Chilled ceiling and radiator (CLC02) 2 lighting groups, on/off 2 lighting groups, dimmed 2 blinds, up/down • • • • • • • • •
INT07
Heating with radiator and cooling with chilled ceiling Modulating heating and cooling valve Dew point monitoring On/off control of two lighting groups Dimming control of two lighting groups Control of two motorised window-blinds (up/down) Lighting and blinds operated with momentary-contact switches, or Lighting and blinds operated with flexible room unit via LON bus Option: Automatic lighting control based on occupancy and daylight level
Plant diagram 70164
YC
Room controller Room unit with temperature sensor D1 Window switch D2 Occupancy sensor D3 Dew point sensor D10, D11 Momentary-contact switches for 2 on/off lighting groups, D12…D15 Momentary-contact switches for 2 lighting groups, dimmed D16...D19 Momentary-contact switches for 2 blinds, up/down B1 Daylight sensor via LON bus YH Heating valve YC Cooling valve Q1, Q2 2 lighting groups, on/off Q3, Q4 2 lighting groups, dimmed Q5, Q6 2 motors for blinds
D3
Q1, Q2
Q3, Q4
2x
2x
Q5, Q6 2x
N1 R1
B1 Lux
D10, D11 2x YH D12...D15 4x T
R1
D1
D2
D16...D19
4x
N1 (
)
LON
Operating diagram 70284
Y [%]
Y TR SpH SpC H C YH YC
Output signal Room temperature Effective heating setpoint Effective cooling setpoint Heating sequence Cooling sequence Heating valve Cooling valve
Siemens Building Technologies Building Automation
H
C
100
YH
YC
SpH
SpC
0
DESIGO RXC Applications library Application INT07
TR [°C]
CA2A3825E07 / 07.2001 1/6
Functions
A detailed description of the lighting and window-blind control functions will be found at the beginning of this section in document CA2A3825E00, “INT – Function description”. The HVAC functions are described in CA2A3815E00, " CLC – Function description".
Function
Brief description
See CA2A3825E00
2 lighting groups, on/off 2 lighting groups, dimmed
– – – – –
Manual on/off operation with momentary-contact switches Manual on/off operation via LON bus Control signals Daylight sensor Dimming
3.2, 3.4 3.4, 3.6 3.6 3.6 3.3
2 blinds, up/down
– – – –
Manual operation with momentary-contact switches Manual operation via LON bus Control signals Blind control
4.2, 4.4 4.4, 4.6 4.6 4.3, 4.4
Compatible controllers
INT07 requires the RXC30.1 basic controller, extension module RXC40.1 and extension module RXC41.1
Connection diagram
D2 1) 2)
LON
1)2)
D3
D11) 2)
YH
3)
YC
3)
D10
6)
D11
6)
D12 6) D13 6) D14 6) D15 6)
R1 Lux
B1
4
3
1
2
QAX...
D16 6) D17 6) D18 6) D19 6)
D4
GND
9
10 11 12 13 14 15 16 17
N
N
+
–
N
L
+
–
N
L
N3
M
Q1 L N AC 230 V
4)
Q2
4)
L N AC 230 V
CA2A3825E07 / 07.2001 2/6
Q3 L N AC 230 V
1) 2) 3) 4) 5) 6)
PE
8
N
Q44
D3
6
7
PE
Q34
D2
GND
D1
5
Q14
Q24
4
PE
Y2+
Y2–
PE
3
N2
N
L
N
2
N
D4 N
Q24
Y2+
10 11 12 13 14 15 16 17 15 16
Y2–
9
PE
8
N
7
N1 L
1
RXC41.1
N
6
GND
5
D3
D2
GND
4
Q13
RXC30.1
3
Q14
D1
CLB
CLA
CLB
CLA
2
PE
22 23 24 25 26 27 28 29 30
1
RXC40.1
N
N
16 17
PE
CP+
D4
CP–
Q24
N
GND
D3
10 11 12 13 14 15
PE
G
9
Q14
PE
N
8
Y2
7
G
6
Q13
5
Q13
18 19 20 21
4 GND
D2 N
N
D1 L
L
3
GND
2
Y1
80311A
1
4)
Q4
4)
Q5
5)
M
Q6
5)
L N AC 230 V
Type of contact can be selected Only two of these devices may be connected (either to D1 or D2) Note the maximum simultaneous load on outputs Y1, Y2: Max. 6 VA (RXC30.1, data sheet 3840) Max. load per output: filament lamps: 2.5 kW, fluorescent lamps: 1.5 kVA Max. load per extension module: AC250 V, 3 A (limited with fine-wire fuse) Momentary-contact switches (without mechanical lock)
DESIGO RXC Applications library Application INT07
Siemens Building Technologies Building Automation
Momentary-contact switches
Siemens Building Technologies Building Automation
The table shows how the digital inputs for momentary-contact switches are assigned to the outputs. (The original assignments can be changed with the RXT10.1.)
Switch
Digital input
Output
Lighting group or window blind controlled
D10
D3 (RXC30.1)
Q14 (RXC30.1)
Q1
D11
D4 (RXC30.1)
Q24 (RXC30.1)
Q2
D12
D1 (RXC40.1)
Q14, Y1+ , Y1-
Q3 Brighter
D13
D2 (RXC40.1)
(RXC40.1)
Q3 Darker
D14
D3 (RXC40.1)
Q24, Y2+, Y2-
Q4 Brighter
D15
D4 (RXC40.1)
(RXC40.1)
Q4 Darker
D16
D1 (RXC41.1)
Q14 (RXC41.1)
Q5 Up
D17
D2 (RXC41.1)
Q24 (RXC41.1)
Q5 Down
D18
D3 (RXC41.1)
Q34 (RXC41.1)
Q6 Up
D19
D4 (RXC41.1)
Q44 (RXC41.1)
Q6 Down
DESIGO RXC Applications library Application INT07
CA2A3825E07 / 07.2001 3/6
Device list
Ref.
Description
Type
N1
Room controller
RXC30.1
3840
N2
Extension module for control of lighting
RXC40.1
3842
N2
Extension module for control of blinds
RXC41.1
3843
R1
Room unit
(or flexible room unit via LON bus)
QAX30.1 QAX31.1 QAX32.1 QAX34.1 QAX50.1
1741 1741 1641 1645 1648
Wireless room unit Receiver
QAX90.1, 91.1 RXZ90.1
1643 1644
Daylight sensor via LON bus
Third-party
–
Third-party
–
Third-party
–
B1 D1 D2
1) Type of contact can be selected 2) Only two of these devices may be connected (either to D1 or D2) 3) Note the maximum simultaneous load on outputs Y1, Y2: Max. 6 VA (RXC30.1, data sheet 3840) 4) Max. load per output: filament lamps: 2.5 kW, fluorescent lamps: 1.5 kVA 5) Max. load per extension module: AC250 V, 3 A (limited with fine-wire fuse) 6) Momentary-contact switches (without mechanical lock)
Occupancy sensor
1) 2)
1) 2)
. . . .
D3
Dew point sensor Please provide AC24V supply!
QFX21
D10, D11
Momentary-contact switches for on/off lighting 5)
Third-party
–
D12...D15
Momentary-contact switches for dimmed lighting 6)
Third-party
–
D16...D19
Momentary-contact switches for blinds, up/down 6)
Third-party
–
YH
Heating valve, thermic, on/off (PWM) control 3)
STE71.1 STA71
4874 4877
. . .
YC
Cooling valve, thermic, on/off (PWM) control 3)
T3W..., T4W... STE72 STE71.1 STA71
4829 4873 4874 4877
. . .
Q1, Q2 Q3, Q4 Q5, Q6
CA2A3825E07 / 07.2001 4/6
Window switch
1) 2)
Data sheet
On/off lighting groups 4) Dimmed lighting groups Motors for blinds
DESIGO RXC Applications library Application INT07
5)
4)
1551
Third-party
–
Third-party
–
Third-party
–
Siemens Building Technologies Building Automation
Configuration
Application INT07 incorporates the following parameters, set with the RXT10.1 commissioning and service tool (menu: Device, Configuration, Settings). See CA2A3815E02 (application CLC02) for notes on setting the parameters for the HVAC functions
Menu
Parameters
Values and Range
Default setting
Lighting
Automatic switch-on
Building in use
Enabled / Disabled
Disabled
Building not in use
Enabled / Disabled
Disabled
Automatic switch-off
Enabled / Disabled
Enabled
Off timer
0 ... 90 min
0 min
Manual off disable
Enabled / Disabled
Disabled
State after power-up
On / Off / Last state
Last state
Mode
Master / Slave
Master
Building in use
0 ... 100 %
0%
Building not in use
0 ... 100 %
0%
Off threshold (A)
On/Off hysteresis (B) ... 2500 Lux
750 Lux
On/Off hysteresis (B)
0 ... Off threshold (A)
100 Lux
100 % threshold (C)
0 ... Off threshold (A)
250 Lux
Switch-on delay
0 ... 60 min
10 s
Switch-off delay
0 ... 60 min
10 s
Run time
5 s... 10 min
10 s
Blind Slats
With / Without
With
Step time
0.10 s ... 1.00 s
0.20 s
Slat steps after closing
0 ... 5 steps
3 steps
Minimum dim value Daylight
Blinds
LONMARK bindings
Disable auto-open when closed
Enabled / Disabled
Disabled
Close when building not in use
Enabled / Disabled
Enabled
Close when room unoccupied
Enabled / Disabled
Disabled
Mode
Master / Slave
Master
. . . . . .
See "LONMARK network variables " and "LONMARK binding templates"
Ordering
Room controllers may be ordered either with the application described above or with the appropriate basic application. Please state the quantity, DESIGO RXC device name, type code and application.
Example 1
15 15 15
Notes
• The controllers will be delivered with the basic settings shown above. • Minimum order quantity: 10 controllers
Example 2
2 2 2
Notes
• The controllers will be delivered with the basic application • The application can be loaded into the controllers by means of the RXT10.1 tool • Minimum order quantity: 1 controller
Siemens Building Technologies Building Automation
DESIGO RXC Applications library Application INT07
RXC30.1 room controllers with application INT07 Extension modules for lighting control Extension module for control of blinds
RXC30.1 room controllers Extension modules for lighting control Extension module for control of blinds
RXC30.1/INT07 RXC40.1 RXC41.1
RXC30.1 / 00030 RXC40.1 RXC41.1
CA2A3825E07 / 07.2001 5/6
. . . . . . . . . . . . . . . . . . . . . . . . .
CA2A3825E07 / 07.2001 6/6
DESIGO RXC Applications library Application INT07
Siemens Building Technologies Building Automation