EURO BAT - EURO DOUBLE AUTOMATION The EURO BAT - EURO DOUBLE automation system for swing gates comprises an electromechanical operator which drives the gate leaves by means of a worm screw. The EURO BAT operator is irreversible and locks mechanically when the motor is not in use. Therefore a lock does not need to be fitted. The EURO DOUBLE operator is reversible, so a lock must be fitted.
INSTALLATION DIMENSIONS
Drawing A
B
1. DESCRIPTION AND TECHNICAL SPECIFICATIONS D
45 min.
Z
A
4
Fig. 1
3
L
5
2
Table 1:
6
1) 2) 3) 4) 5) 6)
1
Motor Unit Power cable Worm screw Front bracket Rear bracket Cable cover
Fig. A Table A: Recommended dimensions (in mm)
300
Operator technical specifications
Model Power supply Absorbed power Current drawn Electric motor rpm Thermal cutout Capacitor Max. thrust/traction force Rod stroke
140°C 140°C 8µF/400V 8µF/400V 350 daN 300 daN 250 daN 300 mm / 400 mm
Housing protection Duty cycle (cycles/hour) Maximum leaf length
400
DOUBLE
BAT 230V~-50Hz 24Vdc 280W 70W 1.2A 3A 1400
230V~-50Hz 280W 1.2A
20
IP 44 50 3m/4m
A
B
C (¹)
D (²)
Z (³)
L
90°
145
145
290
100
45
895
110° 90° 110°
125 195 165
125 195 165
290 390 390
80 150 120
45 45 45
895 1090 1090
(¹) useful rod stroke
(²) max. dimension (³) min. dimension
CALCULATING INSTALLATION DIMENSIONS: GENERAL RULES
900
If the dimensions specified in Table A cannot be used, calculate different dimensions as follows: -
1.6 cm/sec -20°C +55°C 6.5 kg
Rod speed Temperature range Operator weight
α
Model
20
-
2. STANDARD INSTALLATION LAYOUT
m 0m 10
300 mm
Fig. 2
For 90° leaf opening: a + b = c For leaf opening over 90°: a + b < c The lower the dimensions of a and b the higher the gate speed. Ensure that current standards are observed. Make sure that the difference between a and b is no more than 4 cm: larger differences cause large variations in speed during opening and closing. Due to the dimensions of the operator, the minimum value for Z is 45 mm (fig. A) If the dimensions of the gate post or the position of the hinge do not allow a to be kept within the required value, make a recess in the gate post as shown in fig. B.
1) 2) 3) 4) 5) 6)
Operators Photocells Control unit Keyswitch Receiver Flashing light
15 0m m
Notes:1) Use suitable rigid/flexible pipes for laying power cables. 2) Always keep low voltage accessory cables separate from 230V~ power cables. To avoid interference, use separate sheaths.
Fig. B
4
ENGLISH 3. INSTALLATION OF THE AUTOMATION SYSTEM 3.1. PRELIMINARY CHECKS To ensure trouble-free operation, make sure that the gate (whether existing or to be installed) has the following specifications: max. length of each gate leaf: 3 metres (with operator with 300 mm stroke); maximum length of each gate leaf: 4 metres (with operator with 400 mm stroke); strong and rigid leaf frame smooth movement of leaves during entire travel; no stiff points hinges in good condition mechanical travel limit stops present electric lock present in reversible version. If any welding or brazing has to be done on the gate, this must be done before installing the automation system. Good condition of the structure is essential for reliability and safety of the automation system.
Fig. 4
3.2. INSTALLATION OF THE OPERATORS Fix the rear bracket to the gate post according to the instructions in Table A. Adjust the length of the bracket if necessary. Warning: Observe the specified dimensions to ensure correct operator operation. In the case of iron gate posts, weld the bracket directly onto the gate post. In the case of brick/concrete gate posts, flush-mount a wall plate (fig. 3), and weld the bracket to the plate. 2) Fix the operator to the rear bracket by means of the screws supplied (fig. 3). Caution: the operators supplied in the kit are right and left hand versions. For correct installation the operator must be positioned as shown in fig. 3. The right hand operator is the one mounted on the right leaf as viewed from inside; the left hand operator is the one mounted on the left leaf, again as viewed from inside. 1)
Fig. 5 7) 8)
Fit the front bracket onto the rod as shown in fig. 5. Close the gate leaf and, keeping the operator perfectly horizontal, locate the leaf attachment position on the front bracket (fig. 6).
Fig. 6
9)
Fix the front bracket temporarily to the leaf by two welds. N.B.: If the gate frame does not allow for secure fixing of the bracket, add a support plate. 10) Release the operator (irreversible version) and ensure that the gate opens smoothly with no stiff points and that it stops on the mechanical travel stops. 11) Completely weld the front bracket to the leaf. When doing this, detach the operator temporarily from the bracket to prevent damage from welding scale. N.B.: 1) Grease all pivots on brackets 2) If welding is not possible, the front and rear bracket plates can be fixed using screws and screw anchors.
Fig. 3 3) 4) 5) 6)
Release the operator (see paragraph 6). Extend the rod to the end of its stroke (fig. 4). Lock the operator (see paragraph 7). N.B.: The release and locking operations, points 3) and 5), must be performed solely for the irreversible version. Rotate the operator rod two full turns clockwise (fig. 4).
5
ENGLISH 12) Repeat the above operations to install the second operator, if required. 13) Install the control unit box according to the dimensions given in the relevant instructions.
8. SPECIAL APPLICATIONS
4. STARTING THE AUTOMATED UNIT
Carry out periodic checks of the gate structure and ensure in particular that the hinges are in perfect working condition. Check periodically that the electronic anti-crushing system is adjusted correctly and that the release mechanism for manual movement is fully operative (see relevant paragraph). Safety devices installed on the system must be checked every six months.
1) 2)
There are no special applications.
9. MAINTENANCE
Program the control unit according to your requirements as described in the relevant instructions. Power up the system and check the state of the LEDs according to the table in the control unit instructions.
5. TESTING THE AUTOMATED UNIT Carefully check operation of the operator and all accessories connected to it. Give the customer the page entitled "End-User Guide". Describe how the operator works and explain how it is to be used correctly. Inform the customer of the potential hazard areas of the automation.
10.REPAIRS For repairs, contact authorised service centres.
6. MANUAL OPERATION In the irreversible version, the gate can be operated manually in the event of a power failure or malfunction by removing the plug and inserting the special release key as shown in fig. 7. To release the operator, turn the key in the leaf closing direction (fig. 7). Open or close the leaves manually. In the reversible version, simply release the lock then operate the gate manually.
7. RETURNING TO NORMAL OPERATION Turn off the electricity supply to the system before re-locking the operators to avoid all risk of starting them accidentally. To re-lock the operator, turn the key in the leaf opening direction (fig. 7).
BLOCCA
SBLOCCA
SBLOCCA
BLOCCA
LOCK
UNLOCK
UNLOCK
DEBLOQUE
LOCK
BLOQUE
DEBLOQUE
BLOQUE
VERRIEGELT BLOQUEAR
ENTRIEGELT DESBLOQUEAR
ENTRIEGELT DESBLOQUEAR
VERRIEGELT BLOQUEAR
Fig. 7
6
LAMPEGGIANTE 230V/24V FLASHER 230V/24V LAMPE CLIGNOTANTE 230V/24V DESTELLADOR 230V/24V
BLINK
BLINKLAMPE 230V/24V INSTALLAZIONE
Nota bene: Lampeggiante 230V 50Hz con intermittenza Lampeggiante 24V senza intermittenza Si installa in ambienti esterni od interni utilizzando lapposito supporto in dotazione (Fig. 1 e 2). COLLEGAMENTI ELETTRICI I cavi A (Fig. 3) devono essere collegati alle apparecchiature elettroniche come da istruzioni relative. La sezione dei cavi non deve essere inferiore a 1,5 mm2. MANUTENZIONE Sostituire la lampadina (E27 - 230V/40W)(E14 - 24V/15W) come da Fig. 4.
INSTALLATION Fig. 1
Note: 230Vac 50Hz light with flasher unit. 24Vdc light without flasher unit. The lamp can be installed either indoors or outdoors by using the support supplied (Fig. 1 and 2). ELECTRICAL CONNECTIONS Cables A (Fig. 2) must be connected to the electronic control units as shown in according to relevant instructions. Connecting wires must have a cross section of at least 1,5 mm2. MAINTENANCE Change bulb (E27 - 230V/40W)(E14 - 24V/15W) as shown in Fig. 4.
INSTALLATION
Fig. 2
Nota bene: Feu clignotant 230Vca 50Hz. Fonctionnement par intermittence. Feu clignotant 24Vcc sans carte de fonctionnement par intermittence. Elle sinstalle à lextérieur ou à lintérieur au moyen du support fourni avec lappareil (Fig. 1 et 2). BRANCHEMENTS ELECTRIQUES Les câbles A (Fig. 3) doivent être reliés aux platines électroniques conformément aux indications des instructions spécifiques. La section des câbles ne doit pas être inférieure à 1,5 mm2. ENTRETIEN Remplacer lampoule (E27 - 230V/40W)(E14 - 24V/15W) comme indiqué dans Fig. 4.
INSTALACION A
Fig. 3
Nota bien: Destellador 230 V c.a. 50 Hz con intermitencia. Destellador 24 V c.c. sin tarjeta de intermitencia. Se instala en ambientes externos o internos utilizando el soporte que se suministra (Fig. 1 y 2). CONEXIONES ELECTRICAS Los cables A (Fig. 3) han de conectarse a los aparatos electrónicos tal como se desprende de correspondientes instrucciones. La seccion de los cables no tiene que ser inferior a 1,5 mm2 MANTENIMIENTO Sustitución de la bombilla (E27 - 230V/40W)(E14 - 24V/15W) como Fig. 4.
MONTAGE
Fig. 4
Anmerkung: 230Vac 50Hz Blinklampe mit Blinkkarte. 24Vdc Blinklampe ohne Blinkkarte. Wird im Außen-oder Innenbereich mit Hilfe der mitgelieferten Halterung montiert (Abb. 1 und 2). ELEKTROANSCHLUSS Die Kabel A (Abb. 3) sind gemäß den entsprechenden anleitungen an die Steuerungen anzuschließen. Der Kabelquerschnitt muß mindestens 1,5 mm2 betragen. INSTANDHALTUNG Zum Austausch der Glühlampe (E27 - 230V/40W)(E14 - 24V/15W) siehe Abb. 4.