Transcript
POWER MONITORING CURRENT SWITCH AND RELAY RIBX SERIES
DESCRIPTION The Relay in a Box RIBX Series provides a unique and cost-effective solution to on/off motor control and current sensing status indication. Combined in a single, convenient junction box with high and low voltage separation are a control relay and a current sensing status switch. A three-position closed/open/auto switch is available to override the output of the relay. This versatile product allows both control and status sensing of electrical loads by a BAS, all in a self-contained, easyto-install housing.
RIBX - Ring Remote Current Sensing
RIBX - Internal Current Sensing
FEATURES • Cost-effective current sensing with a control relay • Self-contained housing with high and low voltage isolation • LED indication of relay and sensor trip • Optional relay contact override switch • Plenum rated housing • UL listed for UL 916 Energy Management and UL 864 Fire
RIBX - Split Ring Remote Current Sensing
APPLICATION Internal Current Sensing (for single-phase loads) Models with internal current sensing are great for direct control and current sensing of exhaust fans, pumps, and other single phase electrical loads up to 20A. The control relay contacts of these models wire directly in series with single-phase motors using the wires that exit the housing through the 1/2" conduit hub. The current of the load is sensed within the housing. Low voltage wiring from the controller for the control relay coil and status switch enter the separate Class 2 wiring compartment in the housing through star bushings or conduit and are connected to screw terminals. Remote Current Sensing (for loads with motor starters) Models with remote current sensing are great for control and status sensing of electrical loads that require a motor starter. The control relay contacts of these models are wired in series with the motor starter coil using the two wires that exit the housing through the 1/2'' conduit hub. Currents up to 150A are sensed externally with a current sensing ring connected to the two gray wires that also exit through the 1/2'' conduit hub. Low voltage wiring from the controller for the control relay coil and status switch enter the separate Class 2 wiring compartment in the housing through star bushings or conduit and are connected to screw terminals. KELE • www.kele.com
BAS Controller Status In
Optional Override Switch Closed/Open/Auto
Class 2
Control Out
Single Phase Exhaust Fan
On/Off
RIBX Current Sensor and Control Relay with Override Switch
Current is sensed internally.
120-277 VAC 10 or 20A
Internal Current Sensing
BAS Controller Status In
Current Sensor and Control Relay with Override Switch Optional Override Switch Closed/Open/Auto
Class 2
Control Out RIBX
Toroid has no open circuit voltage to prevent electrical shock hazard.
Relay Switches Starter Input Coil Contactor 3-Phase Power Motor Starter
3-Phase Motor
Remote Current Sensing
USA 901-937-4900 • International 901-382-6084
POWER MONITORING CURRENT SWITCH AND RELAY RIBX SERIES SPECIFICATIONS - GENERAL Enclosure size
4"W x 4"H x 1.8"D with 1/2" NPT (10.2 x 10.2 x 4.6 cm) -30° to 140°F (-34° to 60°C) 5% to 95% noncondensing 10 million cycles min mechanical
Operating temp Humidity Life rating (all relays) Status indication LED#1 ON LED#2 ON LED#3 ON LED#2 & 3 OFF
Remote sensor inside diameter Ring 0.75'' (1.9 cm) Split ring 0.75'' x 0.87'' (1.9 x 2.2 cm) Relay coil frequency 50/60 Hz Relay coil pull-in/drop-out Coil Drive
Relay activated Current switch closed Current switch open No current
Status switch Status switch Off-state leakage On-state voltage drop
10-30 VAC/DC 24 VAC/DC
30 VAC/DC @ 0.4A max <30 micro-amps @ 30 VAC/DC <0.3V @ 0.1A <1.6V @ 0.4A
Wire length Weight Approvals
Pull-in DC AC 10 9 22 18
Drop-out DC AC 2.8 2.1 3.8 3
16" (40.6 cm) Approx 1 lb (0.45 kg) UL listed: UL 916 Energy Management, UL 864 Fire, UL listed Canada
ORDERING INFORMATION MODEL RIBXLCA RIBXLCF RIBXLCJA RIBXLCJF RIBXLCRA RIBXLCRF RIBXLSA RIBXLSF RIBXLSJA RIBXLSJF RIBXLSRA RIBXLSRF
CURRENT CURRENT SENSING OVER SENSING RANGE/THRESHOLD SW Internal Split Ring Ring Internal Split Ring Ring
RIBX24BA
3-150A / Fixed, 3A
10A resistive 480 VA Pilot Duty 480 VA Ballast 600W Tungsten 240W Tungsten 1/3 hp for N.O. 1/6 hp for N.C. 1/4 hp for N.O. 1/8 hp for N.C.
120/240/277 VAC - 28 VDC 240/277 VAC 277 VAC 120 VAC N.O 120 VAC N.C. 120/240 VAC 120/240 VAC 277 VAC 277 VAC
0.5-10A / Adjustable 0.5-10A / Fixed, 0.5A 10-150A / Adjustable 10-150A / Fixed, 10A 3-150A / Adjustable 3-150A / Fixed, 3 A
10A resistive 480 VA Pilot Duty 480 VA Ballast 600W Tungsten 240W Tungsten 1/3 hp for N.O. 1/6 hp for N.C. 1/4 hp for N.O. 1/8 hp for N.C.
277 VAC 277 VAC 277 VAC 120 VAC N.O 120 VAC N.C. 120/240 VAC 120/240 VAC 277 VAC 277 VAC
0.5-10A / Adjustable 0.5-10A / Fixed, 0.5A 10-150A / Adjustable 10-150A / Fixed, 10A 3-150A / Adjustable
–
Yes
–
Internal 0.5-20A / Fixed, 0.5A 0.5-20A / Adjustable
RIBX24SBA Internal
0.5-20A / Fixed, 0.5A
RIBX24SBF RIBXF RIBXA RIBXRF RIBXRA RIBXJF RIBXJA
–
0.5-20A / Adjustable
RIBX24BF
Internal Internal Ring Ring Split Ring Split Ring
RELAY CONTACT RATINGS
Yes
20A resistive 1110 VA Pilot Duty 770 VA Pilot Duty 20A Ballast 10A Ballast 10A Tungsten 240W Tungsten 2 hp 1 hp
277 VAC 277 VAC 120 VAC 277 VAC N.O. 277 VAC N.C. 120 VAC N.O. 120 VAC N.C. 277 VAC 120 VAC
RELAY CONTACT WIRING
RELAY COIL & CURRENT SWITCH Relay Input Current
1- SPDT Relay
(blue)
NC
(yellow)
COM
(orange)
NO
1- SPST Relay (orange) (orange)
12 mA @ 10 VDC 14 mA @ 12 VDC 16 mA @ 24 VDC 18 mA @ 30 VDC
Relay Coil Wiring 10-30 VAC/DC Common
}
Current Switch Wiring Closed Open Auto
1
30 mA @ 10 VAC 32 mA @ 12 VAC 42 mA @ 24 VAC 50 mA @ 30 VAC
Current Sensor Status
}
Ring & Split Ring Models (grey) Current (grey) Sensor
1- SPDT Relay (blue) (yellow) (orange)
NC COM NO
1- SPST Relay (orange) (orange)
1
Closed Open Auto
– Current Switch only 0.5-30A / Fixed, 0.5A Current Sensor Wiring – Internal Models Current Switch only 0.5-30A / Adjustable (purple) Current – Current Switch only 3-150A / Fixed, 3A (purple) Sensor – Current Switch only 3-150A / Adjustable Ring & Split Ring Models – (grey) Current Switch only 10-150A / Fixed, 10A – Current (grey) Sensor Current Switch only 10-150A / Adjustable – 1 Internal Yellow jumper determines if SPST contacts are N.O. or N.C.
Relay Input Current 75 mA @ 24 VAC
32 mA @ 24 VDC
Relay Coil Wiring 24 VAC/DC Common
}
Current Switch Output Current Sensor Status
}
Current Switch Wiring Current Sensor Status
}
Order by Model Number above. Also available in unenclosed circuit board configurations. Contact Kele for more information. KELE • www.kele.com
USA 901-937-4900 • International 901-382-6084