Request for Information 239
4706 - Wilkes University - New Science Center 150-180 South River Street Wilkes-Barre, PA
RFI #: 239
Project # 4706 Tel: (570) 408-6305
Importance:
Fax: (570) 408-6304
Date Created: 8/27/2012
Subject
Discipline
Brick parapet details, flashing & brick pattern joint layout
Architectural
Author Company
From
Author RFI Number
Casler Masonry, Inc.
Dan Cerro
Co-Respondent Question
Date Required: 9/3/2012
1. The X-Seal Veneer anchor can not be used at the at the backside of the parapet for masonry veneer anchoring because there is no insulation. Is it acceptable to use the DW-10HS (product data attached) at these locations? 2. Is it acceptable to 4" CMU below the roof counter flashing (Roofers Material) as shown in detail 5/A314? 3. There is no thru-wall flashing (Textroflash) shown on detail 5/A314 over counter flashing. Is thru-wall flashing required? 4. The checker board pattern shown on detail 11/A503 causes straight joints vertically up the wall. What is the joint treatment (mortar or caulk) at the straight joints as I see these joints are prone to cracking?
Answer Company
Answered By
SaylorGregg Architects
Tom Breslin
Date Answered: 8/30/2012
Answer 1. The proposed DW-10HS anchor is acceptable. 2. 4" CMU is acceptable at concealed areas below the counter flashing.
3. Provide adhered thru-wall flashing to prevent water from ponding behind the brick at the roof level. 4. See attached cSK-30 showing the checker board area updated to reflect the changes made on cSK-17a and cSK-17b (in response to RFI 148). As the checker board area is under cover, north facing and only 2'-4" wide the stresses on the joints should be less than in other areas of the building. The intention is that the area have horizontal reinforcing, mortar joints with soft joints at the relieving angles. If Casler has specific recommendations for alternate installation please let me know.
Sketch Numbers
Prolog Manager
Printed on: 8/31/2012
SCS PA
Page 1
Revisions Mark
Date
By
08.03.2012
TEB
Description
Architect
A A.1
SaylorGregg Architects 1100 LAND TITLE BUILDING 100 SOUTH BROAD STREET PHILADELPHIA, PA 19110 P: 215.972.0500 F: 215.972.8060 Consultants
Lab Architecture Nalls Architecture, Inc. 201 Sabine Avenue Suite 200 Narberth, PA 19072-1611 Phone: 610.667.9551 Fax: 610.667.9553
Mech/Elec/Plumb Engineer Martin Rogers Associates, P.C. 185 N. Pennsylvania Avenue Wilkes-Barre, PA 18701 Phone: 570.826.1000 Fax: 570.825.0888
Structural Engineer E.D. Pons & Associates 70 South Franklin Street Wilkes-Barre, PA 18701 Phone: 570.824.6340 Fax: 570.824.6720
FACE BRICK TYPE 1
Civil Engineer
Pennoni Associates 100 North Wilkes-Barre Boulevard Wilkes-Barre, PA 18702 Phone: 570.824.2200 Fax: 570.824.0800
Acoustical Designer
8"
8"
140 South River Street Wilkes-Barre, PA 18701
8" 8"
NOTE: OPPOSITE FACE OF OPENING (WEST) IS FACE BRICK TYPE 1
New Science Building
Metropolitan Acoustics, LLC 40 W. Evergreen Avenue, Suite 108 Philadelphia, PA 19118 Phone: 215.248.4352 Fax: 215.248.4353
FACE BRICK TYPE 2 FACE BRICK TYPE 1
Owner
Wilkes University All dimensions and existing conditions shall be checked and verified by the contractor at the site. The Work shall comply with applicable codes and regulations of governing authorities having jurisdiction. c SaylorGregg Architects
Date
Drawn By
08/30/12
TEB
Sheet Title
Revised Masonry 'Checker Board'
1
Large Opening Brick Pattern - Revised 1/8" = 1'-0"
Sheet No.
cSK-30