RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 1 OF 7
Rotary Push-switch Wall Dimmer RPS 1-10V dimming and mains switching rotary module to fit into plates and grid systems
Contents
Product order codes
Technical specification and installation
2
Related product options
3
RPS1 Mains switching and 2-wire control of a single drive unit
One-way switching and dimming of drive units
4
RPS2 Mains switching and 2-wire control of between 2-20 drive units
Two-way switching and dimming of drive units
5
For use with VoltMaster only
Individual switching and dimming of drive units
6
Wired to LEDrose LDR400
7
Wiring diagrams
RPS3 3-wire potentiometer control See VoltMaster TechPack
Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44 (0) 20 7794 9152 www.multiload.co.uk
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 2 OF 7
Technical specification and installation
Mains 230V 10A switch terminals
L1
COM
L2
AC 230V 10A
minimum brightness preset
DC 0-10V
maximum brightness preset
C1 C2
0-10V control terminals
front view
back view
top view
Modules can be supplied to fit wall plates and grid systems from UK wall-plate manufacturers. Contact Multiload on +44 (0) 20 7794 9152 to ensure compatibility with specified plate type and finish. Shown above is module supplied for fitting into MKGridPlus.
RPS1
Installation and set up procedure
1-10V dimming and mains switching of a single lighting drive such as LED drivers and fluorescent ballasts
RPS2
Installation should be carried out by suitably qualified personnel in accordance with good electrical practice and the appropriate national wiring regulations.
1-10V dimming and mains switching of between 2 to 20 lighting drives such as LED drivers and fluorescent ballasts
Switch off mains electrical supply before commencing installation.
Technical specification
Protective earth (PE) must be connected for metal back plates, and when standards dictate.
Mains voltage: AC 230V +/- 10% (protect by 10A MCB) Mains output: switched mains output – 3-wire terminal for change-over switching Signal output: 1-10V DC (sink current capability only, allowing use with standard drives, such as LED drivers, fluorescent ballasts or other 1-10V drive units) Mains switching: 10A (resistive). The number of drives that can be switched is determined by the current draw of the drives – up to a total maximum of 10A. Isolation: signal circuitry and terminals are isolated from mains circuitry and terminals (SELV) Dimensions: MK module L:50mm W:25mm D:30mm Knob Diam: 20mm H:13mm Fixing: Bush M10 Shaft:6mm
The device may be used for permanent interior installations in dry locations with suitable surface plates fitted.
Terminals C1 (-ve 0V) C2 (+ve 0-10V) Low voltage 2-wire 0-10V analogue control by rotation of the control knob. The module can be wired to a large number of LED drivers or fluorescent ballasts or other 0-10V controlled drive units without an effect on brightness if some drive units are switched on/off by the mains.
Mains switching – multi-way In addition push on/push off action of the control knob provides on/off switching of mains power (2-core mains cable + earth if required) or changeover switching (3-core mains cable + earth if required) for 2 way mains switching.
Setting minimum and maximum brightness Easy access minimum and maximum brightness screwdriver presets set the dimming range covered by the rotary control.
Environmental specification Temperature range: -10ºC – +50ºC Maximum humidity: Less than 95% non-condensing
Set the minimum preset first: setting the maximum will not affect minimum setting. Brightness levels are not affected by temperature changes around the module.
Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44 (0) 20 7794 9152 www.multiload.co.uk
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 3 OF 7
Rotary Push-Switch Wall Dimmer RPS related product options
02/4%#4%$ -!).3 6/,4!'% 3500,9 6 37)4#(%$ /54054 6 #/.42/, 3)'.!, 6 n /.,9 /.% #/.42/, 3)'.!, /04)/. 4/ "% #/..%#4%$
,%$ $RIVE #ONSTANT 6OLTAGE 6 DIMMING
,%$ $RIVE #ONSTANT #URRENT 6 DIMMING
,%$ $2)6%
,%$ $2)6%
RD 0ARTY #ONSTANT VOLTAGE DRIVERS
RD 0ARTY #ONSTANT CURRENT DRIVERS
)NPUT 6 6 SIGNAL
)NPUT 6 6 SIGNAL
&LUORESCENT 6 DIMMING
2/4!29 $)--).' 203 FOR A SINGLE DRIVE 203 FOR DRIVE UNITS MAINTAINING THE FULL SIGNAL RANGE UP TO 6 MAXIMUM BRIGHTNESS 3WITCHED OUTPUT 6 6 SIGNAL
Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44(0)20 7794 9152 www.multiload.co.uk
&,5/2%3#%.4 "!,,!34
,%$ ,)'(4 %.').%
RD 0ARTY
RD 0ARTY
)NPUT 6 6 SIGNAL
)NPUT 6 6 SIGNAL
RPO-RPS. ISS-1-0116
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 4 OF 7
One-way switching and dimming of drive units
L
SUITABLY RATED CIRCUIT PROTECTION
N E
TOTAL SWITCH LOAD NOT TO EXCEED 10A
E
L1 COM L2
L
N
INPUT
RPS1
0-10V or 1-10V DIMMABLE DRIVE LED / FLUORESCENT
C1 C2
OUTPUT SIGNAL
+ –
– +
Rotary Push-switch Wall Dimmer RPS2 is used when controlling a circuit with more than one dimmable drive 0-10V SIGNAL
DRAWING NOT TO SCALE Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44(0)20 7794 9152 www.multiload.co.uk
WD-RPS-DRIVE1. ISS-1-0116
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 5 OF 7
Two-way switching and dimming of drive units Expansion to multi-way switching by connection of intermediate switch
L
SUITABLY RATED CIRCUIT PROTECTION
N E
TOTAL SWITCH LOAD NOT TO EXCEED 10A
E
L1 COM L2
L
N
INPUT
RPS1
REMOTE SWITCH
0-10V or 1-10V DIMMABLE DRIVE LED / FLUORESCENT
C1 C2
OUTPUT SIGNAL
+ –
– +
Rotary Push-switch Wall Dimmer RPS2 is used when controlling a circuit with more than one dimmable drive 0-10V SIGNAL
DRAWING NOT TO SCALE Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44(0)20 7794 9152 www.multiload.co.uk
WD-RPS-DRIVE2. ISS-1-0116
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 6 OF 7
Individual switching and dimming of drive units Drive units on same 0-10V or 1-10V signal can be individually mains-switched (without affecting brightness)
L
SUITABLY RATED CIRCUIT PROTECTION
N E
L1 COM L2
RPS2 C1 C2
E
L
E
N
L
N
INPUT
INPUT
0-10V or 1-10V DIMMABLE DRIVE LED / FLUORESCENT
0-10V or 1-10V DIMMABLE DRIVE LED / FLUORESCENT
REMOTE SWITCH TOTAL SWITCH LOAD NOT TO EXCEED 10A
OUTPUT SIGNAL
+ –
– +
SIGNAL OUTPUT SIGNAL
+ –– +– +
Rotary Push-switch Wall Dimmer RPS2 is used when controlling a circuit with more than one dimmable drive
DRAWING NOT TO SCALE Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44(0)20 7794 9152 www.multiload.co.uk
WD-RPS-DRIVE3. ISS-1-0116
RPS-1-0116. ROTARY PUSH-SWITCH WALL DIMMER. PAGE 7 OF 7
Rotary Push-switch Wall Dimmer RPS wired to LEDrose LDR400 L
SUITABLY RATED CIRCUIT PROTECTION
N E
– +
– +
– +
– +
A
B
C
D
LED ROSE LDR400 L1 COM L2
L
N
E
SUITABLE POWER SUPPLY 15V DC
DC OUTPUT
15V 0V
– +
RPS1 C1 C2
C1 C2
To additional LEDrose LDR400 Combination of which must be within the rating of power supply
0-10V SIGNAL
Use RPS2 when more than one LEDrose LDR400 is installed
DRAWING NOT TO SCALE Multiload 2 Rosemont Road Hampstead London NW3 6NE Telephone +44(0)20 7794 9152 www.multiload.co.uk
WD-RPS-LDR400. ISS-1-0116