Share

Transcript

Request for Information 379 Detailed, RFIs Grouped by RFI Number 4706 - Wilkes University - New Science Center 150-180 South River Street Wilkes-Barre, PA Project # 4706 Tel: (570) 408-6305 Sordoni Construction Services, Inc. Fax: (570) 408-6304 RFI #: 379 Date Created: 1/31/2013 Answer Company Answered By Author Company Authored By SaylorGregg Architects Tom Breslin 1100 Land Title Building, South Broad Street Philadelphia, PA 19010 Sordoni Construction Services, Inc. Todd Plociniak 146 South River Street Wilkes-Barre, PA 18701 Co-Respondent Author RFI Number Subject VCT flooring pattern orientation Cc: Company Name Discipline Architectural Contact Name Category Copies Notes Question Reference spec section 096519 Date Required: 2/7/2013 Section 3.3 floor tile installation states that the tiles should be laid at a 45 degree angle to the room axis Please provide a marked up plan showing the axis for each room that is to receive VCT Suggestion Answer Date Answered: 2/13/2013 Disregard the 45 degree angle identified in the specifications. The tile should be aligned with the 2x2 ceiling grid above. See cSK-66a and 66b for grid orientation in labs. Prolog Manager Printed on: 2/13/2013 SCS PA Page 1