Single Phase Simplex Control Panel Installation and Operator’s Manual
IM 714, Rev. 0117
WS Series® Simplex Control Panel
Panel Installation:
The WS Series® simplex control panels will control a pump in sewage, wastewater, and dewatering applications. See Water simplex control panels come standard with a clear front NEMA 4X rated enclosure, three floats (stop, start, and high liquid alarm), an IEC rated contactor, a circuit breaker, and adjustable overload. All panels are UL listed for the United States and Canada and come with a three year warranty.
1. Caution: To maintain the NEMA 4X rating, make all wiring connections with seal tight cable grips or conduit connections. 2. Determine mounting location for control panel. Mount panel using mounting feet supplied. 3. The control panel should not be mounted in an area that is subject to submersion. 4. Run pump cable and float cables through conduit. Make field connections as shown on wiring diagram. 5. Run power line conductor through conduit. Wire to terminals per enclosed schematic. Branch circuit protection to be provided by installer. 6. Float cables require separate conduit from power and pump cables. 7. Mount float switches at appropriate levels. Be sure that the floats have a free range of motion to prevent entanglement.
Models (Ratings): WS1P-TP-1001 (0-7 pump full load amps) WS1P-TP-1002 (7-15 pump full load amps) WS1P-TP-1003 (15-22 pump full load amps) WS1P-TP-1004 (22-28 pump full load amps) WS1P-TP-1005 (28-36 pump full load amps) Features: • • • • • • • • • •
Designed to Control One 120/208/240VAC pump in sewage applications NEMA 4X polycarbpmate enclosure with stainless steel lockable latches Pump control visible features: pump hand-off-auto (H.O.A.) switch, green pump run light, red pump fault light with reset button and green power on light Alarm visible features: red beacon alarm light, alarm test and silence buttons Alarm horn sounds at 85 decibels at 10’ Remote monitoring dry contacts: high liquid, pump fault, pump run (normally open) Pump protection: motor protective switch included for pump (branch circuit protection, adjustable overload and disconnect), pump thermal cutout circuit Includes three narrow angle float switches with 20′ cords and mounting hardware Float status indicators (stop, start, high liquid) UL Listed for the United States and Canada
Start up: 1. When the power is applied, the green power light located on the white front swing panel shall light. 2. The Pump HOA Switch shall be placed to the A (auto) position to ensure the pump will turn on from the commands of the floats. The pump can be tested or turned on manually if the HOA switch is held in the H (Hand-Manual) position. To test the alarm circuit, push the test button on the front panel, the audible alarm shall sound and the red beacon will light. Press the silence button to silence the alarm.
www.seewaterinc.com 951.487.8073 • 888.733.9283
[email protected] 22220 Opportunity Way, Suite 104 Riverside, CA 92518 1. All installations must be in accordance with the National Electrical Code, and any other applicable state and local electrical requirements.
Single Phase Simplex Control Panel Additional Panel Options: LL - Low Level Alarm Circuit (optional) Includes normally closed low level float switch. Alarm horn will sound and red beacon will light in the event of a low level. Comes with normally open low level dry contact.
Typical Installation for Simplex Control Panel A typical installation showing a pump on “start” float, pump off “stop” float, and a high liquid alarm float.
Simplex Demand Control Panel
SF - Seal Failure Circuit (optional) The seal fail circuit will indicate when there is water in the pump chamber. The circuit is setup to work with a variety of pumps with a range of resistance sensitivity settings. AF - Alarm Flasher ET - Elapsed Timer Meter w/ LCD display & reset CC - Cycle Counter w/LCD display & reset LA - Lightning Secondary Surge Arrestor MD - Main Disconnect
Conduit sized by end-user
HIGH LIQUID ALARM
Service: Caution: Before checking electrical connections within the control or attempting to replace any components, turn off all branch circuits supplying power to the main control panel.
PUMP ON
Troubleshooting: Alarm Circuit
PUMP OFF
To test the alarm light and buzzer, press the test button on the front panel. If either the light or buzzer do not indicate, replace the light bulb or buzzer with same type. Control Board and Fuse The control board is rated for 120/208/240VAC. If the power on light is not illuminating on the front panel, check the voltage at TS1-1 and TS1-2 with a voltage meter. If voltage present, check the fuse in the fuse block. If fuse is blown, replace fuse with same type. The dry contacts are rated for 0-60VAC, 1 amp maximum. Floats The control board has LED Indicators that will illuminate when the floats are in the closed position. Check floats for entanglement, full range of motion. Replace damaged floats.