Transcript
Installation S19-270HC (Eyewash) S19-270JC (Eye/Face Wash) Cabinet-Mounted Swing-Down Eyewash Table of Contents Pre-Installation Information . . . . . . . . . . . . . . .2 Installation Instructions . . . . . . . . . . . . . . . . . . .3 S19-270HC Components . . . . . . . . . . . . . . . . .4 S19-270JC Components . . . . . . . . . . . . . . . . . .5 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
S19-270HC shown
215-1434 Rev. H; EN 07-523A © 2008 Bradley Corporation Page 1 of 6 1/15/08
P.O. Box 309, Menomonee Falls, WI USA 53052-0309 PHONE 1-800-BRADLEY FAX (262) 251-5817 bradleycorp.com
S19-270HC, S19-270JC
Installation
WARNING Read this installation manual completely to ensure proper installation, then file it with the owner or maintenance department. Compliance and conformity to drain requirements and other local codes and ordinances is the responsibility of the installer.
Installation
Packing List
IS TH SIDE UP
• • • •
Separate parts from packaging and make sure all parts are accounted for before discarding any packaging material. If any parts are missing, do not begin installation until you obtain the missing parts. Flush the water supply lines before beginning installation and after installation is complete. Test the unit for leaks and adequate water flow. Main water supply to the eyewash should be “ON” at all times. Provisions shall be made to prevent unauthorized shutoff.
Da Da te Da tum te
Sig ned Sig ned ned
P.O TES . Box DIE ESS SEST THI 309 Tes AI S , Me Rep t-op HEBGER UNI Ven ort nom DO ÄT T EAC 1ST dur til(e anyera te MA one H Tes ch ) val DAI WÖ WE e sig Un wö ma ve( RE CHE EK Fal un ne t le ters che lfun s) ls, NTL rap en fon WI chr ntli ctio eac ICH por basctio 530 ns h ift. ch t imm. nne ZU immwe Jeg im 51 S'il ek me PRÜ Tes edi and édi y à nt lich tbe FEN Sig ate ate que des e Stö trie Un ned . ly. sig me lqu val n Sig ter nt. e ves run b prü bel g cho ne sch ow sof fen rift . se cha ort , bes qui que Da me ne sem ldetäti Da te va ain n. gt Da te pas e te Sig fait et
R
The ANSI Z358.1 standard requires an uninterruptible supply of flushing fluid at a minimum 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI Z358.1.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA TEL: 1-800-BRADLEY FAX: (262-251-5817) http://www.bradleycorp.com
114-051
The inspection and testing results of this equipment should be recorded weekly to verify proper operation. This equipment should be inspected annually to ensure compliance with ANSI Z358.1. Workers who may come in contact with potentially hazardous materials should be trained regarding the placement and proper operation of emergency equipment per ANSI Z358.1. For questions regarding the operation or installation of this product, visit www.bradleycorp.com or call 1-800-BRADLEY. Product warranties may also be found under ”Product Information” on our web site at www.bradleycorp.com.
2
1/15/08
Bradley Corporation • 215-1434 Rev. H; EN 07-523A
Installation
S19-270HC, S19-270JC
Installation Supplies Required: • • • •
1/2" NPT water supply to inlet on eyewash Bolts for cabinet mounting Pipe sealant Sign-mounting hardware
Step 1: Rough-in NOTE: Flush the water supply before installation. 1. Rough-in wall opening to the dimensions shown in Figure 1. Figure 1 2. Rough-in 1/2" NPT water supply at the dimensions shown in Figure 2. 3. Position unit in wall opening and mount eyewash in wall with four bolts (supplied by installer) at the locations shown in Figure 2. 4. With cabinet door open, connect supply line using the coupling nut and combination tailpiece. Refer to Figure 3a on page 4 (for S19-270HC) or Figure 3b on page 5 (for S19-270JC). 5. Mount the safety sign to the wall with appropriate hardware supplied by the installer.
Figure 2 Bradley Corporation • 215-1434 Rev. H; EN 07-523A
1/15/08
3
S19-270HC, S19-270JC
Installation
Assembly of Components - S19-270HC
1.2 1.3 1.2
1.4 1.5
1.6
1.8
1.9
1.7 1.10
1.11 1.13 1.12 1.14
1.15
NOTE: Shown in the “ON” position.
1.1
1.16
9
1.17
3
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA TEL: 1-800-BRADLEY FAX: (262-251-5817) http://www.bradleycorp.com
114-051
2 R
1.18
P.O. Box 309, Menomonee Falls, WI 53051
TEST THIS UNIT EACH WEEK DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN. ESSAI HEBDOMADAIRE
Test-operate valve(s) each week and sign below. Report any malfunctions immediately. Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.
7
10
6
Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.
Date Datum Date
Signed Unterschrift Signe
Date Date Date
Signed Signed Signed
4 8
5
Figure 3a
4
1/15/08
Bradley Corporation • 215-1434 Rev. H; EN 07-523A
Installation
S19-270HC, S19-270JC
Assembly of Components - S19-270JC
1.2
1.2
1.4
1.3
1.5
1.8
1.6
1.9
1.7 1.10 1.11
1.12
1.1
NOTE: Shown in the “ON” position. 1.13
1.14 9 3
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA TEL: 1-800-BRADLEY FAX: (262-251-5817) http://www.bradleycorp.com
114-051
2 1.15
7 6
4
R
P.O. Box 309, Menomonee Falls, WI 53051
TEST THIS UNIT EACH WEEK DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN. ESSAI HEBDOMADAIRE
Test-operate valve(s) each week and sign below. Report any malfunctions immediately. Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt durch Unterschrift. Jegliche Störung sofort melden.
10
Test le fonctionnement des valves chaque semaine et signe en bas. S'il y à quelque chose qui ne va pas fait un rapport immédiatement.
Date Datum Date
Signed Unterschrift Signe
Date Date Date
Signed Signed Signed
8 5
Figure 3b
Bradley Corporation • 215-1434 Rev. H; EN 07-523A
1/15/08
5
S19-270HC, S19-270JC
Installation
Parts List S19-270HC Description
Item
Part No.
1
Swing-Down Sub-Assembly
1.14
125-001DA
1
O-Ring
S05-092
1
Eyewash Assembly
1.15
131-082
1
Base
1.2
107-371
2
Tethered Dust Cover
1.16
160-428
1
Screw, Set
1.3
113-1075
1
Pipe (Plated)
1.17
113-1058
1
Shank
1.4
118-288
1
Valve Body (Plated)
1.18
110-115
1
Hex Nut
1.5
125-135
1
O-Ring
2
142-045A
1
Spacer
1.6
125-120
1
O-Ring
3
S39-566
1
Cabinet Assembly
1.7
S39-598
1
Actuator Sub-Assembly, Valve
4
169-364
1
90° Elbow
1.8
192-016
1
Insert, Direction (Plated)
5
S27-110
1
Stop Valve
1.9
160-413
1
Screw, Set
6
113-006DH
1
Nipple, Close
1.10
125-001CS
1
O-Ring
7
169-639
1
90° Street Elbow
1.11
132-047
1
Insert, Flow Control
8
169-348
1
Union
1.12
125-032
1
Flow Control
9
114-051
1
Safety Sign
1.13
110-115A
1
Hex Nut (Plated)
10
204-421
1
Emergency Inspection Tag
Item
Part No.
Qty.
1
S39-679A
1.1
Qty.
Description
S19-270JC
6
Description
Item
Part No.
1
Swing-Down Sub-Assembly
1.13
160-428
1
Screw, Set
S05-162
1
Eye/Face Wash Assembly
1.14
113-1058
1
Shank
1.2
S53-063
2
Tethered Dust Cover
1.15
110-115
1
Hex Nut
1.3
113-1075
1
Pipe (Plated)
2
142-045A
1
Spacer
1.4
118-288
1
Valve Body (Plated)
3
S39-160
1
Cabinet Assembly
1.5
125-135
1
O-Ring
4
169-364
1
90° Elbow
1.6
125-120
1
O-Ring
5
S27-110
1
Stop Valve
1.7
S39-598
1
Actuator Sub-Assembly, Valve
6
113-006DH
1
Nipple, Close
1.8
192-016
1
Insert, Direction (Plated)
7
169-639
1
90° Street Elbow
1.9
160-413
1
Screw, Set
8
169-348
1
Union
1.10
110-115A
1
Hex Nut (Plated)
9
114-051
1
Safety Sign
1.11
125-001DA
1
O-Ring
10
204-421
1
Emergency Inspection Tag
1.12
131-082
1
Base
Item
Part No.
Qty.
1
S39-680A
1.1
1/15/08
Qty.
Description
Bradley Corporation • 215-1434 Rev. H; EN 07-523A