SITRANS P300 Operating instructions in brief A5E00359581-01
2
Mode 5 s
3
Please refer to the Instruction Manual prior to installation and startup! A5E00359580 (D) A5E00359579 (GB) A5E00359578 (F) A5E00359577 (I) A5E00359576 (E)
4
5
-2-
Adjusting start of scale Select mode 02
Setting start of scale Select mode 02 Apply reference pressure Connect DC ammeter (recommended) UP and DOWN Keep pressed for 2 s to set MA to 4 mA
Setting full scale: Select mode 3
Apply reference pressure Connect DC ammeter (recommended)
6
UP
DOWN
ZERO ZERO
-3-
11
(12) Violation of lower limit (13) Symbol for measured value (14) Violation of higher limit (15) Communication display
9
Adjusting start of scale Setting start of scale without application of pressure: without application of pressure: Select mode 05 Select mode 05
Adjusting full scale: Select mode 03 Apply reference pressure Connect DC ammeter (recommended)
UP and DOWN keep pressed for 2 s to set ME to 20 mA
Adjust MA using UP and DOWN (variable speed) and save ME using Mode
-9-
Adjust current according to calculation formula, see Instruction Manual, Section 6
- 10 -
Adjusting full scale Setting full scale without application of pressure: without application of pressure Select mode 06 Select mode 06 Set full-scale value to the upper sensor limit using UP and DOWN (2s) Press Mode to save value - 11 -
Adjust pressure which is to correspond to ME using UP and DOWN (variable speed) Press Mode to save value - 12 -
Set and adjust MA
M3
Set and adjust ME
M4
Adjust damping
1) 2) 4) 1) 2) 4)
Current transm., and for 2 s Fault current upper/lower
M10 Keyboard disabling, read-only
Adjust MA without pressure
M6
Adjust ME without pressure
1) 2)
M7
Zero adjustment
M5
M13 mA % measuring mode M14 mA % dimension
2) 4)
MODE Save value UP / DOWN Change value
1) 2)
B Setting start of scale (p. e. 2 bar)
0
Set Zero using UP and DOWN Press Mode to save value
FW: aa . bb . cc FW release Document Revision Device type
HW: xx . yy . zz Compatibility number Connection Board version
Ex Data See Instruction Manual and conformity certificates! (See page -1-)
Measuring cell version
- 13 -
- 14 -
18
2
11
4
16
20 mA
14
16 barr
20 mA
D Calculating output current (p. e. 11 bar)
1) 2)
2)
UP or DOWN change value
3)
MODE ,exit without saving
I=
-7-
11 bar - 2 bar * 16 mA + 4 mA = 16 mA 14 bar - 2 bar Prerequisite: see Instruction Manual, Section 6
-8-
(1) (2A)
Can be read from the approval label
Vent transmitter (pressure, differential pressure, flow, level) or evacuate (absolute presssure <0.1‰ of span)
16 bar
2 4
Connecting the transmitter
FW/HW releases
20 mA
4
C Setting full scale (p. e. 14 bar)
1) 2)
-6-
-5-
16 bar
0
A Initial situation
1) 2)
0
4)
Zero point adjustment Select mode 07
M8 M9
2) 3)
1) 2) 1) 2)
1)
-4-
Set start-of-scale value ro the lower sensor Adjust pressure which is to correspond to Adjust MA using UP and DOWN (variable limit using UP and DOWN (2s) MA using UP and DOWN (variable speed) speed) and save MA using Mode Press Mode to save value Press Mode to save value
Apply pressure corresponding to ME to the transmitter
Note: the keys my be disabled! Remove keyboard disabling See page 3
(1) shield support (2) (+) power supply (3) (-) power supply (4) Test plug for external DC ammeter (5) Mode key C Constant current mode (6) Increment key L Read-only (7) Decrement key LA Keyboard disabled (8) Measured value LO Only MA can be set (9) Unit/bar graph LS MA + ME can be set (11) Mode/button lock LL Keyboard disable (enable only via HART)
7
SPAN SPAN
MODE
-1-
Display mode in mA % pressure
14 13 12
!
Setting start of scale and full scale
MA= zero point ME= limit point
M2
Keyboard diable Read-only OFF
Operation
Operation
Legend 1-15
8
15
1
(1) Supply terminals (2A) Shield support with plastic cable gland (2B) Shield on cable gland (3) Auxiliary power UH (4) Load
(3)
(4)
(2B)
- 15 -