Transcript
Grid Box - EX Series The Grid Box Solution is a turn-key, hassle free grid connection solution for PV integrators in all states of Australia. Central to the Grid Box Solution is a set of grid protection switchboards, AKA “Grid Boxes”, that are premanufactured and programmed to meet the specific requirements of each of the Australian DNSPs. The Grid Box is installed between the PV inverters and site’s main switchboard. This provides a “plug and play” solution to secondary protection and grid integration.
CTP provides fixed fees for a complete package of grid connection application, protection equipment, controls, system commissioning and engineering sign-off.
CTP has connected PV systems in every state with roof mount projects up to 500kW and ground mount projects up to 3,520 kW in size.
CTP works to the utility’s demanding standards every day. All protection equipment used is IEC 60255 approved and our Grid Boxes are manufactured according to AS3439.1, AS3000, AS3008, AS60947, AS60898 The Grid Box – EX series offer secondary protection where export is permitted and is suitable for installation on commercial PV systems across most of Australia’s electricity networks outside of WA and QLD. Features include approved secondary protection, indicator lamps, back-up generator inter-trip, remote monitoring interface, indoor / outdoor rated, commissioning test points and optional surge protection. The Grid Box has an unmatched build quality fully supported by CTP’s renowned customer service and technical expertise.
W: http://www.clean-tech.com.au/ P: 03 9005 7371 E:
[email protected]
Grid Box - EX Series Grid Box – EX Series Specifications Product* MP-CN100-00-04I-EX Electrical Specifications PV System Sizes Number of 3-Ph Inverters Max Inverter Current Main Switch Rating Contactor Rating Form Rating Fault Level Compliance Protection Relay Protection Functions (ANSI) Protection Relay Compliance Standards DNSP Compatibility**
MP-CN160-00-04I-EX
MP-CN160-00-06I-EX
66–100 kW Up to 4
66–100 kW Up to 6
30-65 kW Up to 4
125A 100A
3-Ph 63A (string inverters, central inverter design also available) 160A 160A 1 10 kA (up to 30 kA, upon request) AS3000, AS3008, AS60947, AS60898 ComAp MainsPro 27, 59, 81H, 81L, 78, 81R, 47
160A 160A
IEC 60255, CEI 0-21, G83, G59/2, UL, VDE-V-0126-1-1, VDE-AR-N 4105, IEn NR 005/2012 Ausgrid, Ausnet Services (formerly SP Ausnet), Endeavour Energy, Essential Energy, Jemena, Powercor/CitiPower, SA Power Networks, and United Energy
Mechanical Specifications Dimensions (H x W x D) IP Ratings Construction Material Gland Plates Mounting Colour Temperature Construction Standards
1000 x 700 x 250
1200 x 700 x 250 1200 x 700 x 250 IP42 (standard), IP 56 (optional) 2mm Mild Steel IP42 - Top and Bottom; IP56 - Bottom only Wall - out of direct sun exposure Electric Orange (standard), White, Grey, Vintage Green -20°C to 65°C within enclosure (-approx. -20°C to 45°C ambient) AS3439.1
Additional Features Standard
-
Optional
Back-up Generator Inter-trip Indicator Lights Commissioning Testpoints Remote Monitoring Interfaces (BMS/SCADA) Surge Diverter Additional MCBs Swap Main Isolator for Circuit Breaker Pattern-approved Meter for LGC creation /PPA
*custom Grid Boxes can be made to accommodate your project needs. Please contact CTP for details ** each DNSP requires different protection set points pre-programmed as part of Grid Box
Grid Box Protection Board Grid Box Comprehensive Solution
W: http://www.clean-tech.com.au/ P: 03 9005 7371 E:
[email protected]
In addition to providing quality GRID BOX protection boards – CTP offers a complete range of services required to see your project through to grid connection. CTP can also design custom grid connection solutions for PV projects of any scale including multi-megawatt solar farms.