Fraser Health Telecommunications Standard Drawing List Drawing No.
Rev.
12E-01
Construction Detail: 82” x 96” x ¾” BIX Plywood Backboard
0
12E-02
Hole Detail: 82” x 96” x ¾” BIX Plywood Backboard
0
12E-03
Backboard Layout: 82” x 96” x ¾” BIX Plywood Backboard
0
12E-A-01
Construction Detail: 48” x 96” x ¾” BIX Plywood Backboard
0
12E-A-02
Hole Detail: 48” x 96” x ¾” BIX Plywood Backboard
0
12E-A-03
Backboard Layout: 48” x 96” x ¾” BIX Plywood Backboard
0
Figure 3
Typical Cable Install
0
Figure 4
Typical Labelling
0
NS-01
Telecommunications Drawing Symbols
0
NS-02
Telecommunications Electrical Symbols
0
NS-03
Large Building Main Telecom Closet Plan (max. 1000 sqM)
0
NS-04
Large Building Main Telecom Closet Reflected Ceiling
0
NS-05
Large Building Main Telecom Closet UTP Terminal
0
NS-06
Large Building Local Telecom Closet Plan (max. 800 sqM)
0
NS-07
Large Building Local Telecom Closet Reflected Ceiling
0
NS-08
Large Building Local Telecom Closet UTP Terminal
0
NS-09
Large Building Main Telecom Closet Details
0
NS-10
Stacked Telecom Closets & Pathways in Hospital
0
NS-11
Wall Mount Cable Tray Installation Details
0
NS-12
Wall Mount Cabinet Mounting Details
0
NS-13
Relay Rack Equipment Layout
0
NS-14
Voice/Data Jack, Connector, Faceplate and Patch Panel
0
NS-15
Voice/Data Outlet
0
NS-16
J-Hook Installation Details
0
NS-17
Wiremold 4000 & 6000 Series - Details
0
NS-18
Demarcation for Special Services
0
NS-19
Telecommunications Closet Grounding Bus Bars
0
Cable Information Spreadsheets (5)
0
Appendix A
2117543.06
Descriptions
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Floor line
Note: Backboard to be fire retardant Material or painted with fire retardant paint.
Stand-offs 2" x 6"
¾” plywood Stand-off 2"x6" WALL
6"
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
21in.
20in.
20in.
21in.
41" wide x96" H
21in.
41" wide x96" H
20in.
Plywood Backboard
20in.
Plywood Backboard
21in.
1
Issue No:
GT
Drawn By:
DATE: 27-Jan-05 Drawing No: 12E-01
TITLE: Construction Details 82" x 96" x ¾" Plywood Backboard
Scale: ¾" = 1'
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
7
1234567891011-
A
C
12 34 5 6
7 8 9 101112 1x
7x
9
2x
8x
3x
9x
A
4x
10x
6x
12x
1x
7x
3x
9x
6
2x
8x
B
4x
10x
5x
11x
6x
12x
SGR-12-12
5x
11x
Middle Atlantic Products
Rack label "R"
8
5
Figure 3
4
11
3
1
Fiber
UTP
Horizontal Cable IDC field Data base perfect “C” Harness bale from rack Telephone Riser Intercom Riser (if required) Data base perfect”I” Fiber patch Panel Data Equipment (Supplied by others) at 8U from the top Fiber riser from Data Equipment Room Telephone riser from PBX room or Demarc Intercom riser (if required) IDC cross connect for data supplied in contract UTP Tie Cable to Voice field
11
Ethernet
Future
10
Future
Future
Wall Outlet
V D S
V1
V2
D2
Workstation
Telephone
Not to scale visual presentation only
2
Modular Furniture Adapter
D1
Analog/Digital Telephone
Cat 5e Horizontal Cables
FAX
March 09 PS-03
Workstation
VOIP Telephone
And/ Or
Jack label SBAL-01A
Data icon Closet ID label
013
014
V
D
V - Voice D - Data
C014
S - Spare
S 015 1008
HORIZONTAL CABLE
Closet architecture label
IDC punchdowns Lable strip
014
IDC location as per sample in figure 3 014 A07
A07
IDC CROSS CONNECT
Data switch location Full height relay rack - (rack) R Rack units down from top - (Shelf) at 12U (single Telus router) 14U (dual Telus router)
A07
Ethernet
R1 (1st rack) 8x
9x
1x
2x
3x
10x
11x
12x
7x
8x
9x
4x
5x
6x
1x
2x
3x
10x
11x
12x
4x
5x
6x
7 8 9 101112 A
Figure 4
2117543.06
7x C
12 34 56
A
B
Typical labling using Figure 3 (Community Site)
March 09 PS-04
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
2117543.06
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Network Services Database Horizontal Cable Information
SAMPLE DATA FORMAT ONLY - PLEASE DELETE IT BEFORE ENTER
Note: Submit Telecom Room ID to Network Services for approval upon award of contract.
Use
Type
Cable
Voice Data Data WP WP
UTP UTP UTP UTP UTP
Cat 5E Cat 5E Cat 5E Cat 5E Cat 5E
Originating Endpoint - ( Telecom Closet )
Terminating Endpoint - ( User office )
Teleco Telecom Terminatio m Arch Room ID n type Room #
Bldg Floor Room Terminatio Code Code # n type
20 20 20 20 20
MRM-B1A MRM-B1A MRM-B1A MRM-B1A MRM-B1A
Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix
Cross Connect ID
MRM-B1A-R1-A01 MRM-B1A-R1-A02 MRM-B1A-R1-A03 MRM-B1A-R1-A04 MRM-B1A-R1-A05
Sample Database Appendix A - FHA Spec 24Oct07 - Archibus Test - Horizontal 2117543.06
MRM MRM MRM MRM MRM
B1 B1 B1 B1 B1
25 29 34 38 56
RJ45 RJ45 RJ45 RJ45 RJ45
Full Cable ID
MRM-B1A-H001 MRM-B1A-H002 MRM-B1A-H003 MRM-B1A-H004 MRM-B1A-H005
Company Install Date Name
ABC
10-Nov-07
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Originating Endpoint- ( Main Telecom Closet Floor Telecom Telecom Code Room # Room ID
Type
Cable
UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP UTP
Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair Tel 25 pair
01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01
123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123
UTP UTP UTP UTP UTP UTP
Cat5E Cat5E Cat5E Cat5E Cat5E Cat5E
01 01 01 01 01 01
123 123 123 123 123 123
Terminating Endpoint- ( Local Telecom Closet ) Teleco Telecom Terminatio m Room ID n type Room #
Termination type
Floor Code
MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A
Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix
02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02
234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234 234
MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B
Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix
MRM-01A/02B-V1-001 MRM-01A/02B-V1-002 MRM-01A/02B-V1-003 MRM-01A/02B-V1-004 MRM-01A/02B-V1-005 MRM-01A/02B-V1-006 MRM-01A/02B-V1-007 MRM-01A/02B-V1-008 MRM-01A/02B-V1-009 MRM-01A/02B-V1-010 MRM-01A/02B-V1-011 MRM-01A/02B-V1-012 MRM-01A/02B-V1-013 MRM-01A/02B-V1-014 MRM-01A/02B-V1-015 MRM-01A/02B-V1-016 MRM-01A/02B-V1-017 MRM-01A/02B-V1-018 MRM-01A/02B-V1-019 MRM-01A/02B-V1-020 MRM-01A/02B-V1-021 MRM-01A/02B-V1-022 MRM-01A/02B-V1-023 MRM-01A/02B-V1-024 MRM-01A/02B-V1-025 MRM-01A/02B-V2-001
MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A
Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix
02 02 02 02 02 02
234 234 234 234 234 234
MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B MRM-02B
Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix Giga Bix
MRM-01A/02B-D1 MRM-01A/02B-D2 MRM-01A/02B-D3 MRM-01A/02B-D4 MRM-01A/02B-D5 MRM-01A/02B-D6
Sample Database Appendix A - FHA Spec 24Oct07 - Archibus Test - Copper Riser Intra-Building 2117543.06
Full Cable ID
Compan y Name
Install Date
ABC
10-Nov-07
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Network Services Database - Inter-Building UTP Riser cable information SAMPLE DATA FORMAT ONLY - PLEASE DELETE IT BEFORE ENTERING NE
Originating Endpoint- ( Main Telecom Closet Type
Cable
UTP UTP UTP UTP
Tel 100 pair Tel 100 pair Tel 100 pair Tel 100 pair
Floor Telecom Telecom Code Room # Room ID 01 01 01 01
500 500 500 500
RMH-01A RMH-01A RMH-01A RMH-01A
Terminating Endpoint- ( Local Telecom Closet )
Termination type
Floor Code
Giga Bix Giga Bix Giga Bix Giga Bix
01 01 01 01
Sample Database Appendix A - FHA Spec 24Oct07 - Archibus Test - Copper Riser Inter-Building 2117543.06
Teleco Telecom Terminatio m Room ID n type Room # 100 100 100 100
MRM-01A MRM-01A MRM-01A MRM-01A
Giga Bix Giga Bix Giga Bix Giga Bix
Full Cable ID
RMH-01A/MRM-01B-V1-001 RMH-01A/MRM-01B-V1-002 RMH-01A/MRM-01B-V2-001 RMH-01A/MRM-01B-V2-002
Compan y Name
Install Date
ABC
10-Nov-07
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Network Services Database - Intra-Building Fiber Riser cable information
SAMPLE DATA FORMAT ONLY - PLEASE DELETE IT BEFORE ENTERING NEW DATA
Originating Endpoint- ( Main Telecom Closet ) Type
Cable
Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber Fiber
50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM10G 50MM1G 62.5MM SM
Teleco Teleco Floor m m Code Room Room # ID 01 01 01 01 01 01 01 01 01 01 01 01
123 123 123 123 123 123 123 123 123 123 123 123
MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A MRM-01A
Termination type
LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ
Terminating Endpoint- ( Local Telecom Closet )
Rack Patch Cable Strand ID Panel ID R1 R1 R1 R1 R1 R1 R1 R1 R1 R1 R1 R1
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
2117543.06 Sample Database Appendix A - FHA Spec 24Oct07 - Fiber Riser Intra-Building
F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1
1 2 3 4 5 6 7 8 9 10 11 12
Teleco Floor Telecom m Code Room Room ID # 02 02 02 02 02 02 02 02 02 02 02 02
223 223 223 223 223 223 223 223 223 223 223 223
MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A MRM-02A
Termination type
LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ LC, SC, ST or MTRJ
Rack Patch Cabl ID Panel e ID R1 R1 R1 R1 R1 R1 R1 R1 R1 R1 R1 R1
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1
Strand
Full Cable ID
1 2 3 4 5 6 7 8 9 10 11 12
MRM-01AR1P1/02AR1P1-F1-1 MRM-01AR1P1/02AR1P1-F1-2 MRM-01AR1P1/02AR1P1-F1-3 MRM-01AR1P1/02AR1P1-F1-4 MRM-01AR1P1/02AR1P1-F1-5 MRM-01AR1P1/02AR1P1-F1-6 MRM-01AR1P1/02AR1P1-F1-7 MRM-01AR1P1/02AR1P1-F1-8 MRM-01AR1P1/02AR1P1-F1-9 MRM-01AR1P1/02AR1P1-F1-10 MRM-01AR1P1/02AR1P1-F1-11 MRM-01AR1P1/02AR1P1-F1-12
Compan y Name
Install Date
ABC
10-Nov-07
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Network Services Database - Inter-Building Fiber Riser cable information
SAMPLE DATA FORMAT ONLY - PLEASE DELETE IT BEFORE ENTERING NEW DATA
Originating Endpoint- ( Main Telecom Closet ) Type
Cable
Fiber Fiber
SM SM
Teleco Telecom Floor m Room ID Code Room # 01 01
123 123
Termination type
RMH-01A LC, SC, ST or MTRJ RMH-01A LC, SC, ST or MTRJ
Terminating Endpoint- ( Local Telecom Closet )
Rack Patch Cable Strand ID Panel ID R1 R1
P1 P1
F1 F1
2117543.06 Sample Database Appendix A - FHA Spec 24Oct07 - Archibus Test - Fiber Riser Inter-Building
1 2
Teleco Floor Telecom m Code Room Room ID # 01 01
100 100
MRM-01A MRM-01A
Termination type
LC, SC, ST or MTRJ LC, SC, ST or MTRJ
Rack Patch Cabl Strand ID Panel e ID R1 R1
P1 P1
F1 F1
1 2
Full Cable ID
Compan y Name
RMH-01AR1P1/MRM-01AR1P1-F1- ABC RMH-01AR1P1/MRM-01AR1P1-F1-2
Attachment 1 to Appendix 3E - Telecommunication Drawings (Surrey Memorial Hospital Project) EXECUTION COPY
Install Date 10-Nov-07