ENERGY RECOVERY VENTILATORS
MODEL
RX5 SERIES
Concentrating what we can do. more, ever and definitely...
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN http://Global.MitsubishiElectric.com
Y08-003 Nov.2008(MEE)
Specifications subject to change without notice.
Simple and Effective Excellent air quality and unbeatable Heat Exchange Efficiency
LOSSNAY's Energy Recovery Technology and Simultaneous Ventilations (Supply and Exhaust) Contribute to Excellent Indoor air Quality and Significantly Reduce the Outdoor air load. Energy-Recovery Concept by Hyper Eco LOSSNAY Core In summer
In winter
Temperature difference between air supply and room: 1.7 ºC
About 4kg/h of water vapor is recovered.
Supply air
Supply air
LOSSNAY Conventional ventilator
Try blowing into a rolled up piece of paper. The warmth of your breath travels through the paper to your hands.
Dry bulb temperature (ºC)
27.7
33
Absolute humidity (g/kg'(DA))
13.4
20.1
Relative humidity (%)
58
63
Enthalpy (kJ/kg(DA))
62.1
84.6
Total heat recovered (kW)
7.5
0
Outdoor air load (kW)
3.1
10.6
Outdoor air load ratio (%)
71
100
LOSSNAY Conventional ventilator
Exhaust air
Room air Absolute humidity
Air conditioner
26ºC
Dry bulb temperature
10.5g/kg'(DA)
Absolute humidity
50%
Relative humidity
Relative humidity Enthalpy
problems arising in the workplace or in the home. It is believed to contribute to a significant loss in productivity, low morale and Heat exchange unit (LOSSNAY core)
higher rates of sickness among many employees. The object of providing good
Stale exhaust air
ventilation alongside air condition in residential and commercial buildings is to
Fresh air from outside
52.9kJ/kg(DA)
Enthalpy
20.1g/kg'(DA) 63% 84.6kJ/kg(DA)
{
}
Stale room air extracted
the recovery of waste energy. The units reduce overall energy costs by extracting stale air and then recovering the heating or incoming fresh air. By utilising this energy, the
LOSSNAY Core Construction & Principle Stale air exhaust (dirty indoor-air)
EA
Fresh air exhaust (fresh heating/cooling air)
SA Indoors
initial capital costs of heating and cooling
OA Fresh air induction (fresh air)
1
50
29.2
4.7
Total heat recovered (kW)
8.2
0
Outdoor air load (kW)
3.1
11.3
Outdoor air load ratio (%)
72.5
100
Exhaust air
Room air Dry bulb temperature Air conditioner
Absolute humidity Relative humidity Enthalpy
Outdoor air 20ºC
Dry bulb temperature
7.3g/kg'(DA)
Absolute humidity
50%
Relative humidity
38.5kJ/kg(DA)
Enthalpy
0ºC 1.9g/kg'(DA) 50% 4.7kJ/kg(DA)
{
Indoor supply-air Indoor _ Outdoor = × Temp recovery + Outdoor temperature (ºC) temperature (ºC) temperature (ºC) efficiency (%) temperature (ºC) Calculation example : 16ºC=(20ºC _ 0ºC)×80%+0ºC
}
The remarkable technology that permits the intake of fresh air with minimal loss to indoor temperature is know as the LOSSNAY Core. The cross-flow, plate-fin structure of the energy-recovery unit along with a specially processed diaphragm keep supply and exhaust air separate, ensuring that only fresh air is introduced to the indoor environment while also allowing for the efficient transfer of heat.
The improvements Outdoors
LOSSNAY system can save up to 30% on plant.
46
Enthalpy (kJ/kg(DA))
The basic principle
cooling energy to either warm and cool Fresh air supply to the room
Relative humidity (%)
Every building needs a supply of fresh air to keep its inhabitants healthy and comfortable. Outdoor air though is rarely, if ever, , the same temperature as that maintained by the building s air conditioning system. In the summer, it is too hot. In the winter, it is too cold. This puts added stress on the air conditioner to compensate for the intake of the hot or cold air adding to the expense of operating the system. LOSSNAY all but eliminates this problem with original energy-recovery technology that uses the heat of the stale indoor air to be expelled in order to either heat or cool the incoming fresh air to a temperature much closer to the existing indoor air. This process reduces the load on the air conditioning system without cutting off the supply of vitally necessary fresh air.
live and work comfort and safety.
years, the LOSSNAY system has perfected
1.9
Energy-recovery calculating equation
Indoor supply-air Outdoor Temp recovery _ Indoor _ Outdoor temperature (ºC) = temperature (ºC) temperature (ºC) temperature (ºC) × efficiency (%) Calculation example : 27.7ºC=33ºC_(33ºC _ 26ºC)×76% * The above applies to the case of LGH-100RX5 (High notch).
provide conditions under which people can
Developed and refined over the past 30
0
5.2
33ºC
Energy-recovery calculating equation
Poor air quality can be attributed to many
16
Absolute humidity (g/kg'(DA))
Outdoor air
Dry bulb temperature
Some 38 years ago, that simple principle led to the development of our most advanced air-conditioning technology.
Dry bulb temperature (ºC)
RA Stale air induction (dirty heating/cooling air)
The microscopically small pores of the diaphragm have been made even smaller, decreasing the rate at which water soluble gases such as ammonia and hydrogen pass through. Further, a new specially processed paper used to make the diaphragm has been developed with high moisture permeability characteristics that aid in the transference of moisture for improved energy exchange efficiency. These developments further improve moisture permeability and effectiveness in shielding unwanted gases, resulting in a lower rate of gas transference and more highly efficient energy transfer. 2
Hyper Eco Core
New function: "By-pass" Ventilation External Control Setting
Better energy conservation by improved total heat exchange efficiency.
In addition to the automatic damper open/close function, open/close control via external devices is now possible, delivering a“By-pass” ventilation system that is suitable to the installed environment.
Introducing the new Hyper Eco Element Mitsubishi's newly developed Hyper Eco Element is on board, offering the industry's best total heat exchange efficiency. Energy conservation performance has been improved not only by reducing the air conditioning load associated with ventilation, but also by facilitating humidity penetration.
Outdoors EA
(exhaust air)
Indoors SA
(supply air)
Control devices (example) .Temperature sensor .Humidity sensor .Timers Exhaust air
Enthalpy exchange efficiency improve *Cooling, High Fan speed, 50Hz
RX4
RX5
Damper
Return air
Supply air
Fresh air
LOSSNAY core
Establish the wire connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16 (Ventilation mode selector).
Element Structure
"By-pass" operation
Remote display adaptor (Optional) PAC-SA88HA-E Brown 1 Red 2
SW1
(outside air)
SW1: By-pass ventilation operation switch (When closed: For By-pass ventilation operation)
73%
RA
(return air)
Yellow 4 Green 5
Humidity does not penetrate easily.
Humidity penetration is facilitated.
The automatic damper mode automatically provides the correct ventilation for the conditions in the room. The following shows the effect “By-pass” ventilation will have under various conditions.
70% 69% 68%
Improved adhesive agent material
67% 66%
Dividerplates
65% Humidity
Not used. Insulate completely. Max wiring length 10 m
Automatic ventilation setting
71%
Hyper Eco Element
Adhesive agent with low humidity penetration rate
Fan speed/ Ventilation mode selection
72%
Hyper Element Spacerplates
CN16
Orange 3
With SW1 is “ON”, the ventilation mode of LOSSNAY is changed to the By-pass ventilation regardless of the setting on the remote controller.
74%
OA
LOSSNAY control board
New adhesive agent with high humidity penetration rate
64% 15RX Type
25RX Type
35RX Type
50RX Type
65RX Type
80RX Type
100RX 150RX 200RX Type Type Type
1. Reduces cooling load If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night), “By-pass” ventilation will draw in the cooler outside air and reduce the cooling load on the system.
Extra Low Mode
CO2 Sensor
Additional energy conservation by using a four-level air volume system that allows more precise control.
The system allows you to measure CO2 density and thereby control the amount of fresh air supplied. By connecting a CO2 sensor to the connector CN16, which is added to the LOSSNAY main unit, the setting can be switched to High, Low, or Extra Low operation, which is selected when the sensor is turned ON. This system produces additional energy conservation.
In addition to the conventional Extra High, High, and Low modes, an Extra Low mode is added to provide a more dynamic range of air volume settings and versatility in a variety of installation environments, yielding much better energy conservation. Using a simplified timer function, it switches to Extra Low operation when the operation stop button is activated and it is accordingly possible to implement 24-hour energy conservation ventilation.
A)
Extra Low
Low
2. Night purge “By-pass” ventilation can be used to release hot air from inside the building that has accumulated in buildings a business district during the hot summer season. 3. Office equipment room cooling During cold season, fresh air can be drawn in and used as is to cool rooms where the temperature has risen due to the use of office equipment. * When the outdoor air tempereture drops lower than 8ºC it changes to the heat exchange ventilation. (Display of the remote controller does not change) * In the case of “By-pass” ventilation, the supply air temperature slightly rises more than the outside air temperature because of the heat effect around the ducts or the unit motors.
Fan speed High
High CO2 density
Fan speed Extra-Low
Low CO2 density CO2Sensor
CO2Sensor
High
Air volume can be set using a pin position. To force High fan speed externally B)
Extra Low
Low
Extra High
CO2 sensor, etc. (When CO2 increases: Closed) SW1
* The Extra High and High ventilation modes are selectable by the initial setting. * Extra-Low not equipped LGH-150RX 5 and 200RX 5. * The ventilation mode is actually selected in three levels, and the remote controller also displays these three levels. SW1: High fan speed operation switch (When closed: For High fan speed operation)
3
Remote display adaptor (Optional) PAC-SA88HA-E Brown 1 Red 2 Orange 3 Yellow 4 Green 5
LOSSNAY control board CN16
When SW1 is "ON", fan speed of the LOSSNAY will be set to "High"(Extra-High) regardless of the remote control setting. Use this in such a way that it ventilates at Low or Extra-Low fan speed normally, and when the external sensor detects contamination of indoor air, it changes to High (Extra High) fan speed operation.
Fan speed/ Ventilation mode selection
Not used. Insulate completely. Max wiring length 10 m
4
Multi-ventilation Mode enables the appropriate supply/ exhaust balance to be selected to suit the usage environment and location Featuring "Multi-ventilation Mode," which allows the air supply/exhaust balance to be varied dynamically. The supply/exhaust balance can be selected to suit the usage environment and location, such as allowing for air exhausted via extractor fans. Modes can be selected easily by setting the connectors on the circuit board.
Control switch Hand-held remote control for microprocessor type
High
Low
Ventilation mode
Supply airflow Exhaust airflow
Unit setting * Factory setting is "High" for both supply and exhaust. Air supply
Air exhaust High
Power air supply/exhaust mode
High
High
High
Power air supply mode
High
Low
High
Low
Power air exhaust mode
Low
High
Low
High
Energy-saving ventilation mode
Low
Low
Newly Adopted Dot Matrix Display Available in Eight Languages ARIAESTERNA
VENTILATION
ITALIANO
ENGLISH
e
Air supply and exhaust are "Low" irrespective of unit setting.
* "High notch" can also be further set to "Extra High" using the unit switch.
Offers choice of 9 air supply/exhaust combination patterns.
Geblasebetrieb Deutsch
Normal office, etc.
Providing efficient ventilation while maintaining air supply/exhaust balance...
Power air supply /exhaust
Smaller offices or tenant buildings, etc.
Using LOSSNAY compensates for using extractor fans...
Power air supply
Smoking areas, etc.
Priority on air exhaust...
Power air exhaust
New Remote Controller PZ-60DR-E
Energy Saving by
VENTILACIoN
VENTILATION
ESPANOL
FRENCH
timer
Air volume level can be set hourly (max 8 times) and weekly. You can pre-set air volume according to the predictable requirement so that LOSSNAY can automatically operate at only necessary air-speed at the specified time period, which saves power consumption while maintaining the indoor air quality. Besides, once the weekly timer has been set, no switching on-off is required.
Example A (Hourly) current RX4 series with PZ-41SLB controller 8:00
new RX5 series with PZ-60DR-E 8:00
9:00
low
13:00
low
17:00
high
19:00
low
22:00
extra low
1,210W (18%) less
Example B (Weekly) 8:00
Saturday to Sunday
9:00
low 8:00
Friday
Energy Saving by
12:00
high
Tolal power consumption in one day : LGH-100RX4-E : 6,600W (14 hours) LGH-100RX5-E : 5,390W (14 hours)
Monday to Thursday
A new remote controller for the RX5 series is now available. In addition to boosting the energy conservation performance of the main unit, the remote controller features a variety of new functions which also pursue additional energy conservation. The appearance of the remote controller conforms to Mitsubishi air conditioner interface design standards. Functions that were set using Dip-Switch on the LOSSNAY main unit can now be configured as needed using the new remote controller. This eliminates the need to crawl under the eaves to change operation settings. Also, a newly adopted dot matrix display provides much more information, making it easy to check maintenance indications, operation status display, and explanations required when configuring settings.
22:00
high
12:00
high
9:00
low
13:00
low 12:00
high
17:00
high
13:00
low
19:00
low 17:00
high
22:00
extra low 22:00
extra low
8:00
22:00
extra low
Night Purge Function
During the summer season, the Night Purge function draws cooler outside air into the room to suppress temperature rises at night. This energy conservation function reduces the load when air conditioning is started the next morning. Dot matrix display
While air conditioning and ventilation are not operating, the room temperature rises as a result of heat from the skeleton and OA equipment.
When the outside temperature becomes lower than the room temperature, ventilation starts automatically.
At night, the outside temperature drops.
Hot air is discharged.
When the room becomes sufficiently cool, ventilation is stopped.
ON/OFF button Fan speed Adjustment button Button CLEAR button Filter button
Return button Timer MENU (MONITOR/SET) button Set time buttons Back Ahead
OPERATION buttons Back Ahead Function selector button
"Extra Low" fan speed button OPERATION button
The air conditioning load required to reach the set temperature the next morning is reduced.
Timer ON/OFF (DAY) button The out door temperture (OA) setting can be selected either 17゜ C or 28゜ C by using Dip-Switch (SW2-7) in the LOSSNAY control box. Refer to the Instillation Manual for more information. *Do not use the night purge function if fog and heavy rain is expected. The entry of rain water may occur in the night.
5
6
Control The New Remote Controller PZ-60DR-E enable simple control setting Interlocked with Air conditioners LOSSNAY independent Interlocked with City Multi
Interlocked with Mr.Slim
M-NET transmission line
City Multi
Slim-LOSSNAY connection cable
LOSSNAY RX5
Mr.Slim
Can Be Used With AG-150A Centralized Controller Controllers are one of the most important and familiar devices in an air conditioning system. Not only does it control to provide optimum air environment but supports operations to minimize running costs and to preserve energy. Through studies and development, we've visualized a new system controller meeting needs with versatile options. With a new coloured touch panel, new functions, and continuation of all the current G-50A functions, AG-150A visualizes its functions from basic control to advanced operations and bringing an ultimate controller to reality.
LOSSNAY RX5 (Max 15 unit)
– Design your control with our new centralized controller; AG -150A. System structure
LOSSNAY RX5
M-NET Switching Hub
LOSSNAY remote controller PZ-60DR-E can be connected PZ-52SF-E can be used insted of PZ-60DR-E, However, function is limited and connecting position is different.
LOSSNAY remote controller PZ-60DR-E The LOSSNAY remote controller (PZ-60DR-E, PZ-41SLB-E) can not be used with this system.
PZ-41SLB-E can be connected however function is limited.
M-NET adapter
LAN (100BASE-TX)
M-NET
A Control
AG -150A
Remote Monitoring PC Remote monitoring via a Web browser
Power supply unit (PAC-SC51KUA)
Centralized Controller System
General Equipment DIDO Controller (PAC-YG66DCA) Hub
Centralized controller AG-150A
Temp/Humidity sensor Lights
M-NET
Outdoor unit Hub
Interlocked with City Multi indoor units Indoor unit
LOSSNAY RX5
Power supply unit (PAC-SC51KUA) Network remote controller
Mr.Slim indoor unit
PI Controller (PAC-YG60MCA)
Network remote controller
LOSSNAY remote controller PZ-60DR-E
ON/OFF
Operation mode switching
LOSSNAY remote controller PZ-60DR-E
Temperature setting
Interlocked with external devices LOSSNAY RX5 LOSSNAY remote controller PZ-60DR-E
Ext. signal source
Modem
VPN Router
Internet
Remote monitoring PC
Mobile phone of service person
Note : Use a security device such as a VPN router when connecting the AG-150A to the Internet to prevent unauthorized access.
Item Controllable unit
LOSSNAY units only
LOSSNAY remote controller PZ-60DR-E
Modem
: Each unit
Mr.Slim remote controller
LOSSNAY RX5
Service company /Sales office
Remote monitoring via a Web browser
Functions
LOSSNAY RX5
LOSSNAY RX5
AG-150A / GB-50A
VPN Router
Interlocked with Mr. Slim indoor units Mr.Slim outdoor unit
Watt hour meter
Central Control PC (TG-2000A) *Ver. 5.50 or later
Indoor unit
Ventilation
AI Controller (PAC-YG63MCA)
Fan speed setting
Air flow direction setting Schedule operation Permit / Prohibit local operation Indoor unit intake temperature Error Test run Ventilation interlock
External input/output
: Each group
: Each block
: Each floor
: Collective
Description
: Not available
Operations
Display
Up to 50 units/groups. Run and stop operation for the air conditioner units and general equipment. (To operate general equipment, PAC-YG66DCA is required.) Switches between Cool / Dry / Auto / Fan / Heat. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) depending on the air conditioner unit. Auto mode is for City Multi R2 and WR2 series only. Cool/Dry : 19 (67 ) - 30 (87 ) [14 (57 ) - 30 (87 )] Heat : 17 (63 ) - 28 (83 ) [17 (63 ) - 28 (83 )] Auto : 19 (67 ) - 28 (83 ) [17 (63 ) - 28 (83 )] [ ] in case of using middle-temperature on PDFY, PEFY-VML/VMR/VMS/VMH-by setting DipSW7-1 to ON. Yet, PEFY-P-VMH-E-F is excluded. Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low Models with 3 air flow speed settings: Hi/Mid/Low Models with 2 air flow speed settings: Hi/Low Fan speed setting (including Auto) varies depending on the model. Air flow direction angles, 4-angle or 5-angle Swing, Auto (Louver cannot be set) Weekly schedule can be set by groups based on daily operation pattern. Individually prohibit operation of each local remote control function (Start/Stop, Change operation mode, Set temperature, Reset filter). Measures the intake temperature of the indoor unit only when the indoor unit is operating. When an error is currently occurring on an air conditioner unit, the afflicted unit and the error code are displayed. This operates air conditioner units in test run mode. The ventilation unit (LOSSNAY) is able to automatically start its operation when operation of the interlocked indoor unit starts. By using optional external input/output adaptor (PAC-YG10HA) you can set and monitor the following. Input : By level signal : "Batch start/stop", "Batch emergency stop" By pulse signal : "Batch start/stop", "Enable/disable local remote controller" Output : "Start/stop", "Error/Normal"
X X
*NOTE: Operation and displayed content vary depending on the indoor unit model.
7
8
List of Remote Controller Settings and Functions
Controllers
The remote controller provides a wide range of functions and features other than the main functions described above, such as sophisticated energy conservation control and an easy to see, easy to use interface.
LOSSNAY remote controller (PZ-60DR-E)
New Controller PZ-60DR-E (V Controlling)
PZ-52SF-E (M-NET) 120
New Function Extra low fan speed (Except LGH-150RX5 and 200RX5) Weekly timer Simple timer Night Purge mode Multi languages display 24-hours ventilation (Except LGH-150RX5 and 200RX5) Operation function limit Clock display Contact number setting for error situation LOSSNAY core cleaning sign Air volume display by external signal By-pass display by external signal Possible setting from the controller in addition to unit Dip-SW setting Extra High / High switch setting Multi Ventilation mode Power supply / exhaust when operation starts Pulse input Inter locking mode Automatic recovery following power supply interruption Delay operation at heating or cooling start-up Operation output monitor Exhaust fan stop at outdoor air lower than -15ºC Exhaust fan stop during defrosting,exhaust fan Low speed operation at outdoor air lower than -15ºC By-pass automatic ventilation priority setting Filter cleaning sign Maintenance display Total operated hours Total LOSSNAY mode operated hours Error history Carry on function In the use of MELANS M-NET 2 controllers display "Central" indication(use prohibition)
PZ-41SLB-E (V Controlling)
19
130
(in unit setting) (in unit setting) (in unit setting) (in unit setting)
(in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting) (in unit setting)
only auto recover mode (in unit setting) (in unit setting) (in unit setting) (in unit setting)
1–15
120 8
70
48
33
70
48
Unit: mm
8
33
Unit: mm
*Stock available only.
*Stock available only. Source power requirement Interface condition for transmission line Number of LOSSNAY units controlled by PZ-41SLB-E
Input voltage: 9VDC-15VDC, 0.02A Power received from a LOSSNAY unit, TM4 1 - 2 Specialized transmission line: DC power+AM modulation 1–15
Source power requirement Interface condition for transmission line
Input voltage: 17VDC – 30VDC, 0.02A Power received from an outdoor unit or a power supply unit via M-NET transmission line. M-NET transmission line: 30VDC+AMI signal (±5VDC)
Number of M-NET controlled LOSSNAY 1–16 units controlled by PZ-52SF-E
Filters
B B
取 付 日
High-efficiency filter This high-efficiency filter (with 65% colorimetricity EU-F7) can be incorporated inside the LOSSNAY unit without the need to attach parts from other systems, as done to date. The main unit external dimensions are unchanged, and processing capacity ranges between 150m3/h and 2,000m3/h.
AIR FLOW 年 月 日
Standard filter Replacement components for the standard air filter supplied with the LOSSNAY LGH main unit.
A
A
C
C
Installation with duct direction changed
Avoid installations where the stale air exhaust aperture would be blocked by lighting or air conditioning units.
Can be installed close to the surface of the wall.
A space is necessary to prevent the influx of rainwater.
OA
EA
Changing the duct direction
Collar Aperture Plate
9
Number of LOSSNAY units controlled by PZ-41SLB-E
LOSSNAY M-NET remote controller (PZ-52SF-E)
LOSSNAY remote controller (PZ-41SLB-E)
Ducts can be connected in two different directions to the outdoor vents thanks to collars and aperture plates that can be interchangeably placed in two different positions. This flexibility allows for installations close to the surface of a wall and helps avoid cases where the stale air exhaust vent would be blocked by an obstruction of some kind. This makes both planning and installation that much simpler.
EA
Power received from a LOSSNAY unit, TM4 1 - 2
Unit: mm
Connect ducts in two different directions (OA, EA side)
Standard installation
Source power requirement
120
Function(Communicating mode)
Exchangeable
OA
Model
Lighting, etc.
EA
OA
Remove the collar (factory-standard direction) and the side panel aperture plate and switch their placements. They are both equipped with screw stoppers making the switch extremely simple. The direction of the ducts can only be changed on the outside (OA and EA). The inside cannot be changed (SA and RA).
The position of the suspension bracket is changed to improve workability.
OA/EA square duct (LGH-150・200R)
By attaching the suspension bracket in the center of the product, the suspension bracket does not need to be moved even when the product is mounted upside down. (Model LGH-15 to 65)
OA/EA is square duct. This simplifies installation and reduces total installation time.
PZ-25RF8-E PZ-35RF8-E PZ-50RF8-E PZ-65RF8-E PZ-80RF8-E PZ-100RF8-E
Number of Dimension (mm) filters per set A 333 399 470 433 451 565
B 156 183 183 218 243 243
Applicable model
Filter material
C Supply Exhaust 2 2 15 LGH-15RX5-E,LGH-25RX5-E 2 2 20 LGH-35RX5-E Nonwoven filter 2 2 15 LGH-50RX5-E Collection efficiency 2 2 15 LGH-65RX5-E (EU-G3) 2 2 15 LGH-80RX5-E,LGH-150RX5-E(2sets) 2 2 15 LGH-100RX5-E,LGH-200RX5-E(2sets)
Dimension (mm) Number of Filter filters Applicable model material per set A B 2 144 327 LGH-15RX5-E,LGH-25RX5-E PZ-25RFM Non combustible 2 171 393 LGH-35RX5-E PZ-35RFM fiber 2 171 464 PZ-50RFM LGH-50RX5-E (Polyester 2 205 427 PZ-65RFM LGH-65RX5-E polyolefin) 2 232 446 PZ-80RFM LGH-80RX5-E,LGH-150RX5-E(2sets) (EU-F7) 2 232 559 PZ-100RFM LGH-100RX5-E,LGH-200RX5-E(2sets) Model
Incorporation into the main unit is simple, and filter changes can be performed via the main unit inspection opening.
10
A Breath of Freshness in Restaurants, Offices, and Schools Restaurants
Offices
Schools
A restaurant can never be too clean and its air never too fresh
Fresh air–improving the overall quality of working life
Creating the best possible environment for our children to succeed
The atmosphere of a restaurant is crucial to securing customers and making them happy enough to come back for more. Cleanliness is the key to an attractive atmosphere and restaurants devote significant effort to ensuring the premises are sanitary. Sanitation and cleanliness, however, are not enough. No matter how clean a restaurant may look, if there are bothersome odors lingering in the air, all those efforts go to waste and the restaurant's clean image is tarnished. For these reasons, we invite restaurant owners to leave the air to LOSSNAY. LOSSNAY's superior ventilation capabilities ensure that every breath is a breath of freshness keeping guests happy. LOSSNAY also keeps owners happy with its remarkable heat recovery technology that supplies fresh outdoor air with minimal change to indoor temperature, saving on energy and expense.
Many office buildings today are heavily insulated air-tight structures with little or no natural ventilation. The unnatural environment created by air conditioners without added ventilation is a breeding ground for bacteria. Factor this in with the accumulation of pollutants and odors in the form of cigarette smoke, formaldehyde, pollen, dust, and carbon dioxide, and the necessity of ventilation becomes ever more apparent. In fact, poorly ventilated buildings can give rise to Sick Building Syndrome, a malady that is known to cause headaches, sore eyes, itching, and concentration loss. This results not only in discomfort at best and sickness at worst for the building's occupants, but also the reduced productivity of the workforce. Fresh air, effectively ventilated throughout the building, is therefore essential to the overall quality of working life.
Children deserve all the help we can give for them to grow up healthy, happy, and prosperous. No matter how good a school's curriculum, no matter how positive and enthusiastic the teacher, a child who does not feel well will have a hard time learning. The constant flow of fresh air is nowhere as important as it is in our schools. In classrooms where large numbers of students are gathered for long periods of time, carbonic gases have the tendency to accumulate, decreasing the levels of oxygen that are vital for alertness and concentration. This is especially true during the winter months when windows tend to remain closed. LOSSNAY ventilates fresh outdoor air into classrooms to replenish the supply of oxygen and expels not only carbon dioxide, but also other pollutants and odors that inevitably sully the air.
If it’s LOSSNAY...
If it’s LOSSNAY...
If it’s LOSSNAY...
Ventilators work to exhaust stale air and supply fresh, clean air free of the odors associated with cooking, cigarettes, and the people working and dining.
Simultaneous forced-air supply and exhaust introduces fresh, outdoor air into the building, effectively ventilating even fully airtight structures.
The continuous influx of fresh, outdoor air and the exhaust of stale, indoor air ensure that the indoor oxygen level is maintained at just the right balance for comfort and health.
Change in room temperature is kept to a minimum during ventilation thanks to the heat-recovery function.
Multiple split-type units operate independently of one another, simplifying system set up and ensuring a layout that optimally matches nearly any office design.
Occupants have the luxury of breathing fresh air at all times even in highly air-tight buildings.
The ventilators operate very quietly so those in the midst of enjoying their meals will not be bothered by any excess noise.
LOSSNAY operation can be interlocked with air-conditioning system operation.
LOSSNAY's sound attenuation qualities prevent outside noise from penetrating into the room, helping to maintain a quiet environment for productive study.
A large array of ventilators is available to match the layout of just about any restaurant.
Heat that is commonly lost due to ventilation is collected and reused thanks to the LOSSNAY Core, reducing air conditioners’ energy load and cutting operating costs.
Heat-exchange technology prevents fluctuations in temperature for significant energy savings when either heating or cooling a room.
What would you most like to see improved in restaurants?
O2 concentration and deficiency
52.3% Improvement in overall cleanliness
Others: No response
21%
Promotion of waste prevention: 5.4%
Improvement in employees’ attitude toward customer service: 20.5%
O2 Concentration (%)
Reduction of time required for food to reach the table: 12.0%
18%
21
Improvement in atmosphere: 6.5%
16%
Normal air 15 10 5 0
Safety minimum
Increased respiration and pulse
12%
10%
8%
Dizziness, nausea,loss of Paleness of Comatose muscle strength skin, vomiting. Unconsciousness (death in 8min) (precursors to death)
6% Convulsions respiration stops, death
1996 Foodstuffs Consumption Monitor, Second Periodic Survey (Ministry of Agriculture, Forestry and Fisheries, Japan)
11
12
Specifications / Dimensions LGH-15 to 100RX5
LGH-15RX5-E LGH-15RX5-E
Model Frequency / Power source
50Hz / Single phase 220-240V LOSSNAY ventilation
By-pass ventilation
Ventilation mode Fan speed
Extra High
High
Low
Extra Low
Extra High
High
Low
Extra Low
Current (A)
0.44-0.46
0.37-0.38
0.25-0.25
0.14-0.15
0.45-0.46
0.37-0.38
0.25-0.26
0.14-0.15
96-110
80-90
53-59
30-35
97-110
81-91
54-61
30-35
(m3/h)
150
150
110
70
150
150
110
70
(L/s)
42
42
31
19
42
42
31
19
(mmH2O)
10.2-10.7
6.6-7.1
3.6-4.1
1.4
10.2-10.7
6.6-7.1
3.6-4.1
1.4
(Pa)
100-105
65-70
35-40
14
100-105
65-70
35-40
14
82.0
82.0
84.0
85.5
Heating
75.0
75.0
77.5
81.0
Cooling
73.0
73.0
76.5
81.0
27.5-28
26.5-27
22-23.5
18
28.5-29
27-28
23-24
18-19
Power consumption (W) Air volume External static pressure
Temperature exchange efficiency (%) Enthalpy exchange efficiency (%)
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Noise (dB) Weight (kg)
20 Under 0.8A Less
Starting current
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 6dB greater than the indicated value.(at High Fan speed)
50Hz/Single phase 220V Enth
Ent
80
30
300
60
25
250
50
20
200
15
150
hal py
exch ange effic ienc exc y(H han eatin ge g) eff icie nc y(C oo ling )
10
20m
Extra high
100 Extra low
15m
10m High 5m
5
0
50
0
50
100
150
200
70
30
300
60
25
250
Temp efficieerature exc Enth hange ncy alpy exch Ent ange hal e py fficie exc ncy han (He ge atin g) eff icie nc y(C oo ling )
50
20
200
Extra high
15
150
80 100mm dia pipe length
Low
Pa
External static pressure mmH 2 O
LGH-150 and 200RX5
70
alpy
50Hz/Single phase 240V
Exchange efficiency (%)
90
Temp e efficie rature exch ncy ange
250
10
20
30
20m
10m
100
High Extra low 5m
5
0
50
0
50
100
(m2/h) 0
100mm dia pipe length
15m
Low 10
Pa
Exchange efficiency (%)
External static pressure mmH 2 O
90
150
200
250
(m2/h)
40
50
60
70
0
10
20
Air volume (L/s)
30
40
50
60
70
Air volume (L/s)
Position where duct direction change is possible 102
768
Air exhaust fan
By-pass damper plate Ceiling suspension fixture (4-13x20 oval) 65 RA (return air) 782 20
150 ~250
Core, air filter, HighEfficiency filter, fan, Maintenance space
More than 600
OA (outside air intake) 102 Inspection opening
LOSSNAY core
Position where duct direction change is possible
13
780
Control box
30 273
Maintenance cover High efficiency filter(sold separately) attachment position 103 97.5 110
30
103
SA (supply air) Power supply cable opening 65 Air supply fan
95
735 530
EA (exhaust air outlet)
Air filters(EU-G3)
Unit: mm
14
LGH-25RX5-E
LGH-35RX5-E LGH-25RX5-E
Model Frequency / Power source
LGH-35RX5-E
Model
50Hz / Single phase 220-240V
Frequency / Power source
LOSSNAY ventilation
By-pass ventilation
50Hz / Single phase 220-240V
Ventilation mode Fan speed
Extra High
High
Low
Extra Low
Extra High
High
Low
Extra Low
Ventilation mode Fan speed
Extra High
High
Low
Extra Low
Extra High
High
Low
Extra Low
Current (A)
0.52-0.55
0.47-0.48
0.26-0.27
0.17-0.18
0.53-0.55
0.47-0.48
0.26-0.27
0.17-0.18
Current (A)
0.92-0.92
0.74-0.74
0.5-0.51
0.28-0.3
0.93-0.94
0.77-0.77
0.51-0.52
0.28-0.3
Power consumption (W)
113-129
102-114
56-62
36-42
115-131
103-115
56-63
36-42
Power consumption (W)
195-212
160-169
105-116
58-69
197-217
164-173
105-116
58-69
(m3/h)
250
250
155
105
250
250
155
105
(m3/h)
350
350
210
115
350
350
210
115
(L/s)
69
69
43
29
69
69
43
29
(L/s)
97
97
58
32
97
97
58
32
(mmH2O)
8.2-8.7
5.1-6.1
2-2.5
0.9
8.2-8.7
5.1-6.1
2-2.5
0.9
(mmH2O)
15.8-16.3
7.6-8.2
2.5-3.1
0.9
15.8-16.3
7.6-8.2
2.5-3.1
0.9
(Pa)
80-85
50-60
20-25
9
80-85
50-60
20-25
9
(Pa)
155-160
75-80
25-30
9
155-160
75-80
25-30
9
79.0
79.0
81.5
83.5
80.0
80.0
85.0
88.0
Heating
69.5
69.5
74.0
77.5
Heating
71.5
71.5
76.5
81.5
Cooling
68.0
68.0
72.5
76.0
Cooling
71.0
71.0
75.5
81.0
26-27
25-26
20-21.5
18-19
32-32
28.5-29.5
21.5-23
18
32.5-32.5
29.5-30.5
21.5-24
18
Enthalpy exchange efficiency (%)
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Weight (kg)
Temperature exchange efficiency (%) Enthalpy exchange efficiency (%) 26.5-27.5
25.5-26.5
20.5-22
18-19
20 Under 0.9A Less
Starting current
Weight (kg)
50Hz/Single phase 220V
Exchange efficiency
80 70 60
200
60 50
150 dia pipe length 40m
150 Low 100
5
50
0
0
Exchange efficiency (%)
80
Enth alpy Enth
alpy e
70
exch a
xcha nge
350
nge effic
ienc
effic ie
y(He
ncy(
60
Coo
300
30
30m High
Extra low
20m 10m
50
100
150
200
250
300
350
400
25
250
20
200
150 dia pipe length
Extra high
40m 150
15
30m
Low High 10
100
5
50
0
0
Extra low
10m
50
100
150
(m2/h) 0
20m
200
250
300
350
400
(m2/h)
10 20 30 40 50 60 70 80 90 100
0
25
250
20
200
10
50
Low
0
0
50 100 150 200 250 300 350 400 450 500
0
Air volume (L/s)
20
40
60
80
100
120
LOSSNAY core 780
150mm dia pipe length 30m
High
Extra low
150
20m Low
100
10m
5
50
0
0
50 100 150 200 250 300 350 400 450 500
20
40
Core, air filter, HighEfficiency filter, fan, Maintenance space
60
80
100
120
140
Position where duct direction change is possible By-pass damper plate Ceiling suspension fixture 875 80 (4-13x20 oval)
124
921
874 650 30 273
g)
RA (return air)
124 Inspection opening
LOSSNAY core 64
142 160
SA (supply air) Power supply cable opening Air supply fan Control box
80 55 315
Maintenance cover
888
High efficiency filter(sold separately) attachment position 64
55
30
63
Control box
OA (outside air intake)
Maintenance cover High efficiency filter(sold separately) attachment position 63
eatin
Air volume (L/s)
20
20 Inspection opening
ncy( H
ienc y(
142 160
150 ~250
102
SA (supply air) Power supply cable opening 65 Air supply fan
95
782
735 530 Core, air filter, HighEfficiency filter, fan, Maintenance space
More than 600
OA (outside air intake)
200
EA (exhaust air outlet)
RA (return air)
EA (exhaust air outlet)
20
0
Ceiling suspension fixture (4-13x20 oval) 65
150~250
768
250
140
Air exhaust fan
More than 600
102
effic ie
effic
Coo ling)
Air volume (L/s)
By-pass damper plate
ange
ange
(m2/h)
Position where duct direction change is possible
Air exhaust fan
25
10
10m 50
exch
exch
300
30
15
20m Extra low
Temp efficieerature e xcha ncy nge
Extra high
High
100
5
350
30m
150
15
60
alpy
Enth alpy
70
150mm dia pipe length
Enth
(m2/h)
10 20 30 40 50 60 70 80 90 100
Air volume (L/s)
50
Exchange efficiency (%)
80
ating )
ling)
50Hz/Single phase 240V
90
Temp e efficie rature ex chan ncy ge
Extra high Extra high
15 10
70
50Hz/Single phase 220V
90
Tem effic perature ienc Enth y exchang alpy e exch ange Ent halp effic ienc y ex y(H cha eatin nge g) effic ienc y(Co oling )
Pa
20
50Hz/Single phase 240V
Exchange efficiency
Pa
250
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
80
External static pressure mmH 2 O
25
Pa
External static pressure mmH 2 O
50
90
Tem effic perature ienc En th y exchang alpy e exch ang Ent e halp effic y ex ienc y(H cha eatin nge g) effic ienc y( Co oling )
29 Under 2.4A Less
Starting current
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
90
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Noise (dB)
External static pressure mmH 2 O
Noise (dB)
External static pressure
95
Temperature exchange efficiency (%)
Pa
External static pressure
Air volume
By-pass ventilation
External static pressure mmH 2 O
Air volume
LOSSNAY ventilation
Position where duct direction change is possible
15
Air filters (EU-G3)
Unit: mm
Position where duct direction change is possible
Air filters(EU-G3)
Unit: mm
16
LGH-50RX5-E
LGH-65RX5-E LGH-50RX5-E
Frequency / Power source
LOSSNAY ventilation
By-pass ventilation
Extra High
High
Low
Extra Low
Extra High
High
Low
Extra Low
Current (A)
1.2-1.25
1.0-1.0
0.85-0.85
0.4-0.4
1.25-1.25
1.0-1.0
0.85-0.85
0.4-0.4
Power consumption (W)
255-286
207-228
175-190
80-95
260-290
210-230
180-195
80-95
(m3/h)
500
500
390
180
500
500
390
180
(L/s)
139
139
108
50
139
139
108
50
(mmH2O)
15.3-15.8
6.6-9.2
4.1-6.1
1.0
15.3-15.8
6.6-9.2
4.1-6.1
1.0
(Pa)
150-155
65-90
40-60
10
150-155
65-90
40-60
10
78.0
78.0
81.0
86.0
Heating
69.0
69.0
71.0
78.0
Cooling
66.5
66.5
68.0
77.0
33-34
30.5-32
26.5-28
19
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Weight (kg)
50Hz/Single phase 220V
34-35
31-32.5
27-29
19
350
60
30
300
25
250
20
200
15
150
10
50m
High
40m
Low
100
30m Extra low
5
20m
50 10m
0
0
100
200
300
400
500
600
70
35
350
60
30
300
50
60m
Pa
External static pressure mmH 2 O
50
200mm dia pipe length
700
25
250
20
200
15
150
10
40
60
excha nge efficie ncy ye xchan ge eff icienc Enth y (H alpy eatin exch g) ange efficie ncy (Coo ling) Extra high
60m 50m
30m Extra low
5
50
0
0
0
20m 10m
100
200
20
40
60
300
400
(m2/h)
500
600
700
80 100 120 140 160 180 200
350-380
308-322
248-265
120-140
350-385
310-335
250-265
120-140
(m3/h)
650
650
520
265
650
650
520
265
(L/s)
181
181
144
74
181
181
144
74
(mmH2O)
11.2-12.2
6.1-8.2
4.1-5.1
0.8
11.2-12.2
6.1-8.2
4.1-5.1
0.8
(Pa)
110-120
60-80
40-50
8
110-120
60-80
40-50
8
77.0
77.0
80.0
86.0
Heating
68.5
68.5
70.5
78.0
Cooling
66.0
66.0
68.5
77.0
34-34.5
32-33
28.5-31.5
22
34.5-35
32.5-33.5
28.5-30.5
22-22.5
Air volume External static pressure
Noise (dB)
(Measured at 1.5m under the center of panel in an anechoeic chamber)
50Hz/Single phase 220V
efficiency (%)
rature
exchan geefficie ncy lpy ex change Enth efficienc alpy y excha (Heati nge effic ng) iency (C ooling)
124 Inspection opening
450
60 40
400
50 35
350
30
300
25
250
20
200
15
150
Extra high
10
100
5
50
0
200mm dia pipe length
40m
Low High
30m
Extra low
20m 10m
0
rature exchan ge effic iency lpy ex change Enth efficienc alpy y excha (Heati nge effic ng) iency (C ooling)
450
60 40
400
50 35
350
30
300
25
250
20
200
15
150
0
25
50
Extra high
10
100
5
50
30m
High Extra low
20m 10m
100 200 300 400 500 600 700 800 900
25
Position where duct direction change is possible By-pass damper plate 895 Ceiling suspension fixture (4-13x20 oval) 70 RA (return air)
954 692 Core, air filter, HighEfficiency filter, fan, Maintenance space
75 100 125 150 175 200 225 250
50
Air volume (L/s)
SA (supply air)
OA (outside air intake)
High efficiency filter(sold separately) attachment position 79
40m
Low
0
EA (exhaust air outlet)
30
60m 50m
0
75 100 125 150 175 200 225 250
Air exhaust fan
315
200mm dia pipe length
(m2/h)
Power supply cable opening
133 Inspection opening
70 386
High efficiency filter(sold separately) attachment position
LOSSNAY core 79
Air supply fan Control box Maintenance cover
Maintenance cover
888
Tempe
Entha
0
100 200 300 400 500 600 700 800 900
133
95
SA (supply air) Power supply cable opening 65 Air supply fan Control box
efficiency (%)
70 45
50m
908
79
30
192 208
LOSSNAY core 79
80
Entha
70 45
50Hz/Single phase 240V
90 Exchange
Tempe
1063 20
OA (outside air intake)
Extra Low
40 Under 4.4A Less
Air volume (L/s)
Position where duct direction change is possible By-pass damper plate Ceiling suspension fixture 875 65
1016 745
0.6-0.6
Power consumption (W)
(m /h)
RA (return air)
More than 600 150~250
1.2-1.2
2
Air volume (L/s)
EA (exhaust air outlet)
Core, air filter, HighEfficiency filter, fan, Maintenance space
40m
High
Low
100
80 100 120 140 160 180 200
124
1.5-1.5
80
200mm dia pipe length
Air volume (L/s)
Air exhaust fan
1.7-1.8
rature
Ent halp
(m /h) 20
0.6-0.6
90 Exchange
Tempe
2
0
1.2-1.2
192 208
35
50Hz/Single phase 240V
External static pressure mmH 2 O
70
excha Ent nge halp efficie ncy ye xchan ge e fficien Enth cy (H alpy eatin exch g) ange efficie ncy (Coo ling) Extra high
1.5-1.5
Starting current
Exchange efficiency (%) 400 80
rature
1.7-1.8
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
90
Tempe
Low
Current (A)
Weight (kg)
Pa
Exchange efficiency (%) 400 80
High
Enthalpy exchange efficiency (%)
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 16dB greater than the indicated value.(at High Fan speed)
90
Extra High
Temperature exchange efficiency (%)
32 Under 3.0A Less
Starting current
Extra Low
95
Noise (dB)
Low
Pa
Enthalpy exchange efficiency (%)
High
External static pressure mmH2O
Temperature exchange efficiency (%)
By-pass ventilation
Extra High
1001
External static pressure
LOSSNAY ventilation
Ventilation mode Fan speed
20
Air volume
50Hz / Single phase 220-240V
More than 600 150~250
Ventilation mode Fan speed
LGH-65RX5-E
Model
50Hz / Single phase 220-240V
Pa
Frequency / Power source
External static pressure mmH2O
Model
Position where duct direction change is possible
17
Air filters(EU-G3)
Unit: mm
Position where duct direction change is possible
Air filters(EU-G3)
Unit: mm
18
LGH-80RX5-E
LGH-100RX5-E LGH-80RX5-E
Frequency / Power source
LOSSNAY ventilation
By-pass ventilation
Ventilation mode Fan speed
Extra High
High
Low
Extra Low
Extra High
High
Low
Extra Low
Ventilation mode Fan speed
Current (A)
1.75-1.75
1.6-1.6
1.45-1.45
0.60-0.65
1.75-1.75
1.6-1.6
1.45-1.45
0.60-0.65
Power consumption (W)
380-415
345-370
315-340
125-145
380-415
345-370
315-340
120-145
(m3/h)
800
800
700
355
800
800
700
355
(L/s)
222
222
194
99
222
222
194
99
(mmH2O)
14.8-15.3
10.7-12.2
8.2-9.7
2
14.8-15.3
10.7-12.2
8.2-9.7
2
(Pa)
145-150
105-120
80-95
20
145-150
105-120
80-95
20
79.0
79.0
80.5
87.5
Heating
71.0
71.0
72.5
79.5
Cooling
70.0
70.0
71.5
79.5
33.5-34.5
32-33
30-31
22
Weight (kg)
50Hz/Single phase 220V
34.5-35.5
33-34
nge exch ange effic Enth ienc effic alpy e y (H ienc xcha eatin y(C nge g) ooli ng)
50
Extra high
400
40
60 250mm dia pipe length
300
30
200
20
31-32
22
60m
100
40m 20m
0
0
200
400
600
800
1000
1200
(m2/h) 0
50
100
150
200
250
300
nge exch ange effic Enth ienc y(H effic alpy exc eatin ienc hang y(C g) ooli e ng) y
80m 60m
100
40m 20m
0
200
400
600
800
1000
1200
(m2/h)
350
0
50
100
150
200
250
300
350
Air volume (L/s)
Position where duct direction change is possible By-pass damper plate Ceiling suspension fixture (4-15x20 oval)
165
365-395
175-200
(m3/h)
1000
1000
755
415
1000
1000
755
415
(L/s)
278
278
210
115
278
278
210
115
(mmH2O)
16.3-17.3
10.2-11.2
5.6-6.1
1.8
16.3-17.3
10.2-11.2
5.6-6.1
1.8
(Pa)
160-170
100-110
55-60
18
160-170
100-110
55-60
18
80.0
80.0
83.0
87.0
Heating
72.5
72.5
74.0
80.0
Cooling
71.0
71.0
73.0
79.0
36-37
34-35
31-32.5
21-22
37-38
35-36
32-33
21-22
Air volume External static pressure
Noise (dB)
(Measured at 1.5m under the center of panel in an anechoeic chamber)
165 Inspection opening
50Hz/Single phase 220V Exchange efficiency (%)
Ent
halp
En
y ex
tha
lpy
cha n
exc
50
ge
500
50
40
400
30
300
ge
ge efficie effic
ncy(H eatin
ienc
Position where duct direction change is possible
Exchange efficiency (%)
y(C
Ent
80
En
halp y
tha lpy
exc han
exc
ge
ge
han
500
50
Tem effic peratur e ex ienc cha y n
ge
g)
70
efficie
ng)
250mm dia pipe length 100m
Extra high
60
50
40
400
30
300
20
200
ncy(H
effic ienc
eatin
y(C
ooli
g)
ooli
ng)
250mm dia pipe length 100m
Extra high
80m
80m 200
20
60m High
Low 10
40m
Extra low
100
20m
0
0
200 0
50
400 100
600 150
800 200
1000 250
1200
300
350
1400
High
60m
Low 10
40m
Extra low
100
20m
0
0
200 0
400
50
400 100
600 150
800 200
1000 250
300
1200
1400
350
400
Air volume (L/s)
Air volume (L/s)
Position where duct direction change is possible By-pass damper plate Ceiling suspension fixture 1010 (4-15x20 oval) RA (return air)
1231 917 95 389 399 Core, air filter, HighEfficiency filter, fan, Maintenance space
High efficiency filter(sold separately) attachment position 79
SA (supply air) Power supply cable opening 165 Inspection opening
79
Air filters(EU-G3)
Unit: mm
Position where duct direction change is possible
Air supply fan Control box
399
Maintenance cover
LOSSNAY core
242 258
1144
50Hz/Single phase 240V
90
Tem effic peratur e ex ienc cha y n
OA (outside air intake)
Maintenance cover
LOSSNAY core 79
Air supply fan Control box
Extra Low
59 Under 4.6A Less
1036
1004 690
460-485
EA (exhaust air outlet)
SA (supply air) Power supply cable opening
OA (outside air intake) More than 600 150~250
510-550
Air exhaust fan
RA (return air)
EA (exhaust air outlet)
175-200
165
1010
Air exhaust fan
350-380
100m
200
0
445-475
han
Extra low 10
500-535
70
250mm dia pipe length Low
20
0.9-0.9
Power consumption (W)
60
300
30
1.7-1.7
80
Extra high
Air volume (L/s)
Core, air filter, HighEfficiency filter, fan, Maintenance space
alp
Tem effic peratu ienc re e xch y a
High
80m Extra low
10
50
100m
Low
Pa
External static pressure mmH 2 O
High
2.1-2.1
90
400
40
2.3-2.4
50Hz/Single phase 240V
500
50
0.9-0.9
Starting current
En th
70
1.7-1.7
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 17dB greater than the indicated value.(at High Fan speed)
80
External static pressure mmH 2 O
60
500
50
2.1-2.1
Weight (kg)
Exchange efficiency (%)
Pa
En tha lpy
80
70
90
Tem effic perat ienc ure e xch y a
2.3-2.4
Enthalpy exchange efficiency (%)
53 Under 3.8A Less
Exchange efficiency (%)
Low
Current (A)
Temperature exchange efficiency (%)
Starting current *The Air outlets noise (45 angle,1.5meters in front of the unit) is about 16dB greater than the indicated value.(at High Fan speed)
90
High
95
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Extra High
Pa
Noise (dB)
Extra Low
1144
High efficiency filter(sold separately) attachment position 79
Air filters(EU-G3)
242 258
Enthalpy exchange efficiency (%)
By-pass ventilation
Low
External static pressure m mH 2 O
Temperature exchange efficiency (%)
LOSSNAY ventilation High
Pa
External static pressure
50Hz / Single phase 220-240V Extra High
External static pressure mmH 2 O
Air volume
19
LGH-100RX5-E
Model
50Hz / Single phase 220-240V
More than 600 150~250
Frequency / Power source
1263
Model
Unit: mm
20
LGH-150RX5-E
LGH-200RX5-E LGH-150RX5-E
Low
Extra High
High
Low
3.5-3.5
3.2-3.2
2.9-2.9
3.5-3.5
3.2-3.2
2.9-2.9
Current (A) Power consumption (W)
760-830
690-740
630-680
765-835
695-745
635-685
1500
1500
1300
1500
1500
1300
(L/s)
417
417
361
417
417
361
(mmH2O)
16.3-17.8
13.3-13.8
9.7-10.2
16.3-17.8
13.3-13.8
9.7-10.2
(Pa)
160-175
130-135
95-100
160-175
130-135
95-100
80.0
80.0
81.0
Heating
72.0
72.0
72.5
Cooling
70.5
70.5
71.5
38-39
36-37.5
33.5-35
External static pressure
Temperature exchange efficiency (%) Enthalpy exchange efficiency (%)
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Weight (kg)
Enthalpy exchange efficiency (%) 39-40.5
37.5-39
35.5-37
E nth
Enth alp
External static pressure (mmH 2 O)
50
400
40
300
20
200
70
60
50
Low High
0 0
500 0
100
1000
1500
2000
(m2/h)
200
300
Enth
Enth a
e ef y ex ficie ch a ncy nge (He effic atin ienc g) y(C ooli ng)
100
50Hz/Single phase 240V
ang
Extra high
30
10
exch
400
500
600
Low
4.2-4.2
3.4-3.4
4.8-4.8
4.2-4.2
3.4-3.4
1035-1100
910-980
715-785
1040-1110
915-980
720-785
2000
2000
1580
2000
2000
1580
(L/s)
556
556
439
556
556
439
(mmH2O)
16.3-16.8
10.2-10.7
6.1-6.6
16.3-16.8
10.2-10.7
6.1-6.6
(Pa)
160-165
100-105
60-65
160-165
100-105
60-65
80.0
80.0
83.0
Heating
72.5
72.5
73.5
Cooling
71.0
71.0
72.0
39.5-40
37-38
32.5-34
40.5-41
38-39
33.5-35
alpy
lpy e
exch
xcha
ang
nge
400
40
90
300
20
200
enc y(H effic eat ing ienc ) y(C ooli ng)
100 High
0
700
100
1000
1500
2000
(m2/h)
200
300
400
2500
exch
ange
chan
ge e fficie nc
efficie
exch
ange
ncy(H
20
10
y
eating
)
High Low
100
0 1000
1500
2000
600
700
0
100
200
300
400
500
600
10
High
200 Low 100
0 500 0
700
1010
Core, air filter, HighEfficiency filter, fan, Maintenance space
Power supply cable opening
270
Inspection opening
Air supply fan
21
200
300
400
500
600
700
399 798
Control box
242 258
44
Power supply cable opening
High efficiency filter(sold separately) attachment position
LOSSNAY core 1144
79
Unit: mm
Air filters(EU-G3)
242 258
242 258
700
700 Air filters(EU-G3)
100
242 258
High efficiency filter(sold separately) attachment position 79
2500
917 1272 27
SA (supply air)
Maintenance cover
1144
2000
Ceiling suspension fixture (4-15x30 oval)
270 150~250
Maintenance cover
44
1500
RA (return air)
1231 917 110
OA (outside air intake)
399 798
Control box
LOSSNAY core
1000
Air volume (L/s)
EA (exhaust air outlet)
690 1045 27 Air supply fan
20
300
0
Air exhaust fan
SA (supply air)
Inspection opening
ooling )
(m2/h)
More than 600
270 150~250
More than 600
Core, air filter, HighEfficiency filter, fan, Maintenance space
efficie ncy(C
By-pass damper plate
Ceiling suspension fixture (4-15x30 oval)
270
OA (outside air intake)
30
Air volume (L/s)
RA (return air)
1004 690
EA (exhaust air outlet)
1010
ncy
cy(He ating)
Extra high
2500
By-pass damper plate Air exhaust fan
ange
(m /h) 500
fficie
e eff icien
exch
2
Air volume (L/s)
ge e
400 40
50
chan
hang
50
300
500
alpy
500
70
efficie
re ex
y exc
Enth
Extra high
0
eratu
Enth alp
60
200
Tem p
80
400
30
50Hz/Single phase 240V
Exchange efficiency (%)
ncy(C ooling )
40
Low
Air volume (L/s)
alpy
500 50
50
500
pera ture ex
alpy
70
90
Tem Enth
60
0
50Hz/Single phase 220V
Exchange efficiency (%)
Enth
e ef fici
0
2500
118 Under 11.9A Less
80
Extra high
30
10
Temp effic erature e ienc xcha y nge
500
50
(Measured at 1.5m under the center of panel in an anechoeic chamber)
Starting current
80
External static pressure (mmH 2 O)
60
500
50
(Pa)
70
alpy
High
4.8-4.8
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 20dB greater than the indicated value.(at High Fan speed)
Exchange efficiency (%)
(Pa)
80
90
Temp effic erature e ienc xcha y nge
Noise (dB)
External static pressure (mmH 2 O)
50Hz/Single phase 220V
Exchange efficiency (%)
Extra High
Weight (kg)
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 19dB greater than the indicated value.(at High Fan speed)
90
Low
Temperature exchange efficiency (%)
105 Under 7.3A Less
Starting current
High
(m3/h)
Air volume External static pressure
By-pass ventilation
Extra High
110
Air volume
LOSSNAY ventilation
Ventilation mode Fan speed
High
(m3/h)
50Hz / Single phase 220-240V
(Pa)
Power consumption (W)
By-pass ventilation
Extra High
Current (A)
Noise (dB)
Frequency / Power source
LOSSNAY ventilation
Ventilation mode Fan speed
LGH-200RX5-E
Model
50Hz / Single phase 220-240V
External static pressure (mmH 2 O)
Frequency / Power source
(Pa)
Model
Unit: mm
22
Wiring Diagrams LGH-15RX5 to 100RX5
LGH-150RX5 and 200RX5 GREEN/YELLOW BROWN RED
BLACK GREY YELLOW
M2
TM1 L
TAB5
TAB3
BLUE
TAB1
CN10
TAB2
BROWN
C
SUPPLY FAN MOTOR
N
POWER SUPPLY 220-240V 50Hz Isolator
BROWN RED
N
(*2)
SUPPLY FAN MOTOR
BLUE ORANGE BLUE WHITE
M1
RED
CN7
YELLOW
(*2)
C
x103
x102
(*2)
TAB5
TAB3
BLACK x103 GREY YELLOW x102
RED ORANGE BLUE WHITE
RED
M1
GM
EXHAUST FAN MOTOR
TAB1
CN10
TAB2
LS
PE
BLUE BROWN
x101 BLUE
TR1
CN1 x203 ORANGE BLUE x202 WHITE
x203
C
(*2)
x202
RED RED
CN9 CN7
x201
WHITE RED WHITE
BROWN CN32
TH1(OA) ORANGE ORANGE ORANGE ORANGE
CN16
SW2
SW1
CN5 SW5
BROWN
CN6
ORANGE ORANGE
TM4
SA1 SA2
TH2(RA)
CN2
X10
9
X12 X11 TM3 6
7
8
PZ60DR-E
2 TM2 1
1
TB5 2
3
A
B
S
12V or 24V DC By-pass or Delay2 M-NET monitor output 6 , 7 transmission Mr.Slim Malfunction monitor (non-polar) MELANS cable output 7 , 8 MAX 240VAC 1A External control input 24VDC 1A 1 3 MIN 220VAC 100mA 5VDC 100mA
*When the optional Remote Controller PZ-60DR-E is used as the M-NET System ,connect it to 1 2 of TM4 terminal block,and connect M-NET transmission wire to A , B on TB5 terminal block. (*1) TM4 Optional Remote controller 2 (PZ-60DR-E) 1 2nd remote controller (Max.2 remote controllers TB5(M-NET) installable)
Unchanged a-conntact
*Attention
(*1)
M-NET transmission cable
A
B
EXHAUST FAN MOTOR
S Sheild Wire
(*1)PZ-41SLB-E and PZ-52SF-E cannot be used when using PZ-60DR-E
With this product, the wiring installation method will 2nd or later main units vary according to the design of the system. Perform electrical installation to meet local electrical regulations. .Always use double insulated PVC cable for the transmission cables. .Wiring work must be performed by qualified professionals. .All supply circuits must be disconnected before obtaining access to the terminal devices.
HI LO
M
BY-PASS
C
CN16 (Unchanged a-conntact) BROWN HI LO EXTRA-LO BY-PASS
RED ORANGE YELLOW GREEN
(*2)
C
(*2)
x201
RED ORANGE YELLOW GREEN
BLACK TR2
TR3
BLACK
LS GM MG
BLACK
BROWN CN32 TH1(OA) ORANGE ORANGE ORANGE ORANGE
CN16
SW2
SW1
CN2
BROWN
CN5 SW5
TM4 10
SA1 SA2
X10 9
X12 X11
2
TM3 8
MIN 220VAC 100mA 5VDC 100mA
2
3
A
12V or 24V DC Mr.Slim (non-polar)
By-pass or Delay2 monitor output 6 , 7 Malfunction monitor output 7 , 8 MAX 240VAC 1A 24VDC 1A
1
1
TB5
TM2 7
LS BLACK
TH2(RA)
6
CN16 (Unchanged a-conntact) BROWN
(*2) LGH-100RX5 has 2 capacitors per mortor as following drawing.
C
C
RED ORANGE BLUE WHITE
M1
2nd remote controller (Max.2remote controllers installable cable) 2nd LOSSNAY unit (Up to max 15 units) Transmission cable (non-polar)
Sheild Wire
NOTE 1.TM1, TM2, TM3, TM4, TB5 shown in dotted lines are field work. 2.Isolator should be provided by the customer. 3.Be sure to connect the grounding wire.
M2 SUPPLY FAN MOTOR
Operation or Delay1 monitor output MAX 240VAC 2A MIN 220VAC 100mA 5VDC 100mA 24VDC 2A
10
BROWN BLACK GREY YELLOW
L N
N
x101
TR
CN9
C
EXHAUST FAN MOTOR
BROWN BLACK GREY YELLOW
PE
Isolator
TM1 L
L
M2
CN1
POWER SUPPLY 220-240V 50Hz
GREEN/YELLOW
B
S
Sheild Wire M-NET transmission MELANS cable
GM MG
Operation or Delay1 monitor output MAX 240VAC 2A MIN 220VAC 100mA 24VDC 2A 5VDC 100mA
(*1) PZ60DR-E 2nd remote controller (Max.2remote controllers installable cable) 2nd LOSSNAY unit (Up to max 15 units) Transmission cable (non-polar)
External control input 1
3
Unchanged a-conntact
NOTE 1.TM1, TM2, TM3, TM4, TB5 shown in dotted lines are field work. 2.Isolator should be provided by the customer. 3.Be sure to connect the grounding wire.
*Attention
*When the optional Remote Controller PZ-60DR-E is used as the M-NET System ,connect it to 1 2 of TM4 terminal block,and connect M-NET transmission wire to A , B on TB5 terminal block. (*1) TM4 Optional Remote controller 2 (PZ-60DR-E) 1 2nd remote controller (Max.2 remote controllers TB5(M-NET) installable) A B S
(*2) LGH-200RX5 has 2 capacitors per mortor as following drawing.
M C
C
M-NET With this product, the wiring installation method will transmission Sheild Wire (*1)PZ-41SLB-E and PZ-52SF-E cannot cable vary according to the design of the system. be used when using PZ-60DR-E Perform electrical installation to meet local electrical regulations. 2nd or later main units .Always use double insulated PVC cable for the transmission cables. .Wiring work must be performed by qualified professionals. .All supply circuits must be disconnected before obtaining access to the terminal devices.
*Specifications may be subject to change without notice.
Definition of Symbols *Specifications may be subject to change without notice.
Definition of Symbols M1: M2: C: GM: LS: TH1: TH2: SW1: SW2, 5: TM1: TM2: TM3: TM4 : TB5 : TAB1,TAB2: TR1: X10,X11,X12:
23
Motor for exhaust fan Motor for supply fan Capacitor Motor for By-pass operation Microswitch Thermistor for outside air Thermistor for return air Switch (Main/Sub change) Switch (Function selection) Terminal block (Power supply) Terminal block (External control input) Terminal block (Monitor output) Terminal block (Transmission cable and monitor output) Terminal block (M-NET Transmission cable) Connector(Power supply) Control circuit transformer Relay contact
CN1: CN2: CN5: CN6: CN7: TAB3: TAB5: CN9: CN10: CN16: CN32: SA1: SA2: SYMBOL
Connector (Transformer primary) Connector (Transformer secondary) Connector (Thermistor) Connector (Microswitch) Connector (Motor for By-pass operation) Tab connector(Fan motor) Tab connector (Fan motor) Connector (Fan motor) Connector (Fan motor) Connector (High/Low/By-pass switch) Connector (Remote control selection) Address setting rotary switch (10 digit) Address setting rotary switch (1 digit) : Indicates terminal block. : Connector. : Board insertion connector or fastening connector of control board.
M1: M2: C: GM: LS: TH1: TH2: SW1: SW2, 5: TM1: TM2: TM3: TM4:
Motor for exhaust fan Motor for supply fan Capacitor Motor for By-pass operation Microswitch Thermistor for outside air Thermistor for return air Switch (Main/Sub change) Switch (Function selection) Terminal block (Power supply) Terminal block(External control input) Terminal block (Monitor output) Terminal block (Transmission cable and monitor output) TB5: Terminal block (M-NET Transmission cable) TAB1,TAB2: Connector(Power supply) TR1: Control circuit transformer TR2,TR3: By-pass operation transformer
X10,X11,X12: Relay contact X101,X102,X103: Relay Supply fan speed control X201,X202,X203: Relay Exhaust fan speed control CN1: Connector (Transformer primary) CN2: Connector (Transformer secondary) CN5: Connector (Thermistor) CN6: Connector(Microswitch) CN7: Connector (Motor for By-pass operation) CN9: Connector (Fan motor) TAB3: Tab connector (Fan motor) TAB5: Tab connector (Fan motor) CN9: Connector (Fan motor) CN10: Connector (Fan motor) CN16: Connector(High/Low/By-pass switch) CN32: Connector (Remote control selection) SA1: Address setting rotary switch (10 digit) SA2: Address setting rotary switch (1 digit) SYMBOL : Indicates terminal block. Board insertion connector or fastening connector of control board.
24
Sample Installations LGH-15RX5 to 100RX5
LGH-150RX5 and 200RX5 Exhaust air grille A
Exhaust grille (user supplied)
Suspension bolt position
Suspension bolt position
Air-supply grille (user supplied)
150 to 250
600 or more
Suspension bolt position
Inspection opening
LOSSNAY core/ air filter/ fan maintenance space
Supply air grille 414
Air-supply grille (user supplied) OA (fresh-air intake) Duct (user supplied)
Duct diameter 200 (ordered by customer)
450( 600) Inspection port
Duct (user supplied)
EA (Exhaust air) OA (Outside air) Suspension bolt position (ordered by customer)
Exhaust grille (user supplied) EA (exhaust-air outlet)
Inspection opening RA (Return air)
Duct diameter 200 (user supplied)
Heat exchanger/filter maintenance space
Y piping,Dwindle pipe (user supplied) Ceiling suspension bolt position Air-supply grille (user supplied)
Supply/ exhaust air grille SA (Supply air)
•Always leave inspection holes ( 450 or 600) on the air filter and LOSSNAY core removal side. • Always insulate the two ducts outside the room (intake air and exhaust air ducts) to prevent condensation. •It is possible to change the direction of the outside air ducts (OA and EA side). • Do not install the vent cap or round hood where it will come into direct contact with rain water. Unit: mm
Ceiling suspension bolt position
B
OA (Outside air)
Duct diameter 250 Ceiling suspension (user supplied) bolt position A
150~250 Min. 600
B
414
EA (Exhaust air)
Duct downward slope 1/30 or more (to wall side) (Rainwater entrance prevention) Deep-type hood or weather cover
LOSSNAY model selection advices
Duct incline Over 1/30 (toward the wall) to prevent entry of rainwater EA (exhaust-air outlet)
Ceiling suspension bolt (user supplied)
(user supplied)
OA (fresh-air intake) Exhaust grille 450( 600) Inspection port
Air-supply grille
SA RA SA RA (return air) (return air) (supply air) (supply air)
•Always leave inspection holes ( 450 or 600) on the air filter and LOSSNAY core removal side. • Always insulate the two ducts outside the room (intake air and exhaust air ducts) to prevent condensation. •If necessary, order a weather cover to prevent rain water from direct contact or entering the unit.
Model
A
B
LGH-15RX5
768
782
LGH-25RX5
768
782
LGH-35RX5
875
921
LGH-50RX5
875
1063
LGH-65RX5
895
1001
Model
A
B
LGH-80RX5
1010
1036
LGH-150RX5
1010
1045
LGH-100RX5
1010
1263
LGH-200RX5
1010
1272
Unit: mm
Attention for specifications 1.Cold operation mode(*1) is to start repeating in the case that LOSSNAY's detected OA temperature is less than-10°C. *1.Supply air(SA) in the operation for 60min. followed by stop operation for 10min. 2.The current, power consumption and efficiency are based on the air flow rate in the specification. 3.Fan speed is selectable by the remote controller from High (Extra-High), Low, Extra-Low(Extra-Low not equipped LGH150RX5 and 200RX5). Multi Ventilation Mode should set on LOSSNAY unit or remote controller (PZ-60DR-E). 4.LOSSNAY ventilation mode is to start automatically in the case that LOSSNAY's detected OA temperature is less than +8°C,even if By-pass ventilation is set by remote controller. Remote controller continue to show "By-pass ventilation" in this case. 5.Temperature Exchange efficiency(%) are based on winter condition. 6.Mitsubishi Electric measures the machine according to the Japan Industrial Standards(JIS B 8628)
Attention 1.When using the product where it is exposed to high temperatures and humidity (40°C or higher, RH 80% or higher), or where fog occurs frequently, moisture is likely to condense in the core, and may result in condensation build up in the unit.The product should not be used under such conditions. 2.Outdoor air may enter the LOSSNAY owing to the pressure difference between indoor and outdoor or external winds even when the product is not operated. It is recommended to install an Electrically operated damper to block the outdoor air. 3.In a cold weather area, an area with strong external winds or where fog occurs frequently, cold outdoor air, external winds or fog may be introduced into the product when its operation is stopped. It is recommended to install an Electrically operated damper. 4.In a cold weather area, or others, dewing or freezing could occur on the main unit, where the duct is connected, or other sections, depending on the conditions of outdoor air and indoor temperature and moisture, even if they are within the range of operating conditions. Make sure to confirm the operating conditions and other precautions, and do not use the product if dewing or freezing is anticipated. 5.The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor louvres from LOSSNAY, and properly insulated. (The entry of rain water may cause power leakage, fire, or damege to household property) 6.The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the summer air conditioning season, it is recommended that the indoor ductwork be covered with insulation material. 7.Inspection opening (450 × 450 or 600 × 600mm)must be installed on the filter and LOSSNAY core removing side. 25
1.Operating environment Install this product in an environment where the temperature ranges from -10°C to +40°C and the relative humidity is less than 80%RH. If condensation is expected to form,heat up the fresh outside air should be treated. 2.Do not use under high temperature and humidity condition Condensation will occur and water will gather inside the LOSSNAY cores under high temperature and humidity condition, such as warm swimming pool, bathroom, greenhouse or foggy place. 3.Condition of outdoor, indoor and return air Avoid using LOSSNAY under air condition with acid, alkalis, organic solvent , oil mist, paint, or harmful gas as presticide, corrosive gas, etc. 4.Insulation failure caused by salt or sulphur air and hot spring steam, Rust, fire or malfunction may occur. Installing high quality filters inside outdoor air duct if the LOSSNAY operates in salt or sulphur air conditions. 5.Intake of mist or outdoor air during off-mode operation Outdoor air or mist may flow through the duct into your room when LOSSNAY is in off-mode at windy and foggy area. To prevent intake of outdoor air or fog, a damper is advised to be installed. 6.Entry of insects When using the product in an environment where there is a window,or opening near the outdoor hood,so that insects are likely to gather around the interior or exterior light,take note that small insects may intrude into the LOSSNAY filters. 7.By-pass ventilation In the case of "By-pass" ventilation, the supply air temperature slightly rises more than the outside air temperature. because of the effect around the ducts or the unit motors. 8.Usage of M-NET. When solely using LOSSNAY units, power supply unit is required to connect to centralized control. Number of power supply units or the transmission boosters should correspond with the connected LOSSNAY units.
Caution for installation 1.Do not modify the unit as it may cause malfunction. 2.Leaving sufficient space for maintenance purpose. 3.The location of the air inlet Take care in locating air inlet to prevent intake of dirty air or disgusting smell from exhaust gas of factory, air from rubbish disposal, etc. 4.Take precautions when using the product in quiet location. 5.Heat insulation foam for duct Take care as below to prevent the contaminate ceiling by duct condensation. 1)The two outdoor ducts(OA and EA) must be covered with heat-insulating material in order to prevent condensation. 2)If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the summer air conditioning season, it is recommended that the indoor ductwork be covered with insulation material. 3)Outdoor air may come into unit during not operating unit by the pressure difference between indoor and outdoor or the outdoor wind. In this case you should install a damper. 4)It is possible for condensation and freezing to occur in the cold regions inside the unit because of the outdoor air condition or humidity condition above ceiling. Make sure to install supplemental insulation foam. 5)In the case that air condition around LOSSNAY unit is high temperature in summer, it is recommended that there are heat insulation foam on indoor side duct to prevent heat recovery decreased by warming indoor duct. In winter, it is possible to cool indoor side duct without heat insulation foam on indoor side duct. 6.Prevent entry of rainwater into LOSSNAY unit Install weather louvre or "Weather cover" for OA inlet & EA outlet. This is to prevent rainwater entering the LOSSNAY unit. Ducts to outdoor (OA and EA) should decline by 1/30 or more. 1)Install the anchor bolts to ensure the product's weight or earthquake load. (Correctly rated wire/chain may also be used) 2)Do not install this product in a place where it is exposed to ultraviolet light. (UV may be damage covering insulation.) 7.Electrical Work A single pole isolator must be installed at the origins of mains power supply. Use single flush box, to support remote controller. Must connect ground wiring. When connecting external devices (electrically operated damper, lamp, monitoring unit, etc.) using output signals of the LOSSNAY unit, make sure to install safety equipment for the external devices. (It could cause fire, damage, etc. without safety equipment)
26