Transcript
vi
S/90 Installation Guide Model 1000 Door Processing Unit DPU 1000
Control Systems International
®
TCON077.—.04/97
We at Control Systems International (CSI) have tried to make the information contained in this manual as accurate and reliable as possible. Nevertheless, CSI disclaims any warranty of any kind, whether express or implied, as to any matter whatsoever relating to this manual, including without limitation the merchantability or fitness for any particular purpose. CSI will, from time to time, revise the product(s) described in this manual and reserves the right to make such changes without obligation to notify the purchaser. In no event shall CSI be liable for any indirect, special, incidental, or consequential damages arising out of purchase or use of this manual or the information contained herein. 1991, 1997 by Control Systems International. All rights reserved. Printed in the United States of America. Document Number: TCON077–04/97 I/NET, Control Systems International, and the Control Systems International logo are registered trademarks of Control Systems International. FrameMaker and Minion are trademarks of Adobe Systems Incorporated. Canvas is a trademark of Deneba Software. All other trademarks mentioned belong to their respective owners.
About this manual: This book was written and produced using FrameMaker workstation publishing software and the Minion font from Adobe. Illustrations were created or modified using Canvas.
Installation Guide
Contents FCC Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Overview .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Key/Card Reader Installation .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Physical Installation . . . . . . . . . . . Required Tools . . . . . . . . . . . . . Installation Procedure . . . . . . . . . . Single Key/Card Reader Installation . .
. . . .
. . . . Key/Card Reader/Pushbutton Installation . Pedestal Installation . . . . . . . . . . . Electrical Installation . . . . . . . . . . . . Key/Card Reader Grounding . . . . . . . . . Power/Data Line Connection . . . . . . . . . Key/Card Reader Low Temperature Package Theory Of Operation . . . . . . . . . . . . Low Temperature Package Contents . . . . . Low Temperature Package Installation . . . .
DPU 1000 Installation
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
2 2 3 3 5 5 6 6 7 7 7 8 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Door Sense Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Electrical Installation . . . . . . Memory Backup Battery . . . . . Electrical Installation Procedure . Optional Battery Backup . . . . Optional Tamper Alarm Input . . DPU Address . . . . . . . . . .
System Setup
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. 11 . 11 . 11 . 14 . 14 . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 MODE Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 UP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DPU 1000
iii
Installation Guide
DOWN Switch . ENTER Switch . DELETE Switch RESET Switch . Initialization . .
Operation
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
17 18 18 18 18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Initializing DPU Stand-Alone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Programming Instructions . . . . . . Programming Mode . . . . . . . . . Adding And Deleting Keys/Cards . . Key/Card Issue Level . . . . . . . Key/Card Assignments . . . . . . Programming Time . . . . . . . . Editing The Program . . . . . . . Exiting The Program Mode . . . . Operational Control . . . . . . . . . Adding And Deleting Keys/Cards . . Initial Power Application Or Reset . User Keys/Cards . . . . . . . . . Using Door Release Switch . . . . Door Sense Switch . . . . . . . . Monitoring/Controlling Functions . . . Tamper Monitor . . . . . . . . . Auxiliary Indicators . . . . . . . . Using The Options . . . . . . . . Loss Of Primary Power . . . . . . . . Operation With A Central Terminal . .
Specifications Index
iv
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
20 20 20 21 21 21 22 22 22 22 22 22 22 23 23 23 23 23 23 24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
DPU 1000
Installation Guide
FCC Warning The Federal Communications Commission (FCC) requirements prescribe certification of personal computers and any interconnected peripherals in the FCC rules and regulations. This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: this device may not cause harmful interference, and this device must accept any interference received, including interference that may cause undesired operation. This equipment generates and uses radio frequency (rf) energy for its operation and, if not installed and used in accordance with the installation and operation manual, may cause interference to radio and television reception. It has been found to comply with the limits for a Class A computing device pursuant to the aforementioned regulations. These are designed to provide reasonable protection against such interference when operated in a residential area. Only peripherals (computer input/output devices) certified to comply with the Class A limits may be connected to this device. Operation with noncertified computer peripherals is likely to result in interference with radio and television reception. If this equipment does cause interference to radio or television reception, the user is encouraged to correct the situation by one or more of the following measures. ✦
Relocate the receiver with respect to the computer.
✦
Move the computer away from the receiver.
✦
Plug the equipment into a different outlet, so that the computing device and receiver are on different branch circuits.
✦
Disconnect and remove any unused cables that may be acting as a transmission source.
✦
Make certain that the computing device is plugged into a grounded outlet receptacle.
If necessary, contact CSI for additional suggestions.
DPU 1000
v
Installation Guide
vi
DPU 1000
27
Installation Guide
Overview
Overview The Model DPU 1000 is designed to provide management and control of individual access to restricted areas when used in conjunction with other components of the S/90 access control system. The DPU is a solid state device which utilizes control switches and microprocessor circuitry to program and control access to a specified area. This is accomplished by programming the DPU to respond to specific coded keys/cards that are inserted into the key/card reader, to which the DPU is connected. If a valid read is received from the key/card reader, the DPU will relay an enabling signal to a door strike, or similar device, allowing entry. Each DPU provides control for one separate point of entry.
DPU 1000
1
Key/Card Reader Installation
Installation Guide
Key/Card Reader Installation Physical and electrical installation instructions for the key/card reader are provided in this section.
Physical Installation The key/card reader (see Figure 1) may be installed for use with both inside and outside doors. It may also be installed in a pedestal for use in operating vehicle traffic controlling devices.
Figure 1. Model CARDRDR Card Reader & Model KEYRDR Key Reader All key/card readers should be installed in a location convenient to the intended point of entry and protected from the weather by a shield or hood when located outside. In some locations it may also be necessary to install a key/card reader low temperature package on the key/card reader to ensure proper operation for temperatures below 30° F. (-1° C). Note:
In all applications, an average height for installing the key/card reader for ease of use is approximately 48 inches from the floor or ground level as applicable.
Required Tools
2
✦ ✦ ✦ ✦
Marking Scribe or Pencil Ruler (6" or 15 cm) Hole Saw (1" or 25 mm) or Square Knockout Punch (1" or 25 mm)
✦ ✦ ✦ ✦
Drill 9 ⁄64" (4 mm) or Drill Bit or 3⁄8" (9.5 mm) if Knockout Punch is used Screwdriver, Phillips Number 2 File
DPU 1000
Installation Guide
Key/Card Reader Installation
Installation Procedure Note:
Before installing the key/card reader as shown in the following procedure, insert the reader cable plug into the jack provided on the reader.
Single Key/Card Reader Installation Install the key/card reader as follows: Warning:
Before making mounting holes, ensure that wall, door frame, or other applicable area is clear of obstructions such as conduits, pipes, wiring, etc. A minimum depth of 2.5 inches (6.35 cm) is required between surfaces for clearance of the key/card reader and connector. 1. Locate and make cutout for mounting key/card reader as shown in Figure 2.
Door Jamb or Mullion
Door Jamb or Mullion
1.3" (3.3 cm)
1.3" (3.3 cm)
Cut Out Key Reader Mounting Hole
1.6" (4 cm)
Cut Out Key Reader Mounting Hole
3.6" (9.1 cm)
Figure 2. Key/Card Reader Mounting Hole 2. Make provisions to secure the key/card reader in place by accomplishing either Step a or Step b below. a.
Locate and drill a 9⁄64" (4 mm) diameter hole in the door jamb or mullion opposite the key/card reader mounting hole. Make required electrical connections, then position (with LED up) and secure key/card reader in mounting hole with 6⁄32" (5 mm) screw of appropriate length (see Figure 3). or,
DPU 1000
3
Key/Card Reader Installation
Installation Guide
Door Jamb or Mullion
6/32 (5 mm) Screw
9/64 Inch 3.6 mm) Screw Hole
Key/Card Reader
Figure 3. Key/Card Reader installation in Door Jamb or Mullion b.
Locate and make cutout (large enough to allow access to the key/card reader) in the jamb or mullion opposite the key/card reader mounting hole. Make required electrical connections, then position (with LED up) and secure key/card reader in mounting hole using U-bracket and 6⁄32" (5 mm) screw of appropriate length. Cover access hole with appropriate plate (see Figure 4).
Door Jamb or Mullion U-Bracket 6⁄32 (5 mm) Screw Access Cutout
Cover Plate
Key/Card Reader
Figure 4. Key/Card Reader Installation using a U-Bracket
4
DPU 1000
Installation Guide
Key/Card Reader Installation
3. The key/card reader may be installed in a variety of other ways including flush mounting in a protective enclosure or surface mounted in a protective enclosure. The key/card reader can be flush mounted in a standard single gang switch enclosure. Contact CSI with specific questions regarding mounting methods.
Key/Card Reader/Pushbutton Installation If a key/card reader for entry and a pushbutton (user supplied) for exit are to be installed at a single door, proceed as follows: Warning:
Before making mounting holes, ensure that wall, door frame, or other applicable area is clear of obstructions such as conduits, pipes, wiring, etc. A minimum depth of 2.5 inches (6.35 cm) is required between surfaces for clearance of the key/card reader and connector. 1. Install the key/card reader utilizing a U-bracket in accordance with the instructions previously given for Single Key/Card Reader Installation. 2. Install the pushbutton and cover plate as shown in Figure 5. Using 18 AWG (0.897 mm2), twisted pair, shielded cable, attach the pushbutton to the two terminals, GND and D REL, on the DPU Interface Board (refer to DPU Installation).
Door Jamb or Mullion 6/32 Screw
Key/Card Reader U-Bracket 6⁄32 (5 mm) Screw
OUTSIDE
INSIDE Key/Card Reader
Figure 5. Key/Card Reader/Pushbutton Installation
Pedestal Installation An optional key/card reader pedestal is available from CSI. The pedestal (Figure 6) provides weatherproofing, easy access, and simplifies key/card reader installation. At new concrete installations, or if a separate mounting surface is poured for the pedestal, set four 1⁄4" (6 mm) bolts at pouring according to the dimensions shown in Figure 6.
DPU 1000
5
Key/Card Reader Installation
Installation Guide
5.0" (12.7 cm)
Pedestal Pole Key Reader (for example)
3.95" (10 cm) Conduit*
Mounting Plate Hole Pattern
Mounting Plate * Conduit may be routed either way shown.
Figure 6. Key/Card Reader Pedestal Installation If installation is made on an existing concrete structure, use the mounting plate to locate the holes, and then drill the four holes with a concrete bit. Secure the pedestal to the surface with four concrete mounting bolts.
Electrical Installation The following paragraphs provide instructions for the electrical installation of the key/card reader.
Key/Card Reader Grounding In order to eliminate the harmful effects of static discharge when a user touches the key/card reader, and thus, to ensure uninterrupted operation, the key/card reader must be properly grounded. If the key/card reader is installed on a large metal surface (i.e., door jamb), the surface may serve as a sufficient grounding medium. However, make a thorough check to ensure that the metal surface is in itself well grounded. If it is not installed on a properly grounded metal surface, provide a ground for the key/card reader as follows: Caution:
Failure to properly ground the key/card reader could result in damage to the reader and/or other equipment connected to the reader. To be most effective, the ground wire should be as short as possible (no more than 20 feet long). 1. Connect a piece of 10 AWG (5.27 mm2)or larger, solid wire between the key/card reader grounding screw and the nearest metal object such as a cold water pipe, metal frame, or grounded electrical outlet box as shown in Figure 7. (Use a crimpon lug on the wire end to be connected to the key/card reader grounding screw. Connect the other end of the wire to the metal object by the method best suited to ensure a solid ground connection.)
6
DPU 1000
Installation Guide
Key/Card Reader Installation
10 AWG (5.27 mm2) wire or larger
Crimp-on Spade Lug Key Reader Grounding Screw
Cold Water Pipe
Or Grounded Electrical Box To Key Reader Grounding Screw
Figure 7. Key/Card Reader Grounding 2. If no suitable metal object is available for grounding, consult CSI for a special key/card reader grounding cable. (The special cable is designed to help reduce static problems, but is not intended to replace the preferred grounding wire method described in Step 1 above when that method is at all possible.)
Power/Data Line Connection Connect the key/card reader to the door processing unit (DPU) or entry controller by connecting the telephone plug on one end of the cable supplied to the connector at the rear of the key/card reader. Then route the other end of the cable to the DPU or entry controller. All operating power and data is routed through this single cable.
Key/Card Reader Low Temperature Package If the key/card reader will be exposed to temperatures below 30° F. (-1° C.) for an extended period of time, the key/card reader low temperature package should be installed to prevent frost from accumulating on the key/card slot. Either a Key Reader Low Temperature Package (CSI Part No. 1310-2118) or a Card Reader Low Temperature Package (CSI Part No. 1310-2318) can be ordered from CSI. Consult your distributor for further details. The following paragraphs provide installation instructions for the low temperature package. Also included is a brief theory of operation which describes how the package functions.
Theory Of Operation The Key/Card Reader Low Temperature Package is installed on key/card readers which are exposed to low ambient temperatures in order to provide uninterrupted operation during even the coldest months.
DPU 1000
7
Key/Card Reader Installation
Installation Guide
The key/card reader low temperature package heating element is a self-regulation thermistor which will activate to heat at low ambient temperatures and deactivate at normal or high ambient temperatures. Nominal resistances of the heating element are 25 Ohms at -35° F. and 1500 Ohms at 122° F. Thus, the package may remain in operation year round. However, it is recommended that the power supply (customer furnished) be turned off during the warm season in order to increase the life of the power supply. The operating voltage required for the heating element is 5 VDC to 20 VDC. The lower the voltage the less heat is produced, and the higher the voltage the more heat is produced. A 12 to 18 VDC power supply (customer furnished) with 2.5 A minimum continuous (surge capability in excess of 3 amp) will provide the most efficient operation and prolong the life of the heating element. The heating element will activate at approximately 50° F, and will produce increasingly more heat as the ambient temperature drops in order to maintain the key/card reader at a constant temperature of 45° F to 50° F.
Low Temperature Package Contents The contents of the Key Reader Low Temperature Package and the Card Reader Low Temperature Package are shown below: Key Reader Low Temperature Package (CSI P/N 1310-2118):
✦ ✦ ✦ ✦ ✦ ✦ ✦ ✦ Note:
Heater element with mounting bracket One screw, panhead: #2-56 3⁄8" (10 mm) One screw, panhead: #2-56 5⁄16" (8 mm) Two wire nuts (IDEAL 30-073) Card Reader Low Temperature Package (CSI P/N 1310-2318): Heater element with mounting bracket Two screws, panhead: #2-56 1⁄2" (13 mm) Two wire nuts (IDEAL 30-073)
To complete installation of the key/card low temperature package, the customer must furnish a 12 to 18 VDC power supply.
Low Temperature Package Installation Field installation of the key/card reader low temperature package is accomplished as follows: Warning:
Remove all electrical power from interconnected equipment. Failure to do so while performing electrical installation may result in electrical shock or burns. 1. Use a length of 18 to 20 AWG (0.897 to 0.519 mm2) standard zip cord, or equivalent, (customer furnished) which will reach from key/card reader to the location selected for the power supply. 2. At the key/card reader end, strip back approximately 1⁄2 inch to 3⁄4 inch (13 mm to 19 mm) insulation from the power cord. For best results, the wires should be tinned.
8
DPU 1000
Installation Guide
Key/Card Reader Installation
3. Remove key/card reader and backshell. Remove the three screws from the top of the key/card reader frame (opposite the circuit board). 4. Align the heater element to the screw holes, with the red and black wires to the rear of the key/card reader. 5. Replace the front #2-56 screw with the applicable screw furnished, and the rear screw with the applicable screw furnished. Leave the screws slightly loose and push the heater element flush with edge of key/card reader chassis and secure. Note:
The center screw will also be replaced at this time if chassis grounds are not being used. If a chassis ground will be used, leave the center screw out until entire assembly of heating element to key/card reader has been completed. 6. Re-assemble the backshell onto key/card reader with the red and black wires exiting through the square connector access hole of backshell at rear or bottom of unit.
Note:
Caution:
If key/card reader low temperature package kit was preassembled at the factory, skip Steps 7 through 10 and perform Step 11 at this time. If kit was not preassembled, proceed with Steps 7, observing the WARNING and CAUTION below. When performing Step 7 below, ensure that the polarity of the power wires is observed. 7. Using the two wire nuts provided, connect the wires from the power supply to the red and black wires at the rear of the key/card reader. 8. Replace key/card reader, reassemble, and secure into wall or other mountings. 9. At the power supply, to ensure an effective connection to the terminals, strip a sufficient amount of the insulation from each power wire.A crimp-on connector lug (not furnished) may be used for a better and more positive connection. 10. Observe polarity when connecting wires to power supply as described in the owner’s manual of the applicable power supply. 11. Apply power to the power supply as instructed in the owner’s manual.
DPU 1000
9
DPU 1000 Installation
Installation Guide
DPU 1000 Installation This section provides physical and electrical installation instructions for the Model 1000 DPU. For access control, the DPU is used in conjunction with the following equipment: ✦ ✦
Note:
Key/Card Reader (furnished by CSI) Door Strike - the door strike (customer supplied) may be either a FAIL SECURE strike, which locks when power is lost, or a FAIL SAFE strike, which opens when power is lost.
It is recommended that a varistor (GE33Z1 or equivalent) be connected at the door strike. ✦ ✦
Door Release Switch (optional) - the door release switch (customer supplied) must be a normally open switch. Door Sense Switch (optional) - the door sense switch (customer supplied) must be in the open condition when the door is closed.
In addition, other equipment, such as buzzers and lights may be connected to the DPU as described in the following paragraphs.
Physical Installation Install the key/card reader, door strike, door release switch, door sense switch, and other appropriate equipment in accordance with instructions under the Key/Card Reader Installation section in this manual. Install the DPU in a protected environment, inside location as close to the intended point of entry as possible, but no more than 300 feet (90 m) from the entry. Using the appropriate standard tools and hardware, mount and secure the DPU to the wall surface at the selected location.
Door Sense Switch A normally open door sense switch when used with this system will perform two functions as described below: ✦ ✦
10
When the door closes (and the door sense switch opens) the strike will re-energize overriding the 7-second door open default time. When the door is forced open (the door sense switch closes without being preceded by a valid card read) the forced door relay will close. This dry closure can be used to activate other alarm equipment.
DPU 1000
Installation Guide
DPU 1000 Installation
Install a pair of normally open contacts on the door according to instructions provided by the switch manufacturer. Using 18 AWG (0.897 mm2), twisted pair shielded (Belden 8760 or equivalent), connect the door sense switch to the two terminals, GND and D SEN, on the DPU Interface Board (refer to Step 4 on page 12).
Electrical Installation Memory Backup Battery The printed circuit board contains a backup battery to prevent loss of system data in memory in case of temporary loss of operating power. In order to prevent the memory backup battery from losing its power, the jumper (J6) required to connect it to the memory circuit is stored and shipped in the open position (jumper stored on only one lead of PCB jumper connectors). In order to activate the memory backup circuit at time of installation, change the blue jumper (located on the printed circuit board near the memory backup battery) from the open position to the active position (jumper connected to both leads of PCB jumper connections). See Figure 8.
Blue Jumper
Open Position
Blue Jumper
Active Position
Figure 8. Memory Backup Battery Activation
Electrical Installation Procedure All of the DPU electrical connectors are located on the printed circuit board inside the DPU housing (see Figure 9). Route all wiring as required and make the applicable electrical connections to the DPU in accordance with the following: 1. Connect the key/card reader cable to the key/card reader connector on the DPU. Note:
It is recommended that a varistor be connected at the door strike. General Electric V33ZA1 (CSI P/N 83Z1100), or equivalent, may be used. 2. Connect the wiring from the door strike as follows (See Figure 9): a.
FAIL SECURE strike. Connect wires to the STRIKE C and N.O. connectors on the connector strip.
b.
FAIL SAFE strike. Connect wires to the STRIKE C and N.C. connectors on the connector strip.
3. Connect the wiring from the door release switch to the D REL connectors on the connector strip.
DPU 1000
11
DPU 1000 Installation
Installation Guide
LED Display
Reset (S1) Communications
Unit ID DIP Switch S2
Input Power
Connector Strip
Battery (Optional)
Figure 9. DPU 1000 Board and Switch Locations 4. Connect the wiring from the door sense switch to the D SEN connectors on the connector strip. 5. Connect the wiring from other equipment to the ALARM BYPASS connectors on the connector strip. 6. The three COM terminals located on the upper left side of the printed circuit board (see Figure 10) provide a means of interfacing the DPU with a printer interface unit or a central terminal.Using the recommended cable or equivalent, connect the DPU to other system components as follows (see to Figure 9). a.
Connect one of the wires from the twisted pair to the A terminals, and the other wire from the twisted pair to the B terminals at both ends of the cable.
b.
Connect the drain (shield) wire to the G (ground) terminals at both ends of the cable.
7. Provide standard operating power for the DPU as follows (refer to Figure 9):
12
DPU 1000
Installation Guide
DPU 1000 Installation
To PIPU Or Central Terminal
To 115 VAC 60 HZ
See Detail A
CSI Power Supply N. C. Door Sense Switch Or N. C. Door Sense Switch
12V, 4 AH GEL Cell Battery
Door Release Switch
C
NC NO
Force Door Alarm Relay
C
NC NO
Door Sense Switch
C
Alm Bypass
User Alarm System User Alarm System
Detail A
NC NO Strike
Strike/Alm/Byp/relay
Strike * Power Supply
** Notes: ***
Strike *
* **
Customer Supplied Equipment Connect To Strike N.C. If Fail Safe Strike Is Used. Connect To Strike N.O. If Fail Secure Strike Is Used.
*** Customer Supplied Varistor.
Figure 10. DPU 1000 Interface Board Warning:
Remove all electrical power from interconnected equipment. Failure to do so may, while performing electrical installation, result in electrical shock or burns. a.
DPU 1000
Connect the ground lead (green or green/yellow lead) from the CSI power transformer to the chassis ground terminal next to the AC LO terminal on the lower left side of the printed circuit board.
13
DPU 1000 Installation
Installation Guide
Note:
b.
Connect the two power leads from the CSI power transformer provided to the two AC (AC HI and AC LO) terminals on the lower left side of the printed circuit board.
c.
Plug the CSI power transformer into a standard 115 VAC, 60 Hz outlet.
If excessive AC power line noise, spikes, or brownouts are experienced, it may be necessary to provide a power line noise filter or uninterruptable power supply in order to ensure proper operation of the system.
Optional Battery Backup Note:
Using the CSI battery option will provide approximately 10 hours of backup operating power in the event of a primary power failure. This will not, however, provide door strike power, which must be supplied separately. A backup battery charger is built into the printed circuit board and will support one 12V, 4 AH gell cell battery. If the optional battery is purchased, mount the battery below the printed circuit board, using the battery cable provided (refer to Figure 9). Connect the positive side of the battery to the BATT+ terminal and the negative side to the BATTterminal. The BATT+ and BATT- terminals are located at the lower left side of the printed circuit board (see Figure 9).
Optional Tamper Alarm Input The TAMPER input connector is located on the right side of the printed circuit board (see Figure 9) and provides a means of monitoring the security of a selected area or the DPU itself. In order to monitor the status of this input, the DPU must be interconnected to either a printer (through CSI Model PIU Printer Interface) or a central terminal. Note:
A shorting strap is factory installed between the TAMPER input terminals. Remove the jumper before connecting a tamper switch. Using 18 AWG (0.897 mm2), twisted pair, shielded cable (Belden No. 8760, or equivalent, is recommended), connect the TAMPER input connector to a normally closed switch located not more than 300 feet (90 m) from the DPU.
DPU Address Each DPU in a system must have its own unique identification number. This is accomplished by adjusting the setting of an eight-position DIP switch S2 located on the right side of the PCB (see Figure 10). Table 3 shows the required switch settings for unit identification numbers 1 through 32. If a DPU is not connected to a communications line, set the unit number to 1.
14
DPU 1000
Installation Guide
System Setup
System Setup When switches 6, 7, or 8 are placed in the OFF position, the options in Table 1 are implemented: Table 1. DPU 1000 Address Switch Settings SW2 DIP SWITCH SETTINGS DPU UNIT NUMBER
UNIT ADDRESS 1
2
3
OPTION 4
5
6
7
8
1
OFF
ON
OFF
ON
OFF
XX
XX
XX
2
ON
OFF
ON
OFF
ON
XX
XX
XX
3
OFF
ON
OFF
ON
OFF
XX
XX
XX
4
ON
OFF
ON
OFF
ON
XX
XX
XX
5
OFF
ON
OFF
ON
OFF
XX
XX
XX
6
ON
OFF
ON
OFF
ON
XX
XX
XX
7
OFF
ON
ON
ON
ON
XX
XX
XX
8
OFF
OFF
OFF
OFF
ON
XX
XX
XX
9
ON
ON
ON
OFF
OFF
XX
XX
XX
10
OFF
OFF
ON
ON
ON
XX
XX
XX
11
ON
OFF
OFF
OFF
OFF
XX
XX
XX
12
ON
ON
ON
ON
OFF
XX
XX
XX
13
OFF
OFF
OFF
ON
ON
XX
XX
XX
14
ON
ON
ON
ON
ON
XX
XX
XX
15
ON
OFF
OFF
OFF
OFF
XX
XX
XX
16
OFF
OFF
OFF
OFF
ON
XX
XX
XX
17
ON
ON
ON
ON
ON
XX
XX
XX
18
ON
ON
OFF
OFF
OFF
XX
XX
XX
19
OFF
OFF
OFF
OFF
OFF
XX
XX
XX
20
ON
ON
ON
ON
ON
XX
XX
XX
21
ON
ON
ON
ON
ON
XX
XX
XX
22
ON
ON
ON
ON
ON
XX
XX
XX
23
ON
OFF
OFF
OFF
OFF
XX
XX
XX
24
OFF
OFF
OFF
OFF
OFF
XX
XX
XX
25
OFF
OFF
OFF
OFF
OFF
XX
XX
XX
26
OFF
OFF
ON
ON
OFF
XX
XX
XX
27
OFF
ON
ON
OFF
OFF
XX
XX
XX
* NOT USED ** FORCED DOOR ALARM RELAY. In the OFF position, the relay will activate for one second. In the ON position the relay will remain activated until a manual system reset is accomplished. *** OPTION FIRST KEY AUTO UNLOCK will not allow a door into auto unlock until the first valid key is read. When this option is not selected, the door will unlock at time indicated by the controlling time zone. (Not available on stand-alone mode of operation.
DPU 1000
15
System Setup
Installation Guide
Table 1. DPU 1000 Address Switch Settings (Continued) SW2 DIP SWITCH SETTINGS DPU UNIT NUMBER
UNIT ADDRESS
OPTION
1
2
3
4
5
6
7
8
ON
ON
OFF
OFF
ON
XX
XX
XX
29
ON
OFF
OFF
ON
ON
XX
XX
XX
30
OFF
OFF
ON
ON
OFF
XX
XX
XX
31
OFF
ON
ON
OFF
OFF
XX
XX
XX
32
ON
ON
OFF
OFF
ON
XX
XX
XX
28
* NOT USED ** FORCED DOOR ALARM RELAY. In the OFF position, the relay will activate for one second. In the ON position the relay will remain activated until a manual system reset is accomplished. *** OPTION FIRST KEY AUTO UNLOCK will not allow a door into auto unlock until the first valid key is read. When this option is not selected, the door will unlock at time indicated by the controlling time zone. (Not available on stand-alone mode of operation.
This section contains instructions for initializing the DPU for operation after either initial installation or a power interruption to the DPU. In addition, operation of the equipment is described.
Self-Test Upon each initial application of operating power or depression of the RESET switch S1 (see Figure 9 on page 12), the DPU cycles through an automatic self-test sequence. If the self-test is successful, the DPU will begin normal operation. If any errors are found during self-test, the LED display (on the display board) will show an error message in the form xx, where xx will identify the error. Each of the error messages is described in Table 2. If an error message occurs, contact CSI and/or perform maintenance as required. Table 2. Self-Test Error Messages Error Message
Error Description
01
Not Used
02
Insufficient Ram
03
Ram Error
04
I/O Error
05
Insufficient EEprom
06
EEprom Error
07
Processor Error
08
Clock Chip Error
09
Analog to Digital Chip Error
In addition to the self-test, when power is applied, the unit identification switches will be read.
16
DPU 1000
Installation Guide
System Setup
Note:
If the DPU is in the stand-alone mode, the user must enter the system key/card into one of the key/card readers.
Caution:
In addition to initiating a self-test, if the RESET switch is depressed and then the MODE switch is depressed, approximately 1.5 seconds apart, all previously programmed parameters, including time, will be cleared from the DPU memory. Therefore, exercise caution when using the RESET switch in order not to erase programmed information except when desired. (Waiting approximately 15 seconds between depression of the RESET and MODE switches will ensure that programmed data will not be erased from memory.)
Controls and Indicators Each of the DPU controls and indicators, which are located on the PCB, is described below (see Figure 11). Parameter Group LEDS
Keys
Time/Date
Issue
Key Valid
MODE
UP
DOWN
ENTER
DELETE
RESET
Figure 11. DPU 1000 Controls and Indicators
MODE Switch This pushbutton switch is used to select the parameter to be programmed. The parameters are: KEY #, ISSUE, HOURS, MINUTES, MONTH, DAY, and YEAR. These parameters are arranged into three groups: KEY/ISSUE, TIME, and DATE. With each depression of the switch, the next parameter is selected, its field on the screen begins flashing, and the applicable parameter group LED illuminates.
UP Switch This pushbutton switch is used to alter the data in the selected parameter. While the switch is depressed, the selected parameter will not flash. When the switch is depressed for longer than three seconds, the unit will enter a high speed mode and increase at a higher rate.
DOWN Switch This pushbutton switch is used to alter the data in the selected parameter. While the switch is depressed, the selected parameter will not flash. When the switch is depressed for longer than three seconds, the unit will enter a high speed mode and decrease at a higher rate.
DPU 1000
17
System Setup
Installation Guide
ENTER Switch This pushbutton switch will store the currently displayed data of the selected parameter. If it is held down during KEY # scanning, the keys scanned will all be activated (programmed into the system). If it is held down during ISSUE level programming, the UP and DOWN switches will alter the KEY # field, thus allowing the displayed ISSUE level to be assigned to multiple keys.
DELETE Switch This pushbutton switch will restore the currently selected parameter to its default value. In the case of KEY #, the key will be deactivated. If this switch is held down during KEY # scanning, the keys scanned will all be deactivated (programmed out of the system).
RESET Switch This pushbutton switch resets the system. To perform a COLD start (all data is cleared) press the RESET switch, then press the MODE switch.
Initialization Operational program initialization and control may be accomplished by utilizing the controls and indicators on the DPU printed circuit board. To use the DPU, controls and indicators are used, follow the instructions given below. After the DPU and all associated equipment have been properly installed and interconnected, initialize the DPU for operation as follows: 1. Apply operating power to the DPU 1000 and other system components as applicable. Observe that the DPU accomplished the automatic self-test as previously described and that the time display is shown on the LED display (00:00). 2. Clear the DPU memory by depressing the RESET switch and then the MODE switch within approximately 1.5 seconds. Observe that the DPU accomplishes that automatic self-test as previously described and that the time display is shown on the LED display (00:00).(For more detailed information on initialization of the DPU, refer to the Programming/Operation section in this manual.)
18
DPU 1000
Installation Guide
Operation
Operation When in the stand-alone configuration, operational control is accomplished by using the controls and indicators on the DPU printed circuit board. When the DPU is connected to a central terminal, all operational control is accomplished through the terminal, and any entries attempted using the DPU controls will be superseded by the last entries made using the terminal. However, if required, when a DPU is connected to a central terminal, control may be returned to the DPU by disconnecting the communications line at the DPU terminals. If the communications line is subsequently reconnected to the DPU, operation will once again return to the status of the last entries made at the terminal. This section provides initialization procedures, instructions for determining program requirements prior to actually programming the system, instructions on entering the program data into the system, and an operational description for the Model 1000 DPU.
Initializing DPU Stand-Alone After power-up, press and release the RESET switch. When all digits on the screen illuminate, press and release the MODE switch. This completes a COLD start and memory is cleared. To enable the system to recognize only the keys/cards for one system, insert and remove the SYSTEM key/card in the reader. The green LED on the key/card reader will illuminate and the DPU will enter the PROGRAM mode. Enter and remove the SYSTEM key/card again and observe the door will momentarily unlock. This establishes the system code in the DPU and places it in the PROGRAM mode. (The DPU will now recognize only the keys/cards within this facility code until a COLD start is required.) Observe the program panel indicator alternately displays “- - - -” and “0000”. When in the PROGRAM mode, the “- - - -” represents the program mode display. The “0000” represents the last key/card read. This enables the programmer to verify a key/card # by inserting it into the reader. For example, key/card #1 would display alternately “- - - -” and “0001”. Caution:
DPU 1000
Do not install a DPU that has been initialized as a stand-alone into a new uninitialized central system without removing all power and battery backup (including the memory protect battery, see Figure 8) from the DPU before connection to the central system communication line. Failure to do so could result in the wrong system code being initialized in the central system. This may require the central terminal unit or the floppy disk to be returned to the factory for reinitialization.
19
Operation
Installation Guide
Programming Instructions Upon each initial application of operating power or pressing of the RESET switch, the DPU will cycle through an automatic self-test as previously described. At the successful completion of this self-test, the time function will be shown on the LED display. If the self-test is not successful, the DPU will not begin normal operation and error messages will display as previously described. Also, when operating power is first applied to the DPU, if the optional backup battery is installed, the battery will automatically start charging as required. If primary power to the DPU is lost, the battery will provide up to ten hours of backup operating power. Once the battery is completely discharged, it will require approximately 24 hours with primary operating power applied to the DPU to fully recharge the battery. The programming panel (controls and indicators on PCB) will be inactive until the system key/card has been entered into the key/card readers. During this time the realtime hours and minutes (or an incrementing time display beginning at zero time (00:00) if either no time is programmed, or if RESET has been activated to clear memory) will be displayed on the LED display and the colon between the hours and minutes will flash to indicate that the unit is in the normal operating mode. Once the system key/card has been read, the display will alternately show - - - - and 0000", to indicate that the program mode is active. At this time the three SELECT switches will also become functional. The FUNCTION SELECT switch can be pressed to select the programming function desired. (Each function is described in the following paragraphs.) If any of the other switches are pressed, the programming mode will be terminated.
Programming Mode Place the DPU into the PROGRAMMING mode by inserting and removing the system key in the reader. This initiates the PROGRAMMING TIMER. The TIMER resets to two minutes each time the SYSTEM key is entered, PROGRAMMING mode is initiated, or if any key, except RESET, is pressed. At this time, the display will flash between a dash in each digit and the last key number read by the reader.
Adding And Deleting Keys/Cards Individual Keys/Cards
Enter the PROGRAMMING mode as previously described. Press MODE switch until the KEY/ISSUE LED lights on the display. The first three digits of the display will flash with the number 001 which represents the first user key 001. (The next digit is the ISSUE level for the user and will be discussed later.) In order to enable this key/card and allow door entry, press ENTER. To delete key/card from the system, press DELETE. The KEY VALID LED will light for valid user and will not light for an invalid user. Groups of Keys/Cards
To program a sequence of numbers, press the ENTER and UP or DOWN switch at the same time and the numbers will increase or decrease as applicable. As the number is scanned, it will automatically be programmed into the system.
20
DPU 1000
Installation Guide
Operation
If the DELETE switch is pressed with the UP or DOWN switch, then the key numbers scanned will be deleted from the system.
Key/Card Issue Level During key/card programming, press the MODE switch. Observe that the first three digits display key 001 and the fourth digit flashes with the current issue level for that key. All keys/cards start at issue level 1 and must be programmed with the user’s current issue level. For example, if a key/card is lost, then the user can be issued level 2 with the same user number. To provide high speed programming of a block of keys/cards to the same issue level set the issue level for the first key of the block to be programmed then press ENTER and UP or DOWN switches at the same time. The key/card numbers will be scanned up or down as applicable. The DELETE switch does not function in this mode. An issue level cannot be deleted, only changed.
Key/Card Assignments The next step in the completion of system data input is the assignment of keys/cards. At this time, personnel, and doors are linked together. In the example below, the following keys/cards will be assigned. (Note that gaps are left for the addition of personnel at a later date.)Employee or Department Table 3. Key/Card Assignment Example Allowed Access
Issue
1-3
Yes
1
Staff
10-30
Yes
1
Cleaning
50-53
Yes
1
Employee or Department
Key/Card
Management
Each DPU 1000 will allow programming of time, to Time Stamp activity; keys, to allow entry for each user programmed in; and issue, to replace a lost or stolen key. The programmer should now copy and complete Table 5, “Key/Card Assignment Worksheet,” on page 25.
Programming Time When the TIME function is selected the LED display will show the currently programmed hour and minute in 24-hour format (00:00 to 24:00). The UP and DOWN switches are used to move the time forward or backward until the correct time is displayed but the data will not be programmed until the ENTER switches is pressed. When the ENTER switch is pressed, the mode will increment to the minutes mode automatically. If the ENTER switch is not pressed and only the next mode is desired, then press MODE switch to advance. The Minutes, month, day, and year are all programmed in the same way as the hours. The DELETE switch does not work during this mode.
DPU 1000
21
Operation
Installation Guide
Editing The Program To edit any of the program parameters, place the DPU in the PROGRAMMING mode as previously described. Press the MODE switch until the applicable program parameter is flashing. Edit the parameter using the UP, DOWN, ENTER, or DELETE switches as applicable.
Exiting The Program Mode One of the steps listed below should be used when all program parameters have been entered and exiting from the program mode is desired: ✦ ✦ ✦
Press RESET switch or Wait on PROGRAMMING mode 2 minute time-out or Press any switch (except MODE).
Operational Control After the DPU and the associated equipment has been installed and programmed, operation will be as described in the following paragraphs.
Adding And Deleting Keys/Cards Individual keys/cards or groups of keys/cards may be added or deleted at any time by inserting and removing the SYSTEM key/card into the key/card reader one time to enter the PROGRAMMING mode, and then follow the instructions given in Programming Mode.
Initial Power Application Or Reset Upon each initial application of operating power or depression of the RESET switch, the DPU will cycle through an automatic self-test sequence as previously described. During this self-test, the key/card reader LED will alternately flash red and green, the key/card displays will flash and the red LED on the PCB will flash. Upon completion of the selftest, the LED will extinguish.
User Keys/Cards When a user key/card which has been programmed into the system is inserted and removed from the key/card reader with one smooth, continuous motion, the door strike will unlock. The door will then remain unlocked for 7 seconds or until it is opened and then closed (if the DPU is interfaced to a door sense switch), whichever occurs first after the valid key/card read. If a key/card which is not programmed into the system is used, or if a bad read occurs due to either improper insertion and removal of key/card or leaving the key/card in the reader, an invalid read signal will be received by the DPU. In addition, the key/card reader LED will illuminate red, and the door will remain locked.
Using Door Release Switch Pressing the door release switch will unlock the door, thus allowing personnel to exit. After pressing the door release switch, the door will remain unlocked for 7 seconds or until it is opened and then closed (if the DPU is interfaced to a door sense switch), whichever occurs first. The key/card reader LED will illuminate green during the time the door is unlocked. If the door is not closed within 7 seconds after the release switch is
22
DPU 1000
Installation Guide
Operation
pressed, the door strike will relock. Auxiliary indicators can be used to sense and report this condition. in addition, if a PIPU and printer are connected, a DOOR-OPEN-TOOLONG condition message will be printed.
Door Sense Switch The door sense switch provides a constant monitor of the state (either open or closed) of the controlled door, and allows the door strike to relock immediately upon closure. The door sense switch also detects forced door openings.
Monitoring/Controlling Functions During normal operation, the DPU will perform the monitoring and/or control functions as programmed in accordance with specific system parameters. Proper operation may thus be determined by the evidence that the programmed functions are actually being accomplished as desired.
Tamper Monitor If a tamper switch is installed and the area it is monitoring is accessed in an unauthorized manner, a TAMPER ALARM message will be enabled by the DPU. This message will be routed to and printed/displayed by a printer and/or the central terminal if either or both of these are connected to the system.
Auxiliary Indicators If user supplied indicators are installed using the FORCED DOOR ALARM output, they will activate/deactivate, to indicate the status of the controlled door in accordance with Switch S2, position 7 selection (refer to Table 3). Both the alarm bypass and door strike functions are processed by the same relay on the printed circuit board. The ALARM BYPASS OUTPUT can be used to detect forced doors, DOTL conditions, and shunt door alarm system during a valid entry when used in conjunction with existing door sensing hardware.
Using The Options When the DPU is used in a central system configuration, Switch S2-8 in the OFF position will not allow the door to AUTO UNLOCK except after the first valid key/card presented during an unlock cycle. When the DPU is used in a central system configuration, Switch S2-7 in the OFF position will activate the FORCED DOOR ALARM relay for only one second. When the DPU is used in a central system configuration, Switch S2-7 in the ON position will activate the FORCED DOOR ALARM relay which will remain activated until a manual RESET is executed.
Loss Of Primary Power In the event primary operating power is lost during normal operation a POWER FAIL message will be generated by the DPU. This message will be routed to and printed/displayed by a printer and/or the central terminal if either or both of these are connected to the system. If the optional backup battery is installed, it will provide up to ten hours of backup operating power.
DPU 1000
23
Operation
Installation Guide
Operation With A Central Terminal The DPU 1000 may be operated with a Central Terminal. This terminal can provide the user with the ability for expanded capacity as shown in Table 4. Table 4. Central Terminal Operation Central Keys
2000
1000
Key Issue
4
4
Daytypes
16 with 4 period
1 24-hour fixed
15
1 7-day fixed
Latch Time
1 sec. to 59:59
7 seconds fixed
DOTL Time
1 sec to 59:59
5 minutes fixed
1
None
Access Cycles
Auto Unlock
24
Stand-Alone
DPU 1000
Installation Guide
Operation
Table 5. Key/Card Assignment Worksheet Programmer__________________________________________ DCU Number _________________
Name or Department
DPU 1000
Key/Card Number or Group of Keys/Cards
Date ______________________
Access Yes/No
Issue Level 1
2
3
4
25
Specifications
Installation Guide
Specifications Dimensions
Outputs
11.75" H × 9.50" W × 4.5" D (29.8 cm × 24.1 cm × 11.4 cm)
One Strike/Alarm Bypass Relay (28 VDC/2A DPDT relay) One Forced Door Alarm Relay (28 VDC/2A DPDT relay)
Weight
Enclosure
5.5 lbs (2.5 kg)
For indoor use
Operating Environment
Communications Line (from DPU to Printer Interface or Central Terminal)
Operating Temperature: 32° – 122°F (0° – 50°C) Storage Temperature: 32° – 158° F (0° – 70°C)
CSI protocol standard RS485 differential driven communication loop
Humidity: 0 to 80% noncondensing Input Power: 18 VAC, 50 to 60 Hz at 800 MA. (115 VAC to 18 VAC transformer, CSI supplied.) Output Power: 12 VDC (From CSI power supply)
Door and Key/Card Capacity One Door 2000 key/card users with 1 facility code
Battery Backup (Optional): 12V, 4A gel cell Key/Card Reader Dimensions Cables 18 AWG (0.897 mm2), twisted pair, shielded (Belden No. 8760
Key Reader: 1.5" H × 1.47" W × 2.5" D (3.8 cm × 3.7 cm × 6.4 cm)
cable, or equivalent, is recommended). Maximum loop length 4000 feet (3,660 m). Maximum one way distance 2000 feet (1,830 m). (Customer Supplied.)
Card Reader: 3.8" H × 1.47" W × 2.5" D (9.7 cm × 3.7 cm × 6.4 cm)
Key/Card Reader Cable: 18 AWG (0.897 mm2), twisted pair, shielded (Belden 8760 or equivalent).Maximum 300 feet (90 m) from CSI.
Key/Card Reader Weight Key Reader: 4.5 ozs. (127.57 g) Card Reader: 9.0 ozs. (255.14 g)
Inputs One Tamper Input (tamper switch, customer supplied) One Door Sense Input (monitor status of door) One Door Release Input (to activate door unlock from external N.O. switch) (All inputs require a relay or switch closure)
Key/Card Reader Operating Environment Temperature: 20° – 131° F (-7° – 55° C) Humidity: 0 to 95% noncondensing Input Power: 11 to 15 VDC @ 50 mA maximum
26
DPU 1000
Installation Guide
Specifications
Key/Card Reader Cable 300 feet (90 m) maximum.
Outputs: Clock and Data Both outputs are open collector with a maximum voltage of 30 VDC, and a maximum sink current of 18 mA.
DPU 1000
27
30
Index
Installation Guide
Index A–C Auto unlock setting
23
Battery backup See Optional battery backup See Memory battery backup Central terminal operation with
24
Central terminal, connection of Controls Delete 18 Down 17 Enter 18 initialization Mode 17 Reset 18 Up 17
12
18
D description of
16
Door release switch operation 22 Door release switch, installation of
11
Door sense switch operation 23 Door sense switch, installation of Door strike, installation of
12
11
DPU 1000 central terminal, operation with 24 controls Delete 18 Down 17 Enter 18 Mode 17 Reset 18 Up 17 door sense switch installation 10 electrical installation 11–14 central terminal 12
28
dooptional battery backup 14 door release 11 door sense switch 12 door strike 11 DPU identification 14 tamper alarm 14 initialization Mode 18 monitoring/controlling functions alarm bypass 23 forced door alarm 23 settings for 23 tamper 23 operation adding key/cards 22 deleting key/cards 22 door release switch 22 door sense switch 23 initial power application 22 reset 22 user key/card 22 physical installation 10 power 12 programming instructions description of 20 programming mode adding keys/cards 20 deleting keys/cards 20 editing 22 exiting 22 key/card assignments 21 key/card issue level 21 time 21 self-test 16 stand-alone description of 19
E–I error messages
16
Forced door alarm setting Grounding key/card reader
23
6
DPU 1000
Installation Guide
Index
Installation DPU 1000 door sense switch 10 electrical 11–14 central terminal 12 door release 11 door sense switch 12 door strike 11 DPU identification 14 optional battery backup 14 tamper alarm 14 physical 10 power 12 low temperature package 8–9 pedestal 5 reader and pushbutton 5 single key/card reader 3–5
Power loss 23
S–T Self-test description of 16 error messages 16 Tamper alarm
14
K–P Key/Card reader data line connection 7 grounding 6 installation required tools 2 low temperature package 2 contents of 8 description of 7 heating element resistance 8 installation 8–9 pedestal installation 5 power connection 7 reader and pushbutton installation single installation 3–5 Low temperature package contents of 8 description of 2, 7 heating element resistance installation 8–9
5
8
Memory battery backup 11–?? Optional battery backup, installation of Power DPU 1000, connection of key/card reader 7
DPU 1000
14
12
29
Warranty Repair or Replacement
Purchaser’s Responsibility
If this unit fails to operate because of a defect in materials or workmanship within two (2) years of the date you purchased it, it will either be repaired or replaced by Control Systems International, Inc. (CSI) at no charge to you. Before contacting CSI, it is recommended that you first contact the dealer from whom you purchased this equipment to determine whether they will have it repaired or replaced. If the dealer will not, please contact CSI to arrange to have this equipment repaired or replaced.
In order to obtain service under this warranty, you must deliver the equipment to the place of purchase or to CSI and provide proof of the original purchase date along with the returned equipment. Failure to provide adequate proof of the original purchase date could result in denial of warranty service.
CSI EXPRESSLY RESERVES THE RIGHT TO REPAIR OR REPLACE THIS EQUIPMENT WITH NEW OR REFURBISHED PARTS OR EQUIPMENT.
Direct requests for information on out-of-warranty service to Product Service Manager at the address below.
Exclusions and Limitations Your warranty does not cover:
•
Damage by negligence, misuse, or accident
•
Compatibility with the equipment of any other manufacturer
•
Modifications to the equipment to make it compatible with the equipment of any other manufacturer
•
Damage to the equipment resulting from improper installation or operation.
Legal Rights and Limits All applicable implied warranties, including the implied warranty of merchantability and of fitness for a particular purpose given to you by law are hereby limited in durability to the duration of this warranty. Under no circumstances will CSI be liable for any incidental or consequential damages.
Out of Warranty Service
Control Systems International
®
P.O. Box 59469, Dallas, Tx 75229 Phone: (972) 323-1111 FAX Phone: (972) 242-0026 CSI Europe Unit B3, Armstrong Mall Southwood, Farnborough Hampshire GU14 ONR, United Kingdom Phone: 44 1252 370900 FAX Phone: 44 1252 372470 CSI Pacific 36 Hasler Rd. Osborne Park, Western Australia 6017 Phone: 61-9-244 2799 FAX Phone: 61-9-244 4335 You may obtain copies of this document by ordering document number TCON077.
Some states in the U.S.A. do not allow limitations on how long implied warranties last, or exclusions or limitations of incidental or consequential damages, so exclusions or limitations mentioned may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
TCON077.–.04/97