Sealed lead-acid battery
EPL FTNG Series
Model: EPL 155 - 12 FTNG
EPL-FTNG series are batteries with over 12 years of the design life at 20°C - according to Eurobat (10 years at 25°C), made in the gel technology. They have front terminals and a special case construction that allows them to be mounted in 19” and 23” cabinets. The EPL FTNG series is equipped with a Central Degassing System, consisting of a small conduit which can lead the small amount of gas liberated during operation outside the sealed cabinet in which the batteries are installed. EPL FTNG batteries have repeatable parameters and excellent discharge characteristics and this is why they are very often and readily used for the standby use in important telecommunication systems. Owing to the gel technology they are very often used for outdoor systems prone to large operating temperature changes.
TECHNICAL DATA
APPLICATIONS
after 1 month after 6 months after 12 months standard Container material optional Terminal insert terminal Terminal hardware initial torque
Capacity retention o during storage @ 20 C (self discharge)
*) - According to Eurobat (Very Long Life group)
uninterruptible power supplies (UPS) emergency lighting systems telecommunication power plants
telecommunication PABX GSM base stations server rooms
DIMENSIONS mm(inch)
558(21.969)
125(4.921)
98 % 86 % 73 % ABS UL 94-HB ABS UL 94-V0** I2 5,5 Nm
TERMINALS M6
I2
2.0(0.79)
12 V 155 Ah / C10 6 GEL over 12 years @ 20oC* Design life 10 years @ 25oC height 270,0 mm length Dimensions 558,0 mm width 125,0 mm Weight ~52,5 kg 162,5 Ah 20h 8,26A @1,80V/cell. 155,0 Ah 10h 15,5A @1,80V/cell. Capacity o 140,0 Ah 5h 28,0A @1,75V/cell. @ 25 C 96,8 Ah 1h 96,8A @1,60V/cell. charge Ambient nominal 0oC ~ 40oC temperature discharge -40oC ~ 50oC range storage -20oC ~ 40oC Internal resistance @ fully charge battery £4,30 mW 13,5V do 13,8V standby use Charging voltage (-18 mV/oC) o @ 20 C 14,4 V do 15,0V cycle use (-24 mV/oC) recommended 15,50 A Charging current maximum 38,45 A
270(10.620)
Nominal voltage Nominal capacity Cell per unit Technology
**) - Flame-retardant
NO TRANSPORT RESTRICTED Not restricted for air, surface and water transport. Classified as nonhazardous material (IATA/ICAO Special Provision A67, DOT-CFR Title 49 parts 171-189, IMDG amendment 27) [Bolt M6]
DISCHARGE CHARACTERISTICS o
o
• Constant current (Current [A], 25[ C] / 77[ F]) F.V. V/cell
5 min
15 min
30 min
45 min
1h
3h
5h
6h
8h
1,85 1,80 1,75 1,70 1,67 1,60
346,6 388,7 433,6 471,5 475,7 506,6
207,7 233,0 249,8 258,2 262,4 272,2
138,4 151,6 158,6 160,0 162,8 165,6
104,3 112,3 117,0 117,9 118,7 119,7
85,0 91,7 94,1 95,5 96,2 96,8
36,4 38,6 38,9 39,3 39,6 40,3
25,9 27,4 28,0 28,2 28,7 28,8
22,5 23,9 24,3 24,5 24,8 25,0
17,6 18,7 18,8 19,0 19,0 19,1
o
o
• Constant power (Power [W/cell], 25[ C] / 77[ F]) F.V. V/cell
5 min
15 min
30 min
45 min
1h
3h
5h
6h
8h
1,85 1,80 1,75 1,70 1,67 1,60
619,5 693,7 755,4 810,1 814,3 846,5
389,6 435,9 461,1 463,9 469,5 477,9
263,5 287,3 294,3 295,7 295,7 298,5
201,8 217,2 221,4 222,8 222,8 224,2
164,9 177,5 179,0 181,8 181,8 183,2
71,0 74,8 75,0 75,8 75,8 76,8
51,7 54,1 55,0 55,0 55,8 55,8
44,8 47,1 47,6 47,8 48,1 48,4
35,2 36,6 36,8 37,1 37,4 37,6
Discharge time 10h 20h 14,7 15,5 15,6 15,7 15,7 15,9
8,08 8,26 8,35 8,36 8,38 8,46
Discharge time 10h 20h 29,5 30,6 30,6 30,6 30,9 31,2
16,4 16,7 16,7 16,7 16,7 16,9
F.V. - Final voltage
EPL FTNG
EPL 155 - 12 FTNG Battery life characteristics of standby use
Battery life characteristics of cycle use
14 Temperature: 25[oC] / 77[oF]
12 Charging voltage 2.275 V/cell 10
Retention Capacity [%]
Life expantancy [year]
8 6 4
100[%] Depth of discharge
50[%] D.O.D
30[%] D.O.D
2
0 20 68
30 86
40 104
[oC] [oF]
50 122
0
300
600
900
1200
1500
Number of cycles
Battery Temperature
Battery discharge characteristics
Battery self discharge characteristics 100
13.0
Temperature: 25[oC] / 77[oF]
11.0
Capacity Retention Ratio [%]
Terminal Voltage [V]
12.0
0.05C[A] 0.01C[A] 0.25C[A]
10.0 0.6C[A] 1C[A]
9.0
8.0
80
o
10[ C]/50[oF] 60
o
o
o
20[oC]/68[oF]
30[ C]/86[ F]
o
40[ C]/104[ F] 40
7.0 1
2
3
5
10
20 30
60
2
3
[min]
5
10
20 30
0
3
6
9
12
15
18
21
24
27
30
Storage time [months]
[hr] Discharge time
Battery charging characteristics for the standby use
15.0
0.42
140
15.0
0.42
Battery charging characteristics for the cycle use 140 Charge voltage
14.0
0.36
120
Charge voltage
120
0.12
100 80
12.0 Discharge 100% (0.05C[A] x 20[h]) 50% (0.05C[A] x 10[h]) Charging constant voltage: 2.275[V/cell] constant current: 0.1C[A] o o Temperature: 20[ C](68[ F])
11.0 10.0
60
0.06
0.24 0.18
40
0.12
20
0.06
100
12.0
80 Discharge 100% (0.05C[A] x 20[h]) 50% (0.05C[A] x 10[h]) Charging constant voltage: 2.45[V/cell] constant current: 0.1C[A] Temperature: 20[oC](68[oF])
11.0 10.0
0 0
2
4
6 Charge time [hr]
8
10
60 40 20 Charge current
Charge current
0
lume
13.0
0.30
Charge voltage [V]
0.18
lume
Charge current [CxA]
0.24
Charge vo
Charge volume [%]
13.0
0.30
Charge voltage [V]
Charge current [CxA]
Charge vo
Charge volume [%]
14.0
0.36
0 12
0
0 0
2
4
6
8
10
12
0
Charge time [hr]
Battery discharge current and final discharge voltage Discharge current [A] Final discharge voltage [V/cell]
0.2C > I 0.2C £ I < 0.5C 0.5C £ I < 1.0C 1.0C £ I 1.75
1.70
1.55
1.30
Pb
*) C - Capacity Date of issue: 18.11.2014; change number: 2; date of change: 02.06.2016