Generic cabling
FTP Cat.5E 125 MHz 4x2/0,5mm - 2x4x2/0,5mm PVC / LSOH / LSFROH FTP (Foil screened Twisted Pair) for use as horizontal cable in generic cabling systems. The FTP cable has solid copper conductors insulated with PE. The screen is an overall Al-foil and an earth wire. The cable is supplied with PVC or Halogen free outer sheath material. All cables are approved in accordance with the most stringent test procedures. They are also 3P-Verified in accordance with the following standards: EN 50173, prEN 50288-2-1, ISO/IEC 11801 and EIA/TIA 568A Adendum-5
Cable construction Number of pairs
Sheath material
4 2x4
PVC/LSOH/LSFROH PVC/LSOH/LSFROH
Conductor dimension (mm) 0,5 0,5
Insulation Diameter (mm) 1,1 PE 1,1 PE
Binder diameter (mm) 5,0 5,0
Weight
Cable diameter (mm) 6,1/6,2/6,2 6,1x12,8/6,2x13,0/6,2x13,0
(kg/km) 39 / 38 / 42 79 / 76 / 84
Cable properties Bending Minimum bending radius, installation/installed Tensile strength Maximum tensile load, installation Maximum tensile load, installed Temperatur window Operation Installation
Fire classification 8xD/4xD PVC LSOH 100N LSFROH - Heat release (4 pair)
IEC 60332-1 IEC 61034, IEC 60754, IEC 60332-1 IEC 61034, IEC 60754, IEC 60332-3C
PVC
430MJ/km 649 MJ/km 391 MJ/km
-20°C - +60°C LSOH 0°C - +50°C LSFROH
Electrical data at 20°C Frequency
Attenuation, nom
NEXT
ACR
Return Loss
PS NEXT
PS ACR
ELFEXT
PS ELFEXT
(dB/100m)
(dB)
(dB)
(dB)
(dB)
(dB)
(dB)
(dB)
2,0 3,8 6,0 7,6 8,6 10,8 15,7 20,3 22,9
75 65 59 56 54 51 46 43 41
73 61 53 48 45 40 30 23 18
23,0 25,0 25,0 25,0 23,6 21,5 20,1 19,4
72 62 56 53 51 48 43 40 38
70 58 50 45 42 37 27 20 15
73 61 53 49 47 43 37 33 31
70 58 50 46 44 40 34 30 28
1 MHz 4 MHz 10 MHz 16 MHz 20 MHz 31,25 MHz 62,5 MHz 100 MHz 125 MHz
Characteristic impedance (4 MHz