Preview only show first 10 pages with watermark. For full document please download

Similar Pages

   EMBED


Share

Transcript

INSTALLATION GUIDE RELAYS TM V100D V100D Dual 10A SPDT Enclosed Relays 10-30 VDC/AC or 120 VAC Coil Installer’s Specifications Operating Temperature -40°C to 55°C (-40° to 131°F) Operating Humidity 10-90% non condensing Expected Relay Life Electrical (at rated current): 100,000 cycles Mechanical (unpowered): 10,000,000 cycles Relay Status LED ON=energized Wire Specifications: Lead Length 14” (356mm) min. Gauge UL1015; Coil: 18 AWG; Contacts: 16 AWG Insulation Class 600 VAC RMS Agency Approvals UL508 enclosed device listing INSTALLATION Disconnect and lock out all power sources before beginning the installation. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • • • • • Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Turn off all power supplying equipment before working on or inside the equipment. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Failure to follow these instructions will result in death or serious injury. NOTICE • • • • This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure. DIMENSIONS 3.8" (97 mm) Relay #1 3. Connect Coil: • Choose the coil common lead (white with yellow stripe) and connect it to the (-) source termination point. • Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (120VAC, white with black stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.* NOTE: When connecting the control side of this device (#18 wires) to power line circuits, provide current limiting at 7 amps max. 4. Connect Relay Contacts: • Choose the relay common wire (yellow) and connect to switched load. 5. Connect Coil: • Choose the coil common lead (white with violet stripe) and connect it to the (-) source termination point. • Choose either the low voltage (10-30VAC/DC, grey with white stripe) or high voltage (120VAC, white with red stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.* NOTE: When connecting the control side of this device (#18 wires) to power line circuits, provide current limiting at 7 amps max. 2.0" (52 mm) 2.3" (59 mm) 3/4" NPT Nipple PAGE 1 2. Secure with the conduit nut provided. Relay #2 4.0" (103 mm) Z203399-0C 1. Using the threaded nipple connect the relay to the desired enclosure through a knock out hole. 2.5" (64 mm) 6. Connect Relay Contacts: • Choose the relay common wire (violet) and connect to switched load. • Choose the relay N.O. (brown) and/or* N.C. (grey) lead and connect to switched load. 7. Secure the enclosure and reconnect power. * Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut. ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 02122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. INSTALLATION GUIDE V100D TM WIRING COLOR CODES WIRING EXAMPLE Relay 1 Nipple mount directly to a panel CONTROL SYSTEM INPUT White 120VAC Common 10-30VAC/DC White COIL w llo ye w llo ye COMM wht/yellow CON TAC TS YELLOW White e blu e blu LOW wht/blue To Load N.C. ck bla ck bla HI wht/black CONTACT OUTPUT To Controls Common ORANGE N.O. Relay 2 CONTROL SYSTEM INPUT HI wht/red CONTACT OUTPUT 120VAC To Load CONTACTS COIL N.C. Nipple mount to any 2x or 4x electrical box LOW grey/wht COMM wht/violet Wire Nut Common 10-30VAC/DC To Controls N.O. COMMON CONTACT AND COIL SPECIFICATIONS LED CONFIGURATION Relay 2 Relay 1 10V.......................................... 12V.......................................... 24V.......................................... 30V.......................................... 120V........................................ AC DC 8 9 78 AC DC 2 3 18 Coil Current AC DC 25mA 14mA 25mA 14mA 31mA 16mA 39mA 18mA 22mA - RELAY 1 Pull in Voltage 10-30V..................................... 120V........................................ Drop Out Voltage 10-30V..................................... 120V........................................ Voltage RELAY 2 TYPICAL COIL PERFORMANCE CONTACT RATINGS Resistive.............. 10A@277VAC, 28VDC Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C. 240VAC, 1/3HP N.O. & 1/6HP N.C. 277VAC, 1/4HP N.O. & 1/8HP N.C. Pilot Duty............. 277VAC, (1.7A), 480VA N.O. Ballast.................. 277VAC, 1.7A Tungsten............... 120VAC, TV3 N.O. TV2 N.C. Gold Flash............. Yes Z203399-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 02122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.