20 05
Contactors - new line
• mini-contactors • contactors up to 100 A • contactors over 100 A • thermal overload relays • auxiliary contacts and accessories
www.relpol.com.pl
Contents 4
Contactors Mini-contactors,
Mini-contactors,
AC operation
DC operation
CRMI05 ................................ 6 CRMI09 ................................ 6
11 CRMI09 ............................. 11
Contactors up to 100 A,
Contactors up to 100 A,
AC operation
DC operation
CRNI09 ................................. 6 CRNI12 ................................. 6 CRNI16 ................................. 7 CRNI22 ................................. 7 CRNI32 ................................. 7 CRNI38 ................................. 7 CRNI45 ................................. 8 CRNI63 ................................. 8 CRNI75 ................................. 8 CRNI85 ................................. 8
Contactors over 100 A, AC operation CRLI110 ............................... 9 CRLI140 ............................... 9 CRLI170 ............................... 9
CRMI05 .............................
11 CRNI12 .............................. 11 CRNI16 .............................. 12 CRNI22 .............................. 12 CRNI32 .............................. 12 CRNI38 .............................. 12 CRNI45 .............................. 13 CRNI63 .............................. 13 CRNI75 .............................. 13 CRNI85 .............................. 13 Coding system ..................... 14 Add-on blocks ...................... 15 Technical data ...................... 16 Dimensions ......................... 18 Permissible mounting positions 19 CRNI09 ..............................
CRLI205 ............................... 9
10 CRLI300 ............................ 10 CRLI400 ............................ 10 CRLI250 ............................
Thermal overload relays 20 RSTN1 ............................... 20 RSTN2 ............................... 20 RSTN3 ............................... 21 RSTN4 ............................... 21 RSTL1 ................................ 21 RSTL2 ................................ 21 RSTM .................................
www.relpol.com.pl
22 RSTL4 ................................ 22 RSTL3 ................................
Add-on blocks for independent
22 Technical data ...................... 23 Dimensions ......................... 28 mounting .............................
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
5
The new line of contactors of Relpol S.A. includes three groups divided due to the current switching capacity and sizes related hereto, i.e. mini-contactors CRMI up to 9 A, contactors of type CRNI up to 100 A and contactors of CRLI type over 100 A. The contactors may operate at the frequency of 50/60 Hz. Rated voltages of the contactors are from 690 V to 1000 V at rated switching current from 5 A to 400 A, for AC3 Class. The contactors provide controlling the operation of long electrical circuits, switching on and off electrical AC motors The contactors are compliant with the following standards: IEC/EN 60947 and VDE 0660. Operating conditions: - the altitude of the installation site shall not exceed 2000 meters over sea level, - ambient temperature: from -25 oC to +55 oC, - atmospheric conditions: air shall not contain explosive gases, media, caustic gases or conductive dust, - shock and vibrations shall not exceed the values specified by the manufacturer, - the contactors shall not be used in the rain or snow. Characteristics: - the conductive parts are covered for better safety, - the design of the main contact set is unique , which results in extended electrical life, - the special design of the supply system provides low noise level, high reliability and significant strength, - the contactors co-operate with auxiliary contact blocks, - the terminals provide easy and reliable connection, and high resistance to shock.
•••••••••••••••••••••••• Thermal overload relays of RSTM, RSTN and RSTL types are used for protection of AC motors of 50/60 Hz frequency against overload and phase error. Rated voltages of the relays are from 690 V to 1000 V, at rated switching current from 0,1A to 400 A. The relays may also be used for protection of DC electromagnets and DC motors against overload. Individual functions provide protection against phase errors, compensation of temperature impact, indication of ON/OFF status, manual or automatic reset, etc. The relays may be mounted on contactors or as separate devices. Operating conditions: - the altitude of the installation site shall not exceed 2000 meters over sea level, - ambient temperature: from -25 oC to +55 oC, - relative humidity shall not exceed 90% at 25 oC.
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
CRMI, CRNI Mini-contactors and contactors up to 100 A, AC operation
6
Type of contactor
CRMI05
CRMI09
CRNI09
CRNI12
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ – CRNI12-30-10-... 1 CRMI05-30-10-... 1 – CRMI09-30-10-... 1 – CRNI09-30-10-... 1 –
Ordering codes
❶
CRMI05-30-01-... – ❶
CRMI05-40-00-... –
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V AC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [VA] Power cosφ at closing consumption of AC coil (50 Hz) closed [VA] cosφ at closed Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] Rated operating current AC15 of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg] three-pole four-pole
1 –
❶
CRMI09-30-01-... – ❶
CRMI09-40-00-... –
1 –
❶
1
CRNI12-30-01-... –
❷
–
CRNI12-40-00-... –
CRNI09-30-01-... – CRNI09-40-00-... –
❶
1
❷
–
690 5 1,9 1,3 2,2 2,9 3,8 – 0,81 0,86 10 0,8 0,2 1000 – (0,8 - 1,1) Us 15 0,41 6,8 0,42 16 10
690 9 2,6 2,4 4 4 4 – 1,10 1,10 10 0,4 0,2 1000 – (0,8 - 1,1) Us 15 0,41 6,8 0,42 16 10
690 9 3,3 2,4 4 5,5 5,5 – 1,48/1,4 2,54/2,4 15 1,2 0,2 1000 250 (0,8 - 1,1) Us 68 0,82 10 0,29 20 10
690 12 4,3 3,3 5,5 7,5 7,5 – 2/1,9 3,45/3,3 15 1,2 0,2 1000 250 (0,8 - 1,1) Us 68 0,82 10 0,29 20 10
690
690
690
690
–/4
–/4
6/10
6/10
0,5/0,3
0,5/0,3
0,9/0,45
0,9/0,45
0,18 0,19
0,18 0,19
0,37 0,37
0,37 0,37
Ordering coil codes ❶ A024 - 24 V AC 50 Hz A230 - 230 V AC 50 Hz ❷ A230 - 230 V AC 50 Hz For other voltages, contact Relpol S.A.
Coil of contactor 50 Hz Operating at 50 Hz 24 V 230 V
60 Hz 29 V 277 V
Thermal overload relays Type of thermal overload relay Module for installing as a single unit Relay base for installing as a single unit
www.relpol.com.pl
RSTM CRI-310 –
RSTM CRI-310 –
RSTN1 – CRI-320
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
RSTN1 – CRI-320
CRNI Contactors up to 100 A, AC operation Type of contactor
CRNI16
CRNI22
7 CRNI32
CRNI38
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRNI16-30-00-... – – CRNI22-30-00-... – – CRNI32-30-00-... – – CRNI38-30-00-... – –
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V AC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [VA] Power cosφ at closing consumption of AC coil (50 Hz) closed [VA] cosφ at closed Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] Rated operating current AC15 of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
690 16 7,7 4 7,5 9 11 – 3,5 6 15 1,2 0,2 750 250 (0,8 - 1,1) Us 68 0,82 10 0,29 30 10
690 22 8,5 5,5 11 11 11 – 4 6,6 15 1,2 0,2 750 250 (0,8 - 1,1) Us 68 0,82 10 0,29 30 10
690 32 15,6 8,5 15 21 23 – 7,5 13 10 1,2 0,2 750 250 (0,8 - 1,1) Us 101 0,83 12,1 0,28 55 10
690 38 18,5 11 18,5 25 23 – 9 15,5 10 1,2 0,2 600 200 (0,8 - 1,1) Us 101 0,83 12,1 0,28 55 10
690
690
690
690
4/6
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
1,14/0,48
0,45
0,45
0,68
0,68
Ordering coil codes ❶ A024 - 24 V AC 50 Hz A230 - 230 V AC 50 Hz For other voltages, contact Relpol S.A.
Coil of contactor 50 Hz Operating at 50 Hz 24 V 230 V
Thermal overload relays Type of thermal overload relay Relay base for installing as a single unit
RSTN2 CRI-330
RSTN2 CRI-330
RSTN3 CRI-340
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
60 Hz 29 V 277 V
RSTN3 CRI-340
www.relpol.com.pl
CRNI Contactors up to 100 A, AC operation
8
Type of contactor
CRNI45
CRNI63
CRNI75
CRNI85
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRNI45-30-22-... 2 2 CRNI63-30-22-... 2 2 CRNI75-30-22-... 2 2 CRNI85-30-22-... 2 2
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V AC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [VA] Power cosφ at closing consumption of AC coil (50 Hz) closed [VA] cosφ at closed Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] Rated operating current AC15 of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
1000 45 24 15 22 30 39 7-5 12,6/12 21,8/20,8 10 1,2 0,2 1200 400 (0,8 - 1,1) Us 183 0,6 17 0,29 80 10
1000 63 28 18,5 30 41 55 7-5 14,7/14 25,4/24,3 10 1,2 0,2 1000 300 (0,8 - 1,1) Us 183 0,6 17 0,29 90 10
1000 75 34 22 37 50 67 39 17,9/17 30,9/29,5 10 1,2 0,2 1000 300 (0,8 - 1,1) Us 330 0,5 32 0,23 100 10
1000 85 42 26 45 59 67 39 22/21 38/36 10 1,2 0,2 850 250 (0,8 - 1,1) Us 330 0,5 32 0,23 100 10
690
690
690
690
4/6
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
1,14/0,48
1,4
1,4
2,3
2,3
Ordering coil codes ❶ A024 - 24 V AC 50 Hz A230 - 230 V AC 50 Hz For other voltages, contact Relpol S.A.
Coil of contactor 50 Hz Operating at 50 Hz 24 V 230 V
Thermal overload relays Type of thermal overload relay Relay base for installing as a single unit
www.relpol.com.pl
RSTN4 CRI-350
RSTN4 CRI-350
RSTN4 CRI-350
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
60 Hz 29 V 277 V
RSTN4 CRI-350
CRLI Contactors over 100 A, AC operation Type of contactor
CRLI110
CRLI140
9 CRLI170
CRLI205
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRLI110-30-22-... 2 2 CRLI140-30-22-... 2 2 CRLI170-30-22-... 2 2 CRLI205-30-22-... 2 2
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V AC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [VA] Power cosφ at closing consumption of AC coil (50 Hz) closed [VA] cosφ at closed Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] Rated operating current AC15 of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
1000 110 54 37 55 76 100 65 28,4/27 49/46,9 10 1,2 0,2 1000 300 (0,8 - 1,1) Us 550 0,45 39 0,24 160 10
1000 140 68 43 75 98 100 65 36/35 63/60 10 1,2 0,2 750 200 (0,8 - 1,1) Us 550 0,45 39 0,24 160 10
1000 170 75 55 90 118 156 90 40/38 69/66 10 1,2 0,2 700 200 (0,8 - 1,1) Us 910 0,38 58 0,26 210 10
1000 205 96 64 110 145 156 90 52/50 90/86 10 1,2 0,2 500 130 (0,8 - 1,1) Us 910 0,38 58 0,26 220 10
690
690
690
690
4/6
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
1,14/0,48
3,3
3,3
4,8
4,8
Ordering coil codes ❶ A230 - 230 V AC 50 Hz For other voltages, contact Relpol S.A.
Coil of contactor 50 Hz Operating at 50 Hz 24 V 230 V
Thermal overload relays Type of thermal overload relay Box terminal block for installing as a single unit Links (set - 3 pices) for connections to contactors
60 Hz 29 V 277 V
RSTL1 CRI-360
RSTL2 –
RSTL3 –
RSTL3 –
–
CRI-370
CRI-382
CRI-382
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
CRLI Contactors over 100 A, AC operation
10
Type of contactor
CRLI250
CRLI300
CRLI400
Auxiliary contacts NO NC NO NC NO NC NO NC ❶ ❶ ❶ CRLI250-30-22-... 2 2 CRLI300-30-22-... 2 2 CRLI400-30-22-... 2 2
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V AC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [VA] Power cosφ at closing consumption of AC coil (50 Hz) closed [VA] cosφ at closed Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] Rated operating current AC15 of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
1000 250 110 78 132 178 235 132 61/58 105/100 10 1,2 0,2 700 200 (0,8 - 1,1) Us 1430 0,34 84 0,24 300 10
1000 300 125 93 160 210 235 132 69/66 119/114 10 1,2 0,2 500 130 (0,8 - 1,1) Us 1430 0,34 84 0,24 300 10
1000 400 150 125 200 284 375 250 85/81 147/140 10 1,2 0,2 500 150 (0,8 - 1,1) Us 2450 0,21 115 0,33 400 10
690
690
690
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
6,2
6,2
8,5
Ordering coil codes ❶ A230 - 230 V AC 50 Hz For other voltages, contact Relpol S.A.
Coil of contactor 50 Hz Operating at 50 Hz 24 V 230 V
Thermal overload relays Type of thermal overload relay Links (set - 3 pices) for connections to contactors
www.relpol.com.pl
RSTL4 CRI-390
RSTL4 CRI-390
60 Hz 29 V 277 V
RSTL4 CRI-390
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
CRMI, CRNI Mini-contactors and contactors up to 100 A, DC operation 11 Type of contactor
CRMI05
CRMI09
CRNI09
CRNI12
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRMI05-30-10-... 1 – CRMI09-30-10-... 1 – CRNI09-30-00-... – – CRNI12-30-00-... – –
Ordering codes
❶
CRMI05-40-00-... –
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V DC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [W] Power consumption closed [W] of DC coil Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] AC15 Rated operating current of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg] three-pole four-pole
–
❶
CRMI09-40-00-... –
–
❶
CRNI09-40-00-... –
–
❶
CRNI12-40-00-... –
690 5 1,9 1,3 2,2 2,9 3,8 – 0,81 0,86 20 0,8 0,2 1000 250 (0,8 - 1,1) Us 3 3 16 10
690 9 2,6 2,4 4 4 4 – 1,10 1,10 20 0,4 0,2 1000 250 (0,8 - 1,1) Us 3 3 16 10
690 9 3,3 2,4 4 5,5 5,5 – 1,48/1,4 2,54/2,4 15 1,2 0,2 1000 250 (0,8 - 1,1) Us 6,2 6,2 20 10
690 12 4,3 3,3 5,5 7,5 7,5 – 2/1,9 3,45/3,3 15 1,2 0,2 1000 250 (0,8 - 1,1) Us 6,2 6,2 20 10
690
690
690
690
–/4
–/4
6/10
6/10
0,5/0,3
0,5/0,3
0,9/0,45
0,9/0,45
0,22 0,22
0,22 0,22
0,58 0,58
0,58 0,58
RSTM CRI-310 –
RSTM CRI-310 –
RSTN1 – CRI-320
RSTN1 – CRI-320
–
Ordering coil codes ❶ D024 - 24 V DC For other voltages, contact Relpol S.A.
Thermal overload relays Type of thermal overload relay Module for installing as a single unit Relay base for installing as a single unit
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
CRNI Contactors up to 100 A, DC operation
12
Type of contactor
CRNI16
CRNI22
CRNI32
CRNI38
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRNI16-30-00-... – – CRNI22-30-00-... – – CRNI32-30-00-... – – CRNI38-30-00-... – –
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V DC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [W] Power consumption closed [W] of DC coil Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] AC15 Rated operating current of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
690 16 7,7 4 7,5 9 11 – 3,5 6 15 1,2 0,2 750 250 (0,8 - 1,1) Us 6,2 6,2 30 10
690 22 8,5 5,5 11 11 11 – 4 6,6 15 1,2 0,2 750 250 (0,8 - 1,1) Us 6,2 6,2 30 10
690 32 15,6 8,5 15 21 23 – 7,5 13 10 1,2 0,2 750 250 (0,8 - 1,1) Us 11,7 11,7 55 10
690 38 18,5 11 18,5 25 23 – 9 15,5 10 1,2 0,2 600 200 (0,8 - 1,1) Us 11,7 11,7 55 10
690
690
690
690
4/6
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
1,14/0,48
0,70
0,70
1,25
1,25
RSTN2 CRI-330
RSTN2 CRI-330
RSTN3 CRI-340
RSTN3 CRI-340
Ordering coil codes ❶ D024 - 24 V DC For other voltages, contact Relpol S.A.
Thermal overload relays Type of thermal overload relay Relay base for installing as a single unit
www.relpol.com.pl
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
CRNI Contactors up to 100 A, DC operation Type of contactor
CRNI45
CRNI63
13 CRNI75
CRNI85
Auxiliary contacts NO NC NO NC NO NC NO NC NO NC ❶ ❶ ❶ ❶ CRNI45-30-22-... 2 2 CRNI63-30-22-... 2 2 CRNI75-30-22-... 2 2 CRNI85-30-22-... 2 2
Ordering codes
Rated insulation voltage [V] Rated operating current (380 V) Rated outputs of three phase AC3 motors at 50 Hz [kW] AC4 Mechanical life (x 106) Electrical life (x 106)
AC3 AC4 230/220 V 400/380 V 500 V 690/660 V 1000 V 400/380 V 690/660 V DC AC3 AC4 AC3 AC4
Maximum switching frequency (1/h) Range of supply coil voltage closing [W] Power consumption closed [W] of DC coil Conventional thermal current Ith [A] Conventional thermal current Ith of auxiliary contacts [A] Rated insulation voltage of auxiliary contacts [V] AC15 Rated operating current of auxiliary contacts [A] 380/220 V DC13 110/220 V Weight [kg]
1000 45 24 15 22 30 39 7–5 12,6/12 21,8/20,8 3 1,2 0,2 1200 400 (0,8 - 1,1) Us 400 2,1 80 10
1000 63 28 18,5 30 41 55 7–5 14,7/14 25,4/24,3 3 1,2 0,2 1000 300 (0,8 - 1,1) Us 400 2,1 90 10
1000 75 34 22 37 50 67 39 17,9/17 30,9/29,5 3 1,2 0,2 1000 300 (0,8 - 1,1) Us 420 2,7 100 10
1000 85 42 26 45 59 67 39 22/21 38/36 3 1,2 0,2 850 250 (0,8 - 1,1) Us 420 2,7 100 10
690
690
690
690
4/6
4/6
4/6
4/6
1,14/0,48
1,14/0,48
1,14/0,48
1,14/0,48
1,4
1,4
2,3
2,3
RSTN4 CRI-350
RSTN4 CRI-350
RSTN4 CRI-350
RSTN4 CRI-350
Ordering coil codes ❶ D024 - 24 V DC For other voltages, contact Relpol S.A.
Thermal overload relays Type of thermal overload relay Relay base for installing as a single unit
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Contactors Coding system
14
Contactors coding system Type of contactor
Type of contactor
Value of current
Value of current
Configuration of operating contacts
Configuration of auxiliary contacts
Type and value of coil voltage
Configuration of auxiliary contacts
❶
75 - 75 A
Configuration of operating / main contacts
05 - 5 A
85 - 85 A
30 - three-pole
00 - failure
D024 - 24 V DC
CRNI - contactors up to 100 A
09 - 9 A
110 - 110 A
40 - four-pole
01 - 1 NC
A024 - 24 V AC 50 Hz
CRLI - contactors over 100 A
12 - 12 A
140 - 140 A
10 - 1 NO
A230 - 230 V AC 50 Hz
16 - 16 A
170 - 170 A
22 - 22 A
205 - 205 A
40 - 4 NO
32 - 32 A
250 - 250 A
31 - 3 NO and 1 NC
38 - 38 A
300 - 300 A
22 - 2 NO and 2 NC
45 - 45 A
400 - 400 A
CRMI mini-contactors
00 -
Contact configuration of contactor relays
Type and value of coil voltage
22 - 2 NO + 2 NC
63 - 63 A ❶ See page 15 - Contactor relays CRMI00
Examples of ordering codes: CRMI09-30-10-A230
mini-contactor, rated operating current 9 A AC3, three-pole, 1 auxiliary contact normally open, coil voltage 230 V AC 50 Hz
CRNI12-30-10-D024
contactor up to 100 A, rated operating current 12 A AC3, three-pole, 1 auxiliary contact normally open, coil voltage 24 V DC
CRNI12-40-00-D024
contactor up to 100 A, rated operating current 12 A AC3, four-pole, failure auxiliary contacts, coil voltage 24 V DC
CRLI110-30-22-A230 contactor over 100 A, rated operating current 110 A AC3, three-pole, 2 auxiliary contacts normally open and 2 auxiliary contacts normally closed, coil voltage 230 V AC 50 Hz
www.relpol.com.pl
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Contactors Add-on blocks
15
Auxiliary contacts for mini-contactors CRMI Ordering codes
Rated operating current Ie (AC-15) AC-14 at voltage: 230 / 400 / 500 V 690 / 220 V 380 V 660 V [A] [A] [A] [A]
Contact number
Weight [kg]
NO NC
CRI10-11
4
3
2
–
1
1
0,04
CRI10-20
4
3
2
–
2
–
0,04
CRI10-02
4
3
2
–
–
2
0,04
CRI10-40
4
3
2
–
4
–
0,04
CRI10-31
4
3
2
–
3
1
0,04
CRI10-22
4
3
2
–
2
2
0,04
CRI10-13
4
3
2
–
1
3
0,04
CRI10-04
4
3
2
–
–
4
0,04
Contactor relays CRMI00 ❶ Ordering codes
Rated operating current Ie (AC-15) AC-14 at voltage: 230 / 400 / 500 V 690 / 220 V 380 V 660 V [A] [A] [A] [A]
Contact number
Weight [kg]
NO NC
CRMI00-40-00-A230
4
3
2
1
4
–
0,19
CRMI00-31-00-A230
4
3
2
1
3
1
0,19
CRMI00-22-00-A230
4
3
2
1
2
2
0,19
Add-on blocks for contactors CRNI, CRLI Ordering codes
Contactor application
Weight [kg]
–
from CRNI09
0,02
1
to CRNI38
0,02
1
from CRNI45
0,042
Contact number
Rated operating current Ie (AC-15) AC-14 at voltage: 230 / 400 / 500 V 220 V 380 V [A] [A] [A]
690 / 660 V [A]
CRI20-10
5,6/6
3,8/4
2,5
1,8/2
1
CRI20-01
5,6/6
3,8/4
2,5
1,8/2
–
CRI20-11
5,6/6
3,6/4
2,5
2,3/5
1
NO NC
to CRLI400 Auxiliary contacts CRI-420
from CRNI45 to CRLI300
Mechanical latches
CRI-430
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
CRLI400
www.relpol.com.pl
Contactors Technical data
16
Strength of main contacts (AC3)
Electrical life 400 V
Electrical life 690 V
Electrical life 500 V
Electrical life 230 V
Type of contactor
Strength of main contacts (AC3)
www.relpol.com.pl
Electrical life 400 V
Electrical life 690 V
Electrical life 500 V
Electrical life 230 V
Type of contactor
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Contactors Technical data
17
Strength of main contacts (AC3)
Electrical life 400 V
Electrical life 690 V
Electrical life 500 V
Electrical life 230 V
Type of contactor
Breaking current Rated operating current
Rated output of three-phase motors with squirrel-cage (at 400 V)
DC circuit diagrams
CRNI45 to CRNI85 (DC economy circuit)
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Contactors Dimensions
18 Dimensions
Additional module
CRMI05 or CRMI09 to be installed as a single unit
CRNI16 or CRNI22 + RSTN2 thermal overload relay
CRNI09 or CRNI12 + RSTN1 thermal overload relay Auxiliary contacts block with position indicator Labelling plate
CRNI32 or CRNI38 + RSTN3 thermal overload relay
Type
a1
a2
a3
b1
b2
b3
CRNI45 to CRNI85 + RSTN4 thermal overload relay
c1
(c1) 1
d1
d2
d3
e
e2
f1
f2
f3
g
g1
g2
CRNI45, CRNI63
90
113 70 117 175 100 123 123
8
26,5
25
94
34
80
63 122 28
4,8
6,1 (M6)
CRNI75
100 123 80 133 194 110 140 140
8
26,5
25
107
36
89
63 122 39
5,5
6,1 (M6)
CRNI85
400 123 80 133 194 110 140 140 10,5 26,5
25
116
31,5 89
63 122 39
5,5
6,1 (M6)
( ) DC operation 1
www.relpol.com.pl
*) Minimum clearance from the earthed parts. **) Dimension for the square OFF button (stroke 3 mm). Dimension for the round RESET button (stroke 2,5 mm) less 2,5 mm.
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Contactors Dimensions, permissible mounting positions
19
Dimensions *) Minimum clearance from the earthed parts. **) Dimension for the square OFF button (stroke 3 mm). Dimension for the round RESET button (stroke 2,5 mm) less 2,5 mm.
Type
h
j
RSTL1
37
M6
RSTL2
42
M8
CRLI110 with box terminal block CRLI140 without box terminal block
CRLI110 + RSTL1 thermal overload relay, CRLI140 + RSTL2 thermal overload relay
a1
Type
a2
a3
b1
b2
b3
c1
d1
d2
d3
e
e1
e2
f1
f2
f3
g
g1
g2
CRLI110
120 143
100 150
232 130 150 15
37
37
130
213
40
93 80 146
45
6,3 6,1 (M6)
CRLI140
120 143
100 150
232 130 150 20
42
37
139
215,5
40,5
93 80 146
45
6,3
b3
f1
g
9 (M8)
CRLI205 to CRLI400
a1
Type CRLI170 + RSTL3 thermal overload relay
a2
a3
b1
c1
e1
d1 d2
g1
CRLI205
135 158 110 180 160 185 159 115 48 25 48
7
CRLI250, CRLI300
145 168 120 200 180 198 168 132 58 25 48
9
CRLI400
160 183 130 200 180 222 178 150 65 25 48
9
Permissible mounting positions The contactors are designed for operation on vertical mounting surface.
CRNI09 to CRNI22 (AC operation)
CRNI32 CRNI45 CRNI09 CRNI45
to to to to
CRNI38 CRLI400 CRNI22 CRNI85
(AC operation) (AC operation) (DC operation) (DC economy circuit)
CRNI32 to CRNI38 (DC operation)
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Thermal overload relays 20
Ordering codes
RSTM RSTM-0V16 RSTM-0V25 RSTM-0V4 RSTM-0V63 RSTM-1 RSTM-1V25 RSTM-1V6 RSTM-2 RSTM-2V5 RSTM-3V2 RSTM-4 RSTM-5 RSTM-6V3 RSTM-8 RSTM-10 RSTM-12
Ordering codes
RSTN1 RSTN1-0V6 RSTN1-0V25 RSTN1-0V4 RSTN1-0V63 RSTN1-1 RSTN1-1V25 RSTN1-1V6 RSTN1-2 RSTN1-2V5 RSTN1-3V2 RSTN1-4 RSTN1-5 RSTN1-6V3 RSTN1-8 RSTN1-10 RSTN1-12V5 RSTN1-14V5
Ordering codes
RSTN2 RSTN2-6V3 RSTN2-8 RSTN2-10 RSTN2-12V5 RSTN2-16 RSTN2-20 RSTN2-25
www.relpol.com.pl
Adjustment rated range [A] 0,1 - 0,16 0,16 - 0,25 0,25 - 0,4 0,4 - 0,63 0,63 - 1 0,8 - 1,25 1 - 1,6 1,25 - 2 1,6 - 2,5 2 - 3,2 2,5 - 4 3,2 - 5 4 - 6,3 5-8 6,3 - 10 8 - 12
Adjustment rated range [A] 0,1 - 0,16 0,16 - 0,25 0,25 - 0,4 0,4 - 0,63 0,63 - 1 0,8 - 1,25 1 - 1,6 1,25 - 2 1,6 - 2,5 2 - 3,2 2,5 - 4 3,2 - 5 4 - 6,3 5-8 6,3 - 10 8 - 12,5 10 - 14,5
Adjustment rated range [A] 4 - 6,3 5-8 6,3 - 10 8 - 12,5 10 - 16 12,5 - 20 16 - 25
Fuse links [A] IEC947 - 4 ”1”
”2”
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
0,5 1 1,6 2 4 4 6 6 6 10 10 10 10 10 10 10
Fuse links [A] IEC947 - 4 ”1”
”2”
35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
0,5 1 1,6 2 4 4 6 6 6 10 10 16 16 20 25 25 25
Fuse links [A] IEC947 - 4 ”1”
”2”
63 63 63 63 63 63 63
16 20 25 25 35 35 50
Contactor application
Weight [kg]
CRMI05 CRMI09
0,14
Contactor application
Weight [kg]
CRNI09 CRNI12
0,14
Contactor application
Weight [kg]
CRNI16 CRNI22
0,14
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Thermal overload relays 21
Ordering codes
RSTN3 RSTN3-12V5 RSTN3-16 RSTN3-20 RSTN3-25 RSTN3-32 RSTN3-36 RSTN3-40 RSTN3-45
Ordering codes
RSTN4 RSTN4-20 RSTN4-25 RSTN4-32 RSTN4-40 RSTN4-50 RSTN4-57 RSTN4-63 RSTN4-70 RSTN4-80 RSTN4-88
Ordering codes
RSTL1 RSTL1-80 RSTL1-90 RSTL1-110 RSTL1-120 RSTL1-135
Ordering codes
RSTL2 RSTL2-80 RSTL2-90 RSTL2-110 RSTL2-120 RSTL2-135 RSTL2-150
Adjustment rated range [A] 8 - 12,5 10 - 16 12,5 - 20 16 - 25 20 - 32 25 - 36 32 - 40 36 - 45
Adjustment rated range [A] 12,5 - 20 16 - 25 20 32 25 - 40 32 - 50 40 - 57 50 - 63 57 - 70 63 - 80 70 - 88
Adjustment rated range [A] 55-80 63-90 80-110 90-120 110-135
Adjustment rated range [A] 55-80 63-90 80-110 90-120 110-135 120-150
Fuse links [A] IEC947 - 4 ”1”
”2”
100 100 100 100 100 100 100 100
25 35 50 50 80 80 80 80
Fuse links [A] IEC947 - 4 ”1”
”2”
160 160 160 160 160 160 160 160 250 250
50 50 63 80 100 100 100 125 160 160
Fuse links [A] IEC947 - 4 ”1”
”2”
250 250 315 315 315
160 160 200 224 224
Fuse links [A] IEC947 - 4 ”1”
”2”
250 250 315 315 315 315
160 160 200 224 224 224
Contactor application
Weight [kg]
CRNI32 CRNI38
0,20
Contactor application
Masa [kg]
CRNI45 CRNI63 CRNI75 CRNI85
0,40
Contactor application
Weight [kg]
CRLI110
0,70
Contactor application
Weight [kg]
CRLI140
0,70
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Thermal overload relays Add-on blocks for independent mounting
22
Ordering codes
RSTL3 RSTL3-80 RSTL3-90 RSTL3-110 RSTL3-120 RSTL3-135 RSTL3-150 RSTL3-160 RSTL3-180
Ordering codes
RSTL4 RSTL4-125 RSTL4-200 RSTL4-250 RSTL4-320 RSTL4-400
Fuse links [A]
Adjustment rated range [A]
IEC947 - 4
55 - 80 63 - 90 80 - 110 90 - 120 110 - 135 120 - 150 135 - 160 150 - 180
”1”
”2”
250 250 315 315 315 315 355 355
160 160 200 224 224 224 224 224
Fuse links [A]
Adjustment rated range [A]
IEC947 - 4
80 - 125 125 - 200 160 - 250 200 - 320 250 - 400
”1”
”2”
500 500 500 500 800
250 315 400 400 500
Contactor application
Weight [kg]
CRLI170 CRLI205
0,70
Contactor application
Weight [kg]
CRLI250 CRLI300 CRLI400
2,50
Add-on blocks for independent mounting of thermal overload relays Ordering codes
❶ Set - 3 pieces
www.relpol.com.pl
Name
Contactor application
Weight [kg]
CRI-310
Module for RSTM - for installing as a single unit, this module includes screw terminals
CRMI05, CRMI09
0,01
CRI-320
Relay base for RSTN 1 - for installing as a single unit
CRNI09, CRNI12
0,05
CRI-330
Relay base for RSTN 2 - for installing as a single unit
CRNI16, CRNI22
0,05
CRI-340
Relay base for RSTN 3 - for installing as a single unit
CRNI32, CRNI38
0,05
CRI-350
Relay base for RSTN 4 - for installing as a single unit
CRNI45, CRNI63,
0,05
CRI-360
Box terminal block for RSTL1 - for installing as a single unit
CRLI110
CRI-370
Links ❶ for RSTL2, RSTL3 - for connections to contactors
CRLI140, CRLI170
CRI-382
Links ❶ for RSTL3, RSTL4 - for connections to contactors
CRLI205, CRLI250
CRI-390
Links ❶ for RSTL4 - for connections to contactors
CRLI250, CRLI300,
CRNI75, CRNI85
CRLI400
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
0,2
Thermal overload relays Technical data
23
Technical data for release times up to 10 s according to IEC/EN 60947 Type of thermal overload relay Release time classification Phase failure protection
RSTM
RSTN1 / RSTN2
RSTN3
RSTN4
RSTL1
RSTL2 / RSTL3
RSTL4
Class 10 A (2 s < tA ≤ 10 s at 7,2 x Ie from cold state and tA ≤ 2 min. at 1,5 x Ie from hot state) Yes Yes Yes Yes Yes Yes Yes
by differential phase shift Changeover to automatic reset RESET button with trip-free feature Temperature compensation Switch position indicator Test button actuates
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No ❶
Yes
Yes
No ❶
No ❶
No ❶
No ❶
the NO and NC contacts Terminal for contactor coil Permanent ambient temperature [°C]
-25...+55
-25...+55 ❷
Degree of protection
IPIP0000 (open) (open) oror IPIP 2020 toto IEC/EN IEC 947-1 60947 and and DIN DIN 4040050 050 8/10
Shock resistance [g/ms] Main circuit Rated current [A]
12 600
Rated voltage [V AC] Rated impulse strength Uimp [kV] Rated voltage of insulation Ui [V] ❸
14,5 / 25 600
45 600
88 600
135 600
150 / 180 600
400 600
6
6
6
8
8
8
8
690
690
690
1000
1000
1000
1000
Type of current frequency
DC, AC up to 400 Hz
AC up to 400 Hz
Conductor cross-sections Terminal screw • solid or stranded [mm2]
M3
M4
M5
M5
M6
M8
M8 / M10 ❹
0,5 to 2,5
2,5 to 6
1,5 to 25
2,5 to 35
25 to 70
50 to 120
185 / 240 ❹
• flat bars [mm]
0,5 to 1,5 –
1,5 to 4 –
1 to 16 –
1,5 to 25 –
25 to 50 –
25 to 95 20×3
– 20×3 /
• tightening torque [Nm]
0,4 to 0,7
1 to 1,5
2,5 to 3
2,5 to 3
6 to 8
10 to 14
• tightening torque [Ib.in]
4 to 6,5
9 to 13
22 to 26,5
22 to 26,5
52 to 50
89 to 124
• finely stranded with end sleeve [mm2]
20×3×5 ❹ 10 to 14 / 14 to 24 ❹ 89 to 124 / 124 to 210 ❹ Power loss per current path (max.) • at lowest value [W (VA)] • at highest value of the setting range [W (VA)]
0,6
0,9
1,2
2,6
5
5
4 (5)
2,3
2,25
3
4
7
7/–
10 (12)
Auxiliary circuit Auxiliary contacts
1NO + 1NC / 1 changeover
1NO + 1NC / 1NC
1NO + 1NC
Conductor cross-sections Terminal screw • solid or stranded [mm2]
M3
M3,5
2×(0,5 to 2,5)
2×(0,5 to 1) / 2×(1 to 2,5) 2×(0,5 to 1) / 2×(0,75 to 2,5)
• finely stranded with end sleeve [mm2] 2×(0,5 to 1,5) • tightening torque [Nm] 0,4 to 0,7 • tightening torque [Ib.in] 4 to 6,5
0,8 to 1,4 7 to 12 600; > 150 same polarity 6
Rated voltage [V AC] Rated impulse strength Uimp [kV] Rated voltage of insulation Ui [V] ❸
690
400
690
NC
Unequal potential (NO + NC)
Equal potential (NO + NC connected as changeover contact)
Switching capacity
B 600, R 300 at AC-15
• rated operating voltage Ue [V] • rated operating current Ie [A]
at DC-13
24
60
125
230
400
500
690
24
60
110
220
2
1,5
1,25
1,15
1,1
1
0,8
2
0,5
0,3
0,2
• conventional termal current Ith [A]
6
Short-circuit protection ❶ For 35 mm DIN rail mount, EN 50022
Fusses Class gL/gG - 6 A ❷ For 75 mm DIN rail mount, EN 50023
❸ Pollution severity 3
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
❹ Setting range (≤ 200 A / > 200 A)
www.relpol.com.pl
Thermal overload relays Technical data
24 Release time Adjustment rated range
Conductor cross-sections
[A]
[mm2]
Release time (±20%) with three-pole symmetrical load form the cold state. Adjusted current multiplication factor (x Ie) [s] 3
4
5
6
7,2
8
RSTM 0,1 - 0,16
1
23,8
14,5
10,5
8,3
6,8
5,8
0,16 - 0,25 0,25 - 0,4
1 1
22,5 22,8
14 14
10,1 10
8 7,8
6,5 6,3
5,5 5,4
0,4 - 0,63
1
23,5
14,1
10,2
8
6,5
5,6
0,63 - 1 0,8 - 1,25
1 1
25 27,5
15 16,7
10,8 11,8
8,3 9
6,8 7,2
5,7 6
1 - 1,6
1
25
15,5
11
8,6
7
5,9
1,25 - 2 1,6 - 2,5
1 1
26,5 27,4
17 17,3
12,7 12,7
10 10
8,4 8,3
7,2 7,2
2 - 3,2
1
29,5
18
12,9
10
8,1
6,7
2,5 - 4 3,2 - 5
1 1
28,5 29
17,5 17,6
12,4 12,3
9,6 9,5
7,8 7,5
6,5 6,3
4 - 6,3
1
28,5
17
11,9
9
7,2
5,8
5-8 6,3 - 10
1 1,5
29 25
17,5 14,1
12 9,4
9 6,8
7,1 5,2
5,8 4,2
8 - 12 RSTN1
1,5
29
17,2
12
9,2
7,3
6
0,1 - 0,16
1
16,7
10,3
7,5
5,9
4,8
4,1
0,16 - 0,25 0,25 - 0,4
1 1
20,5 18
12,8 11,2
9,5 8,2
7,5 6,5
6,3 5,4
5,4 4,6
0,4 - 0,63
1
20,8
12,8
9,5
7,6
6,3
5,4
0,63 - 1 0,8 - 1,25
1 1
23,3 28
14,4 17,5
10,5 12,7
8,3 9,8
6,8 8,1
5,8 6,8
1 - 1,6
1
22,6
14,3
10,4
8,3
6,8
5,9
1,25 - 2 1,6 - 2,5
1 1
22,3 24,5
14 15,5
10,3 11,5
8,4 9
6,9 7,5
6,0 6,4
2 - 3,2
1
23,8
15
11
8,8
7,3
6,3
2,5 - 4 3,2 - 5
1 1
24,4 27,5
15,6 17
11,4 12,2
9,1 9,5
7,6 7,8
6,5 6,5
4 - 6,3
1
23,4
14,4
10,4
8
6,5
5,5
5-8 6,3 - 10
1 1,5
22,5 24
13,5 13,9
9,5 9,3
7,2 6,8
5,7 5,3
4,7 4,3
8 - 12,5
2,5
24,5
14,8
10,2
7,8
6,2
5,2
10 - 14,5 RSTN2
2,5
23,2
13,9
9,5
7,2
5,6
4,6
4 - 6,3
1
23,4
14,4
10,4
8
6,5
5,5
5-8 6,3 - 10
1 1,5
22,5 24
13,5 13,9
9,5 9,3
7,2 6,8
5,7 5,3
4,7 4,3
8 - 12,5
2,5
24,5
14,8
10,2
7,8
6,2
5,2
10 - 16 12,5 - 20
2,5 2,5
23,2 23
13,9 13
9,5 8,6
7,2 6,3
5,6 4,8
4,6 3,9
16 - 25
4
31
17
11
7,7
5,8
4,6
RSTN3 8 - 12,5
2,5
24,5
14,8
10,2
7,8
6,2
5,2
10 - 16
2,5
26,2
15,8
10,8
8,1
6,4
5,2
12,5 - 20 16 - 25
2,5 4
26,6 29
14,8 15,4
9,7 9,8
7 7
5,3 15,3
4,3 4,2
20 - 32
6
28
16,1
10,8
8,2
6,3
5,2
25 - 36 32 - 40
10 10
33,4 24,3
19 13,6
12,8 8,8
9,3 6,6
7,2 5
5,8 4,2
36 - 45
10
23
13
8,5
6,2
4,5
3,3
www.relpol.com.pl
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Thermal overload relays Technical data
25
Release time Adjustment rated range
Conductor cross-sections
[A]
[mm2]
Release time (±20%) with three-pole symmetrical load form the cold state. Adjusted current multiplication factor (x Ie) [s] 3
4
5
6
7,2
8
19,5 18,5
13,2 12,8
9,7 9,4
7,6 7,4
6,2 6
RSTN4 12,5-20 16 - 25 20 - 32
4 6
34 33
25 - 40
10
30
17
11,5
8,4
6,5
5,3
32 - 50 40 - 57
10 16
29 35
16,6 19,4
11 12,3
8 8,7
6,2 6,6
5 5,3
50 - 63
16
37
20,5
13,3
9,6
7,3
5,8
57 - 70 63 - 80
25 25
40 40
21,5 21,5
14 13,8
9,8 9,7
7,4 7,3
5,8 5,8
70 - 88
35
33,9
17,6
11,8
8
6,5
4,9
RSTL1, RSTL2, RSTL3 55 - 80
25
36
21
13,5
9,8
7,5
6,1
63 - 90
35
44
24
15,5
11
8,5
6,7
80 - 110 90 - 120
35 50
43 40
22 21,8
14 14
10 10
7,7 7,5
6,1 5,9
110 - 135 120 - 150
50 50
32 35
18 19,5
11,7 12,8
8,4 9,4
6,4 7,2
5,1 5,8
135 - 160
70
38
20,6
13,8
10
7,6
6,2
150 - 180 RSTL4
95
37
20,5
13,5
9,7
7,4
6,0
80 - 125
50
25
16,8
13,1
11,1
9,9
9,1
125 - 200 160 - 250
95 120
24,4 23,8
16,1 13,9
11,9 10,3
9,8 8,5
8,4 7,3
7,4 6,5
200 - 320
185
25,6
15,5
10,9
8,5
7
6,4
250 - 400
240
25
15
10,5
8,5
7
6,2
Protection characteristics Item No.
Adjusted current multiplication factor
Release time
Test condition
1 2
1,05 1,20
>2h❶ <2h❶
Cold state Hot state
3
1,50
< 2 min. ❶
Pre-heated for 2 hours with 1 adjusted current multiplication factor
4
7,2
2 s < Tp < 10 s, Class 10 A
Cold state
Hot state means heat the thermal overload relay into steady state with the current as shown in ”Item No. 1”. Adjusted current multiplication factor Any two phases Another phase 5
1,0
6
1,15
0,9
Release time
Test condition
>2h❷
Cold state
0 >2h❷ Hot state means heat the thermal overload relay into steady state
Hot state
with the current as shown in ”Item No. 1”. ❶ Release time with three-pole symmetrical load at ambient termperature +20 °C ❷ Release time with three-pole unsymmetrical load (phase-failure) at ambient termperature +20 °C
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Thermal overload relays Technical data
26
Tripping characteristics The current-time curves show the relationship between the tripping time from cold state and multiples of the set
Fig. Typical tripping characteristics
current Ie. When the relay is at operating temperature and carrying 1,0 x Ie, the tripping times are reduced to approximately 25%. curve 2 to two-pole loads. For single-pole loads the tripping curves lie between curves 2 and 3. For normal
[min.]
Tripping curve 3 is applicable to three-pole loads and
must be heated. The thermal overload relays RSTM, RSTN, RSTL are suitable for protecting motors with phase control. For protecting single-phase or DC-loads, therefore, all three
Tripping time
operation, all three bimetallic strips of the overload relay
Tripping curve 3 is then applicable. The release current with a three-pole symmetrical load
[s]
main conducting paths must be connected in series.
is between 105% and 120% of the set current.
Tripping current (average) [A]
Internal connection diagrams RESET button
RSTN1, RSTN2, RSTN3
OFF button
RESET button
RSTN4, RSTL1, RSTL2, RSTL3
OFF button
Current transformer RESET button
Thermal overload relay
Connection leads Cu 4 mm2, 4 m long
RSTL4
www.relpol.com.pl
OFF button
RSTL4 separate mounting of current transformer and thermal overload relay
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Thermal overload relays Technical data
27
Installation
1. Marks on panel (marks on thermal overload relays).
❻ ❶
❻ ❺ ❹
❷ ❸ ❼
❺ ❽
❹
❷
❸
❼
Panel RSTN1, RSTN2, RSTN3
Panel RSTN4, RSTL1, RSTL2
❶ Terminal for contactor coil ❷ Setting current adjusting scale ❸ RESET button (blue) H - manual A - automatic
❹ Switch position indicator (green) Tripping of a manual-resetting relay is indicated by a pin projecting from the front-plate
❺ ❻ ❼ ❽
Test button (red) Auxiliary contacts terminals Main circuit connection terminal No. It must correspond with terminal No. of contactor In case of separate mounting of RSTL, the set current must be set on the scale against the reference mark
2. Set the scale to the rated current of the load. 3. If the reset button points to H (manual) and the relay has been tripped, pressing the button puts the relay in operation again. Changing to automatic reset by pressing and turning the button anti-clock wise from H to A. 4. When the test button is actuated, the NC contact opens and the NO contact closes, therefore the auxililary circuit (simulation of overload tripping) can be tested. In the “manual” position, the relay is resetted when the blue reset button is pressed. In the “automatic” postion, the relay is reset automatically. In the automatic mode, there is a risk of self-switching when the button is released. 5. Mounting and operating position, the relays are shown in drawings.
Thermal overload relay with CRNI contactor.
Thermal overload relay with relay base or box terminal block
Tripping relay to be installed as a single unit.
- for installing as a single unit.
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Thermal overload relays Dimensions
28 Dimensions
CRI10 type auxiliary contact Additional module (on thermal overload relay)
RSTM + CRMI05 or CRMI09 contactor
RSTN1 + CRNI09 or CRNI12 contactor
RSTN2 + CRNI16 or CRNI22 contactor
RSTN1 or RSTN2 or RSTN3 + relay base for installing as a single unit Thermal overload relay RSTN3 + CRNI32 or CRNI38 contactor
d
e
f
RSTN1 with CRI-320 RSTN2 with CRI-330
10 14,3
M4 M4
M3,5 M4
RSTN3 with CRI-340
18,2
M5
M5
with relay base
*) Minimum clearance from the earthed parts. **) Dimension for the square OFF button (stroke 3 mm). Dimension for the round RESET button (stroke 2,5 mm) less 2,5 mm. 1) For 35 mm DIN rail mount, EN 50022.
www.relpol.com.pl
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
Thermal overload relays Dimensions
29
Dimensions
RSTN4 + relay base CRI-350 for installing as a single unit
RSTN4 + CRNI45 for CRNI85 contactor
a1
Type
a2
a3
b1
b2
b3
c1
d1
d2
d3
e
e1
f1
f2
f3
g
g1
g2
CRNI45, CRNI63
90
113
70
117
175
100
132
10,5 26,5
25
102
31,5
80
63
122
28
4,8
6,1
CRNI75, CRNI85
100
123
80
133
194
110
140
10,5 26,5
25
116
31,5
89
71
132
39
5,5
6,1
RSTL1 to be installed with contactor CRLI110
RSTL2 to be installed with contactor CRLI140
or with box terminal block CRI-360 for installing as a single unit
RSTL3 to be installed with contactor CRLI170 or CRLI205
*) Minimum clearance from the earthed parts. **) Dimension for the square OFF button (stroke 3 mm). Dimension for the round RESET button (stroke 2,5 mm) less 2,5 mm. 1) For 35 mm DIN rail mount, EN 50022. 2) Height and spacing of the connection rails can accmodated to CRLI110, CRLI170 contactors (not for RSTL2).
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
www.relpol.com.pl
Thermal overload relays Dimensions
30 Dimensions
RSTL1 + CRLI110 contactor, RSTL2 + CRLI140 contactor, RSTL3 + CRLI170 contactor
a1
a2
a3
b1
b2
b3
c1
d1
d2
d3
e
e1
e2
f1
f2
f3
g
g1
g2
CRLI110
120
143
100
150
232
130
150
15
37
37
130
213
40
93
80
146
45
6,3
M6
CRLI140
120
143
100
150
232
130
150
20
42
37
139 215,5 40,5
93
80
146
45
6,3
M8
CRLI170
135
158
110
180
257
160
185
20
42
42
154
115
93
153
48
7
M8
Type
234
40
RSTL4 to be installed as a single unit
Type RSTL4-125, -200 RSTL4-250, -300, -400
a 46 50
b 140 140
c 69 70
d 9 11
e 160 171
*) Minimum clearance from the earthed parts. **) Dimension for the square OFF button (stroke 3 mm). Dimension for the round RESET button (stroke 2,5 mm) less 2,5 mm. 1) Box terminal blocks only for CRLI110. 2) For 75 mm DIN rail mount, EN 50023.
www.relpol.com.pl
Export Sales Department phone +48 68 47 90 838 • Marketing Department phone +48 68 47 90 900
f 20 x 3 25 x 4
31