Transcript
Power Factor Correction
Reactive Energy Management Low Voltage Capacitors Complete reference of power ratings and application tables for 60 Hz networks
Increase in Power Availability
Enhanced safety
Improve your Business Performance
Make the most of your energy! Schneider Electric Capacitors Being a global specialist in Energy Management, Schneider Electric provides you the highest energy efficient, safest and most reliable Power Factor Correction solutions for your power distribution.
Contents
Product Overview
1
VarplusCan 2 - 9 • Range Overview & Technical Particulars • VarplusCan SDuty - Complete reference List • VarplusCan HDuty - Complete reference List • VarplusCan Dimension Details
2 3 5 8
VarplusBox 10 - 17 • Range Overview & Technical Particulars • VarplusBox HDuty - Complete reference List • VarplusBox Energy - Complete reference List • VarplusBox Dimension Details
9 11 13 14
Harmonic Application Tables 18 - 22 •Capacitor Selection Table with Detuned Reactor •VarplusCan HDuty + - Detuned Reactor + Contactor •VarplusCan Energy + - Detuned Reactor + Contactor •VarplusBox HDuty + - Detuned Reactor + Contactor •VarplusBox Energy + - Detuned Reactor + Contactor
18 19 20 21 22
Low Voltage Capacitors 60Hz
Product Overview
This document gives you the complete reference lists of LV Capacitors along with the Power ratings at different service voltages.
Schneider Electric Power Factor Correction LV Capacitors
For more detailed descriptions,
VarplusCan
VarplusBox
VarplusCan SDuty
VarplusBox HDuty
Icontinous = 1.5 IN Life Exp. = 100,000 Hrs
Icontinous = 1.8 IN Life Exp. = 130,000 Hrs
VarplusCan HDuty
VarplusBox Energy
Low Voltage components Catalogue April 2011.
Icontinous = 1.8 IN Life Exp. = 130,000 Hrs
Icontinous = 2.5 IN Life Exp. = 160,000 Hrs
1
Low Voltage Capacitors 60Hz
VarplusCan
Aluminum can capacitors specially designed and engineered to deliver a long working life with low losses in standard, heavy-duty and severe operating conditions. Suitable for Fixed and Automatic PFC, real time compensation,
Main features • Easy installation & maintenance • Optimized design for low weight, compactness and reliability to ensure easy installation. • Unique termination system that allows maintained tightening. • 1 point for mounting and earthing. • Vertical and horizontal position in case of Heavy Duty.
Techinical Particulars
Safety • Self-healing. • Pressure-sensitive disconnector on all three phases. PE90131
• • Finger-proof CLAMPTITE terminals to reduce risk of accidental •
Compacity • Optimized geometric design (small dimensions and low weight). Features • High life expectancy up to 160,000 hours • Very high overload capabilities and good thermal and mechanical properties.
• • Easy maintenance. •
VarplusCan
2
PE90130
PE90131
PE90132
SDuty
HDuty
Construction
Extruded aluminium can
Voltage range
230 V -525 V
230 V -830 V
Power range (three-phase)
1 - 30 kvar
5 - 50 kvar
Peak inrush current
Up to 200 x IN
Up toN 250 x I
Overvoltage
1.1 x UN As per IEC 60831- 1/2
Overcurrent
1.5 x IN
1.8 x IN
Mean life expectancy
Up to 100,000 h
Up to 130,000 h
Safety
Self-healing + pressure-sensitive disconnector + discharge device (50V/1min)
Dielectric
Zn/Al alloy
alloy with Wave cut & slope metallization
Impregnation
Non-PCB, Biodegradable soft resin
Non-PCB, Biodegradable sticky resin (dry)
Ambient temperature
-25°C to max 55°C
Protection
IP20
Mounting
1- point mounting upright
Terminals
• Double fast-on + cable ( < 10 kvar) • CLAMPTITE - Three-phase terminal with electric shock • STUD TYPE for more than 30 kvar
1 - point mounting upright, horizontal
VarplusCan SDuty
Low Voltage Capacitors
50Hz
Rated
240/260V
Voltage
Qn (kvar)
Case Code
Reference Number
260V
@260V
230V
240V
260V
@260V
2.1 2.7 4.2 5.4 6.3 8.3 10.9
2.5 3.2 4.9 6.4 7.4 9.7 12.8
5.5
2.3
2.5 3.3 5 6.5 7.5 10.0 13
3 3.8 6 7.7 8.8 11.7 15.3
6.6
38.7
HC
BLRCS021A025B24
2.5 3.9 5.0 5.8 7.6
7.1
3.0
10.9
4.6
14
6.0
16.4
6.9
21.6
9.2
28.4
12
50Hz
0.9 1.5 1.8 2.3 2.7 3.8 4.5 5.6 6.8 7.5
13.5 9.4 11.3 13.5 13.5 15.1 18.1 18.8 22.6 22.6 22.6
400V 1 1.7 2 2.5 3 4.2 5 6.3 7.5 8.3 9.3 10.4 12.5 13.9 15 16.7 20 20.8 22.2 25 27.7 50Hz
Qn (kvar)
3 5 7.5 10 12.5 14.3 15 16.9 18.2 20 25 26.8 28.5 30.3
In(A)
Qn (kvar)
415V
@400V
1.1
1.4
1.8
2.5
1.8
2.2
2.9
2.2
2.7
3.6
2.7
3.2
4.3
3.2
4.5
6.1
4.5
5.4
7.2
5.4
6.8
9.1
6.8
8.1
10.8
8.1
8.9
12
9
10.0
13.4
10.1
11.2
15
11.3
13.5
18
13.5
15.0
20.1
15.1
16.1
21.7
16.2
18
24.1
18.1
21.5
28.9
21.7
22.4
30
22.5
23.9
32.0
24.0
26.9
36.1
27.1
29.8
40.0
30.0
In(A) 3.9 6.6 9.8 13.1 16.4 18.8 19.7 22.2 23.9 26.2 32.8 35.2 37.4 39.8
8.5
50.1
HC
BLRCS027A033B24
13.1
77.3
HC
BLRCS042A050B24
17.0
100
LC
BLRCS054A065B24
19.5
116
NC
BLRCS063A075B24
26.1
152
NC
BLRCS083A100B24
34.1
200
SC
BLRCS109A130B24
µF
Case
Reference Number
(X3)
Code
60Hz
Qn (kvar)
380V
380/400/415V
µF (X3)
240V
Voltage
440V
In(A)
1.9
Rated
Voltage
Qn (kvar)
230V
10
Rated
60Hz
In(A)
60Hz
Qn (kvar)
3.6 6 9 12 15 17.2 18 20.3 21.8 24 30 32.2 34.2 36.4
380V 1.1
400V 1.2 2 2.4 3 3.6 5 6 7.5 9 10 11 12.5 15 17 18 20 24 25 27 30 33
In(A)
415V
@400V
1.3
1.7
6.6
EC
BLRCS010A012B40
2.2
2.9
11.3
DC
BLRCS017A020B40
2.6
3.5
13.3
DC
BLRCS020A024B40
3.2
4.3
16.6
DC
BLRCS025A030B40
3.9
5.2
19.9
DC
BLRCS030A036B40
5.4
7.3
27.8
HC
BLRCS042A050B40
6.5
8.7
33.1
HC
BLRCS050A060B40
8.1
10.8
41.8
HC
BLRCS063A075B40
9.7
13
49.7
LC
BLRCS075A090B40
10.7
14.4
55.0
LC
BLRCS083A100B40
12.0
16
61.6
MC
BLRCS093A111B40
13.4
18
68.9
MC
BLRCS104A125B40
16.1
21.7
82.9
NC
BLRCS125A150B40
18.0
24
92.1
NC
BLRCS139A167B40
19.4
26
99.4
NC
BLRCS150A180B40
21.6
28.9
111
SC
BLRCS167A200B40
25.8
34.6
133
SC
BLRCS200A240B40
26.9
36
138
SC
BLRCS208A250B40
28.7
38.5
147
SC
BLRCS222A266B40
32.3
43.3
166
SC
BLRCS250A300B40
35.8
48.0
184
VC
BLRCS277A332B40
µF
Case
In(A)
(X3)
Code
4.7
16.4
DC
Reference Number
BLRCS030A036B44
7.9
27.4
HC
BLRCS050A060B44
11.8
41.1
HC
BLRCS075A090B44
15.7
54.8
LC
BLRCS100A120B44
19.7
68.5
NC
BLRCS125A150B44
22.5
78.3
NC
BLRCS143A172B44
23.6
82.2
NC
BLRCS150A180B44
26.6
92.6
SC
BLRCS169A203B44
28.7
99.7
SC
BLRCS182A218B44
31.5
110
SC
BLRCS200A240B44
39.4
137
SC
BLRCS250A300B44
42.2
147
SC
BLRCS268A322B44
44.9
156
SC
BLRCS285A342B44
47.7
166
SC
BLRCS303A364B44
3
Rated
480V
Voltage
Rated
525V
Voltage
4
50Hz
Qn (kvar)
4.2 5.2 6.7 7.5 8.8 10.4 12.5 15.5 17 18.6 20.8 25.8 28.8 31.5 33.9
50Hz
Qn (kvar)
5 10.6 12.5 15.4 20 25 27.5
In(A) 5.1 6.3 8.1 9.0 10.6 12.5 15 18.6 20.4 22.4 25.0 31.0 34.6 37.9 40.8
In(A) 5.5 11.7 13.7 16.9 22 27.5 30.2
60Hz
Qn (kvar)
5 6 8 9.0 10.6 12.5 15 18.6 20.4 22.3 25 31 34.6 37.8 40.7
60Hz
Qn (kvar)
6 12.7 15 18.5 24 30 33
µF
Case
Reference Number
In(A)
(X3)
Code
6.1
19.3
DC
BLRCS042A050B48
7.5
23.9
HC
BLRCS052A063B48
9.7
30.8
HC
BLRCS067A080B48
10.8
34.5
HC
BLRCS075A090B48
12.7
40.5
LC
BLRCS088A106B48
15
47.9
MC
BLRCS104A125B48
18
57.5
NC
BLRCS125A150B48
22.4
71.4
NC
BLRCS155A186B48
24.5
78.3
NC
BLRCS170A204B48
26.8
85.6
SC
BLRCS186A223B48
30
95.7
SC
BLRCS208A250B48
37.2
119
SC
BLRCS258A310B48
41.6
133
VC
BLRCS288A346B48
45.5
145
VC
BLRCS315A378B48
48.9
156
XC
BLRCS339A407B48
µF
Case
Reference Number
In(A)
(X3)
Code
6.6
19.2
HC
BLRCS050A060B52
14.0
40.8
MC
BLRCS106A127B52
16.5
48.1
NC
BLRCS125A150B52
20.3
59.3
NC
BLRCS154A185B52
26.4
77
SC
BLRCS200A240B52
33
96.2
SC
BLRCS250A300B52
36.3
106
SC
BLRCS275A330B52
VarplusCan HDuty
Low Voltage Capacitors 50Hz
Rated
240/260V
Voltage
Qn (kvar)
HC
BLRCH021A025B24
240V
260V
@260V
1.9
2.1 4.2 6.3 8.3 10.9 11.7 13.1
2.5 4.9 7.4 9.7 12.8 13.7 15.4
5.5
2.3
38.7
4.6
13.1
77.3
LC
BLRCH042A050B24
16.4
6.9
19.5
116
RC
BLRCH063A075B24
21.6
9
26.1
152
RC
BLRCH083A100B24
28.4
12
34.1
200
TC
BLRCH109A130B24
30.4
12.9
36.5
215
TC
BLRCH117A140B24
34.1
14.4
3 6 8.8 11.7 15.3 16.4 18.4
6.6
10.9
2.5 5 7.5 10.0 13 14 15.7
40.9
241
TC
BLRCH131A157B24
3.9 5.8 7.6 10 10.7
50Hz
60Hz
Qn (kvar)
2.7 4.5 5.7 6.8
380/400/415V
Code
230V
2.3
7.5 9.4 11.3 13.5 15.1 18.1 18.8 22.6 27.1 30.1 36.1 37.6 45.1
440V
(X3)
@260V
380V
Voltage
Reference Number
260V
Voltage
Rated
In(A)
Case
240V
Rated
Rated
Qn (kvar)
µF
230V
12
Voltage
In(A)
60Hz
400V 2.5 3 5 6.3 7.5 8.3 10.4 12.5 15 16.7 20 20.8 25 30 33.3 40 41.7 50
50Hz
Qn (kvar)
5 7.5 10 12.5 14.3 15 16.9 18.2 20 23.8 25 28.5 30.3 31.5 33.5 40 47.6 50 57.1 50Hz
Qn (kvar)
In(A)
Qn (kvar)
415V
@400V
2.7
3.6
3.2
4.3
3.2
5.4
7.2
5.4
6.8
9.1
6.8
8.1
10.8
8.1
8.9
12
9
11.2
15
11.3
13.5
18
13.5
16.1
21.7
16.2
18
24.1
18.1
28.9
21.7
22.4
30
22.5
26.9
36.1
27.1
32.3
43.3
32.5
35.8
48.1
36.1
43.1
57.7
43.3
44.9
60.2
45.2
53.8
72.2
---
60Hz
Qn (kvar)
6.6
6 9 12 15 17.2 18 20.3 21.8 24 28.6 30 34.2
13.1 16.4 18.8 19.7 22.2 23.9 26.2 31.2 32.8 37.4 39.8 41.3 44.0 52.5 62.5 65.6 74.9 In(A)
2.7
21.5
In(A) 9.8
380V
400V 3 4 6 7.5 9 10 12.5 15 18 20 24 25 30 36 40 48 50 ---
In(A)
µF
Case
(X3)
Code
415V
@400V
3.2
4.3
16.6
DC
BLRCH025A030B40
3.9
5.2
19.9
DC
BLRCH030A036B40
6.5
8.7
33.1
HC
BLRCH050A060B40
10.8
41.8
HC
BLRCH063A075B40
8.1 9.7
13
49.7
LC
BLRCH075A090B40
10.7
14.4
55.0
LC
BLRCH083A100B40
13.4
18
68.9
RC
BLRCH104A125B40
16.1
21.7
82.9
RC
BLRCH125A150B40
19.4
26
99.4
RC
BLRCH150A180B40
21.6
28.9
111
TC
BLRCH167A200B40
25.8
34.6
133
TC
BLRCH200A240B40
26.9
36
138
TC
BLRCH208A250B40
32.3
43.3
166
TC
BLRCH250A300B40
38.8
52
199
VC
BLRCH300A360B40
43
57.7
221
VC
BLRCH333A400B40
51.7
69.3
265
YC
BLRCH400A480B40
53.9
72.2
276
YC
BLRCH417A500B40
---
---
331
YC
BLRCH500A000B40
µF
Case
In(A)
(X3)
Code
Reference Number
7.9
27.4
HC
11.8
41.1
LC
BLRCH050A060B44 BLRCH075A090B44
15.7
54.8
RC
BLRCH100A120B44
19.7
68.5
RC
BLRCH125A150B44
22.5
78.3
RC
BLRCH143A172B44
23.6
82.2
RC
BLRCH150A180B44
26.6
92.6
TC
BLRCH169A203B44
28.7
99.7
TC
BLRCH182A218B44
31.5
110
TC
BLRCH200A240B44
37.5
130
TC
BLRCH238A286B44
39.4
137
TC
BLRCH250A300B44
44.9
156
VC
BLRCH285A342B44
---
---
166
VC
BLRCH303A000B44
37.8 40.2 48 57.1
49.6
173
VC
BLRCH315A378B44
52.7
184
VC
BLRCH335A401B44
63
219
YC
BLRCH400A480B44
75.0
261
YC
BLRCH476A571B44
---
---
274
YC
BLRCH500A000B44
---
---
313
YC
BLRCH571A000B44
µF
Case
Reference Number
(X3)
Code
60Hz
Qn (kvar)
In(A)
Reference Number
5
480V Rated
525V
Voltage
Rated
575V
Voltage
Rated
600V
Voltage
6
4.2 5 7.5 8.8 10.4 11.3 12.5 13.6 14.4 15.5 17 18 19.2 20.8 22.7 25.8 28.8 31.5 33.9 36 40 50Hz
5.1 6 9 10.6 12.5 13.6 15 16.4 17.3 18.6 20.4 21.7 23 25 27 31 34.6 37.9 40.8 43.3 48.1
5 6 9 10.6 12.5 13.6 15 16.3 17.3 18.6 20.4 21.6 23 25 27 31 34.6 37.8 40.7 43.2 48 60Hz
6.1
19.3
HC
BLRCH042A050B48
7.2
23
HC
BLRCH050A060B48
10.8
34.5
LC
BLRCH075A090B48
12.7
40.5
LC
BLRCH088A106B48
15
47.9
RC
BLRCH104A125B48
16.3
52
RC
BLRCH113A136B48
18
57.5
RC
BLRCH125A150B48
19.6
62.6
RC
BLRCH136A163B48
20.8
66.3
RC
BLRCH144A173B48
22.4
71.4
RC
BLRCH155A186B48
24.5
78.3
TC
BLRCH170A204B48
26
82.9
TC
BLRCH180A216B48
28
88.4
TC
BLRCH192A230B48
30
95.7
TC
BLRCH208A250B48
33
104.5
TC
BLRCH227A272B48
37.2
119
TC
BLRCH258A310B48
41.6
133
VC
BLRCH288A346B48
45.5
145
VC
BLRCH315A378B48
48.9
156
XC
BLRCH339A407B48
52
166
XC
BLRCH360A432B48
57.7
184
XC
BLRCH400A480B48
µF
Case
Reference Number
Code
Qn (kvar)
In(A)
Qn (kvar)
In(A)
(X3)
5 10 10.6 12.5 13.5 15 15.4 17.2 18.5 20 25 27.5 30.9 34.4 37.7 40 41.2
5.5
6 12 12.7 15 16.2 18 18.5 20.6 22.2 24 30 33.0 37.1 41.3 45.2 48 49.4
6.6
19.2
HC
13.2
38.5
MC
BLRCH100A120B52
14
40.8
RC
BLRCH106A127B52
16.5
48.1
RC
BLRCH125A150B52
17.8
51.9
RC
BLRCH135A162B52
19.8
57.7
RC
BLRCH150A180B52
20.3
59.3
RC
BLRCH154A185B52
22.7
66.2
RC
BLRCH172A206B52
24.4
71.2
TC
BLRCH185A222B52
26.4
77
TC
BLRCH200A240B52
33
96.2
TC
BLRCH250A300B52
36.3
105.8
TC
BLRCH275A331B52
40.8
119
VC
BLRCH309A371B52
45.4
132
VC
BLRCH344A413B52
49.8
145
VC
BLRCH377A452B52
52.8
154
XC
BLRCH400A480B52
54.4
159
XC
BLRCH412A494B52
µF
Case
Reference Number
Code
50Hz
11.0 11.7 13.7 14.8 16.5 16.9 18.9 20.3 22 27.5 30.2 34 37.8 41.5 44 45.3
60Hz
BLRCH050A060B52
Qn (kvar)
In(A)
Qn (kvar)
In(A)
(X3)
6 12 15 29.2
6
7.2 14.4 18 35
7.2
19.2
LC
BLRCH060A072B57
14.5
38.5
RC
BLRCH120A144B57
18.1
48.1
TC
BLRCH150A180B57
35.1
93.6
VC
BLRCH292A350B57
µF
Case
Reference Number
50Hz
12 15.1 29.3
60Hz
Qn (kvar)
In(A)
Qn (kvar)
In(A)
(X3)
Code
8.3 10.4 12.5 16.7 20.8
8
10 12.5 15 20 25
9.6
24.5
RC
BLRCH083A100B60
12
30.6
TC
BLRCH104A125B60
14.4
36.8
TC
BLRCH125A150B60
19.3
49.2
VC
BLRCH167A200B60
24
61.3
VC
BLRCH208A250B60
10 12 16.1 20
Rated
690V
Voltage
Rated
830V
Voltage
50Hz
60Hz
µF
Case
Qn (kvar)
In(A)
Qn (kvar)
In(A)
(X3)
Code
5.5 10 11.1 12.5 13.8 15 20 25 27.6 30
4.6
5.5
12.3
MC
BLRCH055A066B69
10
22.3
RC
BLRCH100A120B69
11.1
24.7
RC
BLRCH111A133B69
12.6
27.8
RC
BLRCH125A150B69
13.8
30.6
TC
BLRCH138A165B69
15.1
33.4
TC
BLRCH150A180B69
20.1
44.6
TC
BLRCH200A240B69
25.1
55.7
VC
BLRCH250A300B69
27.7
61.4
VC
BLRCH276A331B69
25.1
6.6 12 13.3 15 16.5 18 24 30 33.1 36
30.1
66.8
VC
BLRCH300A360B69
µF
Case
Reference Number
Qn (kvar)
In(A)
Qn (kvar)
In(A)
(X3)
Code
17.1
11.9
20.5
14.3
26.3
VC
50Hz
8.4 9.3 10.5 11.5 12.6 16.7 20.9 23.1
60Hz
Reference Number
BLRCH171A205B83
7
VarplusCan
Low Voltage Capacitors 60Hz
Techinical Particulars
Termination cable (300 mm length)
0.5 + a
Torque
T = 10 Nm
Toothed washer
M10/M12
Hex nut
M10/M12
Terminal screw
M5
Terminal assembly Ht. (t)
50 mm
h h
1
TS
Toothed washer Hex nut VarplusCan DC, EC, FC, HC & LC
3 3 + a (expansion) 3+t
1
Finger proof CLAMPTITE terminal In-built resistor type
16 + 1
Toothed washer Hex nut Tightening Torque = 2.5 Nm
15
15
M12 M
VarplusCan MC, NC, RC & SC
8
TS
TH
M10
10 mm
Ø 63
M12
13 mm
Ø 70
M12
16 mm
Case code DC EC FC HC LC
Diameter d (mm) 50 63 63 63 70
Height h (mm) 195 90 115 195 195
Height h+t (mm) 245 140 165 245 245
Weight (kg) 0.7 0.5 0.6 0.9 1.1
Creepage distance Clearance Expansion (a)
13 mm 13 mm max.12mm
Mounting details (for M10/M12 mounting stud)
h h h
d
Size (d) Ø 50
Case Code: RC & SC
1+5 (t)
d
16 mm 16 mm max.10mm
Mounting details (for M10/M12 mounting stud)
TH
d
Creepage distance Clearance Expansion (a)
19 2 2+t
FAST-ON Terminal 6.35 x 0.8
Case Code: DC, HC & LC
Torque
T = 10 Nm
Toothed washer
J12.5 DIN 6797
Hex nut
BM12 DIN 439
Terminal screw
M5
Terminal assembly Ht. (t)
30 mm
Case code RC SC
Height h (mm) 212 278
Diameter d (mm) 90 90
Height h+t (mm) 242 308
Weight (kg) 1.6 2.3
VarplusCan
Low Voltage Capacitors 60Hz
Case Code: TC, UC & VC
1+5
Finger proof F CLAMPTITE terminal C In-built resistor type
13 mm
Clearance
13 mm
Expansion (a)
max.12mm
3 3 + a (expansion) 3+t
1
Mounting details (for M10/M12 mounting stud) Torque
T = 10 Nm
Toothed washer
J12.5 DIN 6797
Hex nut
BM12 DIN 439
Terminal screw
M5
Terminal assembly Ht. (t)
30 mm
Case code TC
Diameter d (mm) 116
Height h (mm) 212
Height h+t (mm) 242
Weight (kg) 2.5
UC
116
278
308
3.5
VC
136
212
242
3.2
M12 M M12
Toothed washer Hex nut
15
16 + 1
d
Creepage distance
h h h
(t)
d
Mechnanical characteristics
15 5
Tightening Torque = 2.5 Nm
VarplusCan TC, UC & VC
d
Case Code: XC & YC
1+5 M10
3+t h
3 + a (expansion)
1
16 + 1
d
Creepage distance Clearance Expansion (a)
60 mm 34 mm max.12mm
Mounting details (for M10/M12 mounting stud)
h
h
3
t
2
STUD type terminal In-built resistor type
M12
Toothed washer Hex nut
Torque Toothed washer Hex nut Terminal screw Terminal assembly Ht. (t)
T = 10 Nm J12.5 DIN 6797 BM12 DIN 439 M10 43 mm
Case code XC
Diameter d (mm) 116
Height h (mm) 278
Height h+t (mm) 321
Weight (kg) 4.1
YC
136
278
321
5.3
Tightening Torque = 2.5 Nm
47 1
VarplusCan XC & YC
9
VarplusBox
Low Voltage Capacitors 60Hz
Techinical Particulars
VarplusBox capacitors deliver reliable performance in the most severe application conditions, in Fixed & Automatic PFC systems, in networks with frequently switched loads and harmonic disturbances.
Robustness
• Double metallic protection. • Mechanically well suited for “stand-alone” installations. Safety
• Its unique safety feature electrically disconnects the capacitors
PE90135
safely at the end of their useful life. • The disconnectors are installed on each phase, which makes the capacitors very safe, in addition to the protective steel enclosure.
Flexibility
• These capacitors can be easily mounted inside panels or in a • • Unique foot print upto 20 kvar (VarplusBox HDuty Compact) Features
• Metal box enclosure. • High power ratings up to 100 kvar. • Easy repair and maintenance. • Up to 70°C temperature. • High continious current withstand up to 2.5 x I . • Stand-alone PFC equipment. • Direct connection to a machine, in harsh environmental condiN
VarplusBox
tions.
PE90135
PE90137
PE90164
HDuty Construction
Steel sheet enclosure
Voltage range
230 V - 830 V
Power range (three-phase)
5 - 100 kvar
Peak inrush current
Up to 250 x IN
Overvoltage
1.1 x UN As per IEC 60831- 1/2
400 V - 525 V
Up to 350 x IN
Overcurrent
1.8 x IN
2.5 x IN
Mean life expectancy
Up to 130,000 h
Up to 160,000 h
Safety
Self-healing + pressure-sensitive disconnector + discharge device (50V/1min)
Dielectric
10
Energy
alloy with wave cut & slope metallization
Double metallized paper
Impregnation
Non-PCB, Biodegradable sticky resin (dry)
Non-PCB, oil
Ambient temperature
-25°C to max 55°C/Class D
-25°C to 70°C
Protection
IP20
Mounting
Upright, Horizontal
Terminals
Terminals designed for large cable termination and direct busbar mounting for banking
Upright
VarplusBox Hduty
Low Voltage Capacitors
Rated
50Hz
Voltage
380V 2.3 4.5 6.8 7.5 9.4 11.3 13.6 18.1 18.8 22.6 37.6 45.1
400V 2.5 5 7.5 8.3 10.4 12.5 15.1 20.1 20.8 25 41.7 50
Rated
440V
Voltage
Rated
480V
Voltage
Rated Voltage
525V
380/400/415V
60Hz
QN (kvar)
IN(A)
QN (kvar)
415V
@400V
2.7
3.6
5.4
7.2
5.4
8.1
10.8
8.1
8.9
12.0
9.0
11.2
15.0
11.3
13.5
18.0
13.5
16.3
21.8
16.3
21.6
29.0
21.8
22.4
30.0
22.6
26.9
36.1
27.1
44.9
60.2
45.1
53.8
72.2
---
50Hz
380V 2.7
400V 3 6 9 10 12.5 15 18 24 25 30 50 ---
60Hz
IN(A)
µF
Case
(X3)
Code
Reference Number
415V
@400V
3.2
4.3
16.6
AB
BLRBH025A030B40
6.5
8.7
33.1
AB
BLRBH050A060B40
9.7
13.0
49.7
AB
BLRBH075A090B40
10.8
14.4
55.0
AB
BLRBH083A100B40
13.5
18.0
68.9
AB
BLRBH104A125B40
16.1
21.7
82.9
AB
BLRBH125A150B40
19.5
26.1
100.1
GB
BLRBH151A181B40
25.9
34.8
133
GB
BLRBH201A241B40
26.9
36.1
138
GB
BLRBH208A250B40
32.3
43.3
166
GB
BLRBH250A300B40
53.8
72.2
276
IB
BLRBH417A500B40
---
---
331
IB
BLRBH500A000B40
µF
Case
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
10 12.5 25 50
13.1
12 15 30
15.7
54.8
AB
BLRBH100A120B44
19.7
68.5
AB
BLRBH125A150B44
39.4
137
GB
BLRBH250A300B44
---
274
IB
BLRBH500A000B44
µF
Case
Reference Number
50Hz
16.4 32.8 65.6
---
60Hz
Reference Number
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
8.3 8.8 10.4 12.5
10.0
10 10.6 12.5 15
12.0
38.2
AB
BLRBH083A100B48
12.7
40.5
AB
BLRBH088A106B48
15.0
47.9
AB
BLRBH104A125B48
18.0
57.5
AB
BLRBH125A150B48
15.6 17.1 19.3 20.8 21.6 22.7 25.8 28.8 31.5 33.9 41.7 51.6 56.6 61.9
18.8
18.7 20.5 23 25 25.9 27.2 31 34.6 37.8 40.7 50 61.9 67.9
22.5
71.8
GB
BLRBH156A187B48
24.7
78.7
GB
BLRBH171A205B48
27.9
88.8
GB
BLRBH193A231B48
30.0
95.7
GB
BLRBH208A250B48
31.2
99.4
GB
BLRBH216A259B48
32.8
104
GB
BLRBH227A272B48
37.2
119
GB
BLRBH258A310B48
41.6
133
GB
BLRBH288A346B48
45.5
145
GB
BLRBH315A378B48
48.9
156
GB
BLRBH339A407B48
60.2
192
IB
BLRBH417A500B48
74.5
238
IB
BLRBH516A619B48
81.7
261
IB
BLRBH566A679B48
285
IB
BLRBH619A000B48 Reference Number
50Hz
10.6 12.5 15.0 20.6 23.2 25.0 26.0 27.3 31.0 34.6 37.9 40.8 50.2 62.1 68.1 74.5
60Hz
µF
Case
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
10 12.5 16.6 20 25 40 50
11.0
12 15 19.9 24.1 30 48 60
13.2
38.5
AB
BLRBH100A120B52
16.5
48.1
AB
BLRBH125A150B52
21.9
63.9
GB
BLRBH166A199B52
26.5
77.3
GB
BLRBH201A241B52
33.0
96.2
GB
BLRBH250A300B52
52.8
153.9
IB
BLRBH400A480B52
66.0
192
IB
BLRBH500A600B52
13.7 18.3 22.1 27.5 44.0 55.0
11
Rated
690V
Voltage
Rated
830V
Voltage
12
50Hz
60Hz
µF
Case
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
15.1
12.6
18.1
15.1
33.6
GB
BLRBH151A181B69
20
16.7
24
20.1
44.6
GB
BLRBH200A240B69
50
41.8
60
50.2
111
JB
BLRBH500A600B69
µF
Case
Reference Number
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
34.1
23.7
40.9
28.5
52.5
GB
50Hz
60Hz
Reference Number
BLRBH341A409B83
VarplusBox Energy
Low Voltage Capacitors
Rated
50Hz
Voltage
QN (kvar)
380V 7.5 9.4 11.3 13.5 15.1 18.8 22.6 37.6 45.1
Rated
440V
Voltage
Rated
480V
Voltage
Rated Voltage
525V
380/400/415V
60Hz
400V 8.3 10.4 12.5 15 16.7 20.8 25 41.7 50
IN(A)
QN (kvar)
415V
@400V
380V
8.9
12.0
11.2
15.0
11.3
13.5
18.0
13.5
9.0
16.1
21.7
16.2
18
24.1
18.1
22.4
30.0
22.6
26.9
36.1
27.1
44.9
60.2
45.1
53.8
72.2
54.2
50Hz
60Hz
400V 10 12.5 15 18 20 25 30 50 60
IN(A)
µF
Case
(X3)
Code
Reference Number
415V
@400V
10.8
14.4
55.0
DB
BLRBE083A100B40
13.5
18.0
68.9
DB
BLRBE104A125B40
16.1
21.7
82.9
GB
BLRBE125A150B40
19.4
26.0
99.4
GB
BLRBE150A180B40
21.5
28.9
111
GB
BLRBE167A200B40
26.9
36.1
138
GB
BLRBE208A250B40
32.3
43.3
166
GB
BLRBE250A300B40
53.8
72.2
276
IB
BLRBE417A500B40
64.6
86.6
331
IB
BLRBE500A600B40
µF
Case
Reference Number
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
10 12.5 15 20 25 50
13.1
15.7
54.8
DB
BLRBE100A120B44
19.7
68.5
DB
BLRBE125A150B44
23.6
82.2
GB
BLRBE150A180B44
31.5
110
GB
BLRBE200A240B44
39.4
137
GB
BLRBE250A300B44
65.6
12 15 18 24 30 60
78.7
274
IB
BLRBE500A600B44
µF
Case
Reference Number
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
8.8 10.4 11.3 12.5 13.6 15.5 17 20.8 25.8 28.8 31.5 33.9 41.7
10.6
10.6 12.5 13.6 15 16.3 18.6 20.4 25 31 34.6 37.8 40.7 50
12.7
40.5
DB
BLRBE088A106B48
15.0
47.9
DB
BLRBE104A125B48
16.3
52.0
DB
BLRBE113A136B48
18.0
57.5
FB
BLRBE125A150B48
19.6
62.6
FB
BLRBE136A163B48
22.4
71.4
GB
BLRBE155A186B48
24.5
78.3
GB
BLRBE170A204B48
30.0
95.7
GB
BLRBE208A250B48
37.2
119
GB
BLRBE258A310B48
41.6
133
GB
BLRBE288A346B48
45.5
145
IB
BLRBE315A378B48
48.9
156
IB
BLRBE339A407B48
60.2
192
IB
BLRBE417A500B48
µF
Case
Reference Number
50Hz
50Hz
16.4 19.7 26.2 32.8
12.5 13.6 15.0 16.4 18.6 20.4 25.0 31.0 34.6 37.9 40.8 50.2
60Hz
60Hz
QN (kvar)
IN(A)
QN (kvar)
IN(A)
(X3)
Code
10 12.5 15.4 20 25 50
11.0
12 15 18.5 24 30 60
13.2
38.5
DB
BLRBE100A120B52
16.5
48.1
FB
BLRBE125A150B52
20.3
59.3
FB
BLRBE154A185B52
26.4
77.0
GB
BLRBE200A240B52
33.0
96.2
GB
BLRBE250A300B52
66.0
192
IB
BLRBE500A600B52
13.7 16.9 22.0 27.5 55.0
13
VarplusBox
Low Voltage Capacitors 60Hz
Mechnanical characteristics
Case Code: AB DE90158
D Terminal cover
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. H
Enclosure
Case code AB
W1 (mm) 114
W2 (mm) 97
W3 (mm) 76.5
H D Weight (mm) (mm) (kg) 229.5 225.5 3
W3 W2 W1
192
Rubber grommet for cable entry
Enclosure
H
W3 W1
W2
14
DE90159
D
Case Code: DB, EB, FB, GB & HB Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. Case code DB EB FB GB HB
W1 (mm) 263 263 309 309 309
W2 (mm) 243 243 289 289 289
W3 (mm) 213 213 259 259 259
H (mm) 355 260 355 355 455
D (mm) 97 97 97 153 153
Weight (kg) 4.8 3.6 5.4 7.5 8.0
VarplusBox
Low Voltage Capacitors 60Hz
Mechnanical characteristics
Case Code: IB DE90160
D Rubber grommet for cable entry
Creepage distance
Enclosure
H
30 mm
Clearance Phase to phase
25 mm (min.)
Phase to earth
19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. Case code IB
W1 (mm) 309
W2 (mm) 289
W3 (mm) 259
H (mm) 497
D Weight (mm) (kg) 224 10.0
W3 W1
W2
Top To cover
Al Busbar M 10x35 Bolt Bolt
Case Code: LB & SB
Capacitor units Capaci pacitoru W1
250
DE90161
D
H 125
Unit 1
Unit 2
Unit 3
Unit 4
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)
Mounting details: mounting screw M6, 4 Nos. Case code LB SB
W1 (mm) 795 545
W2 (mm) 630 390
W3 (mm) 670 430
H (mm) 455 455
D (mm) 315 315
Weight (kg) 45 32.4
W2 W3 Cable entry plate
Earthing ng Bolt
7x14 Slots 4 Nos
15
VarplusBox
Low Voltage Capacitors 60Hz
Mechnanical characteristics
Case Code: JB
To cover Top
Al Busbar M 10x35 Bolt
Capaci pacitor units u Capacitor
Creepage distance
W1
DE90162
250
Phase to phase
25 mm (min.)
Phase to earth
19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. H Unit 1
125
Unit 2
W2 W3 Cable entry plate
W1 (mm) 455
W2 (mm) 290
W3 (mm) 330
H (mm) 455
D Weight (mm) (kg) 315 22.5
Case Code: KB & RB
To cover Top
M 10x35 Bolt
Case code JB
7x14 Slots 4 Nos
ng Bolt Earthing
Al Busbar
Capaci pacitor units u Capacitor W1
250
DE90163
D
Creepage distance Clearance Phase to phase Phase to earth
30 mm 25 mm (min.) 19 mm (min.)
Mounting details: mounting screw M6, 4 Nos. H 125
Unit 1
Unit 2
Unit 3
W2 W3 Cable entry plate
16
30 mm
Clearance
D
ng Bolt Earthing
7x14 Slots 4 Nos
Case code KB RB
W1 (mm) 625 435
W2 (mm) 460 280
W3 (mm) 500 320
H (mm) 455 455
D (mm) 315 315
Weight (kg) 32 24.3
VarplusBox
Low Voltage Capacitors 60Hz
Mechnanical characteristics
Case Code: OB
To Top cover
Al Busbar M 10x35 Bolt
Capaci pacitor units u Capacitor W1
Creepage distance D
30 mm
250
DE90164
Clearance Phase to phase
25 mm (min.)
Phase to earth
19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. Case code OB
H Unit 1
125
Unit 2
W2 W3 Cable entry plate
Capacitor units Capaci
Creepage distance Clearance
D
250
DE90 DE90165 0165 0165
W1
H 125
Unit 1
Unit 2
Unit 3
Unit 4
W2 W3 Cable entry plate
W3 (mm) 470
H (mm) 625
D Weight (mm) (kg) 315 30
Case Code: QB
Top To cover
M 10x35 Bolt
W2 (mm) 430
7x14 Slots 4 Nos
g Bolt Earthing
Al Busbar
W1 (mm) 595
Earthing g Bolt
30 mm
Phase to phase
25 mm (min.)
Phase to earth
19 mm (min.)
Mounting details: mounting screw M6, 2 Nos. Case code QB
W1 (mm) 1080
W2 (mm) 920
W3 (mm) 960
H (mm) 625
D Weight (mm) (kg) 315 60
7x14 Slots 4 Nos
17
Harmonic Application Tables
Low Voltage Capacitors 60Hz
PE90154
PE90131
VarplusCan and VarplusBox Capacitors when used along with Detuned Reactors have to be selected with a rated voltage higher the voltage across the capacitor is higher than the network service voltage (Us). The recommended Rated voltage of the capacitor to be used in
+
voltage (Us) & relative impedance is given in the table below. Capacitor Rated Voltage (UN)
Network Service Voltage (US) 60Hz
PE90154
PE90134
Reactive Impedance (%)
+
18
60Hz
400
690
400
480
600
6%
480
830
480
575
690
13%
480
480
These values ensure a safe operation in the most stringent operating conditions. Less conservative values may be adopted, but a case by case analysis is necessary.
VarplusCan HDuty + Detuned Reactor + Contactor
Low Voltage Capacitors 60Hz
Combination Table
PE90154
PE90131
Network 400V, 60Hz
PE90158
+
Effective QN Capacitor Ref. Power @ (kvar) 480V
5.7% fr = 210Hz D.R Ref
BLRCH075A090B48 × 1 LVR05065B40 × 1
6% / 7% Filter
7% fr = 190Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
LVR07065B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
6.5
9
10
13.6 BLRCH113A136B48 × 1
LVR05100B40 × 1
LVR07100B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
12.5
17.3 BLRCH144A173B48 × 1 LVR05125B40 × 1
LVR07125B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
25
34.6 BLRCH288A346B48 × 1 LVR05250B40 × 1
LVR07250B40 × 1
LC1-DMK11M7 × 1 LC1D32 × 1
50
67.9 BLRCH288A346B48 × 2 LVR05500B40 × 1
LVR07500B40 × 1
LC1-DWK12M7 × 1 LC1D80 × 1
100
135.8 BLRCH288A346B48 × 4 LVR05X00B40 × 1
LVR07X00B40 × 1
---
Network 400V, 60Hz
Capacitor Voltage 480V
LC1D115×1
13% Filter
Effective Power (kvar)
QN @ 480V
Capacitor Ref.
14% fr = 135Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
6.5
8
BLRCH067A080B48 × 1
LVR14065B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
10
12.5
BLRCH104A125B48 × 1
LVR14010B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
12.5
16.3
BLRCH136A163B48 × 1
LVR14125B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
25
31
BLRCH258A310B48 × 1
LVR14250B40 × 1
LC1-DLK11M7 × 1
LC1D25 × 1
50
62.0
BLRCH258A310B48 × 2
LVR14500B40 × 1
LC1-DTK12M7 × 1
LC1D50 × 1
100
124.0 BLRCH258A310B48 × 4
LVR14X00B40 × 1
---
LC1D115 × 1
Network 400V, 60Hz Effective QN Capacitor Ref. Power @ (kvar) 525V
Contactor LC1DPK
Capacitor Voltage 480V
Capacitor Voltage 525V 5.7% fr = 210Hz D.R Ref
6% / 7% Filter
7% fr = 190Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
6.5
10.6 BLRCH088A106B52 × 1 LVR05065B40 × 1
LVR07065B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
10
16.2 BLRCH135A162B52 × 1 LVR05100B40 × 1
LVR07100B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
12.5
20.6 BLRCH172A206B52 × 1 LVR05125B40 × 1
LVR07125B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
25
41.3 BLRCH344A413B52 × 1 LVR05250B40 × 1
LVR07250B40 × 1
LC1-DMK11M7 × 1 LC1D32 × 1
50
82.6 BLRCH344A413B52 × 2 LVR05500B40 × 1
LVR07500B40 × 1
LC1-DWK12M7 × 1 LC1D80 × 1
100
165.2 BLRCH344A413B52 × 4 LVR05X00B40 × 1
LVR07X00B40 × 1
---
Network 400V, 60Hz
Capacitor Voltage 525V
LC1D115×1
13% Filter
Effective Power (kvar)
QN @ 525V
Capacitor Ref.
14% fr = 135Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
6.5
9.6
BLRCH080A096B52 × 1
LVR14065B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
10
14.8
BLRCH125A150B52 × 1
LVR14010B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
12.5
18.5
BLRCH154A185B52 × 1
LVR14125B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
25
37.1
BLRCH309A371B52 × 1
LVR14250B40 × 1
LC1-DLK11M7 × 1
LC1D25 × 1
50
74.2
BLRCH309A371B52 × 2
LVR14500B40 × 1
LC1-DTK12M7 × 1
LC1D50 × 1
100
148.4 BLRCH309A371B52 × 4
LVR14X00B40 × 1
---
LC1D115 × 1
Network 480V, 60Hz Effective QN Capacitor Ref. Power @ (kvar) 575V
Capacitor Voltage 575V 5.7% fr = 210Hz D.R Ref
6% Filter Capacitor Duty Contactor Ref.
Power Contactor Ref.
12.5
18
BLRCH150A180B57 × 1 LVR05125B48 × 1
25
35
BLRCH292A350B57 × 1 LVR05250B48 × 1
LC1-DLK11M7 × 1
50
70
BLRCH292A350B57 × 2 LVR05500B48 × 1
LC1-DTK12M7 × 1 LC1D50 × 1
100
140
BLRCH292A350B57 × 4 LVR05X00B48 × 1
---
Network 600V, 60Hz Effective QN Capacitor Ref. Power @ (kvar) 690V
Capacitor Voltage 690V 5.7% fr = 210Hz D.R Ref
LC1-DFK11M7 × 1 LC1D12 × 1 LC1D25 × 1 LC1D115×1
6% Filter Capacitor Duty Contactor Ref.
Power Contactor Ref.
12.5
16.5 BLRCH138A165B69 × 1 LVR05125B60 × 1
25
33.1 BLRCH276A331B69 × 1 LVR05250B60 × 1
LC1-DFK11M7 × 1 LC1D12 × 1 LC1-DLK11M7 × 1
50
66.2 BLRCH276A331B69 × 2 LVR05500B60 × 1
LC1-DTK12M7 × 1 LC1D50 × 1
100
132.4 BLRCH276A331B69 × 4 LVR05X00B60 × 1
---
LC1D25 × 1 LC1D115×1
19
VarplusCan Energy + Detuned Reactor + Contactor
Low Voltage Capacitors 60Hz
Combination Table
PE90154
PE90131
Network 400V, 60Hz
PE90158
+
Contactor LC1DPK
20
Capacitor Voltage 480V
Effective QN Capacitor Ref. Power @ (kvar) 480V
5.7% fr = 210Hz D.R Ref
6% / 7% Filter
7% fr = 190Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
6.5
8.9
BLRCE075A090B48 × 1
LVR05065B40 × 1
LVR07065B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
10
13.6 BLRCE113A136B48 × 1
LVR05100B40 × 1
LVR07100B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
12.5
17.3 BLRCE144A173B48 × 1
LVR05125B40 × 1
LVR07125B40 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
25
34.6 BLRCE144A173B48 × 2
LVR05250B40 × 1
LVR07250B40 × 1
LC1-DLK11M7 × 1
50
69.2 BLRCE144A173B48 × 8
LVR05500B40 × 1
LVR07500B40 × 1
LC1-DTK12M7 × 1 LC1D80 × 1
100
138.4 BLRCE144A173B48 × 8
LVR05X00B40 × 1
LVR07X00B40 × 1
---
Network 400V, 60Hz
Capacitor Voltage 480V
LC1D32 × 1 LC1D115×1
13% Filter
Effective Power (kvar)
QN @ 480V
Capacitor Ref.
14% fr = 135Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
6.5
8
BLRCE067A080B48 × 1
LVR14065B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
10
12.5
BLRCE104A125B48 × 1
LVR14010B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
12.5
16.3
BLRCE136A163B48 × 1
LVR14125B40 × 1
LC1-DFK11M7 × 1
LC1D12 × 1
25
32.6
BLRCE136A163B48 × 2
LVR14250B40 × 1
LC1-DMK11M7 × 1
LC1D25 × 1
50
65.2
BLRCE136A163B48 × 4
LVR14500B40 × 1
LC1-DWK12M7 × 1
LC1D50 × 1
100
130.4 BLRCE136A163B48 × 8
LVR14X00B40 × 1
---
LC1D115 × 1
VarplusBox Hduty + Detuned Reactor + Contactor
Low Voltage Capacitors 60Hz
PE90154
PE90134
Combination Table
PE90158
+
Network 400V, 60Hz Effective Power (kvar)
QN @ 480V
Capacitor Ref.
25
34.6
50
100
Capacitor Voltage 480V
6% / 7% Filter
6% fr = 210Hz D.R Ref
Capacitor Duty Contactor Ref.
Power Contactor Ref.
BLRBH288A346B48 × 1 or BLRBH144A173B48 × 1
LVR05250B40 × 1
LC1-DMK11M7 × 1
LC1D32 × 1
67.9
BLRBH566A679B48 × 1 or BLRBH192A230B48 × 3
LVR05500B40 × 1
LC1-DWK12M7 × 1
LC1D80 × 1
135.8
BLRBH566A679B48 × 2 or BLRBH192A230B48 × 6
LVR05X00B40 × 1
---
LC1D115×1
Network 400V, 60Hz Effective Power (kvar)
QN @ 480V
Capacitor Ref.
25
31
50
61.9
100
Capacitor Voltage 480V
13% Filter
13% fr = 135Hz D.R Ref.
Capacitor Duty Contactor Ref.
Power Contactor Ref.
BLRBH258A310B48 × 1 or BLRBH136A163B48 × 2
LVR14250B40 × 1
LC1-DLK11M7 × 1
LC1D25 × 1
BLRBH516A619B48 × 1 or BLRBH172A206B48 × 3
LVR14500B40 × 1
LC1-DTK12M7 × 1
LC1D50 × 1
123.8 BLRBH516A619B48 × 2 or BLRBH172A206B48 × 6
LVR14X00B40 × 1
---
LC1D115 × 1
Network 480V, 60Hz
Capacitor Voltage 575V
Effective QN Capacitor Ref. Power @ (kvar) 575V
6% Filter
6% fr = 210Hz D.R Ref
Capacitor Duty Contactor Ref.
Power Contactor Ref.
LC1D25 × 1
25
36
BLRBH300A360B57 × 1 or BLRBH150A180B57 × 2
LVR05250B48 × 1
LC1-DLK11M7 × 1
50
72
BLRBH300A360B57 × 2 or BLRBH150A180B57 × 4
LVR05500B48 × 1
LC1-DTK12M7 × 1 LC1D50 × 1
100
144
BLRBH300A360B57 × 4 or BLRBH150A180B57 × 8
LVR05X00B48 × 1
---
Contactor LC1DPK
Network 600V, 60Hz
Capacitor Voltage 690V
LC1D115×1
6% Filter
Effective QN Capacitor Ref. Power @ (kvar) 690V
5.7% fr = 210Hz D.R Ref
Capacitor Duty Contactor Ref.
Power Contactor Ref.
12.5
16.5 BLRBH138A165B69 × 1
LVR05125B60 × 1
LC1-DFK11M7 × 1 LC1D12 × 1
25
33.1 BLRBH276A331B69 × 1 or BLRBH138A165B69 × 2
LVR05250B60 × 1
LC1-DLK11M7 × 1
50
66.2 BLRBH276A331B69 × 2 or BLRBH138A165B69 × 4
LVR05500B60 × 1
LC1-DTK12M7 × 1 LC1D50 × 1
100
132.4 BLRBH276A331B69 × 4 or BLRBH138A165B69 × 8
LVR05X00B60 × 1
---
LC1D25 × 1
LC1D115×1
Note:Reference Numbers in Green font are VarplusBox HDuty Compact Dimension
21
VarplusBox Energy + Detuned Reactor + Contactor
Low Voltage Capacitors 60Hz
PE90154
PE90134
Combination Table
PE90158
+
Contactor LC1DPK
22
Network 400V, 60Hz
Capacitor Voltage 480V
Effective QN Capacitor Ref. Power @ (kvar) 480V
5.7% fr = 210Hz D.R Ref
6% / 7% Filter
Capacitor Duty Contactor Ref.
Power Contactor Ref.
25
34.6 BLRBE288A346B48 × 1
LVR05250B40 × 1
LC1-DMK11M7 × 1 LC1D32 × 1
50
69.2 BLRBE288A346B48 × 2
LVR05500B40 × 1
LC1-DWK12M7 × 1 LC1D80 × 1
100
138.4 BLRBE288A346B48 × 4
LVR05X00B40 × 1
none
Network 400V, 60Hz Effective Power (kvar)
QN @ 480V
Capacitor Voltage 480V
Capacitor Ref.
14% fr = 135Hz D.R Ref.
LC1D115×1
13% Filter Capacitor Duty Contactor Ref.
Power Contactor Ref.
25
31
BLRBE258A310B48 × 1
LVR14250B40 × 1
LC1-DLK11M7 × 1
LC1D25 × 1
50
62
BLRBE258A310B48 × 2
LVR14500B40 × 1
LC1-DTK12M7 × 1
LC1D50 × 1
100
124
BLRBE258A310B48 × 4
LVR14X00B40 × 1
none
LC1D115 × 1
關 於 施 耐 德 電 機 全球能源管理專家施耐德電機為100多個國家提供整體解決方案,以世界領先地位涵跨多個市場行業:市場能源與基礎設施、工業及機械 製造、非住宅樓宇、資料中心與網路及住宅。致力於為客戶提供安全、可靠、高效能、高產能及環保的能源,施耐德電機擁有130,000+ 名員工,2011年的銷售額為224億歐元,積極致力於幫助個人和組織善盡其效•盡享其能。
www.schneider-electric.com
About Schneider Electric As a global specialist in energy management with operations in more than 100 countries, Schneider Electric offers integrated solutions across multiple market segments, including leadership positions in Utilities & Infrastructures, Industries & Machine Manufacturers, Non-residential Buildings, Data Centres & Networks and in Residential. Focused on making energy safe, reliable, efficient, productive and green, the Group’s 130,000 plus employees achieved sales of 22.4 billion euros in 2011, through an active commitment to help individuals and organizations make the most of their energy.
TWVARPLUS13CH
Schneider Electric - All rights reserved / 施耐德電機-版權所有
www.schneider-electric.com
施耐德電機股份有限公司
台北總公司
林口服務事業部暨物流處理中心
台中機械自動化中心
高雄辦事處
台北市114內湖區基湖路37號2樓
桃園縣龜山鄉工四工業區頂湖路9號1樓
台中市公益路二段51號9樓B1室
高雄市前鎮區中山二路260號21樓A2
電話:02-8751-6388
電話:03-396-0633
電話: 04-2319-3328
電話:07-537-6798
傳真:02-8751-6398
傳真:03-318-4905
傳真: 04-2329-6389
傳真:07-537-6799
www.schneider-electric.com.tw
客戶服務專線:0800-886-399
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. 由於標準與材料因時變更的可能性,如需確認型錄中產品之規格與圖像,請與施耐德電機相關部門確認。