AWUF Wall-Mount Air Handler 1½ to 3 Tons
Standard Features
• Suitable for use with refrigerants R-410A and R-22 • Equipped with a Check Flowrater for cooling-only and heat pump operation • Direct-drive, multi-speed motor allows air volume variation for heating/cooling • Sequence-controlled, rust-resistant nickel chromium heating elements of 3, 5, 8, and 10 kW • Factory-installed pull-type disconnect • Aluminum tubing coils on all models • AHRI Certified • ETL Listed
Cabinet Features
• Thermoplastic drain pan with bottom primary and secondary drain connections • Built-in filter rack (filter included) • Large chassis (2½- and 3-ton units) – front return only • Small chassis (1½- and 2-ton units) – front or bottom return • Wall-hanging bracket provided
Accessories
• Wall access doors: — WAD-1 fits AWUF18 and AWUF24 — WAD-2 fits AWUF30 through AWUF37
* Complete warranty details available from your local dealer or at www.amana-hac.com. To receive the 10Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.
SS-AAWUF
www.amana-hac.com
Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P., Houston, Texas.
3/12
Supersedes 1/11
Product Specifications
Nomenclature A 1
W 2
Brand A Single-piece Air Handler Unit Application C Ceiling Mount PSC Motor D Downflow PSC Motor E Multi-Position Variable-Speed Motor R Multi-Position PSC Motor S Multi-Position EEM Motor W Wall Mount PSC Motor Cabinet Finish U Unpainted P Painted N Uncased Expansion Device F Flowrater T Expansion Valve
2
U 3
F 4
3610 5,6,7,8
1 9
6 10
AA 11,12
Engineering * Major/ Minor Revisions * Not used for inventory management Refrigerant Compatability No Digit = R-22 only 6 = R-410A or R-22 Electrical 1 208/240 V, 1 Phase, 60 Hz Nominal Capacity Range @ 13 SEER Multi-Position & Downflow Applications 1729 1½ to 2½ Tons (for Export Systems) 1830 1½-3½ Tons 3642 3-3½ Tons Ceiling-Mount & Wall-Mount Applications (Nominal Cooling Capacity/ Electric Heat kW) 1805 1½ Tons Cooling/ 5 kW Electric Heat 2405 2 Tons Cooling/ 5 kW Electric Heat 3610 3 Tons Cooling/ 10 kW Electric Heat
www.amana-hac.com SS-AAWUF
3, 5
Electric Heat (kW)
6 ¾”
Width
Coil Drain Connection FPT
17.3 20 20 197 253
Min Circuit Ampacity (208V)
Max. Overcurrent Protection (240V)
Max. Overcurrent Protection (208V)
Minimum VAC
Maximum VAC
1.30 1/5 84
FLA
HP
Ship Weight (lbs)
Blower Motor
15.1
Min Circuit Ampacity (240V)
Voltage
240/208
⅝”
Suction
Electrical Data
⅜”
Liquid
Service Valve
9
Diameter
Blower
18,000
Cooling (BTU/h)
Nominal Ratings
AWUF 180316B
84
1/5
1.35
253
197
30
30
23.3
26.7
240/208
⅝”
⅜”
¾”
6
9
5
18,000
AWUF 18051/16A
84
1/5
1.3
253
197
25
30
23.3
26.6
240/208
⅝”
⅜”
¾”
6
9
5
18,000
AWUF 18051/16B
84
1/5
1.35
253
197
40
40
34.6
39.7
240/208
⅝”
⅜”
¾”
6
9
8
18,000
AWUF 18081/16A
84
1/5
1.3
253
197
35
40
34.6
39.6
240/208
⅝”
⅜”
¾”
6
9
8
18,000
AWUF 18081/16B
84
1/5
1.30
253
197
20
20
17.3
15.1
240/208
⅝”
⅜”
¾”
6
10
3, 5
24,000
AWUF 240316B
84
1/5
1.35
253
197
30
30
23.3
26.7
240/208
⅝”
⅜”
¾”
6
10
5
24,000
AWUF 24051/16A
84
1/5
1.3
253
197
25
30
23.3
26.6
240/208
⅝”
⅜”
¾”
6
10
5
24,000
AWUF 24051/16B
84
1/5
1.35
253
197
40
40
34.2
39.7
240/208
⅝”
⅜”
¾”
6
10
8
24,000
AWUF 24081/16A
Product Specifications
Specifications
SS-AAWUF www.amana-hac.com
3
8
Electric Heat (kW)
6 ¾”
Width
Coil Drain Connection FPT
4 34.6 40 35 197 253
Min Circuit Ampacity (208V)
Max. Overcurrent Protection (240V)
Max. Overcurrent Protection (208V)
Minimum VAC
Maximum VAC
1.3 1/5 84
FLA
HP
Ship Weight (lbs)
Blower Motor
39.6
Min Circuit Ampacity (240V)
Voltage
240/208
⅝”
Suction
Electrical Data
⅜”
Liquid
Service Valve
10
Diameter
Blower
24,000
Cooling (BTU/h)
Nominal Ratings
AWUF 24081/16B
84
1/5
1.35
253
197
50
60
45.6
52.7
240/208
⅝”
⅜”
¾”
6
10
10
24,000
AWUF 24101/16A
84
1/5
1.3
253
197
50
60
45.9
52.7
240/208
⅝”
⅜”
¾”
6
10
10
24,000
AWUF 24101/16B
93
⅓
1.58
253
197
20
20
17.6
15.5
240/208
¾”
⅜”
¾”
8
9
3, 5
30,000
AWUF 300316B
93
⅓
1.58
253
197
25
30
23.6
27
240/208
¾”
⅜”
¾”
8
9
5
30,000
AWUF 30051/16B
93
⅓
1.58
253
197
35
40
34.9
40
240/208
¾”
⅜”
¾”
8
9
8
30,000
AWUF 30081/16B
93
⅓
1.58
253
197
50
60
46.2
53
240/208
¾”
⅜”
¾”
8
9
10
30,000
AWUF 30101/16B
96
1/2
4.1
253
197
30
35
26.8
30.1
240/208
¾”
⅜”
¾”
8
10
5
18,000-30,000
AWUF 310516A*
Product Specifications
Specifications (cont.)
www.amana-hac.com SS-AAWUF
8
Electric Heat (kW)
8 ¾”
Width
Coil Drain Connection FPT
38.1 45 40 197 253
Min Circuit Ampacity (208V)
Max. Overcurrent Protection (240V)
Max. Overcurrent Protection (208V)
Minimum VAC
Maximum VAC
4.1 1/2 96
FLA
HP
Ship Weight (lbs)
Blower Motor
43.1
Min Circuit Ampacity (240V)
Voltage
240/208
¾”
Suction
Electrical Data
⅜”
Liquid
Service Valve
10
Diameter
Blower
18,000-30,000
Cooling (BTU/h)
Nominal Ratings
AWUF 310816A*
96
1/2
4.1
253
197
50
60
49.4
56.2
240/208
¾”
⅜”
¾”
8
10
10
18,000-30,000
AWUF 321016A*
96
⅓
1.58
253
197
25
30
23.6
27
240/208
¾”
⅜”
¾”
8
9
5
36,000
AWUF 36051/16B
96
⅓
1.58
253
197
35
40
34.9
40
240/208
¾”
⅜”
¾”
8
9
8
36,000
AWUF 36081/16B
96
⅓
1.58
253
197
50
60
46.2
53
240/208
¾”
⅜”
¾”
8
9
10
36,000
AWUF 36101/16B
96
1/2
4.1
253
197
30
35
26.8
30.1
240/208
¾”
⅜”
¾”
8
10
5
36,000
AWUF 370516B
96
1/2
4.1
253
197
40
45
38.1
43.1
240/208
¾”
⅜”
¾”
8
10
8
36,000
AWUF 370816B
96
1/2
4.1
253
197
50
60
49.4
56.2
240/208
¾”
⅜”
¾”
8
10
10
36,000
AWUF 371016B
Product Specifications
Specifications (cont.)
SS-AAWUF www.amana-hac.com
5
Product Specifications
Airlfow Data Motor Speed
Model AWUF18XX1/16A* AWUF18XX16B* AWUF24XX1/16A* AWUF24XX16B* AWUF30XX1/16A* AWUF30XX16B*
AWUF310516XX
AWUF310816XX AWUF321016XX
AWUF36XX1/16A* AWUF36XX16B* AWUF37XX16A*
AWUF37XX16B*
CFM Delivered Against External Static Pressure 0.1”
0.2”
0.3”
0.4”
0.5”
High
750
730
690
650
595
Low
710
700
690
635
585
High
755
715
670
615
545
Low
740
700
655
595
535
High
880
845
810
770
735
Low
845
815
780
745
705
High
900
870
835
795
760
Low
865
835
800
765
725
High
1250
1195
1135
1085
1010
Low
1110
1055
1020
955
905
High
1255
1120
1100
1020
950
Low
1115
1010
990
900
820
T5
875
865
830
805
765
T4
1005
975
945
920
890
T3
840
795
785
745
700
T2
645
615
550
500
445
T1
645
615
550
500
445
T5
1090
1065
1040
1015
985
T4
1005
975
945
920
890
T3
840
795
785
745
700
T2
645
615
550
500
445
T1
645
615
550
500
445
High
1280
1190
1110
1010
930
Low
1170
1100
1030
950
890
High
1215
1145
1070
985
890
Low
1120
1065
1000
915
820
High
1325
1285
1230
1180
1115
Low
1085
1060
1030
995
950
T5
1385
1205
1130
1045
950
T4
1235
1180
1115
1040
955
T3
1165
1120
1075
1025
945
T2
1050
1010
970
930
860
T1
1050
1010
970
930
860
Heating Capacity Correction Factor* Supply Voltage
240
230
220
210
208
Correction Factor
1.00
.92
.84
.76
.74
* Multiply 240-volt capacity by correction factor
6
www.amana-hac.com SS-AAWUF
Product Specifications
Dimensions
LOW V OLT P OWE R S UP P LY ( L A R G E C H AS S I S O N L Y )
S UC TION LINE OFFS E T HANG ING B R AC K E T
LIQUID LINE
P U L L O U T DI S C O N N E C T
R E M O V AB L E S E R V I C E DO O R
L OW V OLT P OWE R S UP P LY E L E C T R I C AL P OWE R S UP P LY
F R O N T AC C E S S P AN E L S M AL L C H AS S I S
S T U D AT T A C H M E N T HOLE S
FR ONT R E TUR N FILTE R L AR G E C H AS S I S
B O T T O M P R I M AR Y AN D S E C O N DAR Y DR AI N S C AN B E AC C E S S E D T H R O U G H T H E B O T T O M O F T H E U N I T . ( 3 /4 " N P T F E M AL E C ONNE C TION) N O T E : H AN D T I G H T E N O N L Y
Small Chassis (AWUF18/24)
Large Chassis (AWUF30-37)
A
36”
A
36”
B
3
20 /16”
B
24”
C
16⅛”
C
21”
D
16”
D
19⅞”
E
11”
E
15⅞”
Filter
14” x 18” x 1”
Filter (30/36)
16” x 20” x 1”
Filter (31/32/37)
18” x 20” x 1”
SS-AAWUF www.amana-hac.com
7
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
⚠
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Product Specifications
AWUF18/24/30/36 Wiring Diagram
8
www.amana-hac.com SS-AAWUF
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
⚠ Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Product Specifications
AWUF31/32 Wiring Diagram
SS-AAWUF www.amana-hac.com
9
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
⚠
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Product Specifications
AWUF37 Wiring Diagram
10
www.amana-hac.com SS-AAWUF
Product Specifications
Notes
SS-AAWUF www.amana-hac.com
11
Product Specifications
Notes
Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our continuing commitment to quality products may mean a change in specifications without notice. © 2010 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.
12
www.amana-hac.com SS-AAWUF