Draw ing Guide
2 -3
Solution Isometric
4-6
Solution General Arrangement
7
Solution Anchoring Details
8-13
UPS Internal view s & Details
14-16 17-18
Description Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet Draw ing Guide Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet Solution Isometric Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet Solution General Arrangements Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet Solution Anchoring Details Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet UPS Internal view s & Details
Battery Cabinet Internal View s & Details Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet Battery Cabinet Internal View s System One Line Diagram
Galaxy VM 180 kVA 1 Module UPS w ith Classic Battery Cabinet System One Line Diagram
Floor Loading Data SKU # 0G-GVMPB160K180D (Power Cabinet) 0G-GVMI225KG (I/O Cabinet) GVMSB180KGS (UPS)
77.56x23.62x33.62 [1970x600x854]
Weight in lb [kg] 1032 [469]
77.56x11.81x33.62 [1970x300x854]
463 [210]
168 [820]
77.56x39.45x33.62 [1970x1002x854] 1495 [679]
163 [796]
Dimensions HxWxD in Inches [mm]
GVMCBC2WUE (Battery Cabinet A and B) 77.56x85.04x33.62 [1970x2160x854] 7997 [3635]
Floor Loading in lb/ft 2 [kg/m2] 188 [917]
404 [1971]
CENTER OF GRAVITY Center of Gravity in Inches [mm] X-Distance Y-Distance Z-Distance Power Cabinet 11.81 [300] 37.40 [950] 14.92 [379] I/O Cabinet 7.48 [190] 33.46 [850] 9.02 [229] Battery Cabinet A/B 17.71 [450] 39.37 [1000] 15.75 [400] Cabinet
ELECTRICAL DATA SHEET VIN/VOUT
480V/480V
UPS RATING AT 0.9 PF LAG.
180kVA
INPUT VOLTAGE
480VAC 3PH 60HZ, WIRING : 3 WIRE -3PH+G
BYPASS VOLTAGE
480VAC 3PH 60HZ, WIRING : 3 WIRE -3PH+G, 4WIRE- 3PH+N+G
UPS INPUT NOMINAL INPUT CURRENT
(A)
204
INPUT CURRENT LIMITATION (A)
278
MAXIMUM INPUT CURRENT (A)
278
UPS BYPASS INPUT CURRENT
(A)
217
OUTPUT VOLTAGE
480VAC 3PH 60HZ, WIRING : 3 WIRE -3PH+G, 4WIRE- 3PH+N+G
NOMINAL OUTPUT CURRENT (FULL LOAD) (A)
217
NOMINAL BATTERY VOLTAGE (VDC)
480
END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC)
384
BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A)
352
BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A)
440
THDI
< 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD
THDV
< 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD
MAXIMUM SHORT CIRCUIT WITHSTAND
65kA @ RECOMMENDED BREAKER SIZE
REQUIRED UPSTREAM INPUT BREAKERS 80% RATED/100%RATED
LJL36400U31X- 400A/ LJL36400CU31X-400A
REQUIRED UPSTREAM BYPASS BREAKERS 80% RATED/100%RATED
LJL36400U31X- 400A/JJL36225C-225A
RECOMMENDED INPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 2/0 AWG / (2) 1/0 AWG
RECOMMENDED BYPASS CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 2/0 AWG / 250 kcmil
RECOMMENDED OUTPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 2/0 AWG / 250 kcmil
RECOMMENDED BATTERY CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 4/0 AWG / (2) 4/0 AWG
HEAT DISSIPATION @100% LOAD (BTU/hr) [kW] NORMAL OPERATION / ECO MODE
(21160) [6.2] / (2930) [0.86]
Air flow @ 100% Load
3700m³@40°C, 3200m³@30°C, 2800m³@20°C
ELECTRICAL DATA SHEET VIN/VOUT
480V/480V
UPS RATING AT 0.9 PF LAG.
180kVA
INPUT VOLTAGE
480VAC 3PH 60HZ, WIRING : 3 WIRE -3PH+G, 4WIRE- 3PH+N+G
UPS INPUT NOMINAL INPUT CURRENT
(A)
204
INPUT CURRENT LIMITATION (A)
278
MAXIMUM INPUT CURRENT (A)
278
OUTPUT VOLTAGE
480VAC 3PH 60HZ, WIRING : 3 WIRE -3PH+G, 4WIRE- 3PH+N+G
NOMINAL OUTPUT CURRENT (FULL LOAD) (A)
217
NOMINAL BATTERY VOLTAGE (VDC)
480
END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC)
384
BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A)
352
BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A)
440
THDI
< 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD
THDV
< 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD
MAXIMUM SHORT CIRCUIT WITHSTAND
65kA @ RECOMMENDED BREAKER SIZE
REQUIRED UPSTREAM INPUT BREAKERS 80% RATED/100%RATED
LJL36400U31X- 400A/ LJL36400CU31X-400A
RECOMMENDED INPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 2/0 AWG / (2) 1/0 AWG
RECOMMENDED OUTPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 2/0 AWG / 250 kcmil
RECOMMENDED BATTERY CABLE SIZE 80% RATED/ 100% RATED BREAKERS
(2) 4/0 AWG / (2) 4/0 AWG
HEAT DISSIPATION @100% LOAD (BTU/hr) [kW] NORMAL OPERATION / ECO MODE
(21160) [6.2] / (2930) [0.86]
Air flow @ 100% Load
3700m³@40°C, 3200m³@30°C, 2800m³@20°C