Transcript
Perfect integration into the ceiling Nice design with two different panels Fresh air supply possible Individual louver control
4-way cassette DIGITAL INVERTER 4-way cassette is designed to provide
Two louver shape options: straight flow louver and wide
uniform air distribution and total comfort; it
flow louver; optimum air distribution.
is the ideal solution for small commercial
Light-weight unit, for easy and quick installation.
applications. Every component for the air
Built-in high-lift drain pump.
distributuion was designed to guarantee the users the maximum flexibility of operation
Self-cleaning function and the Ag-ion tip for anti-mould
and the optimum air delivery in any
in drain cap.
conditions. The louver shape ensures
Individual setting of louver position: 3 different Swing
uniform distribution and long air throw
modes: standard, diagonally opposite, turn-around.
while the louver motors controls the
Wireless remote control and optional wired remote
direction and patterns of air flow.
controller and timer. Differnet panel option to blend easily in different ceiling design. Accessories: 2 Panel versions: RBC-U31PG(W)-E (moon white, for wide airflow, both blowout options a + b) RBC-U31PGS(W)-E (moon white, for direct airflow; blowout option a)
RAV-SM1404UTP-E
Technical data Heat pump
Indoor unit
Cooling capacity (cooling)
kW
12,00
Range of performance (cooling)
kW
3,00-13,20
Heating capacity (heating)
kW
12,80
Range of performance (heating)
kW
3,00-13,20
Energy label (cooling)
A
Energy label (heating)
A+
Efficiency (EER) (cooling)
2,80
Efficiency (COP) (heating)
3,76
Efficiency (SEER) (cooling)
5,36
Efficiency (SCOP) (heating)
4,19
Power supply
V
230
Fusing
A
25
Power consumption (cooling)
kW
0,60 - 4,71
Power consumption (heating)
kW
0,60 - 4,50
Dimensions (H/W/D)
mm
319x840x840
kg
24 + 4,20
Air power volume
m³/h
2010
Air power volume
l/s
583
Net weight
Sound pressure level (cooling)
db(A)
34/38/44
Sound pressure level (heating)
db(A)
34/38/44
Pipe dimension liquid
mm/"
9,5 (3/8)
Pipe dimension gas
mm/"
15,9 (5/8)
Pipe length, maximum
m
50
Pipe length, pre-charged
m
30 (40g/m)
Refrigerant, charged
kg
2,80
Height difference (outdoor unit higher/lower)
m
30
Outdoor temperature (cooling)
°C
-15 - +46
Outdoor temperature (heating)
°C
-15 - +15