Preview only show first 10 pages with watermark. For full document please download

Similar Pages

   EMBED


Share

Transcript

Uponor plaster system for ceiling and wall cooling/heating MOUNTING INSTRUCTIONS Only for installation by authorised specialists! Pipe system installation ≈ 500 500 ø 6 mm a T Uponor PEX 9,9 Optimal loop length: L = 50 m T 80 100 140 a 60 70 90 Supply pipe installation INSTALLATIONSSYSTEME TECHNISCHE INFORMATIONEN PE-Xa Installationssystem mit Quick & Easy Verbindungstechnik Follow the additional instruction: Uponor Q&E Installation ø 6 mm Q&E 9,9 Q&E 20 Fill pipes/Pressure test 2h max. 6 bar MONTAGEANLEITUNG MOUNTING INSTRUCTIONS D F GB I NL CZ DIN 1264-4 After 2 h leak test Mounting/operating instructions for the Uponor manifolds 2 1048014 03/2010 Plaster work ≈10 14 e.g. Knauf MP75 G/F-Light e.g. Knauf NP75 Diamant ≈ 10 14 While plastering, all circuits have to be held under operating pressure. The system has to be kept frostfree. Operational check The system function has to be tested with the heating function process. For documentation use the Uponor heating function form. The waiting period after palstering should be Cement-bonded plaster: > 21 days Gypsum-bonded plaster: > 7 days Observe also the plaster manufacturer's instructions. 1048014 03/2010 3 Operation ϑSupply ϑSurface 16 – 40° C < 35° C 16 – 50° C < 40° C 1048014 – 03/2010 ME – Subject to modifications The building management must be informed of the location of the system pipes. Uponor GmbH International Sales P.O. Box 1641 97437 Hassfurt Germany T +49 (0)9521 690-0 F +49 (0)9521 690-750 E [email protected] W www.uponor.com/international