Transcript
FA 12-100D
12V100Ah
Front Access SLA Battery Range Summary By combining the newly developed paste formula with up-to-date AGM structures, BSB created the innovation FA range of batteries. The range features 12 years design life and front access connections for fast, easy installation and maintenance. This series is highly suited to telecom applications, UPS systems and other back up applications.
Application · Communication Equipment · Medical Equipment · Emergency Power System
· Telecom · Control Equipment · UPS
General Features · Easy maintenance and installation · No need for extra (wrench space) above battery · Sealed and maintenance free operation · Non-Spillable construction design · ABS containers and covers(UL94 V0,optional) · Safety valve installation for explosion proof · Maximized energy density for installation in relay rack trays · High quality and high reliability · Exceptional deep discharge recovery performance · Flexible design for multiple installation positions
5mm (0.20inch)
18mm (0.71inch)
M6mm (0.24inch)
Construction Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
Safety valve Terminal Separator Electrolyte
Lead dioxide Lead ABS ABS Epoxy Resin
...... ...... ...... ......
EPDR Copper AGM Sulfuric acid
Terminal Dimensions
105mm(4.13inch)
287mm(11.3inch)
390mm(15.4inch)
Battery Model
FA12-100D
Designed Floating Life
12 Years
Capacity(20oC)
Dimensions
20HR(5.29A,1.80V)
10HR(10A,1.80V)
5HR(17.2A,1.75V)
106Ah
100Ah
86.0Ah
Length
Width
Height
Total Height
390mm(15.4inch)
105mm(4.13inch)
287mm(11.3inch)
287mm(11.3inch)
66.0Ah
Approx. Weight
33.5Kg (73.9 lbs)
Internal Resistance
Full charged at 20oC: 0.0063 Ohm
Self Discharge
3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(66.0A,1.60V)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use 14.1-14.4V(-30mV/ oC), max. Current: 25A
Page 1 of 2
Float use 13.5-13.7V(-18mV/ oC)
FA 12-100D
12V100Ah
Charge Voltage
Constant Charge at 0.25CA-2.35V (20oC)
(CA) (V/Cell)
(%) 120 100
0.25
Charge Capacity
Charge Voltage
2.35 80
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20oC)
Charge Characteristic Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Front Access SLA Battery
Charge Current
0
2
4
6
8
10
2.17 2.00 1.83 0.25CA 0.1CA 0.05CA
1.67 1.60
3CA
2CA
1CA
6
12
30
1.33 0
12
2
60
3
Min
Time(hour)
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
0.6CA
2.08
2.00
85 80 75 70 65 60 55 50
1.92
1.83
45
0
10
20
30
40
50
60
70
80
90
40 0
100
o
1
2
20oC
o
40 C
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F.V/Time
5min
10min
15min
30min
1h
3h
4h
5h
10h
20h
1.60V
350
240
175
105
66.0
26.0
20.0
17.7
10.6
5.53
1.67V
315
219
170
102
65.9
25.8
19.9
17.5
10.5
5.51
1.70V
299
211
164
100
65.7
25.7
19.8
17.4
10.4
5.50
1.75V
266
195
155
98.0
65.0
25.5
19.7
17.2
10.2
5.49
1.80V
240
181
148
95.0
64.2
25.2
19.5
17.0
10.0
5.29
1.85V
182
149
128
87.4
63.5
25.0
19.4
16.6
9.83
4.98
Constant power discharge ratings-watts at 20oC F.V/Time
5min
10min
15min
30min
1h
3h
4h
5h
10h
20h
1.60V
577
398
310
198
130
52.4
42.5
36.5
21.2
10.9
1.67V
547
393
307
194
126
52.2
42.3
36.3
20.9
10.7
1.70V
511
383
302
189
122
52.0
42.1
36.2
20.7
10.5
1.75V
476
358
284
184
121
51.6
41.9
36.1
20.4
10.3
1.80V
427
333
267
179
119
50.9
41.3
35.5
20.0
10.1
1.85V
342
276
233
164
118
50.7
40.9
35.0
19.7
9.86
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2
(Updated: 1-Nov-2010)