Uponor plaster system for ceiling and wall cooling/heating
MOUNTING INSTRUCTIONS
Only for installation by authorised specialists!
Pipe system installation
≈ 500
500 ø 6 mm
a T
Uponor PEX 9,9
Optimal loop length: L = 50 m
T 80 100 140
a 60 70 90
Supply pipe installation
INSTALLATIONSSYSTEME TECHNISCHE INFORMATIONEN
PE-Xa Installationssystem mit Quick & Easy Verbindungstechnik
Follow the additional instruction: Uponor Q&E Installation
ø 6 mm
Q&E 9,9
Q&E 20
Fill pipes/Pressure test
2h
max. 6 bar
MONTAGEANLEITUNG MOUNTING INSTRUCTIONS
D
F
GB
I
NL
CZ
DIN 1264-4
After 2 h leak test
Mounting/operating instructions for the Uponor manifolds
2
1048014 03/2010
Plaster work
≈10 14
e.g. Knauf MP75 G/F-Light
e.g. Knauf NP75 Diamant ≈ 10 14
While plastering, all circuits have to be held under operating pressure. The system has to be kept frostfree.
Operational check
The system function has to be tested with the heating function process. For documentation use the Uponor heating function form. The waiting period after palstering should be Cement-bonded plaster: > 21 days Gypsum-bonded plaster: > 7 days Observe also the plaster manufacturer's instructions.
1048014 03/2010
3
Operation
ϑSupply ϑSurface
16 – 40° C < 35° C
16 – 50° C < 40° C
1048014 – 03/2010 ME – Subject to modifications
The building management must be informed of the location of the system pipes.