Transcript
REVISIONS LTR
DESCRIPTION
ENGR DJ
DWN
CHK
DJ
FT FT
A
ECO 06-648 RELEASED
B
ECO 06-826 ADD NOTE 3 & SHEET 12 (JAMACA,BARBADOS)
DJ
DJ
C
ECO 07-656 UPDATE SURGE PROTECTOR WIRING OPTIONS
DJ
DJ
DATE
APVD
5-15-06
DM
10-9-06
DM
5-24-07
PRIMARY ENCLOSURE FLORESCENT LAMP
48VDC AIR CONDITIONER - DC FLORESCENT LAMP
EVAP FANS
Evap Temp Sensor
J11
RMT
A B C
COMPRESSOR
Remote Temp
(+) MML (-)
PWR (+) PWR (-)
J12
1 2
MINOR MINOR MAJOR MAJOR
J10
1 2 3 4
DOOR SW
DOOR SW
L2
L1
N
METER BASE
LOCAL
PWR (+) PWR (-)
18C 23C SHDOWN ALARM 28C 33C 38C NC NC SETPOINT MINOR N0 MAJOR N0
SPEED CONTROL BOARD
AIR COND TEMP CONTROL Evap temp
COND FANS
J1 Cond Temp Sensor
METER
L2
N
875-055-20
HOT LOAD
N
-48VDC POSITIVE GND SYSTEM BLACK (-) HOT RED (+) COMMON
LIGHT RECPT 2 N
HOT
G
BBX 8 CKT LOAD CENTER L1
1
L2
2
60A
3 4 5
15A
6 7 8
30A
NEUT
GND
PCBA - ALARM CROSS CONNECT 1 2 3 2 4 5 3 6 7 4 8 9 5 10 11 6 12 13 7 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 COOLING SYSTEM MAJOR 24 48 49 COOLING SYSTEM MINOR 25 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
COM
HOT
Customer Provided Hook up for meter
20A
GFCI OUTLET LINE G
Gnd Bshg
HOT
L1
N
875-089-20
1
Model RMB-48 with options: 1 Enclosure with one 48VDC Air Cond Door 100A AC Service Load Center 8-position (External Mount) Surge Protector 3W+G 30A Max CB Limited GFCI outlets AC Lights Alarm Terminal Board Enclosure Intrusion Sensors
875-071-20 ML2
ML2
Isolated Bus Bar
Line 1 Line 2
Neutral
GND
SURGE PROTECTOR 30A MAX CB LIMITED 3W+G
ENCL GROUNDBAR 1
875-125-20
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW. 2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING. 1.
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
CHK
F. TARI
6-21-06
ENGR
D. JOHNSTON
5-15-06
MANUF
B. GRIFFITH
6-29-06
Q.A.
D. MATTS
6-29-06
PLOTTED ON:
25-May-2007 14:52:06
ALPHA TECHNOLOGIES TITLE:
SCHEMATIC RADIUM MINI SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W01.SCH
SIZE:
D
SHEET
C 1
OF
12
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
FLORESCENT LAMP
FLORESCENT LAMP
AIR CONDITIONER - DC FLORESCENT LAMP
A B C
COMPRESSOR
Remote Temp
RMT
PWR (+) PWR (-)
J11
(+) MML (-)
SETPOINT
1 J12 PWR (+) 2 PWR (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
DOOR SW
LOCAL
J1
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
Evap temp
SPEED CONTROL BOARD
AIR COND TEMP CONTROL
TAMPER
DOOR SW
DOOR SW
EVAP FANS
Evap Temp Sensor
COND FANS
L2
L1
N
875-089-20
HOT LOAD
N
1 Enclosure with one 48VDC Air Cond Door 1 Side Chamber 1
RSM 48/10 FUSE MODULE E1/2
2
E3/4
3 LVD
Gnd Bshg
TB2 HOT - B
LVD TB3 COMMON - A
LIGHT RECPT 2 N
4
TB1 HOT - A
5
TB4 COMMON - B
6
HOT
7
RIBBON 1-16
8 9
G
10 11
BBX 8 CKT LOAD CENTER L1
12
1
60A
30A
4
1 2 E2
5
20A
6
L1 L2 GND L1 L2 GND
OUTPUT (-)
Module 1
OUTPUT (+)
TB2
Gnd N L2 L1
ENCL GROUNDBAR 1
875-125-20
Line 1 Line 2
GND
GEN INLET
1 2 3 4 5 6 11 16
E7
1ALM 2ALM 31 2 P7 MJR P8 MNR P9 ACF
ALM 1 C ALM 1 ALM 2 C TB 3 ALM 2
TB4 TS COM TS 1 TS 2
75A
1 2 3 4
RSM 48/10 - 19" CABINET
RSM 48/10 -3 W/O SUPI COMMON AUX -48v RSM 48/10 SUPI NC LVD NC LVD C LVD B FU/BRKR FUSE ALM B FU/BRKR C 16 POS. RIBBON CABLE BRKR ALM LVA 1ALM 2ALM 32 1 FUSE ALM A P8 EXMJR LVA C P9 EXMNR NC HVA HVA C P10 LVD RSM MAJOR MINOR P11 LVA RSM MINOR MINOR C P12 HVA HV ALARM MAJOR P13 SUPI AC FAIL MAJOR C P14 FU/BR SUP'Y FAIL AC FAIL LV ALARM AC FAIL C SLAVE IN LVD A COMMON RIBBON 1-16 RIBBON 1-16 RSM 48/10 RLY ALM MDL -002
NEUT GND
15 14 13 12 10 9 8 7
WATER INTRUSION 15
874-978-20
Module 3
8
1 2 3
E8
Module 2
15A
7
SURGE PROTECTOR 2W+G
14
TB1
75A
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
TAMPER
1 2 E1
875-054-20
3
TAMPER
16
AC FAIL
17
RECT. MAJOR
18
RECT. MINOR
19
HVA
20
LVA
21
FUSE/BREAKER
22
BAT COMPARTMENT FAN
23
COOLING SYSTEM MAJOR
24
COOLING SYSTEM MINOR
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
EUSERC Meter w/60A FBX 12-position distribution Surge Protector 2W+G AC Gen Inlet GFCI outlets Battery Heater Mat AC Lights RSM 48/10 3 Modual Rectifier Shelf (W/GMT Fuse Dist) Alarm Terminal Board Enclosure Intrusion Sensors Water Intrusion Sensor
875-063-20
TAMPER
2
875-110-20
L2
13
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Isolated Bus Bar
60A
N
G
1 Battery Storage Unit
PCBA - ALARM CROSS CONNECT
COM
875-258-20
FUSE DISCONNECT
875-055-20
875-056-20
Model RMB-48 with options:
HOT
L1
Gnd Bshg
HOT
G
N
L2
HOT
LIGHT RECPT 2 N
20A
GFCI OUTLET LINE G
METER
N
USERC METER BASE
Cond Temp Sensor
874-933-21
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
875-063-22
875-068-20
75A 875-071-20
TAMPER
100A
12V BATTERY
12V BATTERY
12V BATTERY
875-064-20
875-059-20
875-110-20
TEMP SENSE
12V BATTERY
ML2
TAMPER
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN
Battery Compartment Fan TRAY GROUND ML2
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
1.
BATT HEATER FLOAT SW
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:27:35
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W02.SCH
SIZE:
D
SHEET
C 2
OF
12
PRIMARY ENCLOSURE FLORESCENT LAMP
AIR CONDITIONER - DC FLORESCENT LAMP
EVAP FANS
Evap Temp Sensor
A B C
COMPRESSOR
J1
(+) MML (-)
RMT
PWR (+) PWR (-)
Remote Temp
LOCAL
J11
1 J12 PWR (+) 2 PWR (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
DOOR SW
DOOR SW
L2
L1
N
METER BASE
SETPOINT
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
SPEED CONTROL BOARD
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor
METER
L2
(+) (-)
N
N
Model RMB-48 with options: 75A
BATT 100A
COM
1 2 3 4
LVD LIGHT RECPT 2 N
20A 20A 20A 20A
HOT
875-332-20
OUT
5
CB1 CB2 CB3 CB4
6 7
RIBBON 1-16 RSM 48/10 BREAKER MODULE
8 9
G
10 11
BBX 8 CKT LOAD CENTER L1
12
1
13
60A
1 2 E2
15A
6
L1 L2 GND
TB1 OUTPUT (-)
Module 1
OUTPUT (+)
TB2
E8
WATER INTRUSION 15
E7
874-978-20
Module 2
7
1ALM 2ALM 31 2 P7 MJR P8 MNR P9 ACF
Module 3
8 NEUT
75A
15 14 13 12 10 9 8 7
875-125-20
ENCL GROUNDBAR 1
Line 1 Line 2
GND
Neutral
SURGE PROTECTOR 3W+G
1 2 3 4 5 6 11 16
TS COM TS 1 TS 2
1 2 3 4
RSM 48/10 - 19" CABINET
RSM 48/10 -3 W/O SUPI COMMON AUX -48v RSM 48/10 SUPI NC LVD NC LVD C LVD B FU/BRKR FUSE ALM B FU/BRKR C 16 POS. RIBBON CABLE BRKR ALM LVA 1ALM 2ALM 32 1 FUSE ALM A P8 EXMJR LVA C P9 EXMNR NC HVA HVA C P10 LVD RSM MAJOR MINOR P11 LVA RSM MINOR MINOR C P12 HVA HV ALARM MAJOR P13 SUPI AC FAIL MAJOR C P14 FU/BR SUP'Y FAIL AC FAIL LV ALARM AC FAIL C SLAVE IN LVD A COMMON RIBBON 1-16 RIBBON 1-16 RSM 48/10 RLY ALM MDL -002
GND
1 2 3
ALM 1 C ALM 1 ALM 2 C TB 3 ALM 2
TB4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
TAMPER
16
AC FAIL
17
RECT. MAJOR
18
RECT. MINOR
19
HVA
20
LVA
21
FUSE/BREAKER
22
BAT COMPARTMENT FAN
23
COOLING SYSTEM MAJOR
24
COOLING SYSTEM MINOR
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 Battery Storage Unit 100A AC Service Load Center 8-position (External Mount) Surge Protector 3W+G GFCI outlets AC Lights RSM 48/10 3 Modual Rectifier Shelf (Circuit Breaker Distribution) Alarm Terminal Board Enclosure Intrusion Sensors Water Intrusion Sensor NetCom SNMP Alarm Monitor
WHT GRN RED YEL BLU
875-063-20
BLK HOT
5
20A
L1 L2 GND
14
TAMPER
4
1 2 E1
875-054-20
3
R?
TAMPER
2
875-110-20
L2
1 Enclosure with one 48VDC Air Cond Door
PCBA - ALARM CROSS CONNECT
875-241-20
875-055-20
HOT LOAD
RS 232
Isolated Bus Bar
HOT
Customer Provided Hook up for meter
NetCOM SNMP Alarm Monitor
20A
GFCI OUTLET LINE G
Gnd Bshg
COM
L1
N
875-089-20
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
874-933-21
875-068-20
75A 75A 875-071-20
100A
12V BATTERY ML2
12V BATTERY
875-064-20
875-110-20
TEMP SENSE
875-059-20
12V BATTERY
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
TAMPER
12V BATTERY TAMPER
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN
1.
Battery Compartment Fan TRAY GROUND ML2
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
FLOAT SW
BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:29:33
SCHEMATIC RADIUM MINI BAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W03.SCH
SIZE:
D
SHEET
C 3
OF
12
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
FLORESCENT LAMP
FLORESCENT LAMP
AIR CONDITIONER - DC FLORESCENT LAMP
COMPRESSOR
A B C
PWR (+) PWR (-)
Remote Temp
RMT
J1
J11
(+) MML (-)
SETPOINT
1 J12 PWR (+) 2 PWR (-)
LOCAL
COND FANS
Cond Temp Sensor METER
HOT LOAD
1 Enclosure with one 48VDC Air Cond Coor
N
1 Side Chamber
COMMNET 10 GMT PANEL RECT (-) RECT (+)
GMT1 GMT2 GMT3
G
1
GMT4
2
GMT5
875-056-20
3
GMT6 875-109-21
N
5
GMT8
6
GMT9
7
GMT10
8 9
G
BBX 8 CKT LOAD CENTER L1
HOT
4
GMT7 NO Fuse Fail COM NC
LIGHT RECPT 2
10
1
L2
11
60A
2
12
3
13 30A
20A
1 2 E2
15A
L1 L2 GND
Module 1
OUTPUT (+)
TB2
Gnd N L2 L1 875-125-21
ENCL GROUNDBAR 1
875-125-20
GEN INLET
1 2 3 4 5 6 11 16
ALM 1 C ALM 1 ALM 2 C TB 3 ALM 2
TB4 TS COM TS 1 TS 2 COMMON NC NC LVD B FUSE ALM B BRKR ALM FUSE ALM A NC RSM MAJOR RSM MINOR HV ALARM AC FAIL SUP'Y FAIL LV ALARM LVD A COMMON
Module 5
1 2 3 4
RSM 48/10 - 23" CABINET RSM 48/10 SUPI
AUX -48v LVD LVD C FU/BRKR FU/BRKR C LVA LVA C HVA HVA C MINOR MINOR C MAJOR MAJOR C AC FAIL AC FAIL C
RSM 48/10 RLY ALM MDL -002
GND
Line 1 Line 2
Neutral
GND
SURGE PROTECTOR 3W+G
E7
16 POS. RIBBON CABLE 1ALM 2ALM 32 1 P8 EXMJR P9 EXMNR P10 LVD P11 LVA P12 HVA P13 SUPI P14 FU/BR SLAVE IN
875-108-20
Module 4
15 14 13 12 10 9 8 7
WATER INTRUSION 15
1ALM 2ALM 31 2 P7 MJR P8 MNR P9 ACF
Module 3
1 2 3
E8
Module 2
NEUT
8
OUTPUT (-)
15 14 13 12 11 874-978-20 10 9 8 7 6 5 4 3 2 1
TAMPER
16
AC FAIL
17
RECT. MAJOR
18
RECT. MINOR
19
HVA
20
LVA
21
FUSE/BREAKER
22
BAT COMPARTMENT FAN
23
COOLING SYSTEM MAJOR
24
COOLING SYSTEM MINOR
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
875-110-20
MAIN GROUNDBAR - SIDE CHAMBER
875-071-20
875-059-20
TEMP SENSE
12V BATTERY
12V BATTERY
TAMPER
12V BATTERY
ML2
TAMPER
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN
Battery Compartment Fan ML2
TRAY GROUND
EARTH GROUND
GFCI Outlets Battery heater Mats AC Lights RSM 48/10 5 Modual Rectifier Shelf ComNet 10 GMT Fuse Panel 50amp Alarm Terminal Board Enclosure Intrusion Sensors Water Intrusion Sensor
SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING. 1.
BATT HEATER FLOAT SW
TO CUSTOMER INSTALLED GROUND RING
AC Gen Inlet
3.
75A ANDERSON
12V BATTERY
Surge Protector 3W+G
RIBBON 1-16 RIBBON 1-16
874-933-21
100A
100A AC Service Load Center 8-position
875-063-20
875-068-20
7
14
TB1
875-064-20
6
L1 L2 GND
TAMPER
1 2 E1
TAMPER
875-054-20
5
875-063-21
4
1 Battery Storage Unit
PCBA - ALARM CROSS CONNECT
COM
Customer Provided Hook up for Meter
875-055-20
HOT
Model RMB-48 with options:
N
HOT
LIGHT RECPT 2
20A
GFCI OUTLET LINE G
HOT
L2
L1
N
875-089-20
Gnd Bshg
N
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
DOOR SW
DOOR SW
L2
L1
N
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
Evap temp
SPEED CONTROL BOARD
AIR COND TEMP CONTROL
TAMPER
USERC METER BASE
DOOR SW
EVAP FANS
Evap Temp Sensor
BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:30:23
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W04.SCH
SIZE:
D
SHEET
C 4
OF
12
PRIMARY ENCLOSURE FLORESCENT LAMP
FLORESCENT LAMP (+) (-)
875-060-20
FAN CONTROL - 2
-48v COM TACH PWM -48v COM TACH PWM
-48v COM
MAJOR MAJOR MINOR MINOR
P5 - MML9
5 8 9 6 3 2 7 4 1
DC FAN
P2 - MML2
2 1
CL = ALM C J3OP = ALM
J4
COM -48v
(+) (-)
1 2 3
P3- MML6
P1 - ML2
1 2
DOOR SW
PWR (+) PWR (-)
Model RMB-48 with options: (1) Enclosure with one 48VDC Fan Filter Door Or (1) Enclosure with one 48VDC Heat Exchanger Door
2
E3/4
3 4
LVD
TB3 COMMON - A
5
TB4 COMMON - B
6
HOT
7
RIBBON 1-16
8 9
G
10 11
BBX 8 CKT LOAD CENTER
12
1
13
60A 875-054-20
3
30A
4
1 2 E2
5
20A
6
1 2 E1
L1 L2 GND L1 L2 GND
TB1 OUTPUT (-)
Module 1
OUTPUT (+)
TB2
E8
WATER INTRUSION 15
E7
16
AC FAIL
17
RECT. MAJOR
18
RECT. MINOR
19
HVA
20
LVA
21
FUSE/BREAKER
22
BAT COMPARTMENT FAN
23
COOLING SYSTEM MAJOR
24
COOLING SYSTEM MINOR
25
75A
1ALM 2ALM 31 2 P7 MJR P8 MNR P9 ACF
Module 3
8
TAMPER 874-978-20
Module 2
15A
7
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
TAMPER
TS COM TS 1 TS 2 RSM 48/10 - 19" CABINET RSM 48/10 -3 W/O SUPI COMMON AUX -48v RSM 48/10 SUPI NC LVD NC LVD C LVD B FU/BRKR FUSE ALM B FU/BRKR C 16 POS. RIBBON CABLE BRKR ALM LVA 1ALM 2ALM 32 1 FUSE ALM A P8 EXMJR LVA C P9 EXMNR NC HVA HVA C P10 LVD RSM MAJOR MINOR P11 LVA RSM MINOR MINOR C P12 HVA HV ALARM MAJOR P13 SUPI AC FAIL MAJOR C P14 FU/BR SUP'Y FAIL AC FAIL LV ALARM AC FAIL C SLAVE IN LVD A COMMON RIBBON 1-16 RIBBON 1-16 874-933-21
Surge Protector 3W+G AC Gen Inlet GFCI outlets Battery Heater Mat AC Lights RSM 48/10 3 Modual Rectifier Shelf (W/GMT Fuse Distribution) Alarm Terminal Board Enclosure Intrusion Sensors Water Intrusion Sensor
TAMPER
100A
12V BATTERY
12V BATTERY
875-064-20
875-059-20
875-110-20
TEMP SENSE 875-108-20
875-071-20
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
875-068-20
875-063-21
75A
75A
12V BATTERY
100A AC Service Load Center 8-position
875-063-20
TAMPER
GEN INLET
1 2 3 4 5 6 11 16
ENCL GROUNDBAR 1
875-125-20
Gnd N L2 L1
15 14 13 12 10 9 8 7
1 2 3 4
875-110-20
1 2 3
ALM 1 C ALM 1 ALM 2 C TB 3 ALM 2
TB4
RSM 48/10 RLY ALM MDL -002
NEUT
75A
GND
Line 1 Line 2
GND
Neutral
SURGE PROTECTOR 3W+G
14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Isolated Bus Bar
LVD
TB2 HOT - B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
COM
1
RSM 48/10 FUSE MODULE E1/2
TB1 HOT - A
(2) Battery Storage Units
R? PCBA - ALARM CROSS CONNECT
875-404-20
HOT
5A
N
2
PWM TACH (+) -48v
N
Customer Provided Hook up for meter
875-055-20
HOT LOAD
LIGHT RECPT 2
L2
PWM TACH (+) -48v
L2
L1
Gnd Bshg
L1
APW 48VDC HEAT EXCHANGER
5A FUSE
N
HOT
YEL BLU RED BLK YEL BLU RED BLK
GFCI OUTLET LINE G
METER
N
1 2
PWR (+) PWR (-)
DC FAN
FAN CONTROL (Heat Exchanger)
L2
N
L1
DOOR SW
1 2
1 2 3 4
Fan1 (+) Fan1 (-) Fan2 (+) J2 J1 Fan2 (-)
DC HEAT EXCHANGER Cooling Option
APW HEAT EXCH TEMP CONTL TSTAT
6 3 4 1 2 5
Fan-Filtered Cooling Option
12V BATTERY
ML2
TAMPER
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
Battery Compartment Fan TRAY GROUND
EARTH GROUND
75A
1ST BATTERY STORAGE UNIT
75A
TAMPER 875-110-20
TEMP SENSE
12V BATTERY
12V BATTERY
DRAWN
12V BATTERY
ML2
ENGR
TRAY GROUND
BATT HEATER
FLOAT SW
5-15-06
D. JOHNSTON
5-15-06
ALPHA TECHNOLOGIES
MANUF
TAMPER
Q.A. PLOTTED ON:
875-059-20
D. JOHNSTON
CHK
875-064-20
12V BATTERY
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE
TO CUSTOMER INSTALLED GROUND RING
100A
1.
875-063-21
BATT HEATER
2ND BATTERY STORAGE UNIT
TITLE: 25-May-2007 14:31:09
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W05.SCH
SIZE:
D
SHEET
C 5
OF
12
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
FLORESCENT LAMP
SECONDARY SIDE CHAMBER
SECONDARY ENCLOSURE FLORESCENT LAMP
FLORESCENT LAMP
FLORESCENT LAMP
AIR CONDITIONER - DC FLORESCENT LAMP
Evap Temp Sensor
COMMNET CDM 75A
1
3 4
ALARM
6
GMT7
HOT
7
GMT8
8 9 875-109-20
10
12 13
OUTPUT (+)
TB2
9
11
875-125-20
GND 875-125-21
ENCL GROUNDBAR 1
Neutral
ALM 1 C ALM 1 ALM 2 C TB 3 ALM 2
TB4 TS COM TS 1 TS 2 COMMON NC NC LVD B FUSE ALM B BRKR ALM FUSE ALM A NC RSM MAJOR RSM MINOR HV ALARM AC FAIL SUP'Y FAIL LV ALARM LVD A COMMON
Module 5
75A
1 2 3 4
RSM 48/10 - 23" CABINET RSM 48/10 SUPI
16 POS. RIBBON CABLE 1ALM 2ALM 32 1 P8 EXMJR P9 EXMNR P10 LVD P11 LVA P12 HVA P13 SUPI P14 FU/BR SLAVE IN
75A
15 14 13 12 874-978-20 11 10 9 8 7 6 5 4 3 2 1
AUX -48v LVD LVD C FU/BRKR FU/BRKR C LVA LVA C HVA HVA C MINOR MINOR C MAJOR MAJOR C AC FAIL AC FAIL C
RSM 48/10 RLY ALM MDL -002
NEUT GND
Line 1 Line 2
1 2 3 4 5 6 11 16
E7
875-108-20
Module 4
12
15 14 13 12 10 9 8 7
WATER INTRUSION 15
1ALM 2ALM 31 2 P7 MJR P8 MNR P9 ACF
Module 3
1 2 3
E8
Module 2
10
TAMPER
16
AC FAIL
17
RECT. MAJOR
18
RECT. MINOR
19
HVA
20
LVA
21
FUSE/BREAKER
22
BAT COMPARTMENT FAN
23
COOLING SYSTEM MAJOR
24
COOLING SYSTEM MINOR
25
COMPRESSOR
J1
PWR (+) PWR (-)
Remote Temp
(+) MML (-)
J11
1 2
HOT LOAD
3
N
4 5 6 7 8 9
LIGHT RECPT 2 N
10
HOT
11 12 13
G
14
875-056-20
15 TAMPER
16 17 18 19 20 21 22
23 BAT COMPARTMENT FAN 24 COOLING SYSTEM MAJOR 25 COOLING SYSTEM MINOR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Battery heater Mats AC Lights RSM 48/10 5 Modual Rectifier Shelf KTK Panel Distribution 2 Alarm Terminal Boards Enclosure Intrusion Sensors Water Intrusion Sensor
875-063-20
TAMPER
TAMPER
RIBBON 1-16 RIBBON 1-16 875-110-20
TAMPER
75A
75A
TEMP SENSE
12V BATTERY
12V BATTERY
TAMPER
12V BATTERY
ML2
TAMPER
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
Battery Compartment Fan TRAY GROUND ML2
EARTH GROUND
1 2 3 4 1 2 3
(+) (-)
1 2 3 4
(+) (-)
75A
875-110-20
875-110-20
875-059-20
875-071-20
FEED CURRENT LIMITED SURGE ARRESTOR
TO CUSTOMER INSTALLED GROUND RING
875-125-23
875-059-20
MAIN GROUNDBAR - SIDE CHAMBER
875-125-22
12V BATTERY
GFCI outlets
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
874-933-21
100A
Surge Protector 3W+G 30A Max CB Limited
R? PCBA - ALARM CROSS CONNECT
N
HOT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
HOT
15A
L1 L2 GND
OUTPUT (-)
Module 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
875-068-20
8
1 2 E2
15A
TB1
875-064-20
7
20A
L1 L2 GND
875-063-21
6
1 2 E1
TAMPER
875-054-20
5
14
TAMPER
Customer Provided Hook up for Generator Inlet
EUSERC Meter w/60A FBX 12-position distribution
G
Battery Compartment Fan
1 2 3
Fan1 (+) Fan1 (-) J1
J2
PWR (+) PWR (-)
CL = ALM PWR (+) C J3 J4 PWR (-) OP = ALM
1 2 1 2
100A
TAMPER
DC FAN
12V BATTERY
12V BATTERY ML2
12V BATTERY
1ST BATTERY STORAGE UNIT
ML2
TAMPER TRAY GROUND
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW. 2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
12V BATTERY
BATT HEATER FLOAT SW
GROUNDBAR - SIDE CHAMBER 2
875-259-20
5
GMT6
11
4 30A
2 Battery Storage Units
COM
N
2
GMT3
60A
3
HOT
75A
GMT1
1 2
Cond Temp Sensor
GFCI OUTLET LINE G
R? PCBA - ALARM CROSS CONNECT
GMT5
L2
N
COND FANS
AC Gen Interlock (Customer provided feed)
KTK2
GMT4
L1
2 Side Chambers
LIGHT RECPT 2
KTK1
Gnd Bshg
G
2 Enclosures with two 48VDC Air Cond Doors
ML3
GMT2
BBX 12CKT LOAD CENTER
A B C
HOT
BAT (-) BAT (+)
60A
N
RMT
Model RMB-48 with options:
875-068-20
N
LIGHT RECPT 2
1 J12 PWR (+) 2 PWR (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
875-055-21
RECT (-) RECT (+)
G
LOCAL
20A
875-110-20
HOT LOAD
SETPOINT
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
SPEED CONTROL BOARD
AIR COND TEMP CONTROL Evap temp
875-089-20
875-071-20
HOT
875-353-20
ENCL GROUNDBAR 2
875-258-20
N
ML2
COM
L2
L1
N
FUSE DISCONNECT
20A
GFCI OUTLET LINE G
875-056-20
SURGE PROTECTOR 30A MAX CB LIMITED 3W+G
DOOR SW
DOOR SW
COMPRESSOR
Remote Temp
PWR (+) PWR (-)
J11
(+) MML (-)
SETPOINT
1 J12 PWR (+) 2 PWR (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
DOOR SW
DOOR SW
L2
L1
N
COND FANS
EVAP FANS
Evap Temp Sensor
875-089-20
875-055-20
G
A B C
METER
LIGHT RECPT 2 HOT
RMT
DOOR SW
AIR CONDITIONER - DC
Cond Temp Sensor
Gnd Bshg
N
LOCAL
J1
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
Evap temp
SPEED CONTROL BOARD
AIR COND TEMP CONTROL
TAMPER
USERC METER BASE
DOOR SW
FLORESCENT LAMP
EVAP FANS
1.
BATT HEATER
2ND BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:32:01
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__w06.SCH
SIZE:
D
SHEET
C 6
OF
12
PRIMARY ENCLOSURE
AIR CONDITIONER - DC EVAP FANS
AIR COND TEMP CONTROL
TAMPER
20A
PWR (+) PWR (-)
CL = ALM C J3OP = ALM
J4
FAN CONTROL - 2
875-089-20
HOT
G
(+) (-)
DC FAN
P1 - ML2
P2 - MML2
P5 - MML9 -48v COM TACH PWM -48v COM TACH PWM
1 2 3
DC FAN
FAN CONTROL (Heat Exchanger)
5 8 9 6 3 2 7 4 1
1 2
PWR (+) PWR (-)
Fan1 (+) Fan1 (-) Fan2 (+) J2 J1 Fan2 (-)
P3- MML6
-48v COM
1 2
1 2 3 4
DC HEAT EXCHANGER Cooling Option
APW HEAT EXCH TEMP CONTL TSTAT
2 1
COND FANS
(+) (-)
MAJOR MAJOR MINOR MINOR
Fan-Filtered Cooling Option
6 3 4 1 2 5
COMPRESSOR
PWR (+) PWR (-)
Remote Temp J1
(+) MML (-)
A B C
Cond Temp Sensor
N
LIGHT RECPT 2 N
RMT
TAMPER
875-404-20
HOT LOAD
LOCAL
875-060-20
HOT
J11
N
1 J12 PWR (+) 2 PWR (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
875-055-20
GFCI OUTLET LINE G
SETPOINT
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
Evap temp
COM -48v
FLORESCENT LAMP
SPEED CONTROL BOARD
DOOR SW
DOOR SW
Evap Temp Sensor
1 2
FLORESCENT LAMP
YEL BLU RED BLK YEL BLU RED BLK
APW 48VDC HEAT EXCHANGER PWM TACH (+) -48v PWM TACH (+) -48v
5A FUSE
5A
Model: RMB-48 650W Cordex with options: Customer Provided 240VAC 60Hz Input Power N
L1
L2
GMT FUSE -48VDC A/B 10/10
(+) A
L2
2
60A
3 4
20A
TB3 HOT - B TB4 COMMON - B
TB2 COMMON - A
(+) B
Fuse Fail A COM NC Fuse Fail B COM NC
875-589-20
1
(-) B
1st Encl GFCI
L1
TB1 HOT - A
875-590-20
(-) A
240V- TB3
16
Encl TAMPER
5
17
6 7
15A
18 19
8
2
3
4
L1 L2 GND
TB3
CAN OUT
5
COOLING SYS 1 MAJOR 24
6
COOLING SYS 1 MINOR 25 7
Module 2
Module 4
8
1
9
4 Module 650W Cordex Shelf with CB Dist and LVD GMT Fuse Panel 10A/10B, -48VDC 120VAC 60Hz GFCI outlets 120VAC 60Hz Lights Enclosure Intrusion Sensors Enclosure Alarm Terminal Board
GRN
GRN GRN GRN GRN
3
11
4
12
5
Cordex 48VCD 650w 4 Module Shelf
75A
(OPTIONAL)
875-110-20
12V BATTERY
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
875-068-20
1 2
75A
875-071-20
875-059-20
100A
12V BATTERY
RED
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
875-110-20
75A
12V BATTERY
Surge Protector 3W+G 30A Max CB Limited
2
10
-48VDC POSITIVE GND SYSTEM BLACK (-) HOT RED (+) COMMON
12V BATTERY
23
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
8-Space AC Load Center
875-108-20
SURGE PROTECTOR 30A MAX CB LIMITED 3W+G
22 BAT COMP FAN
75A
GND
ENCL GROUNDBAR 1
Neutral
21
Module 1 TB4
Module 3
Line 1 Line 2
T2
HOT
1 2
L1 L2 GND
T1
75A
GND
V1
(-) LOAD 1 2
BBX 8 CKT LOAD CENTER
D2
(-) BATT
50A 50A 20A 20A 875-588-20
15 16 17 18 19 20 21 2223 HOT
1
(+) COMMON
NEUT
20
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 Battery Storage Unit
COM
GND
Enclosure with 48VDC Air Cond Door
PCBA - ALARM CROSS CONNECT GRN (Cabinet Alarm) GRN 1 1 1 2 2 3 3 2 4 4 5 5 3 6 6 7 7 BRN (GMT Fuse Option)4 GRN 8 8 9 9 5 10 10 11 11 6 12 12 13 13 7 14 14 15 15 8 16 16 17 17 9 GRN BAT COMP FAN 2 18 18 19 19 2E COOLING MAJOR 10 20 20 21 21 2E COOLING MINOR 11 22 22 23 23 GRN 2Encl TAMPER 12 24 24 25 25 13 26 26 27 27 14 28 28 29 29 GRN WATER INTR (option) 15 30 30
1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
1.
DC FAN TAMPER
Battery Compartment Fan
ML2
TRAY GROUND
TAMPER
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
BATTERY STORAGE UNIT
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 5-Jun-2007
11:07:55
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
REV:
044-001-05
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
DRAWING NO:
FILE REF:
04400105___C__W07.SCH
SIZE:
D
SHEET
C 7
OF
12
FLORESCENT LAMP
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
AIR CONDITIONER - DC EVAP FANS
Evap Temp Sensor
N
HOT
HOT LOAD
J1
TAMPER
A B C
COMPRESSOR
Remote Temp
(+) MML (-)
TAMPER
PWR (+) PWR (-)
SETPOINT
RMT
J11
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
875-055-20
GFCI OUTLET LINE G
LOCAL
SPEED CONTROL BOARD
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
FLORESCENT LAMP
1 J12 PWR (+) 2 PWR (-)
DOOR SW
DOOR SW
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor
N
AIR CONDITIONER - DC 20A
EVAP FANS
Evap Temp Sensor
A B C
COMPRESSOR
RMT
PWR (+) PWR (-)
Remote Temp
LOCAL
J1
G
J11 (+) MML (-)
875-089-20
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
HOT
1 J12 PWR (+) 2 PWR (-)
N
SETPOINT
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
LIGHT RECPT 2
SPEED CONTROL BOARD
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor
20A 875-089-20
Customer Provided 240VAC 60Hz Input Power N
L1
L2
30A
5
15A
NEUT
8
16
2 1
Encl TAMPER
17
ALM OUTPUT 1 ALM OUTPUT 2 ALM OUTPUT 3 ALM OUTPUT 4 ALM OUTPUT 5 ALM OUTPUT 6 ALM OUTPUT 7 ALM OUTPUT 8 ALM OUTPUT 0
(+) GND RETURN
18 19 20 21 22
GND
875-528-23
875-527-20 Cordex 48 1kw 6 Mod Bulk Shelf TB1 1 L1 2 L2 OUTPUT (-) Module 1 GND OUTPUT (+) TB2 1 L1 2 L2 Module 2 GND ENCL GROUNDBAR 1
BBX 8 CKT LOAD CENTER
GND SURGE PROTECTOR 3W+G
Module 4
Module 5
COOLING SYS 1 MINOR
25
E2
2 3
GEN INLET
4
-48VDC POSITIVE GND SYSTEM BLACK (-) HOT RED (+) COMMON
5
8-Space AC Load Center Surge Protector 3W+G 6 Module 1KW Cordex Shelf with Controller 584 DIST Panel with Load LVD, 16 BKR POS 120VAC 60Hz GFCI outlets 120VAC 60Hz Lights Enclosure Intrusion Sensors Enclosure Alarm Terminal Board
GRN
YEL RED YEL GRN RED YEL ORG BLU
RED
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
120A
12V BATTERY
12V BATTERY
875-110-21
12V BATTERY
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
875-068-20
125A 875-071-20
875-059-20
ENCL GROUNDBAR 1
24
1
Module 6
12V BATTERY
COOLING SYS 1 MAJOR
E1
120A
Neutral
Module 3
23
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 Battery Storage Unit
CAN OUT
Line 1 Line 2
BAT COMP FAN
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
HOT
7
30A
RS232
Single Side Chamber
120A
6
240V - TB2
8 7 6 5
36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
240V- TB1
RS485
175 A
4
NET CAN 1
Input (-) Input (+)
3
DIGITAL INPUTS
(BREAKERS OPTIONAL)
TEMP 2 (-) TEMP 2 (+) TEMP 1 (-) TEMP 1 (+)
60A
D8 D8 D7 D7 D6 D6 D5 D5 D4 D4 D3 D3 D2 D2 D1 D1
2
(-) CHARGE
L2
-48V BATTERY
1
100A 100A
L1
584 PANEL 48V CXC LLVD 16CB
R?
1st Encl GFCI
875-587-20
Enclosure with two 48VDC air cond doors
COM
GND
Model: RMB-48, 1K CORDEX with options:
PCBA - ALARM CROSS CONNECT GRN (Intrusion) GRN 1 1 1 RED RED(Cool MAJ 2 2 YEL (Cool Min) YEL 3 3 2 ORG (Cust MAJ) ORG 4 4 BLU (Cust Min) BLU 5 5 3 6 6 7 7 GRN (Jumper) 4 GRN 8 8 9 9 ORG (Jumper) 5 ORG 10 10 11 11 BLU (Jumper) 6 BLU 12 12 13 13 7 14 14 15 15 8 16 16 17 17 BAT COMP FAN 29 YEL 18 18 19 19 2E COOLING MAJOR 10 20 20 21 21 2E COOLING MINOR 11 22 22 23 23 2Encl TAMPER 12 GRN 24 24 25 25 COOLING SYS 2 MAJ 13 RED 26 26 27 27 YEL COOLING SYS 2 MIN 14 28 28 29 29 GRN WATER INTR (option) 15 30 30
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
1.
DC FAN TAMPER
Battery Compartment Fan
ML2
TRAY GROUND
TAMPER
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:35:39
SCHEMATIC RADIUM MINIBAY SYSTME
ISSUED DATE:
REV:
044-001-05
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
DRAWING NO:
FILE REF:
04400105___C__W08.SCH
SIZE:
D
SHEET
C 8
OF
12
FLORESCENT LAMP
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
AIR CONDITIONER - DC
SECONDARY ENCLOSURE
FLORESCENT LAMP
EVAP FANS
Evap Temp Sensor
AIR CONDITIONER - DC
N
TAMPER COMPRESSOR
PWR (+) PWR (-)
COND FANS
HOT
AIR CONDITIONER - DC 20A
COND FANS
EVAP FANS
Evap Temp Sensor
20A
875-353-20
A B C
COMPRESSOR
RMT
PWR (+) PWR (-)
LOCAL Remote Temp
875-353-20
(+) MML (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
875-089-20
J11
Cond Temp Sensor
J1
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
Evap temp
SPEED CONTROL BOARD
AIR COND TEMP CONTROL
G
SETPOINT
A B C
COMPRESSOR
Remote Temp
RMT
A B C
Cond Temp Sensor
LIGHT RECPT 2
PWR (+) PWR (-)
SPEED CONTROL BOARD
G
LOCAL
J11 (+) MML (-)
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
HOT
SETPOINT
N
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0 1 J12 PWR (+) 2 PWR (-)
LIGHT RECPT 2
J1
875-089-20
AIR COND TEMP CONTROL Evap temp
SPEED CONTROL BOARD
EVAP FANS
Evap Temp Sensor
RMT
1 J12 PWR (+) 2 PWR (-)
20A
HOT LOAD
N
LOCAL Remote Temp
AIR CONDITIONER - DC
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
J1
HOT
(+) MML (-)
N
AIR COND TEMP CONTROL Evap temp
N
J11
Cond Temp Sensor
TAMPER
EVAP FANS
Evap Temp Sensor
GFCI OUTLET LINE G
SETPOINT
COND FANS
DOOR SW
DOOR SW
TAMPER
COMPRESSOR
J1
PWR (+) PWR (-)
Remote Temp
(+) MML (-)
J11
A B C
FLORESCENT LAMP
1 J12 PWR (+) 2 PWR (-)
HOT LOAD
RMT
TAMPER
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
HOT
SETPOINT
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
N
LOCAL
875-055-21
875-055-20
GFCI OUTLET LINE G
SPEED CONTROL BOARD
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
FLORESCENT LAMP
1 J12 PWR (+) 2 PWR (-)
DOOR SW
DOOR SW
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor ML3
20A
GMT FUSE -48VDC A/B 10/10 (-) A
L1
L2
(+) B
Fuse Fail B COM NC
875-587-20
30A
(Optional) AC Gen Inlet
5 6 7 8 9 10
240V M3&M4 25A 15A 15A
2 1
8 7 6 5
36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
240V M1&M2
25A
DIGITAL INPUTS
NET CAN 1
Input (-) Input (+)
4
TEMP 2 (-) TEMP 2 (+) TEMP 1 (-) TEMP 1 (+)
3
D8 D8 D7 D7 D6 D6 D5 D5 D4 D4 D3 D3 D2 D2 D1 D1
60A
RS485 RS232
11 12
16
Encl TAMPER
17
ALM OUTPUT 1 ALM OUTPUT 2 ALM OUTPUT 3 ALM OUTPUT 4 ALM OUTPUT 5 ALM OUTPUT 6 ALM OUTPUT 7 ALM OUTPUT 8 ALM OUTPUT 0
(+) GND RETURN
(-) CHARGE
2
-48V BATTERY
L2
50A 50A
1
584 PANEL 48V CXC LLVD 8CB
L1
1st Encl GFCI
BBX 12CKT LOAD CENTER
18 19 20 21
NEUT
22
GND
875-594-20
COOLING SYS 1 MAJOR
24
COOLING SYS 1 MINOR
25
1 2
OUTPUT (+)
M2
Module 3 M4
L1 L2
175 A
COOLING SYS 2 MIN 14
GRN
15 16
Encl TAMPER
17 18 19 20 21
YEL
22
RED YEL GRN RED YEL ORG BLU BRN
5
RED
Module 4
CORDEX 48 1800W 4 MOD BULK SHELF
BAT COMP FAN
23
COOLING SYS 1 MAJOR
24
COOLING SYS 1 MINOR
25
2 Battery Storage Unit 12-Space AC Load Center Surge Protector 3W+G 4 Module 1.8KW Cordex Shelf with Controller 584 DIST Pandel with Load LVD, 8 BKR POS 120VAC 60Hz GFCI outlets 120VAC 60Hz Lights Enclosure Intrusion Sensors 2 Enclosure Alarm Terminal Boards
RED
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
875-110-21
875-125-22
875-071-20
1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN TAMPER
125A
12V BATTERY
Battery Compartment Fan
ML2
TRAY GROUND
12V BATTERY ML2
TAMPER
12V BATTERY
12V BATTERY
875-110-21
12V BATTERY
1 2
875-059-20
12V BATTERY
875-110-21
12V BATTERY
120A
875-068-20
125A
875-068-20
120A
12V BATTERY
Single Side Chamber
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
120A
875-059-20
ENCL GROUNDBAR 1
COOLING SYS 2 MAJ 13
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
4
-48VDC POSITIVE GND SYSTEM BLACK (-) HOT RED (+) COMMON
M3
L1 L2
3
DC GEN INLET
Module 2
GND GND
875-125-21
E2
2
HOT
L1 L2
E1
12
120A
1 2
OUTPUT (-)
Module 1
CAN OUT
875-125-20
Neutral
ENCL GROUNDBAR 1
Line 1 Line 2
875-593-20
M1
L1 L2
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1
120A
1 2
SURGE PROTECTOR 3W+G
23
Cordex 48VCD 1.8kw Module Bulk Shelf 1 2
GND
BAT COMP FAN
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Double Wide Enclosure with (4) 48VDC Air Cond Doors
PCBA - ALARM CROSS CONNECT
875-071-20
N
TB4 COMMON - B
875-589-21
GND
TB3 HOT - B
TB2 COMMON - A
Model: RMB-48 1.8K CORDEX with options:
875-529-20
PCBA - ALARM CROSS CONNECT GRN (Intrusion) GRN 1 1 1 RED RED(Cool MAJ 2 2 YEL (Cool Min) YEL 3 3 2 ORG (Cust MAJ) ORG 4 4 BLU (Cust Min) BLU 5 5 3 6 6 7 7 GRN (Jumper) 4 GRN 8 8 9 9 5 BRN (GMT Fuse Optional) ORG 10 10 11 11 BLU (Jumper) 6 BLU 12 12 13 13 7 14 14 15 15 8 16 16 17 17 2E BAT COMP FAN 9 YEL 18 18 19 19 2E COOLING MAJOR 10 20 20 21 21 2E COOLING MINOR 11 22 22 23 23 2Encl TAMPER 12 GRN 24 24 25 25 COOLING SYS 2 MAJ 13 RED 26 26 27 27 YEL COOLING SYS 2 MIN 14 28 28 29 29 GRN WATER INTR (option) 15 30 30
COM
(-) B
Fuse Fail A COM NC
HOT
240VAC 60Hz Input Power
TB1 HOT - A
ENCL GROUNDBAR 1
(+) A
COM
Customer Provided
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
1 2 3 4 1 2 3
(+) (-)
DC FAN
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING. 1.
Battery Compartment Fan
TRAY GROUND
TAMPER
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
TAMPER
2ND BATTERY STORAGE UNIT
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
1ST BATTERY STORAGE UNIT
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:36:47
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
REV:
044-001-05
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
DRAWING NO:
FILE REF:
04400105___C__W09.SCH
SIZE:
D
SHEET
C 9
OF
12
PRIMARY ENCLOSURE
Factroy set to 40C open on rise
875-126-20
FLORESCENT LAMP
ADJ. TSTAT
GND
N
L1
DOOR SW
L2
2 3 4 5 6 7 8
BBX 8 CKT LOAD CENTER
L1
9
1
L2
2
60A
10 11
3 4
15A
TAMPER
12
TAMPER
13
5
14
6
15
7
16
8 NEUT
17 18
GND
19 LINE G
20
N
21
HOT
HOT LOAD GFCI2
22 N
23 24
GROUNDBAR - ENCL
875-075-20
25
5A
INLINE FUSE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
COM
1
Customer Provided Input
HOT
PCBA - ALARM CROSS CONNECT
RMB with 115VAC Heat Exchanger (OR 115VAC Fan Filter) Door
1 2 3 4
Model RMB with options:
5 6
1 Enclosures with 115VAC Heat Exchanger (or Fan Filter) Doo)
7
Battery Riser
8 9
60A FBX 8-position Distribution
10
Alarm Terminal Boards
11 12
Enclosure Intrusion Sensors
13 14
ENCLOSURE OVERTEMP (ADJ) - open on alarm
15
WATER INTRUSION - open on alarm (optional)
16
TAMPER - open on alarm
GFCI outlet & Enclosure Light Enclosure Roof Vent Kit
17 18 19 20 21 22 23 24 25
Heat Exchanger (or Fan Filter Door) Option CLOSE AT 30C / 85F
TSTAT
875-128-20
1 2 3
FAN - AC L N GND
ML3 875-076-21
CUSTOMER INSTALLED GROUND RING
1 2 3
EARTH GROUND
Battery Compartment Fan COOLING FAN 875-076-20 1 L 2 N 3 GND
FAN - AC
MML3
CLOSE AT 30C / 85F
FAN - AC L N GND
5A
INLINE FUSE
FLOAT SW
TSTAT
BATTERY TRAY GND
TAMPER
BATTERY STORAGE UNIT
TAMPER
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW. 2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING. 1.
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. Johnston
5-15-06
D. Johnston
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:37:19
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W10.Sch
SIZE:
D
SHEET
C 10 OF 12
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
SECONDARY SIDE CHAMBER
SECONDARY ENCLOSURE NOTE: OVER TEMP ALARM IS FACTORY SET TO 40C
NOTE: OVER TEMP ALARM IS FACTORY SET TO 40C
875-126-20 TAMPER
875-126-20 ADJ. TSTAT
ADJ. TSTAT TAMPER TAMPER
COND FANS
4 5 6
AC AIR COND
7 8 9
60A
10
N
Gnd Bshg
11 12
875-259-20
13
L1
14 15 16
1
L2
17
60A
2
18
3
19
4
20 #1 240V AC Air Cond
5
21
15A
6
22 #2 240V AC Air Cond
7
23
15A
8
Dual Enclosures with two 240VAC Air Cond Door
24
L2
L1
1 2 G
3 4 5
OUTLET 1X240V
6
1 2 COND FANS
3 4
AC AIR COND
5 6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14 ENCL OVERTEMP (ADJ) - open on alarm
14
15
15
16 TAMPER - open on alarm
16
17
17
18
18
19
19
20
20
21
21
22
22
23
23
24 Cooling system Major - open on alarm
24
25
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Dual Battery Riser
1 2
EUSERC Meter w/60A FBX 8-position Distribution
3
Surge Protector 3W+G
4 5
2 Alarm Terminal Boards
6
Enclosure Intrusion Sensors
7 8
Fiber Managment Panel
9
Enclosure Roof Vent Kit
10 11 12 13 14
ENCL OVERTEMP (ADJ) - open on alarm
15 16
TAMPER - open on alarm
17 18 19 20 21 22 23 24
Cooling system Major - open on alarm
25
SURGE PROTECTOR 3W+G
GROUNDBAR - ENCL
GROUNDBAR - ENCL
Line 1 Line 2
GND
Neutral
GROUNDBAR - ENCL
GND
NEUT
25
Dual Side Chambers
PCBA - ALARM CROSS CONNECT COMPRESSOR
3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
COM
COMPRESSOR
L2
L1
875-258-20
G
2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
HOT
1
L2
L1
ALARM
EVAP FANS PCBA - ALARM CROSS CONNECT
OUTLET 1X240V
BBX 8 CKT LOAD CENTER
Model RMB with options:
MML2 EVAP FANS
COM
ALARM
Gnd Bshg
60A FUSE DISCONNECT
875-315-22 MML2
METER
G
875-377-20
HOT
L2
L1
N
USERC METER BASE
875-377-20 875-315-22
N
TAMPER
RMB with 240VAC Air Cond
TAMPER
TAMPER
875-125-23
875-125-22
MAIN GROUNDBAR - SIDE CHAMBER
875-125-20
875-125-21
3. SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
1ST BATTERY RISER
2ND BATTERY RISER
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING.
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
1.
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE DRAWN
D. JOHNSTON
5-15-06
D. JOHNSTON
5-15-06
CHK ENGR
ALPHA TECHNOLOGIES
MANUF Q.A. PLOTTED ON:
TITLE: 25-May-2007 14:38:06
SCHEMATIC RADIUM MINI BAY SYSTEM
ISSUED DATE:
DRAWING NO:
REV:
044-001-05 FILE REF:
04400105___C__W11.Sch
SIZE:
D
SHEET
C 11 OF 12
FLORESCENT LAMP
PRIMARY SIDE CHAMBER
PRIMARY ENCLOSURE
AIR CONDITIONER - DC EVAP FANS
Evap Temp Sensor
N
HOT
HOT LOAD
J1
TAMPER
A B C
COMPRESSOR
Remote Temp
(+) MML (-)
TAMPER
PWR (+) PWR (-)
SETPOINT
RMT
J11
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
875-055-20
GFCI OUTLET LINE G
LOCAL
SPEED CONTROL BOARD
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
FLORESCENT LAMP
1 J12 PWR (+) 2 PWR (-)
DOOR SW
DOOR SW
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor
N
AIR CONDITIONER - DC 20A
EVAP FANS
Evap Temp Sensor
A B C
COMPRESSOR
RMT
PWR (+) PWR (-)
Remote Temp
LOCAL
J1
G
J11 (+) MML (-)
875-089-20
1 J10 MINOR 2 MINOR 3 MAJOR 4 MAJOR
HOT
1 J12 PWR (+) 2 PWR (-)
N
SETPOINT
18C 23C SHDOWN ALARM 28C 33C 38C NC NC MINOR N0 MAJOR N0
LIGHT RECPT 2
SPEED CONTROL BOARD
AIR COND TEMP CONTROL Evap temp
COND FANS
Cond Temp Sensor
20A 875-089-20
GMT FUSE -48VDC A/B 10/10
N
L1
(+) A
L2
TB1 HOT - A
(-) B
TB3 HOT - B
TB2 COMMON - A
Fuse Fail B COM NC
TB4 COMMON - B
875-589-21
(+) B
PCBA - ALARM CROSS CONNECT GRN (Intrusion) GRN 1 1 1 RED RED(Cool MAJ 2 2 YEL (Cool Min) YEL 3 3 2 ORG (Cust MAJ) ORG 4 4 BLU (Cust Min) BLU 5 5 3 6 6 7 7 GRN (Jumper) 4 GRN 8 8 9 9 GMT FUSE MAJ 5 ORG 10 10 11 11 Cust Min (Option) 6 BLU 12 12 13 13 7 14 14 15 15 8 16 16 17 17 YEL BAT COMP FAN 2 (Jumper) 9 18 18 19 19 10 20 20 21 21 11 22 22 23 23 2Encl TAMPER (Jumper 12 GRN 24 24 25 25 COOLING SYS 2 MAJ 13 RED 26 26 27 27 YEL COOLING SYS 2 MIN 14 28 28 29 29 GRN WATER INTR (option) 15 30 30
Fuse Fail A COM NC
875-587-20
6
25A
7 8 9 10
240V M3&M4 25A 15A 15A
11 12
2 1
8 7 6 5
36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
240V M1&M2
NET CAN 1
Input (-) Input (+)
5
DIGITAL INPUTS
(BREAKERS OPTIONAL)
TEMP 2 (-) TEMP 2 (+) TEMP 1 (-) TEMP 1 (+)
30A
D8 D8 D7 D7 D6 D6 D5 D5 D4 D4 D3 D3 D2 D2 D1 D1
4
(Optional) AC Gen Inlet
RS485 RS232
30A
16
Encl TAMPER
17
ALM OUTPUT 1 ALM OUTPUT 2 ALM OUTPUT 3 ALM OUTPUT 4 ALM OUTPUT 5 ALM OUTPUT 6 ALM OUTPUT 7 ALM OUTPUT 8 ALM OUTPUT 0
(+) GND RETURN
(-) CHARGE
3
-48V BATTERY
2
60A
50A 50A
1
L2
584 PANEL 48V CXC LLVD 16CB
L1
1st Encl GFCI
BBX 12CKT LOAD CENTER
18 19 20 21
NEUT
22
GND
875-528-23
BAT COMP FAN
23
COOLING SYS 1 MAJOR
24
COOLING SYS 1 MINOR
25
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Cordex 48VCD 1.8kw Module Bulk Shelf
Alarm (Optional)
M3
-48VDC POSITIVE GND SYSTEM BLACK (-) HOT RED (+) COMMON
5
Module 3 M4
L1 L2
HOT
4
Module 2
L1 L2
3
GEN INLET
Side chamber riser 2 Battery Storage Unit 12-Space AC Load Center Surge Protector 3W+G 30A Max CB Limited (Alarm Contact Option) 4 Module 1.8KW Cordex Shelf with Controller 584 CB DIST Panel with Load LVD, 16 BKR POS 120VAC 60Hz GFCI outlets 120VAC 60Hz Lights Enclosure Intrusion Sensors
GRN
Enclosure Alarm Terminal Board GMT Fuse Panel A/B (Optional) AC Generator inlet (Optional) YEL RED YEL GRN RED YEL ORG BLU
RED
3.
Module 4
GND GND
875-068-20
120A
125A
12V BATTERY
12V BATTERY
12V BATTERY
875-110-21
875-059-20
ENCL GROUNDBAR 1
SURGE PROTECTOR 30A MAX CB LIMITED 3W+G
1 2
E2
2
CAN OUT
Neutral GND
1 2
OUTPUT (+)
M2
L1 L2
E1
875-071-20
Line 1 Line 2
OUTPUT (-)
Module 1
Single Side Chamber
120A
ENCL GROUNDBAR 1
875-593-20
M1
120A
1 2
L1 L2
1 175 A
1 2
A?
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Enclosure with two 48VDC air cond doors
COM
240VAC 60Hz Input Power GND
CSB: RMB-48, 1.8K CORDEX with options:
(-) A
Customer Provided
12V BATTERY
1 2 1 2
PWR (+) PWR (-) PWR (+) PWR (-)
Fan1 (+) Fan1 (-) J2 J1 CL = ALM C J3OP = ALM
J4
Battery Compartment Fan
ML2
1 2 3 4 1 2 3
(+) (-)
TAMPER
DC FAN
TAMPER
2. WHEN A SEALED MINIBAY EQUIPMENT ENCLOSURE IS USED TO HOUSE BATTERY PACKS, BATTERIES MUST BE VALVE REGULATED AND PROVITIONS SHOULD BE MADE FOR ADIQUIT HYDROGEN VENTING. 1.
BATT HEATER
TRAY GROUND
SYSTEMS WITH 1KW OR 1.8KW CORDEX RECTIFIER OPTIONS MAY REQUIRE AC GENERATOR INLET, TYPE IEC 309-2 WITH 60AMP MINIMUM BREAKER SIZE IF SYSTEM LOAD IS GREATER THEN 5KW.
BATTERY STORAGE UNIT 1
LENGTH OF WIRES CAN BE CUT TO FIT IF REQUIRED. REMAKE TERMINATE USING THE SAME ALPHA WORKMANSHIP & PARTS.
NOTE: UNLESS SPECIFIED OTHERWISE 120A
125A
12V BATTERY
12V BATTERY
12V BATTERY
ML2
DRAWN
D. JOHNSTON
9-14-06
D. JOHNSTON
9-14-06
CHK
875-110-21
12V BATTERY
TAMPER
ENGR MANUF
TAMPER
Q.A. PLOTTED ON:
TRAY GROUND
BATT HEATER
BATTERY STORAGE UNIT 2
ALPHA TECHNOLOGIES TITLE:
25-May-2007 14:38:55
SCHEMATIC RADIUM MINIBAY SYSTEM
ISSUED DATE:
REV:
044-001-05
EARTH GROUND TO CUSTOMER INSTALLED GROUND RING
DRAWING NO:
FILE REF:
04400105___C__W12.SCH
SIZE:
D
SHEET
C 12 OF 12