Transcript
Scroll Enclosure Air Compressor Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Description General
Breathable Air Warning
Powerex Scroll Enclosure Air Compressors are designed to supply continuous oil-free air by using the most advanced scroll technology. These turn-key packages are extremely quiet and offer electronic control that will reduce electrical power consumption.
This compressor/pump is not equipped and should not be used “as is” to supply breathing quality air. For any application of air for human consumption, you must fit the air compressor/ pump with suitable in-line safety and alarm equipment. This additional equipment is necessary to properly filter and purify the air to meet minimal specifications for Grade D breathing as described in Compressed Gas Association Commodity Specification G 7.1 - 1966, OSHA 29 CFR 1910. 134, and/or Canadian Standards Associations (CSA).
The Powerex Oilless Rotary Scroll Air Compressor has advanced scroll compressor technology through the development of a completely oilless unit. The Powerex Scroll Compressor offers a dynamically balanced air end which insures vibration-free operation. The rotary design permits a continuous 100% duty cycle. No oil separation, oil filtration, or inlet valves are required on the Powerex Scroll unit. The compressor is virtually maintenance free.
DISCLAIMER OF WARRANTIES
Safety Guidelines
In the event the compressor is used for the purpose of breathing air application and proper in-line safety and alarm equipment is not simultaneously used, existing warranties are voided, and Powerex disclaims any liability whatsoever for any loss, personal injury or damage.
This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe the following symbols.
Danger indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Avoid damaging the panel with tips of the forklift.
Caution indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
Notice indicates important information, that if not followed, may cause damage to equipment.
Unpacking After unpacking the unit, inspect carefully for any damage that may have occurred during transit. Make sure to tighten fittings, bolts, etc., before putting unit into service.
Do not operate unit if damaged during shipping, handling or use. Damage may result in bursting and cause injury or property damage.
Figure 1
Precautions during transportation and movement
Transportation by crane
Transportation by forklift
Use side openings at the bottom of the unit and lift up by wire, etc.
Use front openings for forklift under both sides of the unit. Powerex • 150 Production Drive • Harrison, OH 45030 • USA 1-888-769-7979 • www.powerexinc.com
IN559300AV 6/10
Scroll Enclosure Air Compressors 4. Never use rubber hoses, plastic piping or soldered joints in any part of the compressed air or gas system. The compressor and system piping must be compatible.
Description (Continued)
Be sure to use pads in order to protect panels.
5. The compressor will shutoff when the pressure reaches a predetermined maximum pressure. Care should be used since the compressor may suddenly restart automatically when the pressure drops to the predetermined minimum pressure. Never assume the compressor is ready for service just because the unit is stopped.
Do not use Forklift spaces for Lift up
6. All pressure must be drained from the compressor and the electrical source must be turned off before attempting to inspect or repair the unit. Spaces for Forklift
Spaces for Lift up
7. Keep clear of all moving parts especially if the compressor is operating with the door panel removed for inspection or repair.
Do not touch HOT parts of the compressor such as the air end, discharge pipe, aftercooler, motor, etc.
Figure 2
The compressor nameplate should be checked to see if the unit is the correct model and voltage as ordered.
8. Keep flammable gases away from the compressor. Parts of the compressor become very hot during operation and the vapors from flammable gases may cause the unit to explode.
General Safety Information
9. Never use flammable or toxic solvents to clean the compressor or any of the unit’s parts.
The operator of this compressor must take the necessary precautions to prevent the level of danger indicated by these symbols. The operator is also required to read and understand this instruction manual and all safety warnings, labels, etc.
10. Do not remove or tamper with any safety devices, guards, panels or insulation parts while compressor is in operation. All guards or panels must be in place before starting or operating the compressor.
Any employer allowing the use of this compressor in their field of work must distribute this instruction manual to all users. The employer must also ensure all users read, understand and follow the instructions as described in the manual, safety warnings, labels, etc. 1. Read and understand all safety warnings and instructions before operating this compressor. Failure to read and follow all safety warnings may result in serious personal injury or death. Property damage and/or compressor damage may also occur if all warnings are not followed.
Install a properly sized Safety Relief Valve in the discharge piping ahead of or before a shut-off valve, heat exchanger, orifice, etc. The compressor or part of the system could rupture or explode if a Safety Relief Valve is not installed.
11. Do not change the pressure setting of the Safety Relief Valve. Do not replace the Safety Relief Valve with a plug or restrict the Safety Relief Valve. The system or the compressor may be over-pressurized if the Safety Relief Valve is tampered with in any way.
MANUAL
2. Air used for breathing or food processing must meet O.S.H.A. 29 C.F.R. 1910.134 or C.F.R. 178.3570 regulations.
12. Do not service the compressor or any compressor part while the unit is in operation.
Motors, electrical equipment and controls can cause electrical arcs that will ignite a flammable gas or vapor. Never operate or repair in or near a flammable gas or vapor. Never store flammable liquids or gases in the vicinity of the compressor.
13. Do not remove, disconnect or tamper with the High Temperature Shutdown Switch. The High Temperature Shutdown Switch must be installed on the compressor to protect against high temperatures damaging the compressor. 14. All electrical connections should be made by a qualified electrician.
3. Safety Valves or Relief Valves used on this compressor must be in accordance with ANSI/ASME B19 safety standards. Improperly sized Safety Valves will result in serious personal injury or death.
Disconnect all power supplies to the compressor before opening the electrical box or before servicing the unit. High voltage may be present.
Do not remove the panel or try to service the air compressor while the compressor is running or while the air receiver is under pressure. Serious personal injury or death will occur.
15. Never remove or alter any safety warning labels, tags, etc. located on or provided with compressor.
2
Scroll Enclosure Air Compressors Magnetic Starter
General Safety Information (Continued)
The magnetic starter is located inside the electrical box accessible from the front door. Motor Overload Protection
16. Always provide a clean air source for your compressor. Keep all piping direct and short when using an outside air source.
The motor overload protection on the scroll compressor is controlled by an overload relay which is attached to the magnetic starter. Please refer to the electrical drawings.
17. Locate compressor inlet system away from possible ingestion of flammable or toxic vapors, water, dirty air or air temperatures exceeding 104°F.
Control Transformer The control transformer on the scroll compressor reduces line voltage to 200 volts for operation of the ventilation fan, circuit board and pressure sensor.
18. Never set the pressure to a higher setting than the one provided from the factory. 19. Check all gauges daily to be sure the compressor is operating correctly.
Three Phase Motor
20 Follow all directions for maintenance. Check all safety devices according to instructions.
Powerex three phase motors are TEFC, NEMA frame motors suitable for 208V, 230V and 460V operation.
21. Never attempt to lift or move the compressor except when using the proper lifting procedures.
Tip Seal
22. Make sure all electrical components follow the National Electric code and all state and local codes when installing the compressor.
The tip seal on the scroll compressor is self-lubricated and allows the unit to operate efficiently without oil and expensive filtration. The tip seal should be replaced every 10,000 hours (5,000 hours for high pressure models) of operation.
23 Do not operate the compressor if unusual noise or vibration occurs. 24. Keep all panels in place at all times.
Bearings
25. Standard motors are not appropriate for dirty, wet or explosive areas. 26. All service should be performed by trained and qualified people only.
The bearings on the scroll compressor are regreaseable to allow extended compressor life. Service should be performed every 10,000 hours (5,000 hours for high pressure models) of operation.
27. The Drive Belt tension should be checked often during initial operation of the compressor.
Air Cooled Aftercooler
28. Never substitute oil bath or oil wetted filters for the inlet filters provided with the compressor.
The air cooled aftercooler on the scroll compressor is a series of deep alloy cooling fins and a high output cooling fan. These cooling features allow the scroll compressor to provide a maximum discharge air temperature of 63°F above the ambient temperature.
Component Description Compression Cycle
Dry Type Inlet Filter
The Powerex Oilless Rotary Scroll Air Compressor is based on the theory of scroll compression. A scroll is a free standing, intricate spiral bounded on one side by a solid, flat plane or base. A scroll set, the basic compression element of a scroll compressor, is made up of two identical spirals which form right and left hand parts. One of these scroll components is indexed or phased 180° with respect to the other so the scrolls can mesh. Crescent-shaped gas pockets are formed and bounded by the spirals and the base plate of both scrolls. As the moving scroll is orbited around the fixed scroll, the pockets formed by the meshed scrolls follow the spiral toward the center and diminish in size. The moving scroll is prevented from rotating during this process so the 180° phase relationship of the scrolls is maintained. The compressor’s inlet is at the outer boundary of the scrolls. The entering gas is trapped in two completely opposite gas pockets and compressed as the pockets move toward the center. The compressed gas is discharged through the outlet at the center of the fixed scroll so no valves are needed.
The inlet filter on the scroll compressor assures 99% of particulate free air is admitted to the unit. Change every 2,500 hours or more often in dirty locations. These filters can be accessed from the front door. Cooling Air Cleanable Filter Screen The cooling air cleanable filter screen on the scroll compressor is located on the rear of the unit and should be cleaned periodically. Digital Hourmeter The hourmeter on the scroll compressor indicates the actual number of total run hours of all air ends that have been in operation. The hourmeter is also used to determine maintenance and service timing. The hourmeter is activated when one or more air ends is/are running.
3
Scroll Enclosure Air Compressors
Wiring
Component Description (Continued)
All electrical hook-ups must be performed by a qualified electrician. Installations must be in accordance with local and national electrical codes.
High Temperature SHUTDOWN feature
1. Use solderless terminals to connect the electric power source.
The high temperature shutdown feature on the scroll compressor protects the unit when an unusually high temperature in the air end is detected. The compressor will shutdown when this high temperature is detected.
2. Remove front panel. 3. Remove the rectangle electrical box cover located beneath air inlet filter on the right front of the unit.
Installation
4. Connect the power inlet cable to the inlet power junction block located on the inlet side of all starter connections.
Installation Site
Consult your NEC and local codes for wire size
1. The scroll compressor must be located in a clean, well lit and well ventilated area. A contaminated area can clog the intake filter and/or intake metal mesh.
Piping These units do not include air receivers. An air receiver can be purchased separately. Please consult our distributors. Use Chart 2 as a guideline for sizing the air receiver.
2. The area should be free of excessive dust, toxic or flammable gases, moisture and direct sunlight.
1. Make sure the piping is lined up without being strained or twisted when assembling the piping for the scroll compressor.
3. Never install the compressor where the ambient temperature is higher than 104°F or where humidity is high. High humidity will cause electrical short circuit and rusting of components.
2. Appropriate expansion loops or bends should be installed at the compressor to avoid stresses caused by changes in hot and cold conditions.
4. Clearance must allow for safe, effective inspection and maintenance. 28 in. of clearance for sides, 48 in. clearance from the top is recommended.
Model
5. If necessary, use metal shims or leveling pads to level the compressor. Never use wood to shim the compressor. Ventilation
Air Receiver Min. Capacities
SEH3007
110 gallons
SEO4007
160 gallons
Chart 2
1. If the scroll compressor is located in a totally enclosed room, an exhaust fan with access to outside air must be installed.
3. Piping supports should be anchored separately from the compressor to reduce noise and vibration.
2. Never restrict the cooling fan exhaust air.
4. Never use any piping smaller than the compressor connection.
3. Vent the exhaust air outside to prevent the compressor from operating at high temperatures and shutting down.
5. Use flexible hose to connect the outlet of the compressor to the piping so that the vibration of the compressor does not transfer to the piping.
4. Never locate the compressor where hot exhaust air from other heat generating units may be pulled into the unit. Suggested ventilation system 1) The following ventilation capacity is designed to keep the temperature rise inside the room to be max. 10°F. Since the calculation is based on zero static pressure, the actual ventilation capacity should be larger than the figure in Chart 1.
Safety Valves
2) Install the exhaust duct in order to minimize the pressure lost of the ducting. Keep the distance between the inlet duct and the compressor exhaust to be at least 12 inches for ease of maintenance. Intake section of the duct should be larger than the dimension of compressor exhaust shown below:
1. The pressure setting of the safety valve must not be greater than the maximum working pressure of the air receiver.
Model Ventilation Capacity (cfm)
These units have a safety valve, but install a safety valve in the air receiver manifold for your safety. The flow capacity of the safety valve is equal to or greater than the capacity of the compressor.
2. Safety valves should be placed ahead of any possible blockage point in the system, i.e. shutoff valve.
SEH3007
SEO4007
3. Avoid connecting the safety valve with any tubing or piping.
7800
10600
4. Manually operate the safety valve every six months to avoid sticking or freezing.
Chart 1
4
Scroll Enclosure Air Compressors
Control Sequence As this compressor uses plural air ends, it employs multistage control. It can start and stop each air end according to pressure and air consumption, automatically select the number of air ends in accordance with air consumption and achieve optimum and uniform operation at all times as well as energy-saving and labor-saving operation.
shorter, thus resulting in equalization of operating time of each air end and operation with a min. quantity of air ends in accordance with air consumption and energy-saving operation by eliminating waste of electricity.
1. Multi-stage control
When operating time of an air end exceeds the set time, it changes operation from that air end to the one which has stopped, prevents long-term operation of one air end, lengthens the lifetime of air ends and equalizes the operating time of air ends.
2. Prevention of long-term operation
Among air ends which are operating under group control, it stops the air end which has been operating for a longer time and restarts the air end whose operating time has been
Multi-stage control 100%
Ratio of air consumption Ration of Load 0%
Max pressure
Pressure Min pressure
No 1
OFF
ON
No 2 No 3
Compressor
No 4 No 5 No 6 No 7 No 8
Chart 3
5
Scroll Enclosure Air Compressors Note: The alarm lamp light will come on if a temperature sensor is not connected. If the sensor is not connected, have a qualified service person reconnect the sensor.
Operation Before start up
4. Open the discharge valve completely.
1. Make sure all safety warnings, labels and instructions have been read and understood before continuing.
5. Push ON button and check that the compressor operates without excessive vibration, unusual noises or leaks.
2. Remove any shipping materials, brackets, etc.
6. Close the discharge valve completely.
3. Confirm that the electric power source and ground have been firmly connected.
7. If the pressure does not rise, turn the unit off, the unit is running backwards. Have a qualified electrician switch the breaker OFF and exchange two out of three phases of electric source.
4. Check the belts for tightness. 5. Be sure all pressure connections are tight.
8. Check the discharge pressure. Also make sure the air pressure rises to the designated pressure setting by checking the discharge pressure gauge.
6. Check to be certain all safety relief valves, etc., are correctly installed. 7. Securely mount all panels and guards. 8. Check that all fuses, circuit breakers, etc., are the proper size.
shut-down 1. Stop the compressor by pushing the OFF button.
9. Make sure the inlet filter is properly installed.
NOTE: If the compressor rotates in reverse for more than five seconds, the check valve needs to be cleaned or replaced.
10. Confirm that the drain valve is closed. 11. Visually check the rotation of the compressor pumps. The rotation should be counterclockwise if viewing the compressor from the pulley or belt side of the motor or the air end. If the rotation is incorrect, have a qualified electrician correct the motor wiring.
2. Switch the breaker OFF if the compressor is not to be used for a long period of time. Stopping the Compressor during Normal Operation
Start-up and Operation
1. Close the discharge valve at air receiver.
1. Follow all the procedures under “Before start-up” before attempting operation of the compressor.
2. Allow the air pressure to build and the compressor to stop.
2. Switch on the electric source breaker.
3. Turn the compressor off by pushing the OFF button.
3. Make sure electric source lamp lights up and that the caution code or alarm code does not show up on the display.
Stopping the Compressor during Emergency Operation 1. Stop the compressor by pushing the OFF button or by turning the power off at the main disconnect panel.
Unit display
Mode display light
Reset switch
Indicates selected display mode
Performs various resettings
Indicates selected unit
Display
UNIT 1
Comp. operating lamp
UNIT 2
RESET
Lights up when ON switch is pushed.
OPERATION MODE TIME MODE SET MODE COMPRESSOR RUN
ON
MODE ITEM
OFF
SELECT
ON switch Starts the unit
OFF switch
MODE button
Stops the unit
Selects the mode to be displayed
Figure 3 - Operating Panel
6
ITEM button Selects the information to be displayed
Scroll Enclosure Air Compressors
Operating Panel
Operation Mode
There are three display modes; Normal Mode, Time Mode, and Setup Mode.
Displays operating conditions (pressure, operating time, module operating conditions). Display information can be changed by pushing the Item Button. This information is useful for maintenance and daily inspection.
Items
Display
Explanation Displays compressor outlet pressure in psig (Display on the left means 68 psig.)
Pressure
Displays operating time in x10 hours. (Display on the left means 230 hours.) * Number of Hours that any pump is running x load factor (between 0 to 1 depending on how many pumps are running)
Operating Time
Displays operating condition of Unit No.1 (left side) which consists of air ends No. 1-4 Displays operating condition of air ends No. 1,2,3 and 4 from left to right of the display (The air end that are located on the bottom of the Unit is designated as No 1) Operating condition of Unit No. 1
means being in operation
Indicates emergency stop when “hyphen” lights up.
Compressor is off when “underline” lights up In the above example, No. 1 and No. 3 air ends are in operation, No.2 air end is in an emergency stop and No. 4 air end is off. As SEH30 has no air end No. 4, The right indicator will always display “underline”.
Operating condition of Unit No. 2
Displays operating condition of present Unit No. 2 (right side) which consists of air ends no. 1~4. Display contents are the same as Unit No. 1.
Chart 4
Time Mode The Early Caution maintenance alarm becomes effective by installing a Early Caution maintenance connector. By doing so, the maintenance alarm will be activated at 7800 hours (2000 hours earlier than maintenance alarm 1).
In order to select the Time Mode, push Mode Button so that Time Mode light is illuminated. By utilizing Item Button, you can scroll the display shown in the chart below. Compressor must be turned off before selecting the Time Mode. Items
Display
Explanation
Maintenance time 1
Shows remaining time until next maintenance and inspection in x10 hrs. (calculated in the same fashion with operating time). It will start at 980 (9800 hrs.) and continue to decrease as the unit is being operated.
Maintenance time 2
Standard unit does not have this function. Becomes effective when Early Caution maintenance connector is used (see page 10). Shows remaining time until scheduled maintenance and inspection.
Running time
Running time records the number of hours during which any or the pump on the system is running (This display means 860 operating hours).
Chart 5
7
Scroll Enclosure Air Compressors
Operating Panel (continued) Set Mode By utilizing Item Button, you can scroll the display shown in the chart below. Compressor must be turned off before selecting the Set Mode.
Items
Display
Explanation
Cut-out Pressure
Shows cut-out pressure in psig. (This display means 115 psig)
Cut-in Pressure
Shows cut-in pressure in psig. (This display means 95 psig)
Time to alternate operating air end
Prevents the same air end from operating for a long time. 1 on display means 15 min. (This display means 2×15=30 min) * Factory setting only. Shows start-up sequence for refrigerated dryer
Preliminary dryer start-up operation (only for unit with dryer option)
means that dryer start 90 seconds before any pump would start means that dryer would start at the same time with the first pump * Option can be changed by pushing reset switch. Shows the condition of Remote Control operation
Remote Control operation
means Remote Control option is activated means Remote Control option is deactivated. * Option can be changed by pushing reset switch. Shows the condition of remote output.
Remote output
means remote output when emergency stop occurs. means remote output when emergency stop or cautions occurs * Option can be changed by pushing reset switch. Shows the condition of Multiple Unit control. means that Multiple Unit control mode ON is set.
Multiple Unit control (not a standard feature)
means that Multiple Unit control mode OFF is set. * If group control mode ON is set, ON/OFF buttons on the Operating Panel do not work. * Option can be changed by pushing reset switch.
Chart 6
8
Scroll Enclosure Air Compressors
Operating Panel (continued)
2. Display of air end No. The first numeric displays air end No. that caused the emergency stop.
Caution Display
3. Display of emergency stop No. The last 2 digits display the content of emergency stop.
When compressor has a minor problem, Unit No. light will flash. Refer to the trouble-shooting section and take necessary measures.
Unit Display
Display 1. Display of Unit Unit Display light will be illuminated when caution occurs. * If caution condition is not related to a specific unit, the Unit Display light will not be illuminated. 2. Display of air end No. The first numeric displays air end No. that requires attention.
Air end No.
3. Display of caution No. The last 2 digits display the content of caution.
Emergency Stop No.
The above example displays emergency that No. 2 (Second from the bottom) air end of unit 2 has “high electric current”.
Unit Display
Figure 5 - Unit 2 air end display
Emergency Stop No.
Air end No.
Caution No.
E 21
Sudden temperature rise of air end
E 22
High temperature of air end
E 32
High electric current
E 41
Abnormally high pressure
E 60, 61, 63
The above example displays caution that No. 1 (Bottom pump) air end of unit 1 has “high temperature”.
Contents of emergency stop
E 91, 92
Communication failure Maintenance time
Chart 8
Figure 4 - Unit 1 air end display
To adjust system pressure settings 1. Change to set mode by utilizing Mode Button.
Caution No.
Contents of caution
c 5
Failure of dryer (only available for unit with dryer option)
2. Display Cut-out pressure or Cut-in pressure by utilizing Item Button.
c 21
High temperature of air end
c 22
Failure of temperature sensor
3. You can decrease the pressure setting by pushing “OFF” Button and “Item” Button at the same time.
c 42
Caution of low pressure (option)
c 91, 92
4. You can increase the pressure setting by pushing “OFF” Button and “Mode” Button at the same time.
Maintenance time Restrictions
Chart 7
• Cut-out pressure does not exceed factory setting. • Pressure difference between Cut-out pressure and Cut-in pressure should be 15 psig or over. • Cut-in pressure should not be under 45 psig.
Emergency Stop Display When compressor has some abnormality, unit display flickers. Refer to Trouble-shooting section and take necessary measures. Display
To reset maintenance counters
1. Display of unit Unit display light will be illuminated when caution occurs. * If emergency condition is not related to a specific Unit, the Unit Display light will not be illuminated.
1. Change to “Set Mode” by utilizing Mode Button. 2. Display “Maintenance Time 1” by utilizing Item Button. 3. Press Reset Button. 4. Cut off circuit breaker and switch on breaker again.
9
Scroll Enclosure Air Compressors
Operating Panel (continued)
Early Caution maintenance connector (Shipped with compressor as an accessory)
Power outage reset connector
Early Caution maintenance will provide an early alarm for maintenance schedule. By installing this connector, the caution alarm for maintenance of one unit will be activated 2,000 hours earlier than the standard maintenance schedule. This will allow you to spread the cost of maintenance over period of times. Another alarm will activated at 9,800 hours.
(Shipped with compressor as an accessory) You can install the power outage reset connector (auto restart connector) to this compressor. When you install this connector, the compressor will automatically start again, after the power to the control panel is restored (without this connector, you have to manually push the start button to activate the unit).
Installation procedure In the same way as stated in the above to install power outage reset connector, insert attached the Early Caution maintenance connector into CN26 on circuit board.
When power outage reset connector is installed on the system, be sure to push stop switch before doing the maintenance to stop compressor and turn off main electric source. Otherwise the system can start automatically after main electric source is energized.
CN26 Installation procedure • Remove printed circuit board (PCB) cover (PCB is installed at the backside of operating panel) by removing 4 screws around this cover (see Figure 6).
Early Caution maintenance connector
• Insert the power outage reset connector into CN11 on circuit board (see Figure 7). • Replace the cover of to the PCB case
CN11 Power outage reset connector
Print board case
Figure 7 - Circuit Board
Front side
Relay print board
Print board cover
Transformer
Main print board Rubber bush Figure 6 - Circuit Board
10
Main print board
Scroll Enclosure Air Compressors
Troubleshooting Guides
• c22: Temperature sensor fails. Items
Caution displays 1. When caution occurs, caution number flashes on the display section of operating panel and on each Unit operating panel (compressor does not stop). When the cause of caution goes away, the light will stop flashing.
Sensor
Possible causes 1. Temperature sensor cable is not properly connected. 2. Temperature sensor fails.
Ambient When temperature is less than about 14° F. Temperature
2. You can check contents of caution by caution display mode of each unit control panel when caution occurs.
Chart 10
• c91, c92: Scheduled maintenance
3. When caution occurs, cut off circuit breaker, solve problem and then turn on electric source again. Caution display will be reset.
It will acknowledge the customer that the remaining time to the scheduled maintenance is less than 200 hours. To view detailed information, refer to the Set Mode. Contact our distributor for scheduled maintenance and inspection.
4. Refer to the chart below for trouble shooting caution codes.
IMPORTANT: Be sure to contact our distributor and ask for scheduled maintenance. Control Panel
Emergency stop displays 1. When emergency stop occurs, emergency stop number flashes on the display section of operating panel and each module operating panel and the particular compressor with the problem will stop. The other compressors without any problem will continue to operate.
Unit 2 Control Panel
Unit 1 Control Panel
2. You can check contents of emergency stop by E.stop display mode of each Unit Control Panel. 3. In case of emergency stop, study the contents, find the causes and take necessary measures. Then push reset switch on module operating panel to cancel flashing emergency number. If you cannot find a reason for the emergency stop, consult the distributor where you purchase our product.
Figure 8 - Unit control panels
4. Refer to the chart below for trouble shooting Emergency codes. Caution codes
Emergency codes
• c21: Temperature of air end is too high. Items
• E21: Sudden temperature rise of air end
Possible causes
• E22: Temperature rise of air end If the temperature rises more than the set temperature, the compressor will stop.
Ambient Ambient temperature is high. Temperature
Failure of cooling
1. 2. 3. 4.
Unit intake wire screen is clogged Exhaust outlet is clogged. Dirty aftercooler fins. Ventilation fan fails or intake hose is damaged. 5. Cooling passage of compressor is clogged 6. High exhaust pressure.
Items Ambient Temperature
Failure of cooling
Chart 9
Chart 11
11
Possible causes Ambient temperature is high. 1. 2. 3. 4.
Air inlet is clogged Air outlet is clogged. Dirty aftercooler fins. Failure of ventilation fan, damaged intake hose. 5. High exhaust pressure.
Scroll Enclosure Air Compressors
Troubleshooting Guides • E32: Rise of current If current becomes very high, thermal overload will be activated and the compressor will stop. Item Electric source
Possible causes Open phase, low voltage
Air end
Failure
Motor
Failure
Chart 12
• E41: Emergency stop by high pressure When pressure is higher than cut-out pressure by 15 psig, E41 displays and compressor stops. • E60, 61 & 63: Communications failure Communications failure between the main panel circuit board and circuit board on each Unit. Item Wiring Circuit board
Possible causes Failure of connections Failure
Chart 13
• E91 - 92: Scheduled maintenance time is reached. When the scheduled maintenance is not performed within 200 hours after c91 or c92 is being displayed and cleared, E91 or E92 will be displayed when customer disconnect and reconnect the power to the system. When the display shows E91 or E92, do the scheduled maintenance and cancel Emergency mode. * As a temporary measure, you can operate by pushing reset switch.
We are not responsible for any failure or accident when you continue operating compressors after scheduled maintenance time is reached.
12
Scroll Enclosure Air Compressors
Troubleshooting Chart Items marked by * are difficult for you to remedy. Please contact our distributor. Problems
Compressor does not operate
No display on the operating panel
Causes
Remedies
• Electric source is not turned on • Fuse on the circuit board was blown • Electric source is not correctly connected • Failure of circuit board
• Failure or wiring failure of magnetic starter • Circuit board failure It does not operate • Motor failure despite displays • Low voltage
• Turn on electric source • Replace • Connect correctly • Inspect, repair or replace* • Inspect, repair or replace* • Inspect, repair or replace* • Inspect, repair or replace* • Check electric source capacity and the size of electric source cable and change to proper one
E60, E61 or E63 are displayed
• Communication failure of circuit board between operating panel and each Unit operating panel
• Inspect wiring around communications circuit board • Replace circuit board
E91 or E92 are displayed
• Scheduled maintenance time has elapsed
• After maintenance, push reset switch to cancel*
• Failure of circuit board
• Disengage and reengage the circuit breaker • Replace circuit board*
• High ambient temperature or bad ventilation • Clogging of aftercooler fins or intake wire screen • Failure of ventilating fan • Damage to intake hose • Cooling passage of air end clogs • High exhaust pressure
• Improve installation environment and ventilation
• Low voltage • Motor failure • Air end failure • Loosened wiring screw • High exhaust pressure • Failure of thermal overload
• Check electric source capacity, size of electric source cable and change to proper on • Inspect, repair or replace* • Inspect, repair or replace* • Tighten • Readjust • Replace*
• High exhaust pressure • Failure of pressure sensor
• Check pressure • Replace pressure sensor
Exhaust pressure does not increase.
• Air leaks from exhaust piping • Air-end rotates backward • Wrong pressure setting • Clogged intake filter
• Inspect, repair • Change phases • Readjust* • clean or replace
Safety valve activates.
• Failure of safety valve • Failure of pressure setting
• Replace* • Readjust*
Abnormal sound
• Air-end rotates backward • Air end failure • Belt slips • Motor failure • Cooling fan contacted • Loosened bolts
• Change phases • Inspect, repair or replace* • Check tension and readjust • Inspect, repair or replace* • Inspect and repair • Inspect and tighten
Err is displayed
It starts but then stops
E21 or E22 are displayed
E32 is displayed
E41 is displayed
Chart 14
13
• Clean • Replace • Replace • Inspect • Inspect
Scroll Enclosure Air Compressors
Specifications Compressor Noise Level (1.5m from front)
Discharge Pressure (PSIG)
Air Delivery (SCFM@ Compressor Driving 100 psig) Speed (RPM) System
Solid State Pressure Driven Control
95-115
88.2
3150
V-belt
< Intake temp. +63°F
1 1/2”
59
SLAE05EHP
Solid State Pressure Driven Control
116-145
73.2
3150
V-belt
< Intake temp. +52°F
1 1/2”
59
SEO4007B
SLAE05E
Solid State Pressure Driven Control
95-115
117.6
3150
V-belt
< Intake temp. +63°F
1 1/2”
60
SEO4007BHP
SLAE05EHP
Solid State Pressure Driven Control
116-145
97.6
3150
V-belt
< Intake temp. +52°F
1 1/2”
60
Model Number
Air End
SEH3007B
SLAE05E
SEH3007BHP
Control System
Discharge Discharge Air Temp. °F Air Outlet
Motor Model Number
Type
Horsepower
Voltage
Starting System
Overload Relay
High Temp. Shut Down
Dimensions (W x L x H)
SEH3007B
3 phase, TEFC
30 (6 x 5)
208 - 230/460
Magnetic starter
Installed
Installed
55.1 x 44.9 x 64.6
SEH3007BHP
3 phase, TEFC
30 (6 x 5)
208 - 230/460
Magnetic starter
Installed
Installed
55.1 x 44.9 x 64.6
SEO4007B
3 phase, TEFC
40 (8 x 5)
208 - 230/460
Magnetic starter
Installed
Installed
55.1 x 44.9 x 64.6
SEO4007BHP
3 phase, TEFC
40 (8 x 5)
208 - 230/460
Magnetic starter
Installed
Installed
55.1 x 44.9 x 64.6
Chart 15 - Specifications for Compressors and Motors
14
Scroll Enclosure Air Compressors
Branch Circuit Protection Table (A) Load Specifications Panel Part Number Motor Size (HP)
(A) Power (V/PH)
(A) motor Load Each (FLA)
Panel Load Total (FLA)
SEH3007B SEH3007BHP
5 5 5
208V/3 230V/3 460V/3
16.7 15.2 7.6
SEO4007B SEO4007BHP
5 5 5
208V/3 230V/3 460V/3
16.7 15.2 7.6
(B) Branch circuit protection provided by installer Non-time Delay Fuse
Time Delay Fuse
Inverse Time Circuit Breaker
100 91 47
135A 125A 60A
120A 110A 55A
125A 125A 60A
134 121 61
175A 175A 80A
150A 150A 70A
175A 175A 80A
Chart 16 - Load Specifications and Branch circuit protection
Maintenance Schedule Operating Hours Item
Action Needed
500
2500
Intake Filter Ventilation Screen
Clean, replace
l
s
Clean
l
Air End/ Blower Fan
Clean
5000
10,000
20,000
Remarks
Every 500 hours or less Every 500 hours or less l
s
Every 5000 hours or less
Fan Duct
Clean
l
Every 5000 hours or less
Compressor Fins
Clean
l
Every 5000 hours or less
Compressor
Grease
s
Tip Seal
Replace
s
(Every 5000 hours for high pressure models)
Dust Seal
Inspect, replace
s
(Every 5000 hours for high pressure models)
V-belt
Inspect, replace
s
* Readjust
l
Confirm operation
*
l
Temperature Sensor Pressure Sensor
Confirm operation
l
Magnetic Starter
Inspect
l
Check valve
Replace
Safety Valve
Confirm operation
Ventilation Fan
Inspect
Pulley
Inspect groove
Motor
Inspect
l
Intake hose
Replace
s
Air Hose
Inspect, replace
After Cooler
Clean outside
O-ring
Replace
Operating Panel
Inspect monitor display
Piping
Inspect for leakage
s (pump)
l
Use genuine Powerex grease (Every 5000 hours for high pressure models)
Replace if contact points deteriorated
s Every 500 hours or less Replace if malfunctions
l
Repair if abnormal wear is detected
l
l
s
l
Replace if abnormal noise is detected Replace if hose is broken Every 5000 hours or less
l s Daily l
l Inspect s Replace
NOTES: 1. Inspect and perform maintenance periodically according to maintenance schedule. 2. The maintenance schedule relates to the normal operation conditions (maximum ambient temperature of less than 104° F and yearly average ambient temperature of 85°F). If the circumstances and load condition are adverse, shorten the cycle time and perform maintenance accordingly. 3. *Marked “Readjust” means the tension of the V-belt should be adjusted during the initial stage and inspected every 2,500 hours afterwards. Chart 17 - Maintenance
15
Scroll Enclosure Air Compressors
Scheduled Maintenance
Per OSHA regulations, lockout compressor system from all power sources BEFORE performing any maintenance.
Intake filter 1. Remove the front panel of the unit. 2. Remove the air inlet housing, the wing nut and the inlet filter element. 3. Clean the inlet filter element with compressed air or replace with a new element. NOTE: Never clean filter element with solvents or water. Ventilation screen 1. Remove the ventilation screen located at the rear of the unit. 2. Clean with compressed air or soap and water, if necessary.
Grease fittings for pin crank bearings
Figure 9
Inspect V-Belt tension 1. Check V-Belt tension with tension gauge. 2. Adjust to the specifications listed in Chart 18.
Existing Belt Load ± Deflection Lbs./ in.
Use only Powerex genuine, grease (Part #IP600000AV), or
equivalent.
25.5 ± 1.5
NOTE: Each pump of the grease gun equals 0.65g of grease. The volume of grease is less after the 2nd pump since some of the grease supply will remain in the grease passage.
Chart 18
Plastic Dust Cap
Grease Gun
Grease Fitting
52°
Extension Adapter
Key Way Counter Weight Figure 10 - Air end: to locate the grease fitting on the counter weight, place the key way on the crankshaft as shown.
16
Scroll Enclosure Air Compressors 3. Remove nuts and bolts that secure fixed scroll.
Scheduled Maintenance (Continued)
4. Remove the fixed scroll housing. 5. Take out the old tip seal from the orbiting scroll housing and fixed scroll housing, see Figure 11.
Grease Compressor Bearings 1. Remove the plastic dust cap from the air end.
Lip Direction
2. Move the compressor pulley until the grease fitting is visible through the dust cap hole.
Enter Side
3. Use a grease gun extension adapter to engage the grease fitting and supply the proper volume of grease as indicated on the grease delivery chart. See Chart 19. Model
1st Time
2nd Time
O.S. Bearing
7 times
6 times
Pin Crank Bearing O.S. Side
7 times
7 times
Lip Surface (Inside)
Lip Side (Grooved bottom)
Chart 19 - Grease Delivery
Figure 11
Grease pin crank bearing 1. Remove the fan duct (2) (Key #6).
6. Remove the old dust seals from fixed scroll, see Figure 12.
2. Remove the nuts and bolts and then the fixed scroll from the air end.
Install the new tip seals and dust seals in the stationary and orbiting scroll housings in the following manner:
3. Grease all three pin crank bearings as indicated on the grease delivery Chart 19 above.
NOTE: Tips seals for Fixed Scroll and Orbit Scroll have opposing seal cut angels (See NOTE and explanatory diagram below).
Use only Powerex genuine grease. (Part # IP600000AV). Pump grease gun before feeding to eliminate air from grease passage of the needle adapter.
The grease fitting, located in the center of the pin crank bearing, feeds only the orbit scroll side bearing. Use a needle adapter to supply grease to the housing side bearing. Pump grease gun before feeding to eliminate air from grease passage of the needle adapter. Hold grease gun for 5 - 10 seconds after feeding to prevent grease blowback from the grease fitting.
Replace Tip Seal 1. Remove intake hose 2. Remove the discharge hose. Figure 12
NOTE: In order to distinguish between the tip seal for Fixed Scroll and the tip seal for Orbit Scroll place the tip seal as shown below then view from the arrow direction and refer to the figures on the right. Fixed Scroll
Lip
Orbit Scroll
(Inside) Lip (Bottom Side)
Facing Left
Figure 13
17
Facing Right
Scroll Enclosure Air Compressors
Scheduled Maintenance (Continued)
4. Insert new backup tube in the FS Scroll in the 6 o’ clock position (See Figure 15). 5. Insert new dust seal on the backup tube. 6. After replacing tip seal set, reassemble Fixed Scroll set to the Orbit Scroll. Tighten nuts and bolts temporarily and confirm if pump pulley rotates smoothly by hand and tighten them firmly. Tightening torques are:
Insert tip seal so that the lip of tip seal is on the bottom of seal groove and inner side of involute and the direction of lip faces the center of involute (curving spiral). See Figure 13. This is to be done for both FS and OS sets. Use caution not to tear or distort lip.
Bolt Torque
1. Insert new HP tip seal from the center section for OS or Orbit Scroll so that there will be no clearance at the tip (start) section (See Figure 11 and 13). 2. Insert so that new LP tip seal will contact closely with HP tip seal inside Scroll Groove.
First
Second
17 in lb.
265 in lb.
Chart 21
NOTE: Assemble so that dust seal and tip seal will not drop between Orbit Scroll set and Fixed Scroll set.
Insert approxi-mately half of the LP tip seal and remove the tip seal to confirm that a notch in the tip seal has been created. This will prevent movement during installation (See Figure 14).
Dust Seal Machined to avoid movement during installation
Figure 14
3. Repeat the same procedure for FS or Fixed Scroll tip seal set, remove both the dust seal and backup tube located on outermost side FS set.
Model
Size
Torque
Pulley bolt
M8
175
Housing Nut (See Figure 1)
M10
265
Back-up Tube
Chart 20 - Bolt Torque (In. - lbs.)
Figure 15
18
A1
A2
A2
DB
MB1
(-)
CN1
CN27
CN13
RST
RSR
(+)
(-)
(+)
CN30
CN26
5/L3
96
CB2
CN28
CN29
CN5
EXB
5/L3
TB1
1234
OCR
TRANS1
CN1 CN12
DB
MB1
(-)
CN1
CN27
CN13
RST
RSR
(+)
(-)
(+)
CN30
CN26
B G RWY
CB2
CN28
MOTOR
CN29
MC
OCR
EXB
1234
A1 TB1
3/L2
5/L3
MOTOR
A2
A1
TRANS1
OCR
MC
3/L2
CN1 CN12
MB2
DB
MOTOR
MC
96
A1 CN10 CN11
96
5/L3
HX
(-)
(-)
(+)
RSR
CN27
CN13
(+)
RST
CN30
CN26
B G RWY
HX
OCR
CN12
Figure 16
CN11
14
1/L1
B G RWY
3/L2
MOTOR
1/L1
14
TRANS1
3/L2
CN1 CN12
CN10
A1 CN4
14 13 CN3
13
1/L1
1A
FF
CN2
96
98 97
CN20 CN21
3/L2
MOTOR
CN6
95
CN22
TH3 TH2 TH1
CN23
A1
CN25
PS
CN24
13
CN31
MOTOR
CN7
95
CN26
95
98 97
A2
OCR
CN20 CN21
OCR
CN22
MC
CN25
98 97
CN27
CN32
1A FF CN2
TH3 TH2 TH1 CN23
A2
PS CN24
14 13 1/L1
MC
CN7
MC
CN31
96 CN6
A2 CN4
95
98 97 CN5
FAN
CN3
14 13 1/L1
14 1/L1
FAN
CN20 CN21
95
98 97
96 98 97 CN22
FUSE
CN25
95 CN23
FAN
CN24
FAN
CN10
5/L3 CN26
5/L3 CN11
3/L2 CN27 CN32
CN29
CB1
CN28
TRANS2
EXB
TB1
1234
external input and output
CN26
13 1A FF CN2
CN27 CN32
FUSE
CN4
HX
CN6
HX
CN31
TRANS 3
NF
TRANS 3 Ground
NF
208 230 460 200 0
Ground
CN5
L1 L2 L3
CN7
19 CN3
208 230 460 200 0
Electrical Diagram - SEH3007B & SEH3007BHP (30HP)
6
Motor Ventilation Van Noise Filter
MOTOR
FAN NF
3 1 1
Main Circuit Board 1 Main Circuit Board 2 Display Board Expansion Circuit Board Communication Board 1 Communication Board 2 Transformer 1 Transformer 2 Control Transformer
MB1 MB2 DB EXB CB1 CB2 TRANS1 TRANS2 TRANS3
1
3
3
1
2
FU 1&2 FNQR 6A
6A
4A
Fuse 208 230 460 Type Volt Volt Volt
CONTROL CIRCUIT PROTECTION 400VA
Fuse Table
2
Temperature Sensor
TH
6
Pressure Transducer
PS
2
2
4
6
Thermal Overload
6
Q'ty
OCR
Part Name Motor Starter
MC
Scroll Enclosure Air Compressors
A1
DB
MB1
CN30
A1
(-)
(+)
(-)
CN1
RST
RSR
CN27
CN13
CN25
(+)
CN26
5/L3
96
CB2
CN28
CN29
CN5
A1 CN4
EXB
3/L2
5/L3
96 TB1
1234
MOTOR
OCR
A2
A2
3/L2
A1
14
TRANS1
96 CN1 CN12
MOTOR
OCR
DB
MB1 CN30
(-)
RST
CN1
CN27
CN13
(+) RSR (-)
(+)
CN26
B G R WY
CB2
CN28
MOTOR
CN29
MC
OCR
EXB
3/L2
1234
A1 TB1
5/L3
MOTOR
MC A1
TRANS1
OCR
3/L2
CN1 CN12
MOTOR
MC
DB
MB2
OCR
(-)
CN26
(-)
RSR
CN27
14 (+)
B G R WY
CN13
(+)
RST
CN30
CN12
5/L3
14
13
Figure 17
TRANS1
CN10
1/L1
A2
CN22
14 13 CN3
14
1/L1
B G R WY CN6
96
98
CN11
3/L2
CN1 CN12
CN20 CN21
3/L2
MOTOR
CN7
95
97
TH4 TH3 TH2 TH1
CN23
MOTOR
PS
CN24
1/L1
1A
F F
CN2
CN26
95
98 97
A2
OCR
CN10
13
CN31
OCR
CN11
13 1/L1
MC
CN20 CN21
95
98 97
CN27
CN32
A2 CN25
14 13 1/L1
MC
CN22
98 97
95
TH4 TH3 TH2 TH1 CN23
5/L3 1A F F CN2
PS CN24
5/L3 CN26
A2
MC
CN7
A2 CN4
96 98 CN6
95 97 CN5
14 13 1/L1
FAN
CN3
95
96 98 97
MC
CN31
3/L2 CN27 CN32
FAN
CN11
14 1A CN2
5/L3 CN10
96 CN20 CN21
FAN
CN23
FAN
CN25
95
98 97 CN22
13 1/L1 F F
5/L3
A1
CN29
CB1
CN28
HX
HX
OCR
FUSE
FUSE
MC
HX
EXB
TRANS2
TB1
1234
NF
TRANS 3 Ground
NF
208 230 460 200 0
external input and output
MOTOR
CN27 CN32
A2 CN24
96 CN26
3/L2
HX
CN4
13 1/L1
L1 L2 L3
CN6
Ground
CN5
A1 CN31
95
98 97 CN7
20 CN3
208 230 460 200 0
Electrical Diagram - SEO4007B & SEO4007BHP (40HP)
3 1 2
Communication Board 1 Communication Board 2 Transformer 1 Transformer 2 Control Transformer
CB1 CB2 TRANS1 TRANS2 TRANS3
1
3
FU 1&2 FNQR 6A
6A
4A
Fuse 208 230 460 Type Volt Volt Volt
CONTROL CIRCUIT PROTECTION 400VA
Fuse Table
2
Expansion Circuit Board
EXB
3 Display Board
1
2
8
DB
Main Circuit Board 1
MB1
2
Main Circuit Board 2
Temperature Sensor
TH
2
MB2
Pressure Sensor
PS
4
Ventilation Van
FAN
Noise Filter
8
Motor
MOTOR
NF
8
Thermal Overload
8
Q'ty
OCR
Part Name Motor Starter
MC
Scroll Enclosure Air Compressors
TRANS 3
21
15
5 2
Figure 19 - SEH3007B, SEH3007BHP
8
7.1 7.2 7.3
14.1 14.2
17
4.2*, 4.3* 4.4*, 4.5* 4.6*, 4.7*
12
13
4.1*, 4.3* 4.4*, 4.5* 4.8* 3 1
11
*See Electrical Diagram
9
16
10
Scroll Enclosure Air Compressors
22
15
5 2
Figure 20 - SEO4007B, SEO4007BHP
8
7.1 7.2 7.3
14.1 14.2
17
4.2*, 4.3* 4.4*, 4.5* 4.6*, 4.7*
12
13
4.1*, 4.3* 4.4*, 4.5* 4.8* 3 1
11
*See Electrical Diagram
9
16
10
Scroll Enclosure Air Compressors
Scroll Enclosure Air Compressors
Replacement Parts List Ref. No.
Description
30 HP SEH3007B
SEH3007BHP
SEO4007B
40 HP SEO4007BHP
1
Air end
SL016502AJ
SL016511AJ
SL016502AJ
SL016511AJ
6, 8
2
Motor
MC022397AV
MC022397AV
MC022397AV
MC022397AV
6, 8
3
Motor pulley
PU009792AV
PU009792AV
PU009792AV
PU009792AV
6, 8
4.1
Main circuit board SET 1 (Unit Control Panel)
92825080
*
92830050
*
2
4.2
Main circuit board SET 2 (Main Control Panel)
92826080
*
92832060
*
1
4.3
Display circuit board
92598010
92598010
92598010
92598010
3
4.4
Expansion circuit board
92501101
92501101
92501101
92501101
3
4.5
Transformer for main circuit board
92599010
92599010
92599010
92599010
3
4.6
Transformer for communication board
90753560
90753560
90753560
90753560
1
4.7
Communication board 1
90753570
90753570
90753570
90753570
1
4.8
Communication board 2
90753580
90753580
90753580
90753580
2
5
V-belt
BT012000AV
BT012000AV
BT012000AV
BT012000AV
12, 16
6
Intake filter element
ST073907AV
ST073907AV
ST073907AV
ST073907AV
2
7.1
Intake hose 1 (55.1 in. length)
92803070
92803070
92803070
92803070
1
7.2
Intake hose 2 (43.3 in. length)
92804070
92804070
92804070
92804070
3, 4
7.3
Intake hose 3 (31.5 in. length)
92805070
92805070
92805070
92805070
2, 3
8
Temperature sensor
02801001
02801001
02801001
02801001
6, 8
9
Pressure transducer
97992133
97992133
97992133
97992133
2
10
Check valve
CV-156
CV-156
CV-156
CV-156
11
Safety valve
SVB-11-88
V-215404AV
SVB-11-88
V-215404AV
1
12
Noise filter
07992186
07992186
07992186
07992186
2
13
Magnetic contactor (for 208, 230V)
97005360
97005360
97005360
97005360
6, 8
Magnetic contactor (for 460V)
92705050
92705050
92705050
92705050
6, 8
14.1
Terminal
97481110
97481110
97481110
97481110
1
14.2
Terminal
97481150
97481150
97481150
97481150
1
15
O-ring
IP603200AV
IP603200AV
IP603200AV
IP603200AV
16
Exhaust fan set
97450022
97450022
97450022
97450022
4
17
Control transformer
933445
933445
933445
933445
2
* Consult Authorized Service Center
23
Qty.
6, 8
6, 8
Scroll Enclosure Air Compressors
6
4
3
1
11
2
7 9 12 5
10 Figure 21
24
8
Scroll Enclosure Air Compressors
Service Parts List Ref. No.
Description
SLAE05E
SLAE05EHP
1
Air end Pulley
02549110
02549110
1
2
Key
IP600600AV
IP600600AV
1
3
Centrifugal Fan
IP601300AV
IP601300AV
1
4
Fan Duct (1)
IP601400AV
IP601400AV
1
5
Fan Duct (2)
02519042
02519042
1
6
Fan Cover
IP601700AV
IP601700AV
1
7
Fan Dust Gasket (1)
IP601900AV
IP601900AV
1
8
Heat Insulation Pipe
IP602000AV
IP602000AV
1
9
Fan Duct Gasket (2)
IP602400AV
IP602400AV
1
10
Long Nipple
96647011
96647011
1
11
Dust Cap
IP603500AV
IP603500AV
1
12
Tip Seal Set
92832070
92832080
1
*
Grease Gun Kit
IP616201AJ
IP616201AJ
*
Grease Gun
IP616101AJ
IP616101AJ
*
Grease
IP600000AV
IP600000AV
* Not Shown
25
Qty.
Scroll Enclosure Air Compressors
Notes
26
Scroll Enclosure Air Compressors
Maintenance / Service Record Date
Maintenance Performed
Replacement Components Required
27
Scroll Enclosure Air Compressors
Powerex Limited Warranty Powerex 3 Year / 10,000 Hour Extended Parts Limited Warranty - Powerex warrants each Compressor Pump or Scroll Air-End against defects in material or workmanship from the date of purchase for a period of Three years or 10,000 hours, whichever may occur first. This warranty applies to the exchange of part(s) of the compressor pump or air-end found to be defective by an Authorized Powerex Service Center. Powerex 1 Year / 5,000 Hour Inlet to Outlet Limited Warranty - Powerex warrants each Compressor Unit, System, Pump, or Air-End against defects in material or workmanship from the date of purchase for a period of One Year or 5,000 Hours, whichever may occur first. This warranty applies to the exchange of defective component part(s) and labor performed by an Authorized Powerex Service Center. Coverage. The above mentioned warranty applies to Powerex manufactured units or systems only. Items listed in the operator’s manual under routine maintenance are not covered by this or any other warranty. Failure to complete maintenance as stated in the maintenance schedule will void this warranty. There is no other express warranty. Implied warranties, including those of merchantability and fitness for a particular purpose, are limited to one year from the date of purchase: and to the extent permitted by law, any and all implied warranties are excluded. This is the exclusive remedy and liability for consequential damages under any and all warranties is excluded to the extent exclusion is permitted by law. Limitation of Liability. To the extent allowable under applicable law, Powerex’s liability for consequential and incidental damages is expressly disclaimed. Powerex’s liability in all events is limited to, and shall not exceed, the purchase price paid. Warranty Disclaimer. Powerex has made a diligent effort to illustrate and describe the products in this literature accurately; however, such illustrations and descriptions are for the sole purpose of identification, and do not express or imply a warranty that the products are merchantable, or fit for a particular purpose, or that the products will necessarily conform to the illustrations or descriptions. Product Suitability. Many jurisdictions have codes and regulations governing sales, construction, installation, and/or use of products for certain purposes, which may vary from those in neighboring areas. While Powerex attempts to assure that its products comply with such codes, it cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, please review the product applications, and national and local codes and regulations, and be sure that the product, installation, and use will comply with them. Claims. Claims pertaining to the merchandise in this schedule, with the exception of warranty claims, must be filed with Powerex within 6 months of the invoice date, or they will not be honored. Prices, discounts and terms are subject to change without notice or as stipulated in specific product quotations. All agreements are contingent upon strikes, accidents, or other causes beyond our control. All shipments are carefully inspected and counted before leaving the factory. Please inspect carefully any receipt of merchandise noting any discrepancy or damage on the carrier’s freight bill at the time of delivery. Discrepancies or damage which obviously occurred in transit are the carrier’s responsibility and related claims should be made promptly directly to the carrier. Returned merchandise will not be accepted without prior written authorization by Powerex and deductions from invoices for shortage or damage claims will not be allowed. Unless otherwise agreed to in writing, these terms and conditions will control in any transaction with Powerex any different or conflicting terms as may appear on any order form now or later submitted by the buyer. All orders are subject to acceptance by Powerex.
Powerex • 150 Production Drive • Harrison, OH 45030 • USA 1-888-769-7979 • www.powerexinc.com