Tag #:
Job Name/Location: Date:
For:
PO No.: Architect:
GC:
Engr:
Mech:
File
Resubmit
Approval
Other
Rep: (Company)
PQRCVCL0QW
(Project Manager)
LH247HV Single Zone High Static Duct Outdoor Unit (ODU) ‐ LUU247 Indoor Unit (IDU) ‐ LHN247HV Operating Range: Outdoor Unit:
Performance: Cooling: Capacity (Btu/h) SEER EER
24,000 17.0 12.0
Heating: Capacity (Btu/h) HSPF
27,000 10.0
HSPF ‐ Heating Seasonal Performance Factor Heating Nominal Test Conditions: Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB
208‐230/60/1
MOP (A)
30
MCA (A) Cooling Rated Amps (A)
18.1 15.1
Heating Rated Amps (A) Compressor (A)
15.1 13.5
Fan Motor (A) Cooling Power Input (kW) Heating Power Input (kW)
0.6 2.00 2.28
MOP ‐ Maximum Overcurrent Protection
MCA ‐ Minimum Circuit Ampacity
Piping: Liquid Line (in, OD)
3/8
Vapor Line (in, OD) Additional Refrigerant (oz/ft)
5/8 0.43
Max Pipe Length (ft)²
164
Pipe Length (no add'l Refrigerant, ft) Max Elevation (ft)
25 98
Features: •ESP control •Hot start •Inverter (variable speed fan) •Internal condensate pump •Auto restart
Indoor Unit: 57‐77 59‐81
Unit Data: Refrigerant Type Refrigerant Control Refrigerant Charge (lbs)
R410A EEV 4.4
ODU Sound Pressure Max (Cool/Heat) ±3 dB(A)³ IDU Sound Pressure (H/M/L) ±3 dB(A)³
Electrical: Power Supply (V¹/Hz/Ø)
5‐118 0‐64
Cooling (°F WB) IDU Heating (°F DB)
SEER ‐ Seasonal Energy Efficiency Ratio EER ‐ Energy Efficiency Ratio
Cooling Nominal Test Conditions: Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB
Cooling (°F DB) Heating (°F WB)
•Control lock func on •Group control •Timer (on/off) •Sleep mode
48/52 38/36/35
ODU Net Weight (lbs) ODU Shipping Weight (lbs) IDU Net Weight (lbs) IDU Shipping Weight (lbs)
133 146 73 95
Fan: ODU Type IDU Type Fan Speeds (Fan/Cooling/Heating)
Propeller Sirocco 3/3/3
1 + 1 Fan Quantity (ODU + IDU) Brushless Digitally Controlled/Direct Motor/Drive ODU Air Circulation (CFM) 2048 688/618/530
IDU Air Circulation H/M/L (CFM) Max External Static Pressure (in wg)
0.39 7.0
Dehumidification Rate (pts/hr)
Notes: 1.Acceptable opera ng voltage: 187V‐253V. 2.Piping lengths are equivalent. 3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996. 4.All communica on/power cable to be minimum 18 American wire gauge (AWG), 4‐ conductor, stranded, shielded and must comply with applicable local and national code. 5.See Engineering Manual for sensible and latent capaci es. 6.Power wiring cable size must comply with the applicable local and na onal code. 7.The indoor unit comes with a dry helium charge. 8.This data is rated 0 above sea level, with 25 of refrigerant line and a 0 level difference between outdoor and indoor units. 9.Must follow installa on instruc ons in the applicable LG installa on manual.
Included Accessories: •Simple Controller with Mode (White) ‐ PQRCVCL0QW
Optional Accessories (sold separately) LG Programmable Controller ‐ PREMTB10U Dry Contact Unit Dry Contact Unit (1 contact, 24 VAC external power) ‐ PQDSB1 AC Ez ‐ PQCSZ250S0
For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
DFS‐SB‐AM‐001‐US 013E28
Page 1 of 3
Job Name/Location:
Outdoor Unit (ODU) ‐ LUU247HV
Tag #:
Single Zone High Static Duct
Date: PO No.:
For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
DFS‐SB‐AM‐001‐US 013E28
Page 2 of 3
Job Name/Location:
Indoor Unit (IDU) ‐ LHN247HV
Tag #:
Single Zone High Static Duct
Date: PO No.:
For continual product development, LG reserves the right to change specifications without notice. LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
DFS‐SB‐AM‐001‐US 013E28
Page 3 of 3