Transcript
Recessed Laboratory Units FF GBF1671 Recessed Emergency Shower, Recess Mounted Shower Head
Application: Recessed emergency shower with ceiling
mounted recessed shower head. Recessed shower conserves valuable floor space, while eliminating the clutter and obstruction created by conventional shower equipment. Unit can be installed in either a corridor or a lab room, close to where accidents might occur.
ADA Compliance: When installed at recommended
mounting heights, unit complies with ADA requirements for accessibility by handicapped persons.
Shower Head: 10” diameter stainless steel with 20 GPM flow control and flange for flush mounting in ceiling.
Valve: 1" IPS brass stay-open ball valve with stainless steel
“panic bar.” Pulling bar down activates shower; shower remains in operation until bar is returned to original closed position. Furnished with stainless steel access panel and 1" IPS unions for valve.
Supply: 1" NPT female inlet. Sign: ANSI-compliant identification sign. U.S. Patent 5,768,721 NOTE: ANSI Z358.1-2014 specifies that shower heads be installed no more than 96" above the finished floor. This unit should therefore not be installed in ceilings over 8 feet. For higher ceiling heights, we recommend either the GBF1670 or GBF1672 showers.
Available Options FF AP250-065 Modesty curtain for wall mounting. FF AP280-235 Electric strobe light and alarm horn unit for
recess mounting in finished wall. Light illuminates and horn sounds when shower is activated. Includes additional leads for remote monitoring.
FF G3800LF Thermostatic mixing valve precisely blends hot
and cold water to deliver warm (tepid) water as required by ANSI Z358.1-2014. Refer to “Tempering Valves” section for complete technical and product selection information.
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 TELEPHONE 312 447 8101 FACSIMILE gesafety.com
Note: Shown with optional AP280-235 electric light and alarm horn unit (sold separately).
Listed 8116. Units have been tested to and comply with ANSI Z358.1-2014 and the Uniform Plumbing Code.
Recessed Laboratory Units FF GBF1671 Recessed Emergency Shower, Recess Mounted Shower Head
NOTES: 1. A MINIMUM OF 4 1/8" IS REQUIRED FROM FINISHED WALL SURFACE TO REAR OF WALL CAVITY TO ACCOMODATE UNIT. 2. U.S. PATENT NO. 5,768,721. 3. PROVIDE 7 1/4" X 14 1/2" CUTOUT IN WALL FOR HOUSING INSTALLATION.
PIPE SUPPORT BY OTHERS
PIPING AND FITTINGS SHOWN IN DOTTED SUPPLIED BY OTHERS
36" (915mm) RECOMMENDED
82"-96" (2083-2438mm) TO FINISHED FLOOR
10" (254mm) MOUNTING HOLE 11 3/4" (299mm) SEE NOTE
STAINLESS STEEL FLANGED SHOWER HEAD WITH 20 GPM FLOW CONTROL
3 5/16" (84mm) TO PIPE CETERLINE
HEAVY DUTY STAINLESS STEEL "PANIC BAR" WITH BLACK VINYL FOAM GRIP (PULL TO ACTIVATE SHOWER) 9" (229mm) 8" (203mm)
REMOVABLE ACCESS PANEL
7 1/4" (184mm)
STAINLESS STEEL CABINET
2 3/4" (60mm) FROM FINISHED WALL SURFACE TO CENTERLINE OF PIPING
1 7/16" (37mm)
1 3/4" (45mm) 1" NPT FEMALE UNION OUTLET 2 1/2" (64mm)
10 1/4" (260mm)
14 3/8" (365mm)
16 1/4" (413mm)
48"MAX. (1219mm) TO FINISHED FLOOR
90° SWING
1" IPS BRASS STAYOPEN BALL VALVE 1" NPT FEMALE UNION INLET
THIS SPACE FOR ARCHITECT/ENGINEER APPROVAL
Due to continuing product improvement, the information contained in this document is subject to change without notice. All dimensions are ± 1/4" (6mm). rev. 0517
Guardian Equipment 1140 N North Branch St Chicago, IL 60642
312 447 8100 TELEPHONE 312 447 8101 FACSIMILE gesafety.com
Sign Included Emergency Shower
Keep Area Clear Test All Emergency Equipment Weekly
Listed 8116. Units have been tested to and comply with ANSI Z358.1-2014 and the Uniform Plumbing Code.