SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 04 Airflow, m3/h Total pressure rise, Pa Fan 85 80 =1,25 4 SFPv 3 2 L w,tot 70dB 0,75 75 80 Total pressure loss, Pa 1 1,00 F7 F5 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018 (calculated for a unit with full face end connection panels). Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 04 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08 Max. airflow m3/h 2160 m3/s 0,60 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13 -6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17 -6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28 -8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34 4 * The integral attenuation of filters is not included. 100 We reserve the right to alter specifications. 20160422 5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46 6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47 7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54 8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 04 Delivery and transport within the site The SILVER C SD 04 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories. Bottom beam/Base frame/Base The design makes it necessary to mount the SILVER C SD 04 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory. Power connection L B E 12 16 A C E 16 D H D SILVER Ø 100 12 Ø 52* F F 50 G 50 Base beams are optional. * The air handling unit can be supplied without end connection panels. Size L B H A C D E F G Ø Weight, kg 04 1099 825 490 937 162 245 412,5 102 561 315 105-119 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 0.8 kW (0.41 kW)*, motor control system: 1 x 230 V, 50 Hz, rated 2.3 A *The motor control system limits the power of the take-off to the value specified. 20160422 We reserve the right to alter specifications. 101 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 05 Airflow, m3/h 95 90 Total pressure rise, Pa Ca Ca 4 va 2 va r. 2 r. 1 SFP v=1, 25 1,00 1 L w,tot 70dB 80 75 85 Total pressure loss, Pa 3 p. Fan p. 0,75 F7 F5 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 0.64 m3/s (2016) and. 0.6 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 05 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08 Max. airflow m3/h 2880 m3/s 0,80 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13 -6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17 -6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28 -8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34 4 * The integral attenuation of filters is not included. 102 We reserve the right to alter specifications. 20160422 5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46 6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47 7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54 8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 05 Delivery and transport within the site The SILVER C SD 05 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories. Bottom beam/Base frame/Base The design makes it necessary to mount the SILVER C SD 05 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory. Power connection L B E 12 16 A C E 16 D H 12 D SILVER Ø 100 Ø 52* F F 50 G 50 Base beams are optional. * The air handling unit can be supplied without end connection panels. Size L B H A C D E F G Ø Weight, kg 05 1099 825 490 937 162 245 412,5 102 561 315 105-119 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 4.3 A alt. 5.5 A 20160422 We reserve the right to alter specifications. 103 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 07 Airflow, m3/h Total pressure rise, Pa 95 90 Ca Ca 4 p. va p. Fan va r. 2 r. 1 SFPv =1,25 2 3 1 0,75 75 80 85 Total pressure loss, Pa L w,tot 70dB 1,00 F7 F5 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018 (calculated for a unit with full face end connection panels). Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 07 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 290 0,08 Max. airflow m3/h 2880 m3/s 0.8 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13 -6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17 -6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28 -8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34 4 * The integral attenuation of filters is not included. 104 We reserve the right to alter specifications. 20160422 5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46 6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47 7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54 8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 07 Delivery and transport within the site The SILVER C SD 07 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories. Bottom beam/Base frame/Base The design makes it necessary to mount the SILVER C SD 07 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory. Power connection L B E 12 16 A C E 16 D H 12 D SILVER Ø 100 Ø 52* F F 50 G 50 Base beams are optional. * The air handling unit can be supplied without end connection panels. Size L B H A C D E F G Ø Weight, kg 07 1174 995 575 1012 162 287,5 497,5 73 730 400 113-133 Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 4.3 A alt. 5.5 A 20160422 We reserve the right to alter specifications. 105 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 08 Airflow, m3/h 90 Total pressure rise, Pa Ca Ca 4 3 p. va r. 1 Fan p. va r. 2 SFPv =1,2 2 1 5 1,00 0,7 L w,tot 75dB 85 Total pressure loss, Pa 80 5 F7 F5 Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units, with capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.07 m3/s (2016) and 1.0 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 08 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20 Max. airflow m3/h 4320 m3/s 1,20 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13 -6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17 -6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28 -8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34 4 * The integral attenuation of filters is not included. 106 We reserve the right to alter specifications. 20160422 5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46 6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47 7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54 8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 08 Delivery and transport within the site The SILVER C SD 08 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders are available for pleated filters. Pleated filters are available as optional equipment. The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. Horizontal GOLD units can be installed outdoors if they are equipped with the roof, air intake section and exhaust air hood accessories. Bottom beam/Base frame/Base The design makes it necessary to mount the SILVER C SD 08 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a stand supplied unmounted is available as an accessory. Power connection L B E 12 16 A C E 16 D H 12 D SILVER Ø 100 Ø 52* F F 50 G 50 Base beams are optional. * The air handling unit can be supplied without end connection panels. Size L B H A C D E F G Ø Weight, kg 08 1174 995 575 1012 162 287,5 497,5 73 730 400 117-137 Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Rated data per fan Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 6.0 A Capacity variant 2: Motor shaft power 1.6 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A 20160422 We reserve the right to alter specifications. 107 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 11 Airflow, m3/h Total pressure rise, Pa 90 Ca Ca 4 3 p. va p. Fan va r. 2 r. 1 SFPv= 1,25 2 1,00 1 0,7 5 L w,tot 75dB Total pressure loss, Pa 80 85 il Co he at e a xc h ng er s F7 F5 Droplet elimin ator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. The air handling unit also complies with requirements to Ecodesign 2018 if the mean supply air and extract air flows do not exceed 0.83 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 11 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20 Max. airflow m3/h 4320 m3/s 1,20 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 4 1 2 3 4 1 2 3 4 -1 -1 -1 -2 -2 -3 -2 -3 -12 -12 -12 -13 -6 -5 -2 -3 -5 -6 0 -1 -20 -19 -16 -17 -6 -8 -6 -5 -4 -9 -6 -4 -29 -31 -29 -28 -8 -8 -15 -13 -11 -7 -16 -11 -29 -29 -36 -34 4 5 -7 -7 -14 -13 -16 -14 -20 -19 -40 -40 -47 -46 6 -7 -9 -16 -14 -13 -11 -19 -16 -40 -42 -49 -47 7 -12 -13 -22 -20 -12 -11 -18 -16 -46 -47 -56 -54 8 -15 -16 -25 -25 -10 -11 -16 -16 -46 -47 -56 -56 * The integral attenuation of the filter and coil heat exchanger are not included. 108 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 11 Delivery and transport within the site Right-hand version Fan with filter, if required The SILVER C SD 11 units are available in right-hand or left-hand version as a fan section or as a fan section + coil heat exchanger. Fan with filter, if required + Coil heat exchanger in extract air. Droplet eliminator is optional. The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. Fan with filter, if required + Coil heat exchanger in supply air. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders for pleated filters are provided inside the fan section. Pleated filters are available as optional equipment. Outdoor air The air handling unit is delivered on wooden beams. Supply air Extract air Exhaust air Airflow direction Duct connection options A: Specify right-hand or left-hand version when ordering. 00 Power connection L1 16 F G 162 16 L2 E D J SILVER SILVER 100 52 52* 52 52* Fan Fan + Coil heat exchanger B** 200 L1 I 16 J Ø H F L2 G 162 16 E * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER SILVER Size 100 50 A 50 Weight, kg Weight, kg fan + filter fan + filter + coil 150-176 321-347 11 52 52* 52 Size L1 L2 B H A D E F G I J Ø 11 1404 2092 1199 648 935 740 1352 540 650 599,5 324 500 Clear space for inspection A clear space of 800 mm should be provided in front of the unit. Rated data per fan Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz, rated 6.0 A Capacity variant 2: Motor shaft power 1.6 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A 20160422 We reserve the right to alter specifications. 109 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 12 Airflow, m3/h Total pressure rise, Pa 90 Ca Ca p. va p. Fan va r. 2 r. 1 SFPv= 1,25 1 3 Total pressure loss, Pa L w,tot 75dB 1,00 2 0,7 5 80 C l oi 85 he at c ex ha 90 ng s er F7 F5 Droplet eliminato r Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.6 m3/s (2016) and 1.5 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 1.43 m3/s (2016) and 0.84 m3/s (2018) respectively. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 12 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20 Max. airflow m3/h 6480 m3/s 1,80 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 1 2 3 1 2 3 -1 -1 -1 -2 -3 -2 -12 -12 -12 -6 -5 -2 -5 -6 0 -20 -19 -16 -6 -8 -6 -4 -9 -6 -29 -31 -29 -8 -8 -15 -11 -7 -16 -29 -29 -36 4 5 -7 -7 -14 -16 -14 -20 -40 -40 -47 6 -7 -9 -16 -13 -11 -19 -40 -42 -49 7 -12 -13 -22 -12 -11 -18 -46 -47 -56 8 -15 -16 -25 -10 -11 -16 -46 -47 -56 * The integral attenuation of the filter and coil heat exchanger are not included. 110 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 12 Delivery and transport within the site Right-hand version Fan with filter, if required The SILVER C SD 12 units are available in right-hand or left-hand version as a fan section or as a fan section + coil heat exchanger. Fan with filter, if required + Coil heat exchanger in extract air. Droplet eliminator is optional. The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. Fan with filter, if required + Coil heat exchanger in supply air. The SILVER C SD can be used as a supply air or an extract air handling unit. Filter holders for pleated filters are provided inside the fan section. Pleated filters are available as optional equipment. Outdoor air The air handling unit is delivered on wooden beams. Supply air Extract air Exhaust air Airflow direction Duct connection options A: Specify right-hand or left-hand version when ordering. 00 Power connection L1 16 F G 162 16 L2 E D J SILVER SILVER 100 52 52* 52 52* Fan Fan + Coil heat exchanger B** 200 L1 I 16 J Ø H F L2 G 162 E * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER SILVER 100 50 16 A 50 52 Size Weight, kg Weight, kg 52* fan + filter 52 fan + filter + coil 12 161-187 332-358 Size L1 L2 B H A D E F G I J Ø 12 1404 2092 1199 648 935 740 1352 540 650 599,5 324 500 Clear space for inspection A clear space of 800 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A alt. 3.8 A 20160422 We reserve the right to alter specifications. 111 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 14 Airflow, m3/h Total pressure rise, Pa 90 Ca Ca p. v ar. p. r. 2 SFPv=1,25 1 2 1,0 0 0,75 1 3 80 85 Total pressure loss, Pa L w,tot 75dB Fan va l he C oi 90 a ch t ex an g er s F7 Droplet eliminato r Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 14 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 720 0,20 Max. airflow m3/h 6480 m3/s 1,80 Correction factors, KOK , dB Sound path To the outlet duct To the inlet duct* To unit’s the surroundings Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 500 1000 2000 4000 8000 1 2 3 1 2 3 1 2 3 -1 -1 -1 -2 -3 -2 -12 -12 -12 -6 -5 -2 -5 -6 0 -20 -19 -16 -6 -8 -6 -4 -9 -6 -29 -31 -29 -8 -8 -15 -11 -7 -16 -29 -29 -36 4 5 -7 -7 -14 -16 -14 -20 -40 -40 -47 6 -7 -9 -16 -13 -11 -19 -40 -42 -49 7 -12 -13 -22 -12 -11 -18 -46 -47 -56 8 -15 -16 -25 -10 -11 -16 -46 -47 -56 * The integral attenuation of the filter and coil heat exchanger are not included. 112 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 14 Right-hand version Delivery and transport within the site The SILVER C SD 14 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 0 21 21 L2 F 208 21 E C L3 D E C 21 J SILVER SILVER SILVER F H J 100 52 52* Fan Fan + filter B** G I Fan + filter + coil heat exchanger L1 200 21 21 L2 208 F 21 E C E * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. 21 J SILVER SILVER F H Size J 100 A 50 50 52 52* 14 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 169-188 254-292 450-518 Size L1 L2 L3 B H A C D E F G I J 14 1040 1875 2615 1400 806 1136 988 740 887 400 1000 200 203 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 2.8 A alt. 3.8 A 20160422 We reserve the right to alter specifications. 113 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 20 Airflow, m3/h Total pressure rise, Pa Ca Ca p. p. va r .1 va Fan r. 2 SFPv=1,2 5 1,0 0 1 2 75 Total pressure loss, Pa L w,tot 70dB 0,75 80 Co 85 e lh at e h xc 90 an ge rs i F7 Droplet e liminator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 2.54 m3/s (2016) and 2.45 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 2.52 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 20 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1080 0.30 Max. airflow m3/h 10080 m3/s 2,80 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 114 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 20 Right-hand version Delivery and transport within the site The SILVER C SD 20 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 0 21 21 L2 F 208 21 E C L3 D E C 21 J SILVER SILVER SILVER F H J 100 52 52* Fan Fan + filter B** G I Fan + filter + coil heat exchanger L1 200 21 21 L2 208 F 21 E C E * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. 21 J SILVER SILVER F H Size J 100 A 50 50 52 52* 20 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 187-206 272-310 498-536 Size L1 L2 L3 B H A C D E F G I J 20 1040 1875 2615 1400 806 1136 988 740 887 400 1000 200 203 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A 20160422 We reserve the right to alter specifications. 115 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 25 Airflow, m3/h Total pressure rise, Pa Ca Ca p. va r .1 p. va Fan r. 2 SFPv=1,25 1,0 0 0,75 1 2 75 80 85 Total pressure loss, Pa L w,tot 70dB l he C oi a 90 ch t ex an g er s F7 Droplet eliminator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 25 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1080 0.30 Max. airflow m3/h 10080 m3/s 2,80 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 116 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Right-hand version Delivery and transport within the site The SILVER C SD 25 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter The sections are jointed together by means of bolts. Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 200 0 Left-hand version SILVER C SD, size 25 21 L3 L2 F 208 21 E E C D C 21 J F 21 SILVER SILVER SILVER H J 100 52 52* Fan B** G I Fan + filter Fan + filter + coil heat exchanger L1 200 21 L2 208 21 F E E C 21 * The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm. J F H Size J A 50 50 100 52 52* 25 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 241-267 330-382 626-678 Size L1 L2 L3 B H A C D E F G I J 25 1145 1980 2720 1600 1026 1336 1093 740 887 500 1200 200 263 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A 20160422 We reserve the right to alter specifications. 117 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 30 Airflow, m3/h p. Fan va r. 1 Ca va 2 r. SFPv=1,25 p. Total pressure rise, Pa Ca 1,0 0 0,75 1 2 75 80 85 Total pressure loss, Pa L w,tot 70dB Co il h 90 e e at xc h g an er s F7 Droplet e liminator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 3.86 m3/s (2016) and 3.7 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 3.47 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 30 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1800 0,50 Max. airflow m3/h 14400 m3/s 4.00 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 118 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Right-hand version Delivery and transport within the site The SILVER C SD 30 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 200 0 Left-hand version SILVER C SD, size 30 21 L3 L2 F 208 21 E E C D C 21 J F 21 SILVER SILVER SILVER H J 100 52 52* Fan B** G I Fan + filter Fan + filter + coil heat exchanger L1 200 21 L2 208 21 F E E C 21 * The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm. J F H Size J A 50 50 100 52 52* 30 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 261-287 350-402 646-698 Size L1 L2 L3 B H A C D E F G I J 30 1145 1980 2720 1600 1026 1336 1093 740 887 500 1200 200 263 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 8.9 A 20160422 We reserve the right to alter specifications. 119 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 35 Airflow, m3/h Total pressure rise, Pa Ca p. va Ca r. 1 Fan p. SFPv=1,25 va r. 2 1,0 0 0,75 1 2 75 80 Total pressure loss, Pa L w,tot 70dB 85 l he C oi 90 at ha e xc nge rs F7 Droplet elimina tor Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 35 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 1800 0,50 Max. airflow m3/h 14400 m3/s 4.00 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 120 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Right-hand version Delivery and transport within the site The SILVER C SD 35 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 200 0 Left-hand version SILVER C SD, size 35 21 L3 L2 F 208 21 E E C D C 21 J F 21 SILVER SILVER SILVER H J 100 52 52* Fan B** G I Fan + filter Fan + filter + coil heat exchanger L1 200 21 L2 208 21 F E E C 21 * The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm. J F H Size J A 50 50 100 52 52* 35 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 316-350 418-486 793-861 Size L1 L2 L3 B H A C D E F G I J 35 1145 1980 2720 1990 1126 1726 1093 740 887 600 1400 295 263 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 8.9 A 20160422 We reserve the right to alter specifications. 121 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 40 Airflow, m3/h Total pressure rise, Pa Ca Ca p. va p. va r. 2 SFPv=1,25 r. 1 1,0 0 2 1 80 85 Total pressure loss, Pa L w,tot 75dB 0,75 Co 90 il h t ea ex c n ha ge rs F7 Droplet e liminator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 5.9 m3/s (2016) and 5.7 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 4.9 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows Correction factors, KOK , dB The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 40 1 2 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 2700 0,75 Max. airflow m3/h m3/s 180001/216002 5,001/6,002 Capacity variant 1. Capacity variant 2. 122 Sound path We reserve the right to alter specifications. Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 20160422 SILVER C Sizing, installation, dimensions and weights Right-hand version Delivery and transport within the site The SILVER C SD 40 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The air handling unit is delivered on wooden beams. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). Outdoor air Supply air Extract air Exhaust air Airflow direction Power connection L1 200 0 Left-hand version SILVER C SD, size 40 21 L3 L2 F 208 21 E E C D C 21 J F 21 SILVER SILVER SILVER H J 100 52 52* Fan B** G I Fan + filter Fan + filter + coil heat exchanger L1 200 21 L2 208 21 F E E C 21 * The air handling unit can21be supplied without end connection panels. SILVER SILVER ** Width of coil heat exchanger (if required) = B + 200 mm. J F H Size J A 50 50 100 52 52* 40 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 341-375 443-511 818-886 Size L1 L2 L3 B H A C D E F G I J 40 1145 1980 2720 1990 1126 1726 1093 740 887 600 1400 295 263 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 5.0 kW (3.9 kW*) alt. 6.5 kW, motor control system: 3 x 400 V, 50 Hz, rated 7.2 A alt. 11.9 A *The motor control system limits the power of the take-off to the value specified. 20160422 We reserve the right to alter specifications. 123 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 50 Airflow, m3/h Total pressure rise, Pa Ca Ca p. va p. Fan va r. 2 SFPv=1,25 r. 1 1,0 0 0,75 1 2 80 85 Total pressure loss, Pa L w,tot 75dB 90 l he C oi xc at e han ger s F7 Droplet elimin ator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 50 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 2160 0,6 Max. airflow m3/h 20160 m3/s 5,60 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 124 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 50 Right-hand version Delivery and transport within the site The SILVER C SD 50 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). 21 21 J E 100 21 E C Exhaust air Airflow direction C D Power connection 21 SILVER Supply air Extract air L3 L2 L1 F Outdoor air SILVER SILVER F H J 100 28 28* 100 Fan Fan + filter B** G I Fan + filter + coil heat exchanger E on 100100 mm high support feet. The feet can be reC 21 moved or kept as 21 they are when the unit is at its final location. The unit has provision 21 for mounting adjustable support feet. 21 J E D Size J 100 28 A 28* 50 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 379-410 558-620 1093-1155 Size L1 L2 L3 A B H C D E F G I J 50 1078 1947 2687 2166 2318 1320 1050 762 919 800 1600 359 260 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2 x 2.4 kW alt. 2 x 3.4 kW,* motor control system: 3 x 400 V, 50 Hz, rated 4.2 A alt. 5.9 A * Two fans/motor control systems per airflow direction. 20160422 C SILVER SILVER SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H 45 L3 L2 L1 SuppliedF 200 We reserve the right to alter specifications. 125 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 60 Airflow, m3/h Total pressure rise, Pa Ca p. va Ca r. 1 p. SFPv=1,25 va Fan r. 2 1,0 0 2 0,75 1 80 85 90 Total pressure loss, Pa L w,tot 75dB 95 Co il h t ea ex c n ha ge rs F7 Droplet eliminato r Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. The air handling unit also complies with requirements for Ecodesign 2018 if the mean supply air and extract air flows do not exceed 7.8 m3/s. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 6.9 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 60 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 3600 1,00 Max. airflow m3/h 28800 m3/s 8,00 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 126 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 60 Right-hand version Delivery and transport within the site The SILVER C SD 60 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. Fan The unit is always supplied as one unit. The air handling unit can be split at the building site to facilitate transporting it within the site. Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). 21 21 J E 100 21 E C Exhaust air Airflow direction C D Power connection 21 SILVER Supply air Extract air L3 L2 L1 F Outdoor air SILVER SILVER F H J 100 28 28* 100 Fan Fan + filter B** G I Fan + filter + coil heat exchanger E on 100100 mm high support feet. The feet can be reC 21 moved or kept as 21 they are when the unit is at its final location. The unit has provision 21 for mounting adjustable support feet. 21 J E D Size J 100 28 A 28* 60 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 419-450 589-660 1133-1195 Size L1 L2 L3 A B H C D E F G I J 60 1078 1947 2687 2166 2318 1320 1050 762 919 800 1600 359 260 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW,* motor control system: 3 x 400 V, 50 Hz, rated 7.3 A alt. 11.2 A * Two fans/motor control systems per airflow direction. 20160422 C SILVER SILVER SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H 45 L3 L2 L1 SuppliedF 200 We reserve the right to alter specifications. 127 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 70 Airflow, m3/h Total pressure rise, Pa Ca p. va Ca r. 1 p. va SFPv=1,25 Fan r. 2 1,0 0 0,75 2 95 1 80 85 90 Total pressure loss, Pa L w,tot 75dB C h oil ea te a xc h ng er s F7 Droplet el iminator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 7.7 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 70 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 3600 1,00 Max. airflow m3/h 28800 m3/s 8,00 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 128 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 70 Right-hand version Delivery and transport within the site The SILVER C SD 70 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel. Fan Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air Outdoor air Duct connection options A: Specify right-hand or left-hand version when ordering. Supply air Extract air Exhaust air Airflow direction B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). 21 21 J L3 L2 L1 F 164 21 E C Power connection 21 SILVER D E C SILVER SILVER F H J 100 52 52* 100 Fan Fan + filter B** G I Fan + filter + coil heat exchanger L3 L2 L1 200 SuppliedF on 100 164 mm high supportE feet. The feet Ccan be re21moved or kept as21they are when the unit is at its final location. The unit has provision for mounting adjustable support feet. 21 J 21 D E SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER F H Size J 100 45 A 52 52* 70 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 552-590 783-859 1563-1639 Size L1 L2 L3 A B H C D E F G I J 70 1327 2550 3452 2485 2637 1320 1275 902 1275 1000 1800 419 160 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz, nom. 7.3 A alt. 11.2 A* * Two fans/motor control systems per airflow direction. 20160422 We reserve the right to alter specifications. 129 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 80 Airflow, m3/h Total pressure rise, Pa Ca p. Ca va p. r. 1 va Fan r. 2 SFPv= 1,25 1,0 0 2 1 Total pressure loss, Pa L w,tot 75dB 80 0,75 85 Co e lh at e 90 h xc an g 95 s er i F7 le t D ro p e li m i n a to r Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 11.5 m3/s (2016) and 11.0 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 7.8 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 80 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 5400 1,50 Max. airflow m3/h 43200 m3/s 12.0 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 130 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights Left-hand version SILVER C SD, size 80 Right-hand version Delivery and transport within the site The SILVER C SD 80 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. The unit is supplied on 100 mm high support feet made of steel. Fan Fan + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air Outdoor air Duct connection options A: Specify right-hand or left-hand version when ordering. Supply air Extract air Exhaust air Airflow direction B: Specify fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). 21 21 J L3 L2 L1 F 164 21 E C Power connection 21 SILVER D E C SILVER SILVER F H J 100 52 52* 100 Fan Fan + filter B** G I Fan + filter + coil heat exchanger L3 L2 L1 200 SuppliedF on 100 164 mm high supportE feet. The feet Ccan be re21moved or kept as21they are when the unit is at its final location. The unit has provision for mounting adjustable support feet. 21 J 21 D E SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. SILVER F H Size J 100 45 A 52 52* 80 Weight, kg Weight, kg Weight, kg fan fan + filter fan + filter + coil 602-640 833-909 1613-1689 Size L1 L2 L3 A B H C D E F G I J 80 1327 2550 3452 2485 2637 1320 1275 902 1275 1000 1800 419 160 Clear space for inspection A clear space of 900 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A*** * Two fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422 We reserve the right to alter specifications. 131 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 100 Airflow, m3/h Total pressure rise, Pa Ca p. va Ca r. 1 p. va Fan r. 2 SFPv= 1,25 1,0 0 2 0,75 1 80 85 90 Total pressure loss, Pa L w,tot 75dB Co e il h 95 at ex n cha ge rs F7 Droplet elim inator Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 100 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 5400 1,50 Max. airflow m3/h 43200 m3/s 12.0 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 132 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 100 Delivery and transport within the site The SILVER C SD 100 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. Fan + Section for power conn. Fan + Section for power conn. + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. Outdoor air B: Specify upper fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,500 x 800 mm. L2 L1 E 56 21 C 21 SILVER L3 D E 191 M 21 J Supply air Extract air Exhaust air Airflow direction C SILVER SILVER Power connection F H J 100 56* Fan Filter + fan I N Filter + coil heat exchanger + fan L2 L1 B** G O I N 200 E 56 21 E 191 M 21 J C 21 SILVER SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H Size 122 77 1048 45 J 100 1000 3186 56* 100 1048 Weight, kg Weight, kg Weight, kg fan filter + fan filter + coil + fan 654-834 1183-1363 2187-2367 77 Size L1 L2 L3 B H C D E F G I J M N O 100 1182 2252 3396 3340 1620 1126 1144 1126 1200 2400 470 210 800 170 2500 Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A*** * Two fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422 We reserve the right to alter specifications. 133 L3 D SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 120 Airflow, m3/h Ca Total pressure rise, Pa Fan p. va 2 r. p. va Ca r. 1 100 v=1 ,25 SFP 2 1,00 1 Total pressure loss, Pa L w,tot 80dB 85 Co il he 90 e at xc h 95 g an er 0,7 5 s F7 t Drople elimin a to r Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air handling units without coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016/2018 if the mean supply air and extract air flows do not exceed 17.0 m3/s (2016) and 16.4 m3/s (2018) respectively. Air handling units with coil heat exchangers, capacity variant 2 and full face end connection panels, comply with requirements to Ecodesign 2016 if the mean supply air and extract air flows do not exceed 12.7 m3/s. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size 120 Min. flow (For units operating in the airflow reg. mode) m3/s m3/h 9000 2,50 Max. airflow m3/h 64800 m3/s 18,0 Correction factors, KOK , dB Sound path Octave band, no./mid-frequency, Hz Range in diagram 1 2 3 63 125 250 4 5 6 7 8 500 1000 2000 4000 8000 To the outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11 2 2 -4 -7 -7 -10 -12 -16 -17 To the inlet duct* 1 -5 -6 -2 -10 -14 -12 -10 -6 2 0 1 -2 -11 -16 -14 -15 -11 1 -15 -23 -30 -26 -41 -42 -45 -42 2 -9 -18 -30 -28 -43 -45 -50 -48 To unit’s the surroundings * The integral attenuation of the filter and coil heat exchanger are not included. 134 We reserve the right to alter specifications. 20160422 SILVER C Sizing, installation, dimensions and weights SILVER C SD, size 120 Delivery and transport within the site The SILVER C SD 120 units are available in right-hand or left-hand version as a fan section, fan + filter or fan + filter + coil heat exchanger. The air handling units are supplied as one unit if they each consist of a fan or fan+filter. If the unit consists of a fan + filter + coil heat exchanger, it is supplied as two units. The one unit then consists of a fan + coil heat exchanger and the other unit consists of a filter. The air handling unit can be split at the building site to facilitate transporting it within the site. The sections are jointed together by means of bolts. The SILVER C SD can be used as a supply air or an extract air handling unit. Fan + Section for power conn. Fan + Section for power conn. + Filter Fan + Filter + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan + Filter + Coil heat exchanger in supply air Duct connection options A: Specify right-hand or left-hand version when ordering. Outdoor air B: Specify upper fan outlet for upward air discharge when placing orders (Does not apply to units installed outdoors). N.B.! Duct connection size: 2,500 x 800 mm. L2 L1 E 56 21 C 21 SILVER L3 D E 191 M 21 J Supply air Extract air Exhaust air Airflow direction C SILVER SILVER Power connection F H J 100 56* Fan Filter + fan I N Filter + coil heat exchanger + fan L2 L1 B** G O I N 200 E 56 21 E 191 M 21 J C 21 SILVER SILVER * The air handling unit can be supplied without end connection panels. ** Width of coil heat exchanger (if required) = B + 200 mm. F H 122 77 1048 45 Size J 100 1000 3186 1048 56* 120 77 Weight, kg Weight, kg Weight, kg fan filter + fan filter + coil + fan 757-968 1286-1497 2290-2501 Size L1 L2 L3 B H C D E F G I J M N O 120 1182 2252 3396 3340 1620 1126 1144 1126 1200 2400 470 210 800 170 2500 Clear space for inspection A clear space of 1,000 mm should be provided in front of the unit. Rated data per fan Motor shaft power: 3 x 6.5 kW alt 3 x 10 kW*, motor control system: 3 x 400 V, 50 Hz, rated 11.9 A** alt. 7.5+12 A*** * Three fans per airflow direction. ** One motor control system per fan (Cap. var. 1). *** Two motor control systems per fan (Cap. var. 2). 20160422 We reserve the right to alter specifications. 135 L3 D SILVER C 136 We reserve the right to alter specifications. 20160422