SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 04 Airflow, m3/h
Total pressure rise, Pa
Fan
85 80 =1,25
4
SFPv
3
2 L w,tot 70dB
0,75 75
80
Total pressure loss, Pa
1
1,00
F7 F5
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018 (calculated for a unit with full face end connection panels). Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
04
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08
Max. airflow
m3/h 2160
m3/s 0,60
Correction factors, KOK , dB Sound path To the outlet duct
To the inlet duct*
To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13
-6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17
-6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28
-8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34
4
* The integral attenuation of filters is not included.
100
We reserve the right to alter specifications.
20160422
5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46
6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47
7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54
8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 04 Delivery and transport within the site
The SILVER C SD 04 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories.
Bottom beam/Base frame/Base
The design makes it necessary to mount the SILVER C SD 04 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory.
Power connection L
B E
12
16
A
C
E
16
D H
D SILVER
Ø
100
12
Ø
52* F
F
50
G
50
Base beams are optional. * The air handling unit can be supplied without end connection panels. Size
L
B
H
A
C
D
E
F
G
Ø
Weight, kg
04
1099
825
490
937
162
245
412,5
102
561
315
105-119
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 0.8 kW (0.41 kW)*, motor control system: 1 x 230 V, 50 Hz, rated 2.3 A *The motor control system limits the power of the take-off to the value specified.
20160422
We reserve the right to alter specifications.
101
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 05 Airflow, m3/h 95
90
Total pressure rise, Pa
Ca
Ca
4
va
2
va
r. 2
r. 1
SFP
v=1,
25
1,00
1
L w,tot 70dB
80
75
85
Total pressure loss, Pa
3
p.
Fan p.
0,75
F7 F5
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 0.64 m3/s (2016) and. 0.6 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
05
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08
Max. airflow
m3/h 2880
m3/s 0,80
Correction factors, KOK , dB Sound path To the outlet duct
To the inlet duct*
To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13
-6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17
-6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28
-8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34
4
* The integral attenuation of filters is not included.
102
We reserve the right to alter specifications.
20160422
5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46
6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47
7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54
8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 05 Delivery and transport within the site
The SILVER C SD 05 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories.
Bottom beam/Base frame/Base
The design makes it necessary to mount the SILVER C SD 05 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory.
Power connection L
B E
12
16
A
C
E
16
D H
12
D SILVER
Ø
100
Ø
52* F
F
50
G
50
Base beams are optional. * The air handling unit can be supplied without end connection panels. Size
L
B
H
A
C
D
E
F
G
Ø
Weight, kg
05
1099
825
490
937
162
245
412,5
102
561
315
105-119
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 4.3 A alt. 5.5 A
20160422
We reserve the right to alter specifications.
103
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 07 Airflow, m3/h
Total pressure rise, Pa
95
90
Ca
Ca
4
p.
va
p.
Fan va
r. 2
r. 1
SFPv
=1,25
2
3
1
0,75
75
80
85
Total pressure loss, Pa
L w,tot 70dB
1,00
F7 F5
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018 (calculated for a unit with full face end connection panels). Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
07
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08
Max. airflow
m3/h 2880
m3/s 0.8
Correction factors, KOK , dB Sound path To the outlet duct
To the inlet duct*
To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13
-6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17
-6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28
-8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34
4
* The integral attenuation of filters is not included.
104
We reserve the right to alter specifications.
20160422
5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46
6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47
7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54
8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 07 Delivery and transport within the site
The SILVER C SD 07 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories.
Bottom beam/Base frame/Base
The design makes it necessary to mount the SILVER C SD 07 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory.
Power connection L
B E
12
16
A
C
E
16
D H
12
D SILVER
Ø
100
Ø
52* F
F
50
G
50
Base beams are optional. * The air handling unit can be supplied without end connection panels. Size
L
B
H
A
C
D
E
F
G
Ø
Weight, kg
07
1174
995
575
1012
162
287,5
497,5
73
730
400
113-133
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 4.3 A alt. 5.5 A
20160422
We reserve the right to alter specifications.
105
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 08 Airflow, m3/h 90
Total pressure rise, Pa
Ca
Ca
4 3
p.
va
r. 1
Fan p.
va
r. 2 SFPv
=1,2
2
1
5 1,00
0,7
L w,tot 75dB
85
Total pressure loss, Pa
80
5
F7 F5
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.07 m3/s (2016) and 1.0 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
08
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20
Max. airflow
m3/h 4320
m3/s 1,20
Correction factors, KOK , dB Sound path To the outlet duct
To the inlet duct*
To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13
-6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17
-6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28
-8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34
4
* The integral attenuation of filters is not included.
106
We reserve the right to alter specifications.
20160422
5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46
6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47
7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54
8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 08 Delivery and transport within the site
The SILVER C SD 08 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories.
Bottom beam/Base frame/Base
The design makes it necessary to mount the SILVER C SD 08 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory.
Power connection L
B E
12
16
A
C
E
16
D H
12
D SILVER
Ø
100
Ø
52* F
F
50
G
50
Base beams are optional. * The air handling unit can be supplied without end connection panels. Size
L
B
H
A
C
D
E
F
G
Ø
Weight, kg
08
1174
995
575
1012
162
287,5
497,5
73
730
400
117-137
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Rated data per fan
Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 6.0 A Capacity variant 2: Motor shaft power 1.6 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A
20160422
We reserve the right to alter specifications.
107
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 11 Airflow, m3/h
Total pressure rise, Pa
90
Ca
Ca
4 3
p.
va
p.
Fan va
r. 2
r. 1
SFPv=
1,25
2
1,00
1
0,7
5
L w,tot 75dB
Total pressure loss, Pa
80
85
il Co
he
at
e
a xc h
ng
er s
F7 F5
Droplet elimin
ator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. The air handling unit also complies with requirements to Ecodesign 2018 if the mean supply air and extract air flows do not exceed 0.83 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
11
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20
Max. airflow
m3/h 4320
m3/s 1,20
Correction factors, KOK , dB Sound path To the outlet duct
To the inlet duct*
To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13
-6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17
-6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28
-8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46
6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47
7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54
8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56
* The integral attenuation of the filter and coil heat exchanger are not included.
108
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 11 Delivery and transport within the site
Right-hand version
Fan with filter, if required
The SILVER C SD 11 units are available in right-hand or left-hand version as a fan section or as a fan section + coil heat exchanger.
Fan with filter, if required + Coil heat exchanger in extract air. Droplet eliminator is optional.
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts.
Fan with filter, if required + Coil heat exchanger in supply air.
The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders for pleated filters are provided inside the fan section. Pleated filters are available as optional equipment.
Outdoor air
The air handling unit is delivered on wooden beams.
Supply air Extract air
Exhaust air
Airflow direction
Duct connection options
A: Specify right-hand or left-hand version when ordering.
00
Power connection
L1 16
F
G
162
16
L2
E
D
J SILVER
SILVER
100
52
52*
52
52*
Fan
Fan + Coil heat exchanger
B**
200
L1
I
16
J
Ø
H
F
L2 G
162
16
E
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER
SILVER
Size 100
50
A
50
Weight, kg
Weight, kg
fan + filter
fan + filter + coil
150-176
321-347
11
52
52*
52
Size
L1
L2
B
H
A
D
E
F
G
I
J
Ø
11
1404
2092
1199
648
935
740
1352
540
650
599,5
324
500
Clear space for inspection
A clear space of 800 mm should be provided in front of the unit.
Rated data per fan
Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 6.0 A Capacity variant 2: Motor shaft power 1.6 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A
20160422
We reserve the right to alter specifications.
109
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 12 Airflow, m3/h
Total pressure rise, Pa
90
Ca
Ca
p.
va
p.
Fan va
r. 2
r. 1
SFPv=
1,25
1
3
Total pressure loss, Pa
L w,tot 75dB
1,00
2
0,7
5
80
C
l oi
85
he
at
c ex
ha
90
ng
s er
F7
F5
Droplet
eliminato
r
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.6 m3/s (2016) and 1.5 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.43 m3/s (2016) and 0.84 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
12
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20
Max. airflow
m3/h 6480
m3/s 1,80
Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 1 2 3 1 2 3
-1 -1 -1 -2 -3 -2 -12 -12 -12
-6 -5 -2 -5 -6 0 -20 -19 -16
-6 -8 -6 -4 -9 -6 -29 -31 -29
-8 -8 -15 -11 -7 -16 -29 -29 -36
4
5 -7 -7 -14 -16 -14 -20 -40 -40 -47
6 -7 -9 -16 -13 -11 -19 -40 -42 -49
7 -12 -13 -22 -12 -11 -18 -46 -47 -56
8 -15 -16 -25 -10 -11 -16 -46 -47 -56
* The integral attenuation of the filter and coil heat exchanger are not included.
110
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 12 Delivery and transport within the site
Right-hand version
Fan with filter, if required
The SILVER C SD 12 units are available in right-hand or left-hand version as a fan section or as a fan section + coil heat exchanger.
Fan with filter, if required + Coil heat exchanger in extract air. Droplet eliminator is optional.
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts.
Fan with filter, if required + Coil heat exchanger in supply air.
The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders for pleated filters are provided inside the fan section. Pleated filters are available as optional equipment.
Outdoor air
The air handling unit is delivered on wooden beams.
Supply air Extract air
Exhaust air
Airflow direction
Duct connection options
A: Specify right-hand or left-hand version when ordering.
00
Power connection
L1 16
F
G
162
16
L2
E
D
J SILVER
SILVER
100
52
52*
52
52*
Fan
Fan + Coil heat exchanger
B**
200
L1
I
16
J
Ø
H
F
L2 G
162
E
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER
SILVER
100
50
16
A
50
52
Size
Weight, kg
Weight, kg
52*
fan + filter 52
fan + filter + coil
12
161-187
332-358
Size
L1
L2
B
H
A
D
E
F
G
I
J
Ø
12
1404
2092
1199
648
935
740
1352
540
650
599,5
324
500
Clear space for inspection
A clear space of 800 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A alt. 3.8 A
20160422
We reserve the right to alter specifications.
111
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 14 Airflow, m3/h
Total pressure rise, Pa
90 Ca
Ca
p. v
ar.
p.
r. 2 SFPv=1,25
1
2
1,0 0
0,75
1
3
80
85
Total pressure loss, Pa
L w,tot 75dB
Fan
va
l he
C oi
90
a
ch t ex
an g
er s
F7
Droplet eliminato
r
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
14
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20
Max. airflow
m3/h 6480
m3/s 1,80
Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 1 2 3 1 2 3
-1 -1 -1 -2 -3 -2 -12 -12 -12
-6 -5 -2 -5 -6 0 -20 -19 -16
-6 -8 -6 -4 -9 -6 -29 -31 -29
-8 -8 -15 -11 -7 -16 -29 -29 -36
4
5 -7 -7 -14 -16 -14 -20 -40 -40 -47
6 -7 -9 -16 -13 -11 -19 -40 -42 -49
7 -12 -13 -22 -12 -11 -18 -46 -47 -56
8 -15 -16 -25 -10 -11 -16 -46 -47 -56
* The integral attenuation of the filter and coil heat exchanger are not included.
112
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 14
Right-hand version
Delivery and transport within the site
The SILVER C SD 14 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
0 21
21
L2 F
208
21
E
C
L3 D
E
C
21
J SILVER
SILVER
SILVER
F H J 100
52
52*
Fan
Fan + filter
B** G
I
Fan + filter + coil heat exchanger
L1
200 21
21
L2 208
F
21
E
C
E
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. 21
J
SILVER
SILVER
F H
Size
J 100
A
50
50
52
52*
14
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
169-188
254-292
450-518
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
14
1040
1875
2615
1400
806
1136
988
740
887
400
1000
200
203
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A alt. 3.8 A
20160422
We reserve the right to alter specifications.
113
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 20 Airflow, m3/h
Total pressure rise, Pa
Ca
Ca p.
p.
va r .1
va
Fan r. 2
SFPv=1,2
5
1,0 0
1
2
75
Total pressure loss, Pa
L w,tot 70dB
0,75
80
Co
85
e lh
at
e
h xc
90
an
ge
rs
i
F7
Droplet e
liminator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 2.54 m3/s (2016) and 2.45 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 2.52 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
20
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1080 0.30
Max. airflow
m3/h 10080
m3/s 2,80
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
114
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 20
Right-hand version
Delivery and transport within the site
The SILVER C SD 20 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
0 21
21
L2 F
208
21
E
C
L3 D
E
C
21
J SILVER
SILVER
SILVER
F H J 100
52
52*
Fan
Fan + filter
B** G
I
Fan + filter + coil heat exchanger
L1
200 21
21
L2 208
F
21
E
C
E
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. 21
J
SILVER
SILVER
F H
Size
J 100
A
50
50
52
52*
20
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
187-206
272-310
498-536
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
20
1040
1875
2615
1400
806
1136
988
740
887
400
1000
200
203
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A
20160422
We reserve the right to alter specifications.
115
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 25 Airflow, m3/h
Total pressure rise, Pa
Ca
Ca p.
va r .1
p.
va
Fan r. 2
SFPv=1,25
1,0 0
0,75
1
2
75
80
85
Total pressure loss, Pa
L w,tot 70dB
l he
C oi
a
90
ch t ex
an g
er s
F7
Droplet eliminator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
25
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1080 0.30
Max. airflow
m3/h 10080
m3/s 2,80
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
116
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Right-hand version
Delivery and transport within the site
The SILVER C SD 25 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter
The sections are jointed together by means of bolts.
Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
200
0
Left-hand version
SILVER C SD, size 25
21
L3
L2 F
208 21
E
E
C
D
C
21 J
F
21
SILVER
SILVER
SILVER
H
J 100
52
52*
Fan B** G
I
Fan + filter
Fan + filter + coil heat exchanger
L1
200 21
L2 208 21
F
E
E
C
21
* The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm.
J
F
H
Size
J A
50
50
100
52
52*
25
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
241-267
330-382
626-678
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
25
1145
1980
2720
1600
1026
1336
1093
740
887
500
1200
200
263
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A
20160422
We reserve the right to alter specifications.
117
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 30 Airflow, m3/h p.
Fan va
r. 1
Ca va 2 r.
SFPv=1,25
p.
Total pressure rise, Pa
Ca
1,0 0
0,75
1
2 75
80
85
Total pressure loss, Pa
L w,tot 70dB
Co
il h
90
e
e at
xc
h
g an
er
s
F7
Droplet e
liminator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 3.86 m3/s (2016) and 3.7 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 3.47 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
30
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1800 0,50
Max. airflow
m3/h 14400
m3/s 4.00
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
118
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Right-hand version
Delivery and transport within the site
The SILVER C SD 30 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
200
0
Left-hand version
SILVER C SD, size 30
21
L3
L2 F
208 21
E
E
C
D
C
21 J
F
21
SILVER
SILVER
SILVER
H
J 100
52
52*
Fan B** G
I
Fan + filter
Fan + filter + coil heat exchanger
L1
200 21
L2 208 21
F
E
E
C
21
* The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm.
J
F
H
Size
J A
50
50
100
52
52*
30
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
261-287
350-402
646-698
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
30
1145
1980
2720
1600
1026
1336
1093
740
887
500
1200
200
263
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 8.9 A
20160422
We reserve the right to alter specifications.
119
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 35 Airflow, m3/h
Total pressure rise, Pa
Ca
p.
va
Ca
r. 1
Fan p.
SFPv=1,25
va
r. 2
1,0 0
0,75
1
2 75
80
Total pressure loss, Pa
L w,tot 70dB
85
l he
C oi
90
at
ha e xc
nge
rs
F7
Droplet elimina
tor
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
35
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1800 0,50
Max. airflow
m3/h 14400
m3/s 4.00
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
120
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Right-hand version
Delivery and transport within the site
The SILVER C SD 35 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
200
0
Left-hand version
SILVER C SD, size 35
21
L3
L2 F
208 21
E
E
C
D
C
21 J
F
21
SILVER
SILVER
SILVER
H
J 100
52
52*
Fan B** G
I
Fan + filter
Fan + filter + coil heat exchanger
L1
200 21
L2 208 21
F
E
E
C
21
* The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm.
J
F
H
Size
J A
50
50
100
52
52*
35
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
316-350
418-486
793-861
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
35
1145
1980
2720
1990
1126
1726
1093
740
887
600
1400
295
263
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 8.9 A
20160422
We reserve the right to alter specifications.
121
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 40 Airflow, m3/h
Total pressure rise, Pa
Ca
Ca
p.
va
p.
va
r. 2
SFPv=1,25
r. 1 1,0 0
2
1 80
85
Total pressure loss, Pa
L w,tot 75dB
0,75
Co
90
il
h
t ea
ex
c
n ha
ge
rs
F7
Droplet e
liminator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 5.9 m3/s (2016) and 5.7 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 4.9 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows
Correction factors, KOK , dB
The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
40 1 2
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 2700 0,75
Max. airflow
m3/h m3/s 180001/216002 5,001/6,002
Capacity variant 1. Capacity variant 2.
122
Sound path
We reserve the right to alter specifications.
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
20160422
SILVER C
Sizing, installation, dimensions and weights Right-hand version
Delivery and transport within the site
The SILVER C SD 40 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
Outdoor air
Supply air Extract air
Exhaust air
Airflow direction
Power connection L1
200
0
Left-hand version
SILVER C SD, size 40
21
L3
L2 F
208 21
E
E
C
D
C
21 J
F
21
SILVER
SILVER
SILVER
H
J 100
52
52*
Fan B** G
I
Fan + filter
Fan + filter + coil heat exchanger
L1
200 21
L2 208 21
F
E
E
C
21
* The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm.
J
F
H
Size
J A
50
50
100
52
52*
40
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
341-375
443-511
818-886
Size
L1
L2
L3
B
H
A
C
D
E
F
G
I
J
40
1145
1980
2720
1990
1126
1726
1093
740
887
600
1400
295
263
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 5.0 kW (3.9 kW*) alt. 6.5 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.2 A alt. 11.9 A *The motor control system limits the power of the take-off to the value specified.
20160422
We reserve the right to alter specifications.
123
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 50 Airflow, m3/h
Total pressure rise, Pa
Ca
Ca p.
va
p.
Fan
va
r. 2 SFPv=1,25
r. 1
1,0 0
0,75
1
2 80
85
Total pressure loss, Pa
L w,tot 75dB
90
l he
C oi
xc at e
han
ger
s
F7
Droplet elimin
ator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
50
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 2160 0,6
Max. airflow
m3/h 20160
m3/s 5,60
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
124
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 50
Right-hand version
Delivery and transport within the site
The SILVER C SD 50 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
21
21
J
E
100 21
E
C
Exhaust air
Airflow direction
C
D
Power connection
21
SILVER
Supply air Extract air
L3
L2
L1 F
Outdoor air
SILVER
SILVER
F H
J 100
28
28*
100
Fan
Fan + filter B** G
I
Fan + filter + coil heat exchanger E on 100100 mm high support feet. The feet can be reC 21 moved or kept as 21 they are when the unit is at its final location. The unit has provision 21 for mounting adjustable support feet.
21 J
E
D
Size
J 100
28
A
28*
50
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
379-410
558-620
1093-1155
Size
L1
L2
L3
A
B
H
C
D
E
F
G
I
J
50
1078
1947
2687
2166
2318
1320
1050
762
919
800
1600
359
260
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2 x 2.4 kW alt. 2 x 3.4 kW,* motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A * Two fans/motor control systems per airflow direction.
20160422
C
SILVER
SILVER
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm.
F H
45
L3
L2
L1 SuppliedF
200
We reserve the right to alter specifications.
125
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 60 Airflow, m3/h
Total pressure rise, Pa
Ca
p.
va
Ca r. 1
p.
SFPv=1,25
va
Fan r. 2
1,0 0
2
0,75
1 80
85
90
Total pressure loss, Pa
L w,tot 75dB
95
Co
il h
t ea
ex
c
n ha
ge
rs
F7
Droplet
eliminato
r
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. The air handling unit also complies with requirements for Ecodesign 2018 if the mean supply air and extract air flows do not exceed 7.8 m3/s. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 6.9 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
60
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 3600 1,00
Max. airflow
m3/h 28800
m3/s 8,00
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
126
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 60
Right-hand version
Delivery and transport within the site
The SILVER C SD 60 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger.
Fan
The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site.
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional.
The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel.
Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
21
21
J
E
100 21
E
C
Exhaust air
Airflow direction
C
D
Power connection
21
SILVER
Supply air Extract air
L3
L2
L1 F
Outdoor air
SILVER
SILVER
F H
J 100
28
28*
100
Fan
Fan + filter B** G
I
Fan + filter + coil heat exchanger E on 100100 mm high support feet. The feet can be reC 21 moved or kept as 21 they are when the unit is at its final location. The unit has provision 21 for mounting adjustable support feet.
21 J
E
D
Size
J 100
28
A
28*
60
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
419-450
589-660
1133-1195
Size
L1
L2
L3
A
B
H
C
D
E
F
G
I
J
60
1078
1947
2687
2166
2318
1320
1050
762
919
800
1600
359
260
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW,* motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 11.2 A * Two fans/motor control systems per airflow direction.
20160422
C
SILVER
SILVER
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm.
F H
45
L3
L2
L1 SuppliedF
200
We reserve the right to alter specifications.
127
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 70 Airflow, m3/h
Total pressure rise, Pa
Ca
p.
va
Ca r. 1
p.
va
SFPv=1,25
Fan r. 2
1,0 0
0,75
2
95
1 80
85
90
Total pressure loss, Pa
L w,tot 75dB
C
h oil
ea
te
a xc h
ng
er
s
F7
Droplet el
iminator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 7.7 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
70
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 3600 1,00
Max. airflow
m3/h 28800
m3/s 8,00
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
128
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 70
Right-hand version
Delivery and transport within the site
The SILVER C SD 70 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel.
Fan
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air
Outdoor air
Duct connection options
A: Specify right-hand or left-hand version when ordering.
Supply air Extract air
Exhaust air
Airflow direction
B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
21
21
J
L3
L2
L1 F
164 21
E
C
Power connection
21
SILVER
D
E
C
SILVER
SILVER
F H
J 100
52
52*
100
Fan
Fan + filter B** G
I
Fan + filter + coil heat exchanger L3
L2
L1
200
SuppliedF on 100 164 mm high supportE feet. The feet Ccan be re21moved or kept as21they are when the unit is at its final location. The unit has provision for mounting adjustable support feet.
21 J
21
D
E
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER
F H
Size J 100
45
A
52
52*
70
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
552-590
783-859
1563-1639
Size
L1
L2
L3
A
B
H
C
D
E
F
G
I
J
70
1327
2550
3452
2485
2637
1320
1275
902
1275
1000
1800
419
160
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz, nom. 7.3 A alt. 11.2 A* * Two fans/motor control systems per airflow direction.
20160422
We reserve the right to alter specifications.
129
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 80 Airflow, m3/h
Total pressure rise, Pa
Ca
p.
Ca
va
p.
r. 1
va
Fan r. 2 SFPv=
1,25
1,0 0
2
1
Total pressure loss, Pa
L w,tot 75dB
80
0,75
85
Co
e lh
at
e
90
h xc
an
g
95
s er
i
F7
le t D ro p
e li m i
n a to
r
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 11.5 m3/s (2016) and 11.0 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 7.8 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
80
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 5400 1,50
Max. airflow
m3/h 43200
m3/s 12.0
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
130
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights Left-hand version
SILVER C SD, size 80
Right-hand version
Delivery and transport within the site
The SILVER C SD 80 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel.
Fan
Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air
Outdoor air
Duct connection options
A: Specify right-hand or left-hand version when ordering.
Supply air Extract air
Exhaust air
Airflow direction
B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors).
21
21
J
L3
L2
L1 F
164 21
E
C
Power connection
21
SILVER
D
E
C
SILVER
SILVER
F H
J 100
52
52*
100
Fan
Fan + filter B** G
I
Fan + filter + coil heat exchanger L3
L2
L1
200
SuppliedF on 100 164 mm high supportE feet. The feet Ccan be re21moved or kept as21they are when the unit is at its final location. The unit has provision for mounting adjustable support feet.
21 J
21
D
E
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER
F H
Size J 100
45
A
52
52*
80
Weight, kg
Weight, kg
Weight, kg
fan
fan + filter
fan + filter + coil
602-640
833-909
1613-1689
Size
L1
L2
L3
A
B
H
C
D
E
F
G
I
J
80
1327
2550
3452
2485
2637
1320
1275
902
1275
1000
1800
419
160
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A***
* Two fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422
We reserve the right to alter specifications.
131
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 100 Airflow, m3/h
Total pressure rise, Pa
Ca
p.
va
Ca
r. 1
p.
va
Fan r. 2 SFPv=
1,25
1,0 0
2
0,75
1 80
85
90
Total pressure loss, Pa
L w,tot 75dB
Co
e il h
95
at
ex
n cha
ge
rs
F7
Droplet elim
inator
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
100
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 5400 1,50
Max. airflow
m3/h 43200
m3/s 12.0
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
132
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 100 Delivery and transport within the site
The SILVER C SD 100 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit.
Fan + Section for power conn.
Fan + Section for power conn. + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. Outdoor air
B: Specify upper fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,500 x 800 mm.
L2
L1 E
56 21
C
21
SILVER
L3 D
E
191
M
21 J
Supply air Extract air
Exhaust air
Airflow direction
C
SILVER
SILVER
Power connection F H
J 100
56*
Fan
Filter + fan
I N
Filter + coil heat exchanger + fan L2
L1
B** G O
I N 200
E
56 21
E
191
M
21 J
C
21
SILVER
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H
Size 122 77
1048
45
J 100 1000 3186
56*
100
1048
Weight, kg
Weight, kg
Weight, kg
fan
filter + fan
filter + coil + fan
654-834
1183-1363
2187-2367
77
Size
L1
L2
L3
B
H
C
D
E
F
G
I
J
M
N
O
100
1182
2252
3396
3340
1620
1126
1144
1126
1200
2400
470
210
800
170
2500
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A***
* Two fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422
We reserve the right to alter specifications.
133
L3 D
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 120 Airflow, m3/h
Ca
Total pressure rise, Pa
Fan p.
va
2 r.
p.
va
Ca
r. 1
100 v=1 ,25
SFP
2
1,00
1
Total pressure loss, Pa
L w,tot 80dB
85
Co
il
he
90
e at
xc
h
95
g an
er
0,7
5
s
F7
t Drople
elimin
a to r
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 17.0 m3/s (2016) and 16.4 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 12.7 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels.
Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
120
Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 9000 2,50
Max. airflow
m3/h 64800
m3/s 18,0
Correction factors, KOK , dB Sound path
Octave band, no./mid-frequency, Hz
Range in diagram
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-5
-6
-2
-10
-14
-12
-10
-6
2
0
1
-2
-11
-16
-14
-15
-11
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
To unit’s the surroundings
* The integral attenuation of the filter and coil heat exchanger are not included.
134
We reserve the right to alter specifications.
20160422
SILVER C
Sizing, installation, dimensions and weights SILVER C SD, size 120 Delivery and transport within the site
The SILVER C SD 120 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit.
Fan + Section for power conn.
Fan + Section for power conn. + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air
Duct connection options
A: Specify right-hand or left-hand version when ordering. Outdoor air
B: Specify upper fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,500 x 800 mm.
L2
L1 E
56 21
C
21
SILVER
L3 D
E
191
M
21 J
Supply air Extract air
Exhaust air
Airflow direction
C
SILVER
SILVER
Power connection F H
J 100
56*
Fan
Filter + fan
I N
Filter + coil heat exchanger + fan L2
L1
B** G O
I N 200
E
56 21
E
191
M
21 J
C
21
SILVER
SILVER
* The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H
122 77
1048
45
Size
J 100 1000 3186
1048
56*
120
77
Weight, kg
Weight, kg
Weight, kg
fan
filter + fan
filter + coil + fan
757-968
1286-1497
2290-2501
Size
L1
L2
L3
B
H
C
D
E
F
G
I
J
M
N
O
120
1182
2252
3396
3340
1620
1126
1144
1126
1200
2400
470
210
800
170
2500
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Rated data per fan
Motor shaft power: 3 x 6.5 kW alt 3 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A***
* Three fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422
We reserve the right to alter specifications.
135
L3 D
SILVER C
136
We reserve the right to alter specifications.
20160422