Preview only show first 10 pages with watermark. For full document please download

Similar Pages

   EMBED


Share

Transcript

Product Manual Applies to Index remote cooler range: - Index21 AC, Air cooled models with part code commencing– 06 1 3601xx - Index21 WC, Water cooled models with part code commencing– 06 1 3602xx Contents Section Content 1. Introduction 2. Installation Instructions 3. Service Maintenance instructions 4. Fault Finding 5. Product Photos 6. Data Sheets 7. Parts Lists and exploded views 8. Wiring Diagrams 1. Introduction The Index remote cooler is a functional and robust remote cooler, designed with the installer and service technician in mind. It’s simple and effective operation delivers reduced operating costs and reduced life costs. The Index is built to BDA standards, ensuring that the lid is interchangeable, there is simple exchange of serviceable parts and standard cassette product coils. Index also has a small footprint, minimising the valuable space taken up in account cellars or back room IMI Cornelius is able to offer one of the most extensive ranges of equipment together with a support package which is second to none. 2. Installation 2.1. Requirements Summary Installation must be carried out by a suitably trained person and comply with national and local codes for connection to the electrical supply. - Unit must be installed indoors on a dry, level surface Good ventilation (minimum 100 mm gap around unit) Access to side, top and front Electrical - 13 amp, 230V Grounded, switched (preferably an RCCB) Socket within 2m of unit INDEX 21 AC (air cooled) - Outside a chilled cellar, close to beer storage - Ambient temperature 10 to 43°C INDEX 21 WC (water cooled) - Base unit inside chilled cellar - Ambient temperature o Base unit 10 to 38°C o Heat Discharge Unit -10 to 35°C - Maximum distance between base unit and heat discharge unit o 30 metres using 1.5mm2 cable o 50 metres using 2.5mm2 cable - Glycol Mix- must be pre-mixed before adding to the unit o Glycol 30% / Water 70% (minimum) o Glycol 40% / Water 60% (maximum) - Prepare maximum 12 litres for 50m flow and return of 11.5mm ID - Minimum glycol flow rate 4.5 litres/min 2.2 Installation Instructions PLEASE READ CAREFULLY BEFORE INSTALLING THE UNIT Please follow these instructions carefully. Only if the remote unit is properly installed and maintained will trouble free operation and customer satisfaction be achieved. GENERAL DESCRIPTION This is a remotely sited cooler used for cooling drinks such as beer, lager, cider & stout. Incorporating mechanical temperature control this unit is suitable for the utilization of water as the product cooling medium and for the formation of an ice reserve. A recirculation pump provides both constant agitation of the water bath and a flow of re-circulating chilled cooling medium for python cooling. The remote cooler is fully automatic, therefore, the electrical supply must not be interrupted (unless access for maintenance is required), otherwise reduced performance and reliability will occur. SAFETY Read this booklet before undertaking installation or maintenance. Recognize safety alerts – isolate the power supply before removing panels. DANGER - Indicates an immediate hazardous situation which, if not avoided, WILL result in serious injury, death, or equipment damage. WARNING - Indicates an immediate hazardous situation which, if not avoided, COULD result in serious injury, death, or equipment damage. CAUTION - Indicates an immediate hazardous situation which, if not avoided, MAY result in minor or moderate injury, or equipment damage. HANDLING & TRANSPORTATION    Keep the remote cooler in an upright position and do not drag over rough floors or down steps. Upon receipt, unpack the unit carefully and visually inspect for any damage which may have been sustained during transit. Record the nature of any damage on the courier’s delivery note and, at the same time inform your supplier. Once the unit is in position, do not move when filled with water INSTALLATION   Installation must only be carried out by suitably trained person and must comply with national and local codes for connection to electrical supplies. It is recommended that the installation is protected by an RCCB (Residual Current Circuit Breaker). SITING Remote A/C & W/C Units   Remote units are designed for indoor use only. The remote units may be sited within cooled cellars, store rooms or other appropriate internal areas where the ambient air temperature is between 5°C and 43°C (A/C), 38°C (W/C).         Remote coolers should not be exposed to liquid spillage, spray, steam or humidity at a higher level than 90% rh. Site the cooler within 40 metre’s of the point of dispense. Locate the cooler within 2 metre’s of an earthed, switched, 13 Amp, 230V 50Hz socket which is accessible for isolation of the equipment. The socket must be installed to comply with current IEE regulations. Site the cooler on a firm level surface, protect from physical damage and do not place items on top of, or underneath the cooler. Clear space must be provided above the unit. Allow 50mm clearance around the unit to aid air circulation and keep the front of the unit clear to allow an unimpeded air supply to enter the cooler. Air vents should never become obstructed or blocked. Access should be possible to the front panel for ease of service. Do not stand on this unit. INSTALLATION General WARNING - The appliance must be earthed.   If not already fitted, fit the appropriate electrical plug to the service cord. The fuse rating is stated on the rating plate. With the unit unpacked and in position, remove all coil caps, but do not connect to an electrical supply at this stage. Filling the product water bath.  Do not use de-ionised water or add any substance to the water (unless approved by Cornelius).  Do not leave hose pipes unattended whilst filling the product water bath as the unit may become flooded.  Open the filler / inspection hatch on the lid of the cooler.  Fill with cool clean water until liquid starts to flow from the overflow  Stop filling and close the filler / inspection hatch on the lid of the cooler  The overflow is a 15mm connection. A fitting or pipe can be pushed directly into this to direct the condensate water to drain Discharge unit (water cooled models) The discharge cooler should be mounted on an exterior wall, not south facing, and provide access for pipes and electrical cable to the base unit (maximum 50m). If no exterior wall is available then mount inside on a wall in a cool room with plenty of fresh air ventilation. Avoid warm areas (i.e. cupboards or small storerooms). Secure the discharge cooler to the chosen location and fix (follow instruction guidance from the discharge cooler). 2 Using a minimum 1.5mm two core cable, connect the Discharge Cooler to the remote W/C cooler. Connect the two core cable to the quick fit terminal block, this is located at the rear of the W/C cooler (Note: This is a nominal 24V 50Hz supply). Complete the glycol circuit by connecting the pipe work between the remote W/C cooler and the discharge cooler utilizing 15mm Service Valves. WARNING - As the glycol lines will circulate a warm glycol mix it is important for safety reasons that suitable tubing is used. Consult a specialist tubing manufacturer or contact Cornelius. WARNING - PVC tubing, whether braided or not, is not suitable for this application. The tubing ID must be sufficient to ensure a minimum flow rate of 4.5 litres/minute in the glycol circuit. It is recommended that an ID of at least 11.5mm be used. Avoid using elbow joints as these cause pressure drops. The tubing must not be routed next to hot surfaces or sharp edges. Avoid ups and downs in each glycol line as this may create air locks. Do not kink or crush the tubing, ensure minimum bend radii of 100mm and support where necessary. WARNING – The lines should never be taped together or insulated. Priming the discharge unit coolant circuit (water cooled models) CAUTION – As the python is not connected at this stage disconnect the electrical supply connection for the recirculation pump from the socket on the rear panel at the back of the cooler. Mix monopropylene glycol and water to give a solution of Minimum 30% glycol 70% water, Maximum 40% glycol 60% water. Glycol should be mixed in a clean container. CAUTION – Always mix the water : glycol before filling the system. WARNING - Do not use ethylene glycol. Ensure sufficient glycol/water mixture is available for filling the coolant bottle and topping up during priming before switching the remote W/C cooler on. You will need to prepare: 4 litres of glycol/water mix to fill the water cooled unit coolant system. In addition the complete system will require topping up with the following quantities to give a Minimum 30:70 to maximum 40:60 glycol/water ratio whilst priming:  2.1 litres for every 10m of 11.5mm ID tubing  4.2 litres for every 20m of 11.5mm ID tubing  6.3 litres for every 30m of 11.5mm ID tubing  8.4 litres for every 40m of 11.5mm ID tubing  10.5 litres for every 50m of 11.5mm ID tubing Fill the coolant reservoir to the maximum level (indicated on the front of the coolant reservoir). CAUTION – ensure all service valves are in the open position prior to switching on the remote unit Switch on the mains electrical supply to the remote W/C unit. As the coolant circuit primes, the level of coolant in the reservoir will drop. Keep filling the reservoir with the prepared 30:70 / 40:60 glycol/water mixture, ensuring the level does not drop below the minimum or exceed the maximum levels indicated on the front of the reservoir CAUTION – do not allow the base mounted coolant pump to run dry. Connecting the python & product lines. CAUTION – Ensure the electrical supply connection for the recirculation pump is disconnected from the socket on the rear panel at the back of the cooler. If the mains electrical supply to the remote cooler is not already switched on, switch it on now. CAUTION - All tubing/pythons must be routed to prevent undue stress, tight bends or kinking. From the product python connect the recirculation lines to the flow and return of the top mounted recirculation pump on the remote cooler. It is recommended that this connection is made utilizing 15mm Service Valves to aid with future service requirements. CAUTION - Ensure the recirculation lines are looped at the point of dispense and plug the electrical supply lead for the recirculation pump into the socket on the rear panel at the back of the cooler. Check all plumbing connections for leaks. As the python recirculation lines prime the level of liquid in the product water bath will drop. Refer to section ‘Filling the product water bath’ to top up to correct level. Connect product in and python supply to each connection on the product coils of the remote cooler. Utilize 3/8” push fit connectors. Note: All lines to be well insulated to the requirements of the system. OPERATION Once connected to the mains electrical supply allow time for the cooler to build a full icebank (refer to relevant Product Data Sheet for time to full icebank), the cooler is now ready to use. Note: there are no user adjustable controls on this remote unit. SERVICE INFORMATION There are no user serviceable items inside the equipment. Maintenance and repairs must only be carried out by a properly qualified trained person. Should the unit malfunction, suffer spillage, physical damage or component failure SWITCH OFF AND UNPLUG THE UNIT FROM THE MAINS ELECTRICAL SUPPLY. CAUTION – Do not switch the unit ‘off’ and ‘on’ within 5 minutes. If any maintenance/servicing is required, refer to the fault finding chart, wiring diagram and exploded drawings contained in the manual. Only use Cornelius recommended spare parts for cooler maintenance, failure to do so will invalidate cooler approvals and warranty. Condenser – It is recommended that the condenser is cleaned with a soft brush or vacuum cleaner at least every 6 months. Product water bath – It is recommended that the water in the water bath is replaced annually. - Melt the ice bank. - Drain the water bath. - Refill the water bath. Description of controls Refrigeration system reset The Water Cooled remote utilises a refrigeration system cut out switch. This switch is of manual reset type and is located in the refrigeration system compartment, behind the removable service panel. Upon activation of the switch, diagnose the cause and rectify the problem. Once the problem is resolved allow 10 minutes then press the Refrigeration System Reset button. PREVENTATIVE USER MAINTENANCE For all of the below, once the maintenance is carried out, follow the Installation instructions for re commissioning the unit  Switch off and unplug the unit during user maintenance operations.  In the event of the unit malfunctions or suffers spillage or physical damage, unplug the unit from its electrical supply.  CAUTION - Do not switch the unit ‘off’ and ‘on’ within five minutes.  Do not attempt to remove the protective covers. Product water bath level If the cooler becomes noisy – makes a gurgling sound, this is due to a low product bath water level and will result in reduced cooling capacity. To remedy this follow the instructions for ‘Filling the product water bath’ Sanitizing Product Coils     WARNING - Under no circumstances should boiling water or steam be used with this unit as it may result in permanent damage. The maximum temperature permissible for any liquid used for sanitising is 40°C. Sanitize when taste is tainted or periodically as advised by the beverage supplier. Important flush with potable water, then chlorinated alkaline solution. CAUTION - It is important that the sanitizing agent manufacturer’s procedure and safety precautions are followed when using caustic chemicals. Rinse through with potable water to remove cleaning solution and test with litmus paper. The 1989 Electricity at Work Regulations require periodic testing of electrical equipment and this should only be carried out by a competent person. Directive Compliance: EMC Directive (2004/108/EC) Low Voltage Directive (2006/95/EC) Machinery Directive (89/392/EEC) 3. Service Maintenance Instructions 3.1. INDEX 21 AC 1. Check that the water level in the water bath is up to the overflow. 2. Check and clean the rear Condenser fins. Dirt and dust can block the air vents in the condenser, severely reducing the effectiveness of the refrigeration system. 3. Check that there is adequate airflow through the unit, ensuring enough space all round and that there are no obstructions in the front of the air flow vents. 4. Check ambient temperature is between 10°C and 43°C. 5. Check the condition and the effectiveness of the Python insulation. 6. Check for restrictions in the water recirculation python lines (6 ltr per min) 7. Check for algae growth in the water bath. 8. At regular intervals, to be determined by the owner and/or the user, the cooler should be checked for electrical safety. 3.2. INDEX 21 WC 1. Check that the water level in the water bath is up to the overflow. 2. Check that the Discharge Unit fan is working and that there are no obstructions or blockages of the air vents. 3. Check and clean the heat exchanger fins on the back of the Discharge Unit. Dirt and dust can block the air vents in the heat exchanger, severely reducing the effectiveness of the refrigeration system. 4. Check ambient temperature is between 10°C and 38°C (base unit) -10°C and 35°C (heat discharge unit). 5. Check the condition and the effectiveness of the Python insulation. 6. Check the Python for correct water recirculation. 7. Check for algae growth in the water bath. 8. At regular intervals, to be determined by the owner and/or user, the cooler should be checked for electrical safety. 9. Check the glycol lines are not kinked or crushed. Check for leaks. 10. Check the strength of the glycol/water mix using a refractometer (20% brix minimum) or a hydrometer 11. Check the level of coolant (Water/Glycol) in the reservoir and re-fill as necessary with a 30% Glycol 70% Water mix using a clean container 4. Fault Finding Chart Maintenance and repairs must only be carried out by a properly qualified and trained person., Always switch off and unplug the equipment before servicing or repairing the unit PROBLEM 1. Totally Inoperative Is supply fuse blown or has circuit breaker tripped? Yes Is fuse or circuit breaker size correct? Yes Is line voltage within 240v +6/-10%? No Is line voltage too high or low? No 2. No Cooling Is line voltage within 10% of nameplate voltage? Yes Is compressor cold, fan motor and green neon on? No Compressor doesn’t start, hums and trips on overload No Compressor starts but start winding does not switch off POSSIBLE FAULT REMEDY SERVICE TIP No Loose connection or broken wire in supplying wiring to unit Replace or reconnect wire Install within 2m of an electrical socket No Incorrect size device Install correctly sized device See rating plate for current consumption Yes Loose connection or broken wire in supply wiring to unit Replace or reconnect wire Charred connection indicates poorly crimped electrical connection Yes Improper voltage supply Unit malfunction Consult electrical supplier Contact IMI Cornelius Voltage range 207v to 253v No Go to 1. Totally inoperative Go to 1. Totally inoperative Go to 1. Totally inoperative Yes a) b) c) Faulty thermostat Low water Refrigeration system cut out a) b) c) replace Top up Diagnose cause and reset a) b) c) Do not kink phial tube See install instructions Always isolate electrical supply before undertaking repairs Yes a) b) a) c) d) Check connections, replace capacitor if necessary Check connections, replace relay is necessary Replace compressor Replace compressor a) c) d) Start capacitor shorted or blown Start relay will not close or is burned out Compressor motor is faulty Compressor ceased Check for paper debris of blown capacitor Relay will rattle if OK See rating plate for gas charge Always fit new drier a) b) c) Improper wiring Relay failing to open Excessively high discharge pressure a) b) c) Replace and reconnect wiring Replace relay Clean condenser or replace fan motor a) Yes b) b) c) d) b) Always isolate electrical supply before undertaking repairs Ensure correct relay is used d) e) No Compressor running hot. Compressor starts and runs short, cycling on overload protector 3. Warm Product Is compressor running? Yes Low water bath level No Ice bank build? No Yes a) b) c) d) Open or shorted windings in compressor motor Tight compressor (binding internally) d) e) Defective refrigeration compressor cut out Excessively high discharge pressure Suction gas too hot Low refrigerant charge a) b) c) d) Replace compressor Replace compressor c) d) e) Replace thermal cut out Clean condenser or replace fan motor Water bath too hot- cool to below 30°c Repair leak and recharge refrigerant a) b) c) d) Use vacuum cleaner or soft brush to clean condenser See rating plate for gas charge Always fit new drier Always isolate electrical supply before undertaking repairs Leave 100mm gap around unit Ss Traces of oil are a good indicator of leaks No Go to 2. No Cooling Go to 2. No Cooling Go to 2. No cooling Yes a) b) a) b) Check for leaks and fill to overflow Ensure python is fully primed on install a) a) Plug pump into socket on the base or replace failed pump Check for kinks or algae growth Fit longer coil Change ambient or re-site cooler Clean condenser grille or remove objects in front of the condenser which are restricting air flow into the unit Replace condenser fan motor assembly Check for leaks, repair and recharge Leave for an hour. If ice bank still does not reform, check specification against account requirement Refill with 30% Glycol, 70% Water. Check for leaks Replace Check all stop valves are open. Check glycol lines are not kinked or crushed. Ensure pump priming procedure is strictly adhered to a) Yes a) Leaks Insufficient water recirculation python priming Water recirculation pump not electrically plugged in or failed b) Blockage in python c) Product coil too short Check cooling system a) High ambient b) Condenser blocked c) Defective condenser fan moor assembly d) Loss of refrigerant charge e) Incorrectly specified cooler f) No coolant in glycol tank g) Coolant base pump failed h) Coolant not flowing through discharge cooler i) Discharge cooler airflow blocked j) Discharge fan failed k) Transformer failed l) Mechanical thermostat failed m) Poor airflow through condenser b) c) a) b) c) d) e) f) g) h) b) b) c) a) b) c) d) e) f) g) h) i) j) Ice build will displace water to the overflow Insufficient python insulation seriously reduces cooler performance Run cable to ensure cable cannot be accidentally dislodged in future Add algae inhibitor in the water bath Extra long coil takes up two spaces Ensure unit works within ambient range 5-43°c (A/C) & 5-38°c (W/C) Leave 100mm clearance around unit Unbalanced fans cause motor failures Never leave service valves on cooler after repair 1000 pints per hour peak capacity theoretically. Python load will reduce this Keep tank full to overflow Refrigeration system cut out isolated the base mounted coolant pump Never insulate glycol lines Use 1.5mm2 cable to connect from base unit to discharge cooler Discharge fan runs continuously with n) o) p) 4. No Product 5. Product too Cold Too many coils in the cooler for such a high demand Product inlet temperature too high Excessive python length Ice bank too large. Product frozen a) b) Low throughput Coil too long i) j) k) l) m) Clear blockage. Clean fins as necessary Replace fan motor Replace transformer Replace Check for space around the cooler and airflow obstruction. Clear and clean the condenser fins n) Reduce the number of products on the cooler. Fit further cooler if necessary o) Reduce the temperature of product storage area p) Limit python length to 40m maximum (dependent on product throughput) or install separate cooler for python and separate cooler for product cooling Erode ice around thermostat with warmer water (less that 60°c) then check and replace thermostat if faulty a) Reduce number of taps per product b) Fit shorter coil compressor Trace wiring to supply at unit to eliminate possibility of loose connections l) Always replace phial to correct length in holding tube (mechanical) m) Always leave 100mm air gap n) Maximum 12 spaces o) Maximum 43°c (A/C) & 38°c (W/C) p) Avoid ‘hotspots’ when installing the python k) Do not kink phial tube a) b) Short, long or extra long coils available 5. Product Photos Index21 AC Index21 WC Heat Dump Exchange Unit 6. Product Data sheets PRODUCT DATA SHEET Date: 01st Dec 2009 Issue No: 3 Index21 AC 06 1 3601XX Performance Nominal icebank pull down:( water 10oC at 24oC ambient) Icebank weight: Thermal capacity icebank: Maximum ambient temperature: 5 hours 25kg nominal 8375KJ (2000 Kcal) 43oC Dimensions Height: Width: Depth: Weight: Unloaded Packed Operational 930mm 570mm 600mm 66kg 67kg 130kg Electrical Mains supply: Run current: Start current: Fuse: Supply: 230v 1ph 50Hz 5.0 amps 31 amps 10 amps 2m mains cable 3 pin UK Style plug Refrigeration Compressor: Compressor starting torque: Compressor duty: (-10oC Evap temp) Evaporator type: Condenser type: Expansion device: Refrigerant type charge: Control type: 21cc High starting torque 750 watts 12.7mm dia tube Air Cooled – Cu/Al construction Capillary 3M x 1.5mm I.D. R134a refer rating plate Mechanical thermostat Fan Motor Output: Speed: Direction: Protection: Fan blade: Diameter Pitch 11 watts 1300 rpm Counter clockwise shaft end Impedence 250mm 28o Python Pump / Water Bath Agitator Type: Agitation type: Output: Speed: Protection: Max flow rate @ no pressure: Max lift @ min flow: Connection size: 3-stage semi - submersible Continuous 90watts 2700rpm Thermal trip 20 litres per minute 18m 15mm diameter tube Product coils Short: Long: Super Long: Material: Length 3.8m 5.4m 10.0m Max Qty 12 12 8 316 stainless steel Compliance to Standards and Legislation All coolers comply with Brewers Society Code of Practice for Electrical Safety in Beer Dispense in License Premises. Designed to EN60335 part1 (Safety of Household and Similar Electrical Appliances-General Requirements). Product complies with: EMC Directive (2004/08/EC) Low Voltage directive (2006/95/EC) Machinery Directive (89/392/EEC) PRODUCT DATA SHEET Date: 1st Dec 2009 Issue No: 3 Index21 WC 0613602XX Performance Nominal Icebank pull down:( water 10oC at 24oC ambient) Icebank weight: Thermal capacity icebank: Maximum ambient temperature: 5 hours (max. Icebank) 25kg Nominal 8675KJ (2000 Kcal) 38oC Dimensions Height: Width: Depth: Weight: Unloaded Packed Operational Base Unit 930mm 570mm 600mm 69kg 70kg 137kg Discharge Unit 360mm 460mm 280mm 11kg 12kg 13.5kg Electrical Mains supply: Run current: Start current: Fuse: Supply: Base Unit 230v 1ph 50Hz 6.1 amps 31.0 amps 10 amps 2m mains cable 3 pin UK Style plug Discharge Unit 24v 1ph 50Hz Refrigeration Compressor: Compressor starting torque: Compressor duty: (-10oC Evap temp) Evaporator type: Condenser type: Expansion device: Refrigerant type charge: Control type: Min 1.5mm2 minimum cable from base unit (supplied by Installer) 21cc High starting torque 750 watts 12.7mm dia tube Plate Heat exchanger Capillary 3M x 1.5mm ID R134a refer rating plate Mechanical thermostat Discharge Unit Heat exchanger: Aluminium fins on copper tube Fan motor: Output 12 watts Speed 1250 rpm Direction Clockwise shaft end Protection Thermal trip Fan blade: Diameter 250mm Pitch 31o Noise Levels: @ one metre = 61 Decibels @ three metres = 57 Decibels @ five metres = 54 Decibels Python Pump / Water Bath Agitator Type: Agitation type: Output: Speed: Protection: Max flow rate @ no pressure: Max lift @ min flow: Connection size: 3-stage semi - submersible Continuous 90 watts 2700rpm Thermal trip 20 litres per minute 18m 15mm diameter tube Coolant System Coolant: Coolant mixture: Monopropylene Glycol 30% glycol, 70% water Coolant Pump 3 stage magnetically coupled drive, max lift @ min flow = 15m Product Coils Short: Long: Super Long: Material: Length 3.8m 5.4m 10.0m Max Qty 12 12 8 316 stainless steel Other Controls Refrigeration system cut out Manual reset Compliance to Standards and Legislation All coolers comply with Brewers Society Code of Practice for Electrical Safety in Beer Dispense in License Premises. Designed to EN60335 part1 (Safety of Household and Similar Electrical Appliances-General Requirements). Product complies with: EMC Directive (2004/08/EC) Low Voltage directive (2006/95/EC) Machinery Directive (89/392/EEC) 7. Parts List and Exploded View SPARES LIST ITEM 1a 1b 2 3 4 5 6 7 7a 7b 8 9 10 11 12 13 14 15 16 17a 17b 17c PART No. 58 0420 589 58 0420 567 06 0 105108 2RF738A 06 0 105101 06 0 105113 06 0 190425 58 0900 086 3DF001A 58 0420 143 06 0 274007 220104050 44 0000 058 58 1174 007 58 0475 214 06 0 361104 58 0440 438 58 0446 146 58 0480 145 06 0 100107 06 0 100137 06 0 100138 INDEX21 AC - Model 06 1 3601XX DESCRIPTION TOTTON PUMP MARCHMAY PUMP INSPECTION PANEL COIL SUPPORT BAR BLANK FOAMED TANK HANDLE ASSY - BLACK CONDENSER COMP SET SC21F - DANFOSS COMPRESSOR START RELAY - DANFOSS COMPRESSOR START CAPACITOR - DANFOSS FAN MOTOR MOD’D FAN COWL – MOULDED FAN BLADE ICEBANK THERMOSTAT - MECHANICAL LIFTING HANDLE - LID COIL CLAMP NEON – GREEN SOCKET – SNAP FIT FEMALE CASTOR 2” MERCURY SWIVEL COIL ASSY LG 9.5 x 5.0M: MAX 12 COILS COIL ASSY SH 9.5 x 3.8M: MAX 12 COILS COIL ASSY LG 9.5 x 10.0M: MAX 8 COILS SPARES LIST INDEX21 AC - Model 06 1 3601XX 3 1 17 13 15 12 4 2 6 5 7 14 16 11 10 9 8 SPARES LIST ITEM 1a 1b 2 3 4 5 6 7 7a 7b 8 9a 9b 10 11 12 13 14 15 16 17 18 N/S 19 20a 20b 20c 21 22 PART No. 58 0420 589 58 0420 567 06 0 105143 2RF738A 06 0 105101 06 0 105113 CM011514S 58 0900 086 3DF001A 58 0420 143 58 0440 429 58 0420 610 58 0420 570 58 0446 198 58 1174 007 58 0475 214 58 0440 487 58 0450 115 06 0 361104 58 0440 438 58 0446 146 58 0480 145 2MC824A 15ISV 06 0 100107 06 0 100137 06 0 100138 06 0 105109 06 0 105108 INDEX21 WC - Model 06 1 3602XX DESCRIPTION TOTTON PUMP MARCHMAY PUMP GLYCOL BOTTLE COIL SUPPORT BAR BLANK FOAMED TANK HANDLE ASSY - BLACK ½” BSP TO 15.0mm JG FITTING COMP SET SC21F - DANFOSS COMPRESSOR START RELAY - DANFOSS COMPRESSOR START CAPACITOR - DANFOSS TRANSFORMER GLYCOL PUMP TOTTON GLYCOL PUMP MARCHMAY 24V CONNECTOR ICEBANK THERMOSTAT - MECHANICAL LIFTING HANDLE - LID REFRIGERATION SYSTEM CUT-OUT SWITCH PLATE HEAT EXCHANGER COIL CLAMP NEON – GREEN SOCKET – SNAP FIT FEMALE CASTOR 2” MERCURY SWIVEL GLYCOL BOTTLE 4 LTR BALL VALVE 15mm COIL ASSY LG 9.5 x 5.0M: MAX 12 COILS COIL ASSY SH 9.5 x 3.8M: MAX 12 COILS COIL ASSY LG 9.5 x 10.0M: MAX 8 COILS DOOR INSERT REMOVABLE PANEL SPARES LIST INDEX21 WC - Model 06 1 3602XX 3 20 1 17 15 12 4 22 13 6 2 10 5 7 14 16 18 8 19 11 9 22 8. Wiring Diagram Index21 AC Index21 WC