Relay Panel 32
BlueRidge
Technologies Project
Part Number
Ref.
Data Sheet Overview Relay Panel (RP) is a UL Listed lighting control panel. RP may be controlled from any BACnet BAS and is compatible with all low voltage switches. RP mounts near the circuit breaker panel to provide centralized control of branch lighting circuits. Relay Panel 32 (RP32) features 16, 24, or 32 Lighting Tough Relays (LTR) in a black powder coated steel enclosure with a hinged reversible door. Features UL Listed BACnet MS/TP and BACnet ARCnet communication to BAS network Sub network for Capacitive Touch Stations (CTS-DDN) Line and low voltage compartment separation Upgradable controller firmware Optional UL924 Emergency Bypass General Specifications Construction: 16ga steel with black powder coat finish Dimensions: Enclosure: 25.00”(635mm)H x 18.00”(457mm)W x 5.75”(146mm)D Door Surface Mount: 25.25”(641mm)H x 18.08”(459mm)W Door Recessed (Flush): 26.50”(673mm)H x 19.58”(497mm)W Weight: 47.5lbs(21.5kg) Mounting: Surface or recess mounted Operating Environment: 32-125°F (0-50°C), 20-95%RH, non-condensing, Type 1 (dry / indoor environment) Certifications UL Listed, UL916 Standard for Energy Management Equipment, US/Canada FCC Part 15 CEC Title 24 Electronics meet or exceed IEC Level 3 Warranty Two (2) year limited manufacturer warranty from date of shipment (extended warranty optional). Controller Specifications Power In: 24VAC +/-10%, 30VA, 50-60 Hz Auxiliary Out: 24VAC, 800mA (devices with full wave rectified power supply only) Digital Input (DI) and DDN Network Power Out: 24VDC, 200mA total Digital Input: 24 two-wire inputs Software Configuration: Maintained, state change, momentary on/off, momentary on, or momentary off Jumper Configuration: 8 input segments, dry contact (N) or 24VDC externally powered (R) Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry Contact 500’(152m) or externally powered 1,000’(304m) Analog Input: 6 three-wire 0-5VDC inputs Power Out: 5VDC, 50mA total Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / 250’(76m) BAS Network Specifications BACnet MS/TP Baud Rate: DIP switch selectable 9.6K, 19.2K, 38.4K, or 76.8K Device Profile: BACnet Advance Application Controller (AAC) Address Range: 1 – 99 selectable with rotary dials Unit Load: Full unit load, 32 devices per MS/TP segment Topology: RS-485, half duplex, daisy chain wiring Wire Requirement / Maximum Length: CL3P, 22AWG, 2 conductor, shielded, low cap / 4000’(1216m) Points: See Integration Guide and PIC Statement See Automated Logic Corporation’s ARC156 Wiring Technical Instructions for the latest BACnet ARCnet specifications.
DDN Network Specifications Compatible with CTS-DDN and DDN devices. See data sheet for details. LEXP Specifications Description: 1 Digital Input Expansion Card (standard) Digital Input: 32 two-wire inputs Software Configuration: Maintained, state change, momentary on/off, momentary on, or momentary off Jumper Configuration: 8 input segments, dry contact (N) or 24VDC externally powered (R) Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry Contact 500’(152m) or externally powered 1,000’(304m) Transformer Specifications Type: 30VA Inherently Limited Primary: Dual Tap 120 or 277VAC +/-10%, 30VA, 50-60 Hz Secondary: 24VAC +/-10% Inherently Limited Wire Requirement: 18AWG Minimum (Solid or Stranded) LTR Specifications Type: UL Listed SPST latching with manual override lever Electrically operated mechanically held, pulse driven Short Circuit Current Rating (SCCR) 20,000A @ 277 VAC Ratings: Tungsten 20A @ 120VAC / Ballast 20A @ 277VAC / Ballast 20A @ 347VAC / Resistive 20A @ 277VAC / Resistive 20A @ 347VAC Load Terminal: Universal screw terminal, box type clamp Terminal Capacity (per side): (2) 14-10AWG or (1) 8AWG (Solid or Stranded copper wire) Optional Equipment Specifications UL924 Emergency Bypass provides energy management control of emergency lighting circuits during normal operation while maintaining emergency function during power loss. See the UL924 Data Sheet for details.
Relay Panel 32 www.BRTint.com : 800-241-9173 Blue Ridge Technologies®
Data Sheet
H1
Earth Ground
Retrofit Interior (RI)
Relay Panel (RP)
4
5
6
7
8
SW1 SW3
1 2 3
AUTO
78
78 3
456
2
456
SW4 OVER
Field Devices
Relays 33-64 CTS-DDN (Capacitive Touch Station) RELAYS 33-64
17-24 R
24VAC(+) Auxiliary Out 24VAC(-) Auxiliary Out
AUX VAC
Field Devices
DDN Network
H2 H1
GND DI 56 DI 55 DI 54 DI 53 DI 52 DI 51 DI 50 DI 49
DI 33 DI 34 DI 35 DI 36 DI 37 DI 38 DI 39 DI 40 GND
DI 25 DI 26 DI 27 DI 28 DI 29 DI 30 DI 31 DI 32 GND
GND DI 56 DI 55 DI 54 DI 53 DI 52 DI 51 DI 50 DI 49
Address Controller Board Port Jumper
Baud Rate / Protocol Network Address Rotary Switch 10’s
Field Devices
GND DI 48 DI 47 DI 46 DI 45 DI 44 DI 43 DI 42 DI 41 DI Jumper 41-48* DI Jumper 49-56* Power LED DI Jumper 25-32* DI Jumper 33-40*
BAS Protocol
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
DDN Network Retrofit Interior (RI)
IP
INPUTS 1-16
Lighting Load
N R
Normal Power Distribution Panel
J4
UL924
Internet
J5
DILighting JumperTough Relay 33-40* (LTR)
POWER
Relay Panel (RP)
DDN Network Relay Panel (RP)
LS5 J9
Power LED DI Jumper 25-32*
Field Devices
DDN Network
G
J13
DI 25 DI 26 DI 27 DI 28 DI 29 DI 30 DI 31 DI 32 GND
OCC
Earth Ground DI Jumper 41-48* DI Jumper LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS5 (Light Sensor) Normal (Utility) Power 49-56*
J18 J19 B D
Controller Terminations Test Jumper
Field Devices
Terminations
Generator
347VAC Brown
Emergency Power NeutralEmergency Black LVS Transfer Switch Distribution Panel
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
TEST JP2
Retrofit KitLEXP (RK)
A C ADDRESS
INPUTS 1-16
N R
BAS Router
Manual Override Lever
Field Devices DDN Network
R N
POWER
J4
J5
Wire Strip Length Indicator
IP
BAS Protocol * See Price List for Recessed (Flush) door panels.
TO J26 OF Controller
J9
J13
J18 J19 B D
Relay Output
A C ADDRESS
Line In
Earth Ground CTS-DDN (Capacitive Touch Station) TO J26 OF Controller
LTR Terminations General Architecture
R N
Neutral Black
Earth Ground
Line Voltage Bay at Top of Panel with Dead Front Cover Internet XX = 0H None
INPUTS 17-32
Neutral White
120V White CTS-DDN
LS5
OCC
Relay Panel (RP) Retrofit Interior (RI) Transformer Terminations 347 Transformer Terminations LEXP Terminations Emergency Bypass Structure DDN Network Field Devices 277V Brown
INPUTS 17-32
Neutral Black
Field Devices DDN Network
240V Orange 208V Red
277VAC Brown 120VAC Black
3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND
1 2
GND DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8
GND DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24
BAS Router G
347VAC Brown
BAS
24VAC(+) Power In 24VAC(-) Power In
N
N
GND DI 48 DI 47 DI 46 DI 45 DI 44 DI 43 DI 42 DI 41
1-8 R
LVS
Low Voltage Section at Bottom of Panel
LVS (Low Voltage Switch) Sensor) / LS5 (Light Sensor) XX /=OCC 0L (Occupancy None
LEXP Port
INPUT POWER 24VAC
G 17 18 19 20 21 22 23 24 9-16 R
X0 UL924 - Last 16 relays only
AI (Analog Input) / DI (Digital Input) / GND (Ground) *DI Jumper Position N(Dry Contact) / R(Externally Powered)
CTS-DDN J26 LEXP
Retrofit Kit (RK)
XX = 00 None
Field Devices Relays 1-32
DI Jumper 9-16*
Earth Ground
DDN Network Retrofit Interior (RI) Options Special
DDN NetworkRELAYS 1-32
N
BAS
DDN Network
GND DI 48 DI 47 DI 46 DI 45 DI 44 DI 43 DI 42 DI 41
Power LED
Relay Panel (RP) Run LED
DI 33 DI 34 DI 35 DI 36 DI 37 DI 38 DI 39 DI 40 GND
DDN Network
RUN
32 32 Relays Installed Field Devices
Override Controls
J2
DI Jumper General Architecture 17-24* DI Jumper 1-8*
DI 25 DI 26 DI 27 DI 28 DI 29 DI 30 DI 31 DI 32 GND
XX = 16 16 Relays Installed
Address Controller Board Port Jumper
DDN/CAN
5V A6 A5 A4 A3 A2 A1 G
IP BAS Protocol
24 24 Relays Installed
1 2 3 4 5 6 7 8
5VDC AI 6 AI 5 AI 4 AI 3 AI 2 AI 1 GND
Internet Actual Quantity of Relays Installed
901
901
23
1
BT485 S B- A+
PWR
DDN Network Terminator Jumper
DI Jumper 33-40*
LC32P - XX - XX - XX - XX
Rotary Switch 1’s
ON
Field Devices 24VDC DDN Network(-) DDN Network(+) GND
Power LED DI Jumper 25-32*
Ordering Information*
Baud Rate / Protocol Network Address Rotary Switch 10’s Dip Switch Network Address
BT485 BAS Router Terminator Plug (if applicable)
INPUTS 1-16
Controller Terminations General Architecture
BAS
LS5
OCC
DI Jumper 41-48* DI Jumper 49-56*
Jumper Position N(Dry Contact) / R(Externally Powered) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS5*DI (Light Sensor)
CTS-DDN (Capacitive Touch Station)
BAS (+) In/Out BAS (-) In/Out Shield Out
N R
LVS
J4
CTS-DDN
J5
Wire Strip Length Indicator Manual Override Lever
J18 J19 B D
Field Devices
Relay Output
A C ADDRESS
DDN Network
Line In
Retrofit Kit (RK)
POWER
Field Devices DDN Network
J9
Field Devices DDN Network
J13
LTR Terminations
Field Devices DDN Network
TO J26 OF Controller
Earth Ground
R N
Neutral Black
Earth Ground
Neutral Black
INPUTS 17-32
BAS
BAS Protocol
347VAC Brown
120V White
Neutral White BAS Router
IP
DI 33 DI 34 DI 35 DI 36 DI 37 DI 38 DI 39 DI 40 GND
120VAC Black
H2
240V Orange 208V Red
GND DI 56 DI 55 DI 54 DI 53 DI 52 DI 51 DI 50 DI 49
Internet
277V Brown 277VAC Brown
LEXP Terminations
347 Transformer Terminations
23
H2
Transformer Terminations
Address Controller Board Port Jumper
Transformer Terminations General Architecture
Transformer Terminations nsformer Terminations UL924 Terminations
H1
© 2014 Blue Ridge Technologies International, LLC All Rights Reserved. LC-RP32-DS-V14.02
Retrofit Kit (RK)