Transcript
Sealed lead-acid battery
UPS Series
Model: UPS 12 - 55
UPS type batteries are made in AGM technology and are constructed by plates, separators, safety valves and a container. Since the electrolyte is held by a glass-mat separator and plates, the batteries can be used in any chosen position without the risk of leakage. UPS type batteries have a pressure relief valves that allows safe dispersal of any excess pressure inside the cell (VRLA). UPS type batteries have been designed for standby use in uninterruptible power supplies (UPS). These batteries are the replacement for DYNASTY batteries (C&D Technologies former Johnson Controls). They have the same dimensions but a larger capacity and better constant power and constant current discharge characteristics.
TECHNICAL DATA
APPLICATIONS solar powered systems mobile and portable equipment – cycle use marine wheelchairs golf-carts
18±1 (0.71±0.04)
DIMENSIONS
228±2 (8.98±0.08) 139±2 (5.47±0.08)
182±2 (7.17±0.08)
215±2 (8.47±0.08)
uninterruptible power supplies (UPS) emergency lighting systems telecommunication PABX power station fire and security systems cable TV
133±2 (5.24±0.08)
227±2 (8.94±0.08)
TERMINALS I2
M6
**) - Flame-retardant
2(0.079)
*) - According to Eurobat (Long Life group)
200±2 (7.88±0.08)
12 V 53 Ah / C10 6 AGM o 10~12 years @ 20 C* Design life o 8 years @ 25 C height 215,0 mm length Dimensions 228,0 mm width 139,0 mm Weight ~17,8 kg 53,0 Ah 10h 5,3A @1,75V/cell 50,5 Ah 5h 10,1A @1,75V/cell Capacity o 37,0 Ah 1h 37,0A @1,75V/cell @ 25 C 33,5 Ah 0,5h 67,0A @1,60V/cell o o charge Ambient nominal 0 C ~ 40 C o o temperature discharge -20 C ~ 50 C range o o storage -20 C ~ 40 C Internal resistance @ fully charge battery £5 mW 13,5V to 13,8V standby use o (-18 mV/ C) Charging voltage o @ 20 C 14,4 V to 15,0V cycle use o (-24 mV/ C) recommended 5,5 A Charging current maximum 16,5 A Maximum discharge current (for 5 sec) 550 A after 1 month Capacity retention 97 % o after 6 months 80 % during storage @ 20 C after 12 months 63 % (self discharge) standard ABS UL 94-HB Container material optional ABS UL 94-V0** Terminal insert terminal I2 Terminal hardware initial torque 5,5 Nm Nominal voltage Nominal capacity Cell per unit Technology
NO TRANSPORT RESTRICTED Not restricted for air, surface and water transport. Classified as nonhazardous material (IATA/ICAO Special Provision A67, DOT-CFR Title 49 parts 171-189, IMDG amendment 27)
DISCHARGE CHARACTERISTICS o
o
• Constant current (Current [A], 25[ C] / 77[ F]) F.V. V/cell
1,80 1,75 1,70 1,65 1,60
5 min 176,0 193,0 206,0 215,0 222,0
10 min 123,0 132,0 138,0 142,0 145,0
15 min 101,0 106,0 110,0 113,0 115,0 o
30 min 62,00 64,00 65,00 66,00 67,00
50 min 42,00 43,00 43,00 44,00 44,00
1hr 36,40 37,00 37,40 37,70 38,00
2hr 20,70 21,00 21,20 21,40 21,50
4hr 10,96 11,15 11,24 11,30 11,33
6hr 8,10 8,22 8,27 8,29 8,30
Discharge time 8hr 10hr 6,32 5,20 6,41 5,30 6,45 5,30 6,46 5,30 6,47 5,30
50 min 83,33 85,00 86,00 86,80 87,60
1hr 72,17 73,33 74,10 74,80 75,50
2hr 41,40 42,00 42,40 42,80 43,00
4hr 21,92 22,30 22,49 22,60 22,69
6hr 16,20 16,44 16,53 16,58 16,61
Discharge time 8hr 10hr 12,64 10,40 12,82 10,60 12,90 10,60 12,93 10,60 12,94 10,60
o
• Constant power (Power [W/cell], 25[ C] / 77[ F]) F.V. V/cell
1,80 1,75 1,70 1,65 1,60
5 min 317,5 355,8 379,5 395,0 406,6
10 min 233,3 250,2 260,5 268,6 274,0
15 min 193,8 205,0 211,6 216,6 220,0
30 min 123,3 126,5 128,5 130,0 131,1
F.V. - Final voltage
www.europower.eu
UPS
UPS 12-55 Battery life characteristics of standby use
Battery life characteristics of cycle use
14 Temperature: o o 25[ C] / 77[ F]
12 Charging voltage: 2.275 V/cell
120
10 100
Retention Capacity [%]
Life Expectancy [year]
8 6
4
2
80
60 80[%] 100[%] Depth of discharge D.O.D
50[%] D.O.D
30[%] D.O.D
40
20 0 20 68
30 86
40 104
0
o
50 122
[ C] o [ F]
0
300
600
900
1200
1500
Numbers of cycles
Battery Temperature
Battery discharge characteristics
Battery self discharge characteristics 100
13.0
Temperature: o o 25[ C] / 77[ F]
Capacity Retention Ratio [%]
Terminal Voltage [V]
12.0
11.0 10[A]
10.0
5,3[A]
15[A] 21[A] 38[A]
9.0
8.0 222[A] 145[A] 185[A] 115[A]
7.0 1
2
3
5
10
o
o
5[ C]/41[ F]
60
40[oC]/104[oF]
30[oC]/86[oF]
20[oC]/68[oF]
40
53[A]
20 30
80
60
2
3
5
[min]
10
20 30
0
2
4
6
8
10
12
14
16
18
20
Storage time [months]
[hr] Discharge time
0.15
0.12
0.09
0.06
Charge voltage
Charge vo
13.0
lume
12.0
15.0
120
0.18
14.0
100
11.0
10.0
60
40
0.03
20
0.12
0.09
0.06
100
12.0
80 Discharge 100% (0.05C[A] x 20[h]) 50% (0.05C[A] x 10[h]) Charging constant voltage: 2.45[V/cell] constant current: 0.1C[A] Temperature: 20[oC](68[oF])
11.0
10.0
0 0
10
15 20 Charge time [hr]
40
20 Charge current
0 5
60
0.03
Charge current
0
lume
13.0
0.15
140
120 Charge vo
80 Discharge 100% (0.05C[A] x 20[h]) 50% (0.05C[A] x 10[h]) Charging constant voltage: 2.275[V/cell] constant current: 0.1C[A] Temperature: 20[oC](68[oF])
Charge voltage
Charge volume [%]
14.0
0.21
Charge voltage [V]
0.18
140
Charge current [CxA]
15.0
Battery charging characteristics for the cycle use
Charge volume [%]
0.21
Charge voltage [V]
Charge current [CxA]
Battery charging characteristics for the standby use
0
25
0 0
0 5
10
15 20 Charge time [hr]
25
Battery discharge current and final discharge voltage Discharge current [A] Final discharge voltage [V/cell]
11 > I
11 £ I < 27.5
27.5 £ I < 55
55 £ I
1.75
1.70
1.55
1.30
Pb
*) C - Capacity Date of issue: 30.10.2006; change number: 3; date of change: 24.09.2014
www.europower.eu
UPS