille Assembly: Allows ease of service to the fan motor. • Full Perimeter Base Rail System: Base rails have rigging holes and do not need to be removed for curb applications. Base rails have fork truck slots on three sides. • Durable, Attractive Cabinet: Designed using 20 gauge galvanized steel with a polyester urethane finish. The 950 hour salt spray finish is 1.5 mil thick and resists corrosion 50% better than comparable units.
2
3
High Efficiency Compressors with Crankcase Heaters
High/Low Pressure Switch Protection
Power Wiring Entry
Condenser Coils
Control Wiring Entry
Knockout for Bottom Power Entry
Liquid Line Filter Driers
Condenser Fan Assemblies
Belt Drive Blower Motor
Knockout 3/4” PVC for Bottom Condensate Power Entry** Drain
Evaporator Coils
Flame Observation
+ Field Supplied ** Field Installed Kit Required
Gas Line Inlet
Permament Baserail No Need for Removal with Roof Curb
Exhaust Vent
Electrical Disconnect Mounting Panel +
Easy Access Control Panel
Durable Pre-Coat Paint
Combustion Air Inlet
Quick Release Filter Panel
Model R6GP-120C235C Shown
R6GP – physical data
Dimensions shown in inches (mm) A Corner “D”
Corner “A”
Heat Exchanger
CG
Condenser Fans
Top View Corner weights and center of gravity see Table Page 9
B
Corner “C”
Corner “B” Blower Assembly
HIGH VOLTAGE CONNECTIONS
101 1/2 (2578)
GROUND CONNECTIONS
LOW VOLTAGE CONNECTIONS
4 (102)
INDOOR BLOWER
COMBUSTION AIR INLET
INDUCER EXHAUST
OUTDOOR COMPARTMENT
Front View FLAME OBSERVATION PORT RECOMMENDED DISCONNECT MOUNTING LOCATION
4 (102) BOTTOM POWER KIT MOUNTING LOCATION
CONDENSATE DRAIN
2 (51) 30 3/4
Horizontal Discharge Air Opening* Filter Access 30 (762) 4 (102)
16 1/2 (419)
4 (102)
Condenser Coil
Horz. Return Air Opening*
30 (762)
16 1/2 (419)
7 (178) 7 1/4 (184)
*Shown with optional horizontal duct panels Physical Dimensions for R6GP-072 Series
4
43 1/2 (1403)
Rear View
R6GP – physical data (Continued) Dimensions shown in inches (mm) INDUCER EXHAUST
57 1/2 (1460)
RATING LABEL
RECOMMENDED LOCATION FOR UNIT DISCONNECT
COMBUSTION AIR LOUVERS 43 (1092)
Heat Exchanger End
GAS INLET
14 5/8 (371)
UNIT BASERAIL
6 5/64 (154)
Airflow
Airflow
Compressor Condenser End
7 (178)
Return Air Opening
7 (178) 5-3/4 (146)
30 1/2 (775)
16 1/2 (419)
16 1/2 (419)
Bottom Pan Top View (072, 090, 120)
30 1/2 (775) Discharge Air Opening
8 3/4 (222) † Power Entry
62 (1575) 101 1/4 (2572)
Physical Dimensions for R6GP-072 Series Continued 5
Dimensions shown in inches (mm)
A Corner “A”
Corner “D”
Heat Exchanger
CG
Condenser Fans B
Corner “B”
Corner “C” Blower Assembly Top View
16 (406) Optional Hail Guard Hood
Corner weights and center of gravity see Table Page 9
101 1/2 (2578) Control Access
4 (102) Field Wiring (†)Electric Element Access
Blower Access
Condesate Drain 4 (102) 2 (51) 30 3/4 (781) Front View
Physical Dimensions for R6GP-090 Series 6
*Shown with optional horizontal duct panels
Horizontal Discharge Air Opening*
Filter Access
4 (102)
30 (762)
Condenser Coil
Horz. Return Air Opening*
43 1/2 (1403)
16 1/2 (419)
16 1/2 (419)
Rear View
30 (762)
4 (102) 7 1/4 (184)
INDUCER EXHAUST
7 (178)
57 1/2 (1460)
RATING LABEL
RECOMMENDED LOCATION FOR UNIT DISCONNECT
COMBUSTION AIR LOUVERS 43 (1092)
Heat Exchanger End GAS INLET
14 5/8 (371)
6 5/64 (154)
UNIT BASERAIL
Airflow
Airflow
Compressors (x2) Condenser End
Physical Dimensions for R6GP-090 Series Continued 7
Dimensions shown in inches (mm) A Corner “A”
Corner “D” Filters (x4)
Evaporator
Heat Exchanger
Condenser Fans
Top View
B
Corner “C”
Corner “B” Blower Assembly
16 (406)
4 (102)
101 1/2 (2578)
Optional Hail Guard Hood
Control Access
Inducer Exhaust
Recommended Unit Disconnect Mounting Location
Combustion Air Inlet
Blower Access
Front View
Condensate Drain 4 (102) 2 (51)
Compressor Electric Supply Entries
*Shown with optional horizontal duct panels Horizontal Discharge Air Opening*
Heat Exchanger Access
30 (762)
16 1/2 (419)
30 3/4 (781)
Condenser Coils
Filter Access
Horiz. Return Air Opening*
30 (762)
55 1/4 (1403)
16 1/2 (419)
4 (102) 4 (102)
7 1/4 (184)
7 (178)
Physical Dimensions for R6GP-120 Series 8
Rear View
Airflow
57 1/2 (1461)
Airflow
18 1/2 (470) Optional Fresh Air Intake Hood
Condenser Coil Compressors (2)
9 7/8 (250)
Optional Relief Hood
8 (203)
Gas Inlet
4 (102)
Condenser End
Heat Exchanger End
Physical Dimensions for R6GP-120 Series Continued
Unit Weight ‡ Model No.
Shipping Weight
Center of Gravity Inches (mm)
Corner Weights B C
A
Unit Height* D
Horizontal Duct Applications
Vertical Duct Applications
Lbs.
Kg.
Lbs.
Kg
A
B
Lbs.
Kg.
Lbs.
Kg.
Lbs.
Kg.
Lbs.
Kg.
R6GP-072*-100
934
425
1069
486
48 (1219)
25 5/8 (651)
197
89
245
111
273
124
219
100
43 1/2 (1105)
38 1/4 (972)
R6GP-072*-166
959
436
1094
497
49 (1245)
25 5/8 (651)
206
94
257
117
275
125
221
100
43 1/2 (1105)
38 1/4 (972)
R6GP-090*-200
983
446
1118
507
55 3/8 (1407)
28 (711)
262
119
275
125
229
104
218
99
43 1/2 (1105)
38 1/4 (972)
R6GP-120*-235
1301
590
1441
654
49 (1245)
30 (762)
300
136
328
149
351
159
322
146
55-1/4 (1409)
51 (1295)
* Baserails are not intended to be removed. Information provided is total unit height for horizontal duct applications or height dimension added to selected roof curb height for vertical duct applications. ‡ Unit weight without packaging or field installed accessories.
Center of Gravity & Unit Shipping Weights
MODEL IDENTIFICATION CODE R
6
G
P
-
C
045
C
A Revision
Application R = Rooftop Packaged Unit Series Gas
090
P = 11.0 - 11.9 EER
Cooling Nominal Capacity (000) Btu
C = U.S./Canada - Aluminized Steel Hx S = U.S./Canada - Stainless Steel Hx Heating Capacity (000) Btu Electrical Code C = 208/230-60-3 D = 460-60-3
9
PHYSICAL SPECIFICATIONS DATA Model R6GPNominal Capacity (tons) Performance Data 1,2,3 Total Gross Cooling Capacity (Btuh) Rated Net Cooling Capacity (Btuh) E.E.R. - Cooling Efficiency (Btuh/Watt) IEER - Part load Efficiency Rated Airflow - CFM Compressor Data Compressor(s) Type Quantity (number of refrigeration circuits) Unit Capacity Steps (%) Crankcase Heaters POE Oil Charge (Ea.) Refrigerant Charge (R-410a) Stage 1 Circuit Stage 2 Circuit System Pressure Switches Manual Reset High Pressure Switch (PSIG) Loss of Charge Switch (PSIG) Outdoor Fan Data Fan Diameter / Total Nominal CFM Motor - HP / RPM Quantity Outdoor Coil Data Rows / fpi Type Total Face Area (sq ft) Indoor Coil Data Rows / fpi Type Total Face Area (sq ft) Expansion Device Freeze Protection Thermostat Indoor Blower Data Blower Type (Qty.) - Wheel Diameter Drive Type Standard Blower Drive Motor 4 Motor - Hp / RPM Speeds Frame Size NEMA Efficiency Blower RPM Range Blower ESP Range (in-WC) Installed Filters Style Size[inches] (Qty.) Sound Rating Number dBA
072(C/D)
090(C/D)
120(C/D)
6
7.5
10.0
73,300 72,000 11.2 12.6 2,400
93,500 90,000 11.2 12.3 3,000
125,000 119,000 11.2 11.5 4,000
Scroll 1 100 yes 56 Oz.
Scroll 2 50/50 yes 42 Oz.
Scroll 2 50/50 yes 42 Oz.
240 Oz. -
168 Oz. 168 Oz.
216 Oz. 216 Oz.
Cut Out: 650 +/- 10 Cut Out: 5 +/- 5, Cut In: 20 +/- 5 20” / 7000 1/3 - 1100 2
24” / 8200 1/3 - 1075 2
24” / 8200 1/3 - 1075 2
2 / 18 Cu Tube/Al Fin 17.0
2 / 19 Cu Tube/Al Fin 25.5
2 / 17 Cu Tube/Al Fin 34.0
4 / 14 4 / 14 4 / 14 Cu Tube/Al Fin Cu Tube/Al Fin Cu Tube/Al Fin 8.5 8.5 11.3 TXV TXV TXV Opens (˚F): 28 +/- 5, Closes (˚F): 57 +/- 6 Centrifugal (1) - 12 x 12 Belt
Centrifugal (1) - 12 x 12 Belt
Centrifugal (1) - 15 x 15 Belt
1 / 1725 1 143T Premium Eff. 715 - 971 0.1 - 1.0
1.5 / 1750 1 143T Premium Eff. 777 - 1060 0.1 - 1.3
2/1800 1 143T Premium Eff. 672 - 897 0.1 - 1.0
16x20 (4) 83.5
Disposable - 2” Pleated 16x20 (4) 85.2
16x25 (4) 85.8
Notes: 1) Certified in accordance with AHRI Standard 340/360 at the rated airflow shown and the minimum external static duct pressure allowed by the standard. ARI Rating for units with dual voltages are shown at highest rated unit voltage. 2) E.E.R. - Energy Efficiency Ratio: The EER and Net Capacity is determined @ 95˚F Outdoor DB and with air entering the evaporator at 80˚F DB / 67˚F WB 3) IEER - Intergrated Energy Efficiency Ratio: a measure of merit for part load performance of the unit. 4) Refer to Alternate Accessory Drive Table for other available motor/drive kits
10
UNIT HEATING PERFORMANCE DATA Model R6GPHeater Model High Heating Input (Btuh) 1, 2 High Heating Output (Btuh) Low Heating Input (Btuh) 1, 2 Low Heating Output (Btuh) Steady State Efficiency Number of Capacity Stages Ignition Type Number of Burners Gas Piping Connection (in) Factory Configured 3
072(C/D) -100(c,s) 100,000 80,000 65,000 52,000 80% 2 Spark 3 1/2” NPT Nat. Gas
090(C/D) -200(c,s)a 200,000 160,000 130,000 104,000 80% 2 Spark 6 1/2” NPT Nat. Gas
-166(c,s) 166,000 132,800 108,000 86,400 80% 2 Spark 5 1/2” NPT Nat. Gas
120(C/D) -235(c,s)b 235,000 188,000 150,000 120,000 80% 2 Spark 7 3/4” NPT Nat. Gas
Notes: 1) Units with Heating inputs of 225,000 Btuh or greater are rated in accordance with DOE 10 CFR Part 431 2) Capacities shown represent use with Natural Gas, refer to Table 10 for LP gas capacities 3) Heat Exchangers are convertible to LP with Accessory Kit
Temperature Rise/AirFlow Unit Model
Gas Type
Heating Heating Input Output
Heating Rise Range
CFM Range SCFM
R6GP-072*-100
Natural Gas 100,000 80,000 Propane (LP) 85,000
15 - 45
68,000
Rise (ºF)* SCFM
R6GP-072*-166
Natural Gas 166,000 133,000 Propane (LP) 141,000 112,800
35 - 65
Rise (ºF)* SCFM
R6GP-090*-200
Natural Gas 200,000 160,000 Propane (LP) 175,000 140,000
30 - 60
Rise (ºF)* SCFM
R6GP-120*-235
Natural Gas 235,000 188,000 Propane (LP) 205,000 164,000
25 - 55
Rise (ºF)*
1950
2100
2250
2400
2550
2700
38
35
33
31
29
27
32
30
28
26
25
23
1950
2100
2250
2400
2550
2700
63
59
55
51
48
46
54
50
46
44
41
39
2425
2625
2800
3000
3188
3375
61
56
53
49
46
44
53
49
46
43
41
38
3250
3500
3750
4000
4250
4500
54
50
46
44
41
39
47
43
40
38
36
34
* At Elevations of 2000 Ft or less
Orifice or drill size for natural and propane (LP) gases. Unit Model R6GP-072*-100 R6GP-072*-166 R6GP-090*-200 R6GP-120*-235
Gas Type
Heating Input
Natural Gas
100,000
Propane (LP)
85,000
Natural Gas
166,000
Propane (LP)
141,000
Natural Gas
200,000
Propane (LP)
175,000
Natural Gas
235,000
Propane (LP)
205,000
Number of Burners 3 5 6 7
Orifice Size for Increased Elevation* (Above Sea Level) 0-2,000 Ft
2,001-4,000 Ft
4,001-6,000 Ft
6,001-8,000 Ft 8,001-10,000 Ft
36
38
40
41
43
53
54
54
55
55
36
38
40
41
43
53
54
54
55
55
36
38
40
41
43
51
52
52
52
53
36
38
40
41
43
51
52
52
52
53
* Refer to Instructions for High Altitude Deration to determine heat-exchanger capacity at increased elevations.
Table 10. Approximate Orifice or Drill Size for Natural and Propane (LP) Gases. 11
ELECTRICAL DATA FOR POWER EXHAUST ACCESSORY KITS Part # †
Volts
HP
CFM
FLA
Fuse
MCA
MOP
R6GP-072 & 090
547867
230
1/2
2350
3.00
6A
3.75
6.75
R6GP-072 & 090
547868
460
1/2
2350
1.50
3A
1.88
3.38
Model
R6GP-120
547876
230
3/4
4900
4.00
9A
5.00
9.00
R6GP-120
547877
460
3/4
4900
2.00
4A
2.50
4.50
Indoor Motor 4
Inducer Motor
† See Accessory List, pg 22
ELECTRICAL DATA Model Number 2,3
Nominal Unit Voltage 1
Factory Unit Electrical Data: R6GP -072-(100/166) 208-230 V -072-(100/166) 460 V
Compressors
Outdoor motors (2) ea.
QTY 1 ea. 1 ea.
RLA 19 9.7
LRA 123 62
FLA 1.5 0.8
Hp 1
FLA 3.2-3.1 1.5
Hp
FLA
LRA
1/12
0.5
0.76
Total Unit RLA
Unit Only Circuit
FLA 25.2 12.8
MCA 30-30 16
MOP 45-45 20
-090-200 -090-200
208-230 V 460 V
2 ea. 2 ea.
13.1 6.1
83.1 41
2.3 1.2
1.5
4.4-4.2 2.1
1/12
0.5
0.76
35.2 16.7
39-39 19
50-50 20
-120-235 -120-235
208-230 V 460 V
2 ea. 2 ea.
16.0 7.8
110 52
2.3 1.2
2
6.0-5.8 2.9
1/12
0.5
0.76
42.6 20.9
47-47 23
60-60 30
Notes: 1) To achieve the rated unit performance, unit voltage should be within 2% of 4) Indoor Motors meet 2010 DOE requirements (Premium Efficient) nominal. 5) FLA = Full Load Amps MCA = Minimum Circuit Ampacity 2) For C series units: RLA = Rated Load Amps MOP = Maximum Over-Current Protection Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase LRA = Locked Rotor Amps Minimum allowed unit voltage = 187V Maximum allowed voltage = 253V 3) For D series units: Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase Minimum allowed unit voltage = 414V Maximum allowed voltage = 506V
12
R6GP - EXPANDED RATINGS, COOLING MODE R6GP-072-(100/166) CFM
2250
O.D.T E.D.B. E.W.B. 62 67 75 72
T.C. 68.4 76.1 84.7
85°F S.C. 52.3 41.1 32.3
kW 5.64 5.73 5.82
T.C. 63.1 70.6 78.7
95°F S.C. 49.9 39.0 30.2
kW 6.24 6.33 6.41
T.C. 57.7 65.0 72.8
105°F S.C. 47.6 36.8 28.2
kW 6.85 6.92 7.01
T.C. 52.4 59.5 66.8
115°F S.C. 45.2 34.7 26.1
kW 7.46 7.52 7.60
80
62 67 72
68.7 76.1 84.1
63.0 52.3 41.5
5.65 5.74 5.85
63.7 71.4 78.8
60.5 50.3 39.4
6.21 6.28 6.37
58.6 66.7 73.4
57.9 48.2 37.2
6.78 6.83 6.89
54.4 60.7 67.0
54.2 45.5 34.5
7.47 7.54 7.55
75
62 67 72
69.2 77.1 85.9
54.2 42.4 32.3
5.73 5.81 5.92
63.9 71.6 79.9
51.7 40.0 30.5
6.34 6.41 6.51
58.6 66.2 73.8
49.3 37.6 28.7
6.95 7.01 7.10
53.3 60.7 67.8
46.8 35.2 26.9
7.55 7.61 7.70
80
62 67 72
69.7 77.0 85.1
64.4 54.1 42.7
5.75 5.82 5.92
65.1 72.0 79.5
61.4 51.7 40.3
6.35 6.43 6.50
60.5 65.9 73.9
58.5 49.4 37.9
6.95 7.08 7.09
55.9 60.4 68.2
55.6 47.0 35.5
7.55 7.71 7.67
75
62 67 72
70.0 78.0 87.0
56.0 43.7 32.2
5.82 5.89 6.01
64.7 72.7 81.0
53.5 41.0 30.7
6.43 6.50 6.61
59.5 67.3 74.9
50.9 38.4 29.1
7.04 7.10 7.20
54.2 61.9 68.8
48.4 35.7 27.6
7.65 7.71 7.79
80
62 67 72
70.6 77.9 86.1
65.8 56.0 43.9
5.85 5.90 5.98
66.2 72.6 80.6
62.8 53.4 41.4
6.45 6.50 6.59
62.5 67.4 75.0
60.9 50.9 38.9
6.97 7.11 7.19
57.3 62.2 69.5
56.9 48.3 36.4
7.63 7.71 7.79
55°F S.C.
kW
65°F S.C.
kW
75°F S.C.
kW
85°F S.C.
kW
2400
2550
R6GP-072-(100/166) CFM
O.D.T E.D.B. E.W.B.
T.C.
T.C.
T.C.
T.C.
75
62 67 72
78.6 86.8 95.0
57.9 46.7 36.1
4.49 4.59 4.70
75.2 83.2 91.6
56.0 44.8 34.8
4.87 4.97 5.07
71.8 79.7 88.1
54.2 43.0 33.6
5.25 5.35 5.45
68.4 76.1 84.7
52.3 41.1 32.3
5.64 5.73 5.82
80
62 67 72
79.2 87.3 95.0
68.9 58.2 45.6
4.47 4.57 4.69
75.8 83.8 91.6
66.9 56.3 44.3
4.85 4.95 5.06
72.8 80.6 88.8
65.5 54.9 43.5
5.21 5.31 5.41
68.7 76.1 84.1
63.0 52.3 41.5
5.65 5.74 5.85
75
62 67 72
79.6 87.6 95.6
59.7 48.0 36.0
4.58 4.68 4.79
76.1 84.1 92.4
57.8 46.1 34.8
4.97 5.06 5.17
72.6 80.6 89.1
56.0 44.3 33.5
5.35 5.44 5.54
69.2 77.1 85.9
54.2 42.4 32.3
5.73 5.81 5.92
80
62 67 72
80.2 88.1 95.6
70.6 59.5 45.5
4.57 4.66 4.78
76.7 84.6 92.4
68.7 57.6 44.2
4.95 5.03 5.15
73.6 81.5 89.8
67.3 56.2 43.4
5.31 5.39 5.50
69.7 77.0 85.1
64.4 54.1 42.7
5.75 5.82 5.92
75
62 67 72
80.5 88.3 96.2
61.5 49.3 35.9
4.68 4.77 4.88
77.0 84.9 93.1
59.6 47.4 34.7
5.06 5.15 5.26
73.5 81.5 90.1
57.8 45.6 33.4
5.44 5.52 5.64
70.0 78.0 87.0
56.0 43.7 32.2
5.82 5.89 6.01
80
62 67 72
81.1 88.8 96.2
72.4 60.8 45.4
4.66 4.75 4.88
77.6 85.5 93.2
70.5 58.9 44.1
5.04 5.12 5.24
74.5 82.4 90.8
69.2 57.5 43.4
5.40 5.48 5.60
70.6 77.9 86.1
65.8 56.0 43.9
5.85 5.90 5.98
2250
2400
2550
Notes: 1) T.C. = Total (Net) Cooling Capacity, S.C. = Sensible Cooling Capacity, kW = Kilowatts 2) Expanded Ratings are based on 230 Volt - 60 Hz operation 3) Ratings based on Factory Standard Blower Drive 4) Bolded Values indicate ARI rating points 5) Energy Efficiency Ratio (EER) = T.C. / kW
13
R6GP - EXPANDED RATINGS, COOLING MODE R6GP-090 (Two Compressor Operation) CFM
O.D.T E.D.B.
E.W.B. 62 67 72
T.C. 85.3 93.3 101.9
85°F S.C. 65.2 52.4 39.3
K.W. 7.08 7.19 7.31
T.C. 81.3 88.8 97.3
95°F S.C. 63.9 51.2 38.0
K.W. 7.74 7.84 7.97
T.C. 73.4 80.1 87.7
105°F S.C. 62.7 50.0 36.7
K.W. 8.84 8.94 9.06
T.C. 68.5 74.8 82.0
115°F S.C. 61.2 48.6 35.3
K.W. 9.39 9.46 9.59
80
62 67 72
86.0 92.9 101.7
76.5 64.4 51.4
7.09 7.18 7.31
82.2 88.6 97.0
75.5 63.4 50.4
7.75 7.84 7.96
74.3 80.0 87.5
74.5 62.4 49.3
8.85 8.94 9.06
69.8 74.7 81.6
73.6 61.2 48.1
9.40 9.46 9.58
75
62 67 72
86.8 94.6 103.5
69.4 55.2 40.4
7.27 7.38 7.51
82.7 90.0 98.6
68.1 54.0 39.1
7.93 8.03 8.17
74.5 80.9 88.8
66.8 52.7 37.8
9.05 9.14 9.27
69.5 75.3 82.9
65.3 51.3 36.3
9.57 9.64 9.78
80
62 67 72
87.9 94.5 103.1
81.9 68.5 54.2
7.29 7.38 7.51
84.3 90.0 98.2
81.8 67.5 53.1
7.96 8.04 8.16
76.6 81.2 88.4
80.3 66.5 52.0
9.08 9.14 9.26
72.2 75.6 82.5
76.4 65.3 50.9
9.60 9.65 9.78
75
62 67 72
87.9 95.3 104.6
73.3 57.8 41.4
7.46 7.57 7.71
83.7 90.3 99.5
72.0 56.5 40.1
8.12 8.22 8.36
75.3 81.2 89.6
70.7 55.1 38.7
9.24 9.32 9.46
70.2 75.7 83.5
69.1 53.6 37.3
9.75 9.82 9.95
80
62 67 72
90.3 95.6 104.1
88.4 72.5 56.8
7.50 7.57 7.70
86.7 91.1 98.9
86.3 71.4 55.7
8.16 8.23 8.35
78.7 82.0 88.9
78.3 70.4 54.7
8.49 8.56 8.68
74.0 76.6 82.4
73.7 69.2 53.4
9.80 9.83 9.95
75 2825
3000
3188
R6GP-090 (One Compressor Operation) CFM
O.D.T E.D.B. E.W.B. 75
2825 80
75 3000 80
75 3190 80
T.C.
55 °F S.C.
kW
T.C.
65 °F S.C.
kW
T.C.
75 °F S.C.
kW
T.C.
85 °F S.C.
kW
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
58.5 64.7 71.7 59.3 64.6 70.5 59.0 65.3 72.2 59.8 65.1 71.1 59.5 65.8 72.7
52.6 44.3 35.0 59.3 57.4 49.5 53.7 45.3 36.1 59.8 58.4 50.6 55.3 47.0 37.8
3.74 3.81 3.90 3.78 3.85 3.92 3.77 3.85 3.93 3.82 3.88 3.95 3.77 3.84 3.92
52.5 58.8 65.8 53.3 58.7 64.6 53.1 59.4 66.3 53.9 59.2 65.1 53.6 59.8 66.8
47.2 38.9 29.7 53.3 52.0 44.1 48.3 40.0 30.8 53.9 53.1 45.2 50.0 41.6 32.4
3.88 3.95 4.04 3.92 3.98 4.06 3.91 3.99 4.07 3.96 4.02 4.09 3.90 3.98 4.06
48.0 54.3 61.3 48.8 54.2 60.1 48.6 54.9 61.8 49.4 54.7 60.6 49.1 55.3 62.3
44.1 35.8 26.6 48.8 48.9 41.0 45.2 36.9 27.6 49.4 50.0 42.1 46.8 38.5 29.3
4.10 4.18 4.26 4.15 4.21 4.28 4.14 4.21 4.30 4.18 4.24 4.32 4.13 4.20 4.29
45.0 51.3 58.2 45.8 51.1 57.0 45.5 51.8 58.8 46.3 51.6 57.6 46.0 52.3 59.2
43.2 34.9 25.7 45.8 48.0 40.1 44.3 36.0 26.8 46.3 49.1 41.2 46.0 37.6 28.4
4.42 4.49 4.57 4.46 4.52 4.59 4.45 4.53 4.61 4.49 4.56 4.63 4.44 4.52 4.60
62 67 72
60.3 65.6 71.5
60.3 60.1 52.2
3.81 3.87 3.94
54.4 59.7 65.6
54.4 54.7 46.9
3.95 4.01 4.08
49.9 55.2 61.1
49.9 51.6 43.7
4.17 4.24 4.31
46.8 52.1 58.0
46.8 50.7 42.9
4.49 4.55 4.62
Notes: 1 ) T.C. = total (Net) cooling in kBtuh; S.C. = Sensible Cooling in kBtuh; kW = Kilowatts 2 ) Ratings are based on the Factory Standard blower drive combination 3 ) For 208-230V Units, the ratings shown reflect 230V operation 4 ) Bolded Values indicate AHRI rating points 5 ) Energy Efficiency Ratio (EER) = T.C./kW
14
R6GP - EXPANDED RATINGS, COOLING MODE R6GP-120 (Two Compressor Operation) CFM
O.D.T E.D.B. 75
3500 80
75 4000 80
75 4500 80
E.W.B.
T.C.
85°F S.C.
K.W.
T.C.
95°F S.C.
K.W.
T.C.
105°F S.C.
K.W.
T.C.
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
112.7 123.3 134.7 113.7 122.8 134.4 114.8 125.0 136.8 116.2 124.9 136.3 116.2 125.9 138.2 119.4 126.4 137.6
86.5 69.6 52.2 101.5 85.5 68.3 92.1 73.3 53.6 108.8 91.0 71.9 97.4 76.8 55.0 117.4 96.2 75.4
9.36 9.50 9.67 9.37 9.49 9.67 9.62 9.76 9.93 9.64 9.75 9.93 9.87 10.00 10.19 9.91 10.01 10.18
107.5 117.4 128.6 108.6 117.2 128.2 109.3 118.9 130.3 111.5 119.0 129.8 110.7 119.4 131.6 114.6 120.4 130.7
84.9 68.0 50.5 100.3 84.2 66.9 90.4 71.6 51.9 108.6 89.6 70.5 95.6 75.0 53.2 114.6 94.9 74.0
10.24 10.37 10.53 10.25 10.36 10.53 10.49 10.62 10.80 10.52 10.62 10.79 10.74 10.86 11.05 10.79 10.88 11.04
97.0 105.9 115.9 98.2 105.7 115.6 98.5 107.0 117.4 101.3 107.3 116.9 99.6 107.3 118.4 104.0 108.5 117.5
83.3 66.3 48.7 98.9 82.8 65.5 88.7 70.0 50.1 106.6 88.3 69.1 93.9 73.2 51.4 104.0 93.5 72.6
11.68 11.82 11.98 11.71 11.82 11.98 11.96 12.08 12.25 12.01 12.09 12.25 12.22 12.33 12.51 11.22 11.31 11.48
90.5 98.8 108.4 92.3 98.8 107.9 91.8 99.6 109.6 95.4 100.0 109.1 92.8 100.0 110.4 97.8 101.2 108.9
115°F S.C.
K.W.
81.3 64.5 46.9 97.8 81.3 63.9 86.7 68.1 48.2 101.5 86.7 67.6 91.8 71.2 49.5 97.8 91.9 70.9
12.41 12.50 12.68 12.43 12.51 12.67 12.65 12.74 12.93 12.69 12.75 12.92 12.89 12.98 13.16 12.95 13.00 13.16
R6GP-120 (One compressor operation) CFM
3500
4000
4500
O.D.T E.D.B. E.W.B. 75 62 67 72 80 62 67 72 75 62 67 72 80 62 67 72 75 62 67 72 80 62 67 72
T.C. 65.9 73.8 82.6 69.9 76.7 84.2 66.9 74.9 83.7 68.8 75.5 83.0 68.0 75.9 84.7 67.9 74.4 82.3
55 °F S.C. 49.1 37.5 27.7 58.8 47.9 36.5 50.5 38.8 28.8 58.9 48.4 37.5 51.9 40.0 29.9 59.0 49.0 38.1
kW 4.50 4.70 4.80 4.30 4.50 4.60 4.90 5.00 5.20 5.00 5.10 5.20 5.20 5.40 5.50 5.60 5.70 5.70
T.C. 61.8 69.8 78.6 65.9 72.6 80.1 62.9 70.8 79.6 64.8 71.5 79.0 64.0 71.9 80.7 63.9 70.4 78.2
65 °F S.C. 46.9 35.3 25.5 56.6 45.6 34.3 48.3 36.5 26.6 56.7 46.2 35.3 49.7 37.8 27.7 56.8 46.7 35.9
kW 4.80 5.00 5.10 4.60 4.70 4.90 5.20 5.30 5.40 5.20 5.30 5.40 5.50 5.60 5.80 5.90 5.90 6.00
T.C. 56.8 64.7 73.5 60.9 67.6 75.1 57.9 65.8 74.6 59.8 66.5 74.0 58.9 66.9 75.7 58.9 65.4 73.2
75 °F S.C. 44.3 32.7 22.9 54.0 43.1 31.7 45.7 34.0 24.0 54.1 43.6 32.7 47.1 35.2 25.1 54.2 44.1 33.3
kW 5.10 5.30 5.50 5.00 5.10 5.20 5.50 5.60 5.80 5.60 5.70 5.80 5.80 6.00 6.10 6.20 6.30 6.30
T.C. 50.7 58.7 67.5 54.8 61.5 69.0 51.8 59.7 68.5 53.7 60.4 67.9 52.9 60.8 69.6 52.8 59.3 67.1
85 °F S.C. 41.4 29.8 19.9 51.0 40.1 28.8 42.8 31.0 21.0 51.2 40.7 29.7 44.2 32.2 22.1 51.3 41.2 30.3
kW 5.50 5.70 5.90 5.30 5.50 5.60 5.90 6.00 6.20 6.00 6.10 6.20 6.20 6.40 6.50 6.60 6.70 6.70
Notes: 1 ) T.C. = total (Net) cooling in kBtuh; S.C. = Sensible Cooling in kBtuh; kW = Kilowatts 2 ) Ratings are based on the Factory Standard blower drive combination 3 )For 208-230V Units, the ratings shown reflect 230V operation 4 ) Bolded Values indicate AHRI rating points 5 ) Energy Efficiency Ratio (EER) = T.C./kW
15
BLOWER PERFORMANCE DATA
2588 719 0.72
R6GP-072-100 Factory Standard: 1 Hp Down-flow Performance Chart Extended Unit Static (in-Wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Operating @ 230 or 460 Volts
Indicates a recommended unit operational point
2793 715 0.77
Indicates an allowable setting that is not recommended for unit operation † † These operational points should be carefully examined by the installer for proper unit setup and heating operation
Indicates a setting that is not permitted for unit operation
‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting
Fully Closed
CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW
1/2 Turn Open
2417 960 1.02 2105 964 0.88
1 Turn Open
2528 936 0.97 2220 940 0.85 1854 944 0.77
1.5 Turns Open
2582 908 0.98 2301 912 0.86 2111 908 0.79
2 Turns Open
2680 880 0.97 2399 884 0.86 2074 888 0.76
2.5 Turns Open
2727 854 0.95 2488 858 0.86 2177 862 0.76 1913 866 0.68
3 Turns Open
2975 824 0.98 2763 828 0.95 2582 831 0.86 2295 835 0.76 1913 866 0.68
3.5 Turns Open
2828 800 0.88 2608 804 0.84 2381 808 0.75 2105 801 0.63
R6GP-072-100 Factory Standard: 1 Hp Horizontal Performance Chart Extended Unit Static (in-Wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Operating @ 230 or 460 Volts CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW
2867 771 0.85 2680 775 0.79 2453 760 0.72 2180 784 0.65 1860 786 0.54
4.5 Turns Open
5 Turns Open ‡
2946 741 0.85 2728 745 0.78 2528 749 0.72 2293 746 0.63 1982 750 0.56
2793 715 0.77 2588 719 0.72 2375 722 0.65 2110 726 0.57
‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting
Fully Closed
1/2 Turn Open
2414 959 1.04 2174 964 0.90
1 Turn Open
2545 931 1.02 2306 936 0.92 2013 941 0.81
1.5 Turns Open
2563 903 1.00 2353 907 0.91 2046 912 0.79
2 Turns Open
2626 877 0.99 2349 879 0.87 2100 833 0.78
Values includes losses for: Unit Casing, 2" Disposable (Pleated) Filters & Dry Evaporator Coil For approximate Cfm at 208V Deduct 0.5%
16
4 Turns Open
2.5 Turns Open
2729 850 0.97 2462 853 0.87 2165 855 0.77 1862 858 0.68
3 Turns Open
2812 821 0.96 2590 826 0.85 2298 829 0.76 2018 833 0.68
3.5 Turns Open
2881 792 0.92 2663 795 0.85 2426 799 0.77 2026 800 0.64
4 Turns Open
2955 764 0.88 2738 766 0.81 2514 769 0.74 2261 772 0.68 1957 775 0.58
4.5 Turns Open
5 Turns Open ‡
2999 740 0.86 2785 742 0.79 2558 745 0.72 2289 745 0.68 1995 746 0.60
2848 717 0.76 2615 720 0.69 2377 723 0.64 2085 721 0.56 1802 730 0.46
BLOWER PERFORMANCE DATA R6GP-072-166 Factory Standard: 1 Hp Down-flow Performance Chart Extended Unit Static (in-Wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Operating @ 230 or 460 Volts
‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting
Fully Closed
CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW
1/2 Turn Open
2449 964 1.01 2160 971 0.92
1 Turn Open
2525 937 1.01 2216 941 0.88 1928 946 0.81
1.5 Turns Open
2625 909 1.01 2323 915 0.89 2004 919 0.79
2 Turns Open
2.5 Turns Open
2826 857 0.99 2544 860 0.90 2220 864 0.78 1920 868 0.68
2769 881 1.04 2395 887 0.86 2120 892 0.77
3 Turns Open
2879 831 0.96 2647 834 0.87 2318 838 0.77 2044 840 0.70
3.5 Turns Open
2936 802 0.94 2708 804 0.87 2437 808 0.78 2107 811 0.67
R6GP-072-166 Factory Standard: 1 Hp Horizontal Performance Chart Extended Unit Static (in-Wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Operating @ 230 or 460 Volts CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW CFM RPM kW
2989 775 0.92 2788 776 0.85 2537 777 0.79 2227 782 0.68 1895 784 0.57
4.5 Turns Open
5 Turns Open ‡
3025 721 0.88 2832 749 0.83 2613 751 0.76 2335 753 0.68 2016 756 0.59
2872 719 0.80 2674 722 0.74 2437 725 0.68 2132 726 0.57
‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting
Fully Closed
1/2 Turn Open
2254 971 0.96
1 Turn Open
2572 939 1.07 2303 942 0.95 2043 945 0.85
1.5 Turns Open
2668 912 1.05 2386 971 0.93 2097 920 0.83
2 Turns Open
2.5 Turns Open
2745 884 1.02 2474 888 0.92 2200 894 0.79
Values includes losses for: Unit Casing, 2" Disposable (Pleated) Filters & Dry Evaporator Coil For approximate Cfm at 208V Deduct 0.5%
17
4 Turns Open
2569 862 0.89 2285 865 0.80 1988 870 0.70
3 Turns Open
2879 833 0.97 2655 837 0.89 2392 839 0.77 2095 842 0.69
3.5 Turns Open
2704 807 0.86 2457 811 0.78 2169 813 0.59
4 Turns Open
2771 778 0.84 2529 781 0.75 2259 785 0.67 1946 789 0.60
4.5 Turns Open
2620 755 0.75 2366 757 0.68 2060 760 0.59
5 Turns Open ‡ 2914 724 0.80 2703 728 0.74 2469 731 0.66 2203 732 0.60
BLOWER PERFORMANCE DATA R6GP-090-200 Factory Standard: 1 Hp Down-flow Performance Chart Extended Unit Static (in-Wg)
0.1
Operating @ 230 or 460 Volts
‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting 3.5 Turns Open
4 Turns Open
4.5 Turns Open
5 Turns Open ‡
5.5 Turns Open
6 Turns Open
CFM
3666
3549
3495
3441
3325
3209
RPM
867
843
832
820
799
777
kW
1.49
1.36
1.33
1.29
1.18
1.07
3496
3378
3316
3253
3137
3021
Fully Closed
1/2 Turn Open
1 Turn Open
1.5 Turns Open
2 Turns Open
2.5 Turns Open
CFM
0.2
0.3
0.4
0.5
0.6
3613
RPM
893
870
846
834
822
800
778
kW
1.52
1.40
1.28
1.25
1.21
1.11
1.01
CFM
3439
3315
3190
3135
3080
2946
2811
RPM
895
872
849
836
823
802
780
kW
1.45
1.33
1.20
1.17
1.13
1.03
0.94
CFM
3384
3267
3139
3010
2945
2879
2736
2592
RPM
918
896
875
853
839
824
803
782
kW
1.48
1.37
1.25
1.12
1.09
1.06
0.96
0.86
CFM
3332
3213
3094
2943
2791
2726
2661
2503
RPM
943
921
898
878
857
842
826
805
kW
1.49
1.38
1.28
1.16
1.05
1.01
0.98
0.88
2479
CFM
3312
3195
3039
2883
2727
2571
RPM
968
946
924
902
881
860
845
0.95
0.92
1.52
1.40
1.29
1.19
1.07
CFM
3255
3128
3001
2825
2648
2469
RPM
993
971
949
927
905
885
kW
1.54
1.42
1.31
1.19
1.08
0.97
kW
0.7
0.8
0.9
CFM
3164
3059
2903
2747
2574
RPM
1010
996
974
952
931
kW
1.52
1.44
1.31
1.19
1.09
CFM
2962
2830
2669
2508
RPM
1014
1001
979
956
1.20
1.08
1.39
1.31
CFM
2904
2754
2572
RPM
1039
1018
1005
kW
1.40
1.28
1.19
kW
1.0
1.1
CFM
2693
2528
RPM
1043
1024
kW
1.30
1.17
CFM
1.2
RPM kW CFM
1.3
RPM kW
Values includes losses for: Unit Casing, 2" Disposable (Pleated) Filters & Dry Evaporator Coil For approximate Cfm at 208V Deduct 0.5%
18
3 Turns Open
BLOWER PERFORMANCE DATA R6GP-120-235 Factory Standard: 2Hp Down-flow Performance Chart External Unit Static (in-Wg)
Operating @ 230 or 460 Volts
0.1
0.2
‡ Indicates Factory Sheave Setting for Pre-configured Units Adjustable Motor Sheave Setting 4 Turns Open
4.5 Turns Open
5 Turns Open ‡
5.5 Turns Open
6 Turns Open
CFM
5061
4896
4731
4558
4384
RPM
736
715
694
673
651
Fully Closed
1/2 Turn Open
1 Turn Open
1.5 Turns Open
2 Turns Open
2.5 Turns Open
3 Turns Open
3.5 Turns Open
kW
1.86
1.72
1.57
1.44
1.31
CFM
4849
4679
4508
4321
4134
RPM
737
716
696
674
653
kW
0.3
0.4
1.77
1.63
1.49
1.35
1.22
CFM
5005
4816
4627
4447
4267
4071
3875
RPM
781
760
738
718
697
676
655
kW
2.01
1.83
1.66
1.52
1.38
1.25
1.12
CFM
4773
4593
4413
4202
3990
3777
3564
RPM
782
762
741
720
698
678
657
kW
0.5
1.92
1.74
1.56
1.42
1.29
1.15
1.02
CFM
4719
4534
4336
4137
3923
3708
3477
3245
RPM
803
783
764
744
722
699
679
659
1.05
0.92
kW CFM 0.6
0.7
4685
0.9
1.1
1.2
1.3
1.4
1.61
1.43
1.30
1.18
4059
3845
3603
3361
826
806
786
766
746
724
703
kW
2.04
1.85
1.66
1.50
1.33
1.19
1.05
CFM
4457
4236
4014
3773
3531
3243
RPM
828
808
788
768
747
727
kW
1.91
1.72
1.54
1.37
1.20
1.06
4188
3940
3692
3412
4601
4395
RPM
867
849
832
811
791
771
kW
2.15
1.97
1.78
1.59
1.40
1.22
CFM
4326
4110
3893
3609
3325
RPM
870
853
835
814
793
kW
2.01
1.82
1.63
1.44
1.26
3998
3765
3531
3252
CFM 1.0
1.79 4273
RPM
CFM 0.8
1.98 4479
4251
RPM
890
872
855
839
817
kW
2.03
1.82
1.64
1.45
1.28
3192
CFM
3917
3675
3434
RPM
894
874
858
842
kW
1.83
1.66
1.48
1.31
3358
CFM
3845
3605
RPM
910
897
878
kW
1.89
1.68
1.51
3274
CFM
3551
RPM
913
900
kW
1.73
1.53
CFM
3168
RPM
916
kW
1.56
Values includes losses for: Unit Casing, 2" Disposable (Pleated) Filters & Dry Evaporator Coil For approximate Cfm at 208V Deduct 0.5%
19
BLOWER PERFORMANCE DATA R6GP-120-235 Factory Standard: 2Hp Horizontal Performance Chart External Unit Static (in-Wg)
Operating @ 230 or 460 Volts
0.1
0.2
‡ Indicates Factory Sheave Setting for Pre-configured Units Adjustable Motor Sheave Setting
Fully Closed
1/2 Turn Open
1 Turn Open
1.5 Turns Open
2 Turns Open
2.5 Turns Open
3 Turns Open
3.5 Turns Open
4 Turns Open
4.5 Turns Open
5 Turns Open ‡
5.5 Turns Open
6 Turns Open
CFM
5020
4871
4722
4536
4350
RPM
736
717
697
675
653
kW
1.82
1.68
1.53
1.41
1.29
CFM
4783
4619
4454
4271
4087
RPM
738
718
698
676
655
kW
0.3
0.4
1.73
1.59
1.45
1.33
1.20
CFM
4986
4785
4584
4407
4229
4030
3831
RPM
779
760
740
720
699
678
656
kW
2.00
1.82
1.64
1.50
1.36
1.24
1.12
CFM
4720
4519
4317
4120
3922
3727
3532
RPM
783
762
742
722
701
680
659
kW CFM
0.5
4661
0.7
1.0
1.1
1.2
1.3
1.4
1.39
1.26
1.14
1.02
3858
3643
3436
3229
805
786
765
744
724
703
682
661
1.94
1.76
1.59
1.42
1.29
1.15
1.04
0.92
4445
4252
4037
3821
3569
3316
4637
RPM
827
808
789
767
746
726
706
kW
1.99
1.82
1.64
1.48
1.32
1.18
1.05
CFM
4394
4191
3988
3745
3502
3238
RPM
830
811
792
770
747
728
kW
1.88
1.70
1.53
1.36
1.20
1.06
4173
3916
3658
3422
3186
4350
RPM
851
833
814
794
773
751
kW
1.93
1.76
1.57
1.39
1.23
1.07
4058
3861
3601
3341
CFM
0.9
1.53 4072
kW
CFM
0.8
1.71 4265
RPM
CFM
0.6
1.90 4458
4254
RPM
870
853
836
816
796
kW
1.97
1.80
1.62
1.44
1.26
3270
CFM
4191
3982
3762
3542
RPM
891
874
856
839
816
kW
1.99
1.81
1.64
1.47
1.30
3218
CFM
3892
3685
3452
RPM
894
877
860
843
kW
1.83
1.65
1.49
1.32
3362
CFM
3861
3572
RPM
913
897
883
kW
1.88
1.68
1.51
3244
CFM
3500
RPM
915
902
kW
1.70
1.52
CFM
3191
RPM
917
kW
1.55
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil For operation at 208V: Deduct approximately 0.5% from Cfm
20
ACCESSORIES - 6, 7 1/2 and 10 Ton R6GP Part # 559914 547881 547860 547861 547862 547863 559411 558857 547864 547874 547865 559375 559374 920233 547848 547867 547868 547876 547877 547869 547870 547871 547878 547879 547880 558863 558866 558864 558865 920463 920612 920610 920465 917165 920619 920937
Description Horizontal Supply & Return Kit Horizontal Supply & Return Kit Hinged Roof Curb 8” High - K/D Hinged Roof Curb 14” High - K/D Hinged Roof Curb 18” High - K/D Hinged Roof Curb 24” High - K/D Hooded Hail Guard Hooded Hail Guard 0-35% Manual Outside Air Damper 0-35% Manual Outside Air Damper 0-35% Motorized Damper - Only (Requires 547864 OR 547874) Economizer - Modulating w/ Relief, Adapts Horizontal, Enthalpy Control Economizer - Modulating w/ Relief, Adapts Horizontal, Enthalpy Control Sensor, Enthalpy, C7400A (For Economizer Differential Enthalpy Control) CO2 Sensor for economizer control - 4-9v dc Power Exhaust - Prop (208/230V - 3Ø), Adapts Horizontal See Note Power Exhaust - Prop (460V - 3Ø), Adapts Horizontal See Note Power Exhaust - Prop (208/230V - 3Ø), Adapts Horizontal See Note Power Exhaust - Prop (460V - 3Ø), Adapts Horizontal See Note 20” Supply & Return Transition Round 20” Flush Mount Concentric Diffuser Round 20” Step Down Concentric Diffuser Round 18” x 28” Supply & Return Transition 18” x 28” Flush Mount Concentric Diffuser 18” x 28” Step Down Concentric Diffuser Duct Smoke Detector Photo Elect. Duct Smoke Detector, Remote Multi-signal control SSK 451 Smoke Detector Sampling Tube DST3, 2-4 ft. Smoke Detector Sampling Tube DST5, 4-8 ft. Low Ambient Kit Natural Gas - High Altitude Application Kit LP Gas - Conversion & High Altitude Application Kit Bottom Power Entry Kit Bottom Power Entry Kit Thermostat-3 Stage Heat/2 Stage Cool Flue Exhaust Extension Kit
Weight 39 49 70 125 155 220 62 62 30 41 15 125 181
072 X
090 X
X X X X n/a
X X X X X
X
X
X X
X X
X X X X
X X X X
143 143 152 152 38 154 157 36 162 193 3 1
120 X X X X X X X X X X X
X X X X X
7 7 10
X X X
X X X X X X X X
X X X X X X X X
X X
X X
X X X X X X X X X X X X X
Note: Requires separate branch circuit, see table Electrical Data For Power Exhaust Accessory Kits, page 12.
Accessory Performance Data R6GP
-072* & -090*
-120*
Air Volume (CFM) 2200 2400 2600 2800 3000 3200 3400 3600 3600 3800 4000 4200 4400 4600
Total Resistance (inches water column) † Wet Evaporator Coil
Down Flow Economizer
Horizontal Economizer
0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.22 0.12 0.13 0.14 0.16 0.18 0.20
0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.20 0.22 0.24 0.27 0.30 0.33
0.03 0.04 0.04 0.04 0.04 0.05 0.05 0.05 0.04 0.04 0.04 0.05 0.05 0.05
Step Down Diffuser System
Flush Mount
2 Ends Open
2 Ends Open w/1 Side Open
2 Ends Open w/2 Sides Open
Throw ‡ (Ft)
Diffuser System
Throw ‡ (Ft)
0.15 0.16 0.20 0.25 0.30 0.40 0.50 0.60 0.35 0.40 0.45 0.50 0.55 0.60
0.14 0.16 0.20 0.25 0.30 0.38 0.46 0.55 0.25 0.30 0.35 0.40 0.45 0.50
0.13 0.13 0.15 0.20 0.25 0.30 0.40 0.50 0.20 0.25 0.30 0.35 0.40 0.45
20-24 22-27 24-29 25-30 27-33 28-35 30-37 32-39 25-33 27-35 29-37 32-40 34-42 36-44
0.11 0.13 0.17 0.20 0.25 0.31 0.37 0.43 0.17 0.18 0.21 0.24 0.27 0.30
17-25 18-26 19-26 20-28 21-29 22-29 22-30 23-31 22-29 22-30 24-33 26-35 28-37 30-39
† Pressure drop data are approximate values to allow for use in all design conditions. ‡ The distance the air from the grille travels from the diffuser before it slows down to 50 ft. per minute. All sides open.
21
22
23
For complete catalog information including submittals, energy calculations, dimension drawings, and more go to www.ReznorHVAC.com or call 800-695-1901. © 2015 Reznor LLC. Reznor is registered in at least the United States. All other trademarks are the property of their respective owners. All rights Reserved. Printed in U.S.A. 268E-0315 Form S-R6GP
Note: In keeping with our policy of continuous product improvement, we reserve the right to alter, at any time, the design, construction, dimensions, weights, etc., of equipment information shown here.