Transcript
SIRCO M and MV
corpo_207_a
sircm_132_a
sircm_099_a
Load break switches for machine control
Load break switches from 16 to 160 A ‹ Function
‹ Specific characteristics
SIRCO M and MV are manually operated modulable and modular multipolar load break switches. They make and break under load conditions and provide safety isolation for any low voltage circuit, particularly for machine control circuits.
SIRCO M • Fully visualised breaking. • Contact point technology. • For panel mounting device, use the "Door mounting kit" (see accessories). SIRCO MV • Visible double breaking based on contact carriers equipped with sliding contacts (type SIRCO, see page 38). • Fully visualised breaking.
‹ Conformity to standards • IEC 60947-3 • EN 60947-3 • IS13947-3 • Standard UL: see SIRCO M UL
‹ Approvals and certifications (1) • KEMA • RINA (Registre Naval Italien) (1) Product reference on request.
‹ General characteristics • Double break per phase. • DIN rail mounting, panel or modular panel with 45 mm front cut out. • IP20 devices and accessories. • Severe load duty categories (AC-22 and AC-23).
18
‹ Other products • The changeover switches are composed of two 3 poles SIRCO M switches and conversion kit. • They ensure switching, transfer of sources or transfer of two low voltage circuits on load as well as their safety disconnection.
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV
‹ What you need to know
Complete switch body toggle operation
Direct operation with handle
sircm_030_a_1_x_cat
sircm_029_c_2_x_cat
sircm_028_a_2_x_cat
SIRCO M • SIRCO M can be operated in different ways:
External operation front, left side or right side
• From 16 to 80 A, it is possible to mount the device on a door and transform a 3 pole switch into a 6 or 8 pole switch or a 3 or 4 pole changeover switch, by adding a conversion kit and a switched 4th pole.
coff_337_a_1_cat
• The SIRCO M is a 3 pole device available from 16 to 125 A, complete with an unswitched neutral or PE pole and type M auxiliary pre-break and signalling contacts. The basic 3 pole device is available enclosed in a polyester enclosure from 16 to 100 A (see page 492).
Compact enclosure: see page 492
SIRCO MV
Direct operation
External right side operation
sircm_033_a_1_x_cat
sircm_034_a_2_x_cat
sircm_032_c_1_x_cat
• 3 operations are available:
External front and left side operation
• SIRCO MV can be ordered in 3 or 4 pole from 100 to 160 A. Two types of auxiliary contacts are available: - U type pre-break, - M type signalisation.
SOCOMEC General Catalogue 2011-2012
19
SIRCO M
sircm_132_a
sircm_133_a
‹ SIRCO M and MV - References
External front handle for changeover switches
Shaft extensions for external front and side handle
Rating (A)
No. of poles
Complete switch body toggle operation
Switch body
16 A
3P
2205 3000
2200 3000(1)(2)(3)
1P 2200 1000
20 A
3P
2205 3001
2200 3001(1)(2)(3)
1P 2200 1001
25 A
3P
2205 3002
2200 3002(1)(2)(3) (1)(2)(3)
32 A
3P
2205 3003
2200 3003
40 A
3P
2205 3004
2200 3004(1)(2)(3)
63 A
3P
2205 3006
2200 3006(1)(2)(3)
80 A
3P
2205 3008
2200 3008(1)(2)(3)
100 A
Direct handle
Blue 2299 5012 Red 2299 5013
(2)
3P
2200 3010
Blue 2299 5032 2200 3011(2)
125 A
3P
Rating (A)
No. of poles
Complete switch body toggle operation
Switch body
16 A
3P
2205 3000
2200 3000(1)(2)(3)
20 A
3P
2205 3001
2200 3001(1)(2)(3) (1)(2)(3)
25 A
3P
2205 3002
2200 3002
32 A
3P
2205 3003
2200 3003(1)(2)(3)
40 A
3P
2205 3004
2200 3004(1)(2)(3)
63 A
3P
2205 3006
2200 3006(1)(2)(3)
80 A
3P
2205 3008
2200 3008(1)(2)(3)
100 A
3P
2200 3010(2)
125 A
3P
2200 3011(2)
Unswitched neutral pole
1P 2200 5005
S00 type I-0 Black IP55 1471 1111(4) Black IP65 1473 1111(4) Red/Yellow IP65 1474 1111(4)
S0 type I-0 Black IP55 1481 1111(4) Black IP65 1483 1111(4) Red/Yellow IP65 1484 1111(4) Unswitched protective earth module
External left side handle
S00 type I-0 Black IP65 147A 5111 Red/Yellow IP65 147B 5111
1P 2200 9009
1P 2200 5011
1P 2200 9011
S00 type I - 0 - II Black IP65 1473 1113(4) I - I+II - II Black IP65 1473 1114(4)
Auxiliary contacts
M type 1 contact NO + NC 2299 0001 1 contact 2 NC 2299 0011
4e pole
1P 2200 1002 1P 2200 1003 150 mm 1407 0515 200 mm 1407 0520 320 mm 1407 0532
1P 2200 1004 1P 2200 1006 1P 2200 1008 1P 2200 1010
S0 type I-0 Black IP65 148A 5111 Red/Yellow IP65 148B 5111
1P 2200 9005
1P 2200 5009
(1) For 8 pole device in direct operation, order 2 x 3 pole device + 2 main poles + conversion kit (for external operation, add the shaft + the handle). (2) Front and side operation. (3) For 6-pole device in direct operation, order 2 x 3-pole device + conversion kit (for external operation, add the shaft + the handle).
20
External front and right side handle
1P 2200 1011
Terminal shrouds
1P 2294 1005(5) 3P 2294 3005(5)
1P 2294 1009(5) 3P 2294 3009(5)
Conversion kit
Door mounting kit
Switch 6/8P 2269 6009(6) Changeover switches I - 0 - II 2209 6009(6) Changeover switches I - I+II - II 2299 6009(6)
3/4 P Complete protection IP2X 2299 3309(7)(8) Overall dimensions reduce 2299 3409(7)(8)
1P 2294 1011(5) 3P 2294 3016(5)
(4) Defeatable handle. (5) Top and bottom. (6) Delivered with a direct handle. (7) Available for SIRCO M only. (8) Delivered with a shaft.
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV
sircm_099_a
SIRCO MV Rating (A)
No. of poles
Switch body
3P
2200 3110
4P
2200 4110
100 A
3P
2200 3012
4P
2200 4012
3P
2200 3016
4P
2200 4016
125 A
160 A
Direct handle
External External right External left front handle side handle side handle
S0 type I-0 Black IP55 1491 0111(2) Black IP65 1493 0111(2) I-0 Red/Yellow Blue IP65 2299 5042(1) Blue 1494 0111(2) 2299 5022 S1 type O I-0 Black IP55 1411 2111(2) Red/Yellow IP65 1414 2111(2)
S0 type S0 type I-0 I-0 Black IP55 Black IP65 1491 0111(2) 149A 9111 Red/Yellow Red/Yellow IP65 IP65 1494 0111(2) 149B 9111 S1 type I-0 Black IP55 1415 2111 Red/Yellow IP65 1418 2111
S1 type I-0 Black IP65 141A 2111 Red/Yellow IP65 141B 2111
Shaft extensions for external front and side
S0 type 150 mm 1409 0615 200 mm 1409 0620 320 mm 1409 0632 S1 type 200 mm 1401 0620 320 mm 1401 0632 400 mm 1401 0640
Auxiliary signal contact
Auxiliary contacts for pre-break
Terminal shrouds
Voltage sensing and power supply kit
M type 1 contact U type 3P NO + NC NC contact 2294 3016(3) 2 pieces 2299 0001 3999 0701 4P 1399 4006 1 contact 1 contact NO 2294 4016(3) 2 NC 3999 0702 2299 0011
(1) Standard. (2) Defeatable handle. (3) Top and bottom.
‹ Accessories
sircm_042_b_1_x_cat
M00 handle
M0 handle
sircm_041_a_1_x_cat
M01 handle
acces_268_a
sircm_071_b_1_x_cat
Direct operation handle
For SIRCO M Rating (A) 16 … 80 16 … 80 100 ... 125
Handle colour Blue Red Blue
Handle M00 type M00 type M01 type
Reference 2299 5012 2299 5013 2299 5032
For SIRCO MV Rating (A) 100 ... 160 100 ... 160
Handle colour Blue Blue
Handle M0B type M0 type
Reference 2299 5042(1) 2299 5022
(1) Standard.
M0b handle
SOCOMEC General Catalogue 2011-2012
21
‹ SIRCO M and MV - Accessories (continued)
acces_278_a_2_cat
External handle operation - SIRCO M
acces_263_a_2_cat
S00 handle
S0 handle
Front and right side operation I - 0 Handle Rating (A) colour Handle 16 … 80 Black S00 type 16 … 80 Black S00 type 16 … 80 Red/Yellow S00 type 100 … 125 Black S0 type 100 ... 125 Black S0 type 100 ... 125 Red/Yellow S0 type
External IP IP55 IP65 IP65 IP55 IP65 IP65
Reference 1471 1111 1473 1111 1474 1111 1481 1111(1) 1483 1111(1) 1484 1111(1)
External IP IP65 IP65 IP65 IP65
Reference 147A 5111 147B 5111 148A 5111 148B 5111
Front operation for changeover switches I - 0 - II Handle Rating (A) colour Handle External IP 16 … 80 Black S00 type IP65
Reference 1473 1113
Front operation for changeover switches I - I+II - II Handle Rating (A) colour Handle External IP 16 … 80 Black S00 type IP65
Reference 1473 1114
S0 type handle - Front and right side operation I - 0 Rating (A) Handle colour External IP 100 ... 160 Black IP55 100 ... 160 Black IP65 100 ... 160 Red/Yellow IP65
Reference 1491 0111(1) 1493 0111(1) 1494 0111(1)
(1) Defeatable handle.
Left side operation I - 0 Handle Rating (A) colour 16 ... 80 Black 16 ... 80 Red/Yellow 100 ... 125 Black 100 ... 125 Red/Yellow
Handle S00 type S00 type S0 type S0 type
External handle operation - SIRCO MV
acces_279_a_2_cat
(1) Defeatable handle.
S0 handle
S0 type handle - Left side operation I - 0 Rating (A) Handle colour External IP 100 ... 160 Black IP65 100 ... 160 Red/Yellow IP65
Reference 149A 9111(1) 149B 9111(1)
acces_284_a_2_cat
(1) Defeatable handle.
S1 type handle - Front operation I - 0 Rating (A) Handle colour External IP 100 ... 160 Black IP55 100 ... 160 Black IP65 100 ... 160 Red/Yellow IP65
Reference 1411 2111(1) 1413 2111(1) 1414 2111(1)
(1) Defeatable handle.
S1 handle
22
S1 type handle - Right side operation I - 0 Rating (A) Handle colour External IP 100 ... 160 Black IP55 100 ... 160 Black IP65 100 ... 160 Red/Yellow IP65
Reference 1415 2111 1417 2111 1418 2111
S1 type handle - Left side operation I - 0 Rating (A) Handle colour External IP 100 ... 160 Black IP65 100 ... 160 Red/Yellow IP65
Reference 141A 2111 141B 2111
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV
Shaft for external handle
For SIRCO M
sircm_045_a_2_x_cat
Rating (A) 16 ... 125 16 ... 125 16 ... 125
Use Standard lengths: - 150 mm, - 200 mm, - 320 mm. Other lengths: consult us.
Handle S00 type S00 type S00 type
Shaft length (mm) 150 mm 200 mm 320 mm
Reference 1407 0515 1407 0520 1407 0532
Handle S0 type S0 type S0 type S1 type S1 type S1 type
Shaft length (mm) 150 mm 200 mm 320 mm 200 mm 320 mm 400 mm
Reference 1409 0615 1409 0620 1409 0632 1401 0620 1401 0632 1401 0640
For SIRCO MV Rating (A) 100 ... 160 100 ... 160 100 ... 160 100 ... 160 100 ... 160 100 ... 160
For 3/4 pole switches, shaft extensions for external front and side handle. For 6/8 pole switches and SIRCOVER M changeover switches, shaft extensions for front operation only.
Shaft guide for external operation
acces_260_a_2_cat
Use To guide the extension shaft into the external handle. This accessory enables handle to engage extension shaft with a misalignment of up to 15 mm. Required for a shaft length over 320 mm.
Description Shaft guide Shaft guide
Additional pole for SIRCO M
Rating (A) 16 20 25 32 40 63 80 100 125
Additional pole configuration
N or PE
N or PE
N or PE N or PE
N or PE
N or PE
Reference 1419 0000 1429 0000
4e pole Use Adds one or two poles and transforms: - 3 pole load break switches into a 4 pole, - 6 pole load break switches into a 8 pole, - 3 pole changeover switches into a 4 pole.
sircm_072_b_1_x_cat sircm_078_a_1_gb_cat
Handle type S00 and S0 S1
Type switched switched switched switched switched switched switched switched switched
Reference 2200 1000 2200 1001 2200 1002 2200 1003 2200 1004 2200 1006 2200 1008 2200 1010 2200 1011
Neutral pole Use Transforms the 3-pole switch into a 3-pole + solid neutral. Rating (A) 16 … 40 63 … 80 100 ... 125
No. of poles 1P 1P 1P
Type unswitched unswitched unswitched
Reference 2200 5005 2200 5009 2200 5011
Protective earth module Use Adds 1 protective earth module pole to the switch-disconnector. Rating (A) 16 … 40 63 … 80 100 ... 125
SOCOMEC General Catalogue 2011-2012
No. of poles 1P 1P 1P 1P 1P 1P 1P 1P 1P
No. of poles 1P 1P 1P
Type unswitched unswitched unswitched
Reference 2200 9005 2200 9009 2200 9011
23
‹ SIRCO M and MV - Accessories (continued)
Terminal shrouds
sircm_049_a_1_cat
For SIRCO M Rating (A) 16 … 40 16 … 40 63 … 80 63 … 80 100 ... 125 100 ... 125
No. of poles 1P 3P 1P 3P 1P 3P
Position top / bottom top / bottom top / bottom top / bottom top / bottom top and bottom
Reference 2294 1005 2294 3005 2294 1009 2294 3009 2294 1011(1) 2294 3016(1)
Position top / bottom top / bottom
Reference 2294 3016 2294 4016
(1) Reference composed of 2 pieces.
Use Top and bottom protection against direct contact with the terminals or connection parts. Available in 1 or 3 pole versions for SIRCO M and 3 or 4 pole for SIRCO MV. An opening on each terminal cover makes it possible to insert a probe to measure temperature.
For SIRCO MV Rating (A) 100 … 160 100 … 160
No. of poles 3P 4P
Auxiliary contacts M type
sircm_081_a_1_cat
sircm_075_b_2_cat
Use Pre-break and signalisation of positions 0 and I by NO+NC or 2 NO auxiliary contacts. They allow to anticipate the switching of the main poles. They can be mounted on the left or on the right side of the device. Max 4 auxiliary contacts (2 modules).
Auxiliary contacts configurations for SIRCO M
2
1
2
sircm_098_a_1_cat
1
Pre-break is not guaranteed on the SIRCO MV. Characteristics NO+NC auxiliary contacts: IP2 with front operation.
For SIRCO M Rating (A) 16 … 125 16 … 125
Number of AC 1 AC 1 AC
Type of AC NO + NC 2 NC
Reference 2299 0001 2299 0011
For SIRCO MV Rating (A) 100 … 160 100 … 160
Number of AC 1 AC 1 AC
Type of AC NO + NC 2 NC
Reference 2299 0001 2299 0011
Characteristics
Auxiliary contacts configurations for SIRCO MV 1. Maximum 2 "U" type auxiliary contacts. 2. Maximum 4 "M" type auxiliary contacts
Contact type
Nominal current (A)
Operating current Ie (A) 230 VAC AC-13
NO + NC
10
10
AC-15
6
U type
sircm_048_a_1_x_cat
Use Pre-break and signalisation by NO or NC auxiliary contact. Maximum 2 auxiliary contacts. For use only with SIRCO MV switches. For SIRCO MV Rating (A) 100 … 160 100 … 160
sircm_086_b_1_cat
Conversion kit for 6/8 pole load break switches
24
sircm_097_b_2_x_cat
sircm_050_c_2_cat
Conversion kit
Escutcheon for 3/4-pole changeover switches (I - 0 - II) or (I - I+II - II)
Number of AC 1 AC 1 AC
Use It must be ordered at the same time as the handle for external control. This accessory enables the assembly of two 3 pole switches and additional poles in order to achieve: - 6 or 8-pole SIRCO M load break switches, - 3 or 4-pole SIRCOVER M changeover switches.
Rating (A) 16 … 80 16 … 80 16 … 80
Type of AC NC NO
Reference 3999 0701 3999 0702
SIRCOVER M changeover switches ensure switching, transfer of sources (I - 0 - II) or transfer of two low voltage circuits on load (I - I+II - II), with the continuity of power supply.
Type Load break switches 6 / 8 P Changeover switch 3/4 pole (I - 0 - II) Changeover switch 3/4 pole (I - I+II - II)
Reference 2269 6009 2209 6009 2299 6009
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV Door mounting kit
sircm_051_b_2_cat
Use This kit enables direct mounting of the switch on the door panel, on the right or left side of the panel. Moreover, the connection clamps of the switch are always accessible.
The external handle is quick and easy to install due to an internal locking nut mounted on the inside of the enclosure. 2 kits are available: - one for complete protection IP2X - one with overall dimensions reduced.
For SIRCO M Rating (A) 16 … 80 16 … 80
No. of poles 3/4 P 3/4 P
Description Complete protection IP2X Overall dimensions reduce
Reference 2299 3309 2299 3409
Cap for side operation mounting
sircm_126_a_2_cat
Use Accessory for capping the front face of the SIRCO M when utilising in side operation, 20 units per pack.
For SIRCO M Rating (A) 16 ... 80
This piece can be snapped on the switch body directly.
Pack 20 pieces
Reference 2299 9409
6/8 pole joining accessory
sircm_134_a_2_cat
Use 40 units per pack, they allow the joining of two 3 pole switches (+ additional pole) in order to form a 6 or 8 pole switch for external side operation.
For SIRCO M Rating (A) 16 ... 80
For multi-pole switches, please consult us.
Pack 40 pieces
Reference 2299 9909
DIN rail locking clip
sircm_128_a_2_cat
Use This locking clip prevents the SIRCO MV from sliding when DIN rail mounted.
For SIRCO MV Rating (A) 100 ... 160 100 ... 160
Type M4 M5
Reference 5000 0041 5000 0051
Voltage sensing and power supply tap
atysm_026_a_1_cat
Use It allows connection of 2 x ≤ 1.5 mm2 voltage sensing or power cables.
SOCOMEC General Catalogue 2011-2012
For SIRCO MV Rating (A) 100 ... 160
Pack 2 pieces
Reference 1399 4006
25
‹ Characteristics according to IEC 60947-3
SIRCO M - 16 to 125 A Thermal current Ith (40°C) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV)
16 A
20 A
25 A
32 A
40 A
63 A
80 A
100 A
125 A
800 8
800 8
800 8
800 8
800 8
800 8
800 8
800 8
800 8
Rated operational currents Ie (A) Rated voltage Load duty category 415 VAC AC-21 A / AC-21 B 415 VAC AC-22 A / AC-22 B 415 VAC AC-23 A / AC-23 B 500 VAC AC-21 A / AC-21 B 500 VAC AC-22 A / AC-22 B 500 VAC AC-23 A / AC-23 B 690 VAC AC-21 A / AC-21 B 690 VAC AC-22 A / AC-22 B 690 VAC AC-23 A / AC-23 B
A/B(1) 16/16 16/16 16/16 16/16 16/16 16/16 16/16 16/16 16/16
A/B(1) 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20 20/20
A/B(1) 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25
A/B(1) 32/32 32/32 32/32 32/32 32/32 25/25 32/32 32/32 25/25
A/B(1) 40/40 40/40 40/40 40/40 40/40 25/25 40/40 32/40 25/25
A/B(1) 63/63 63/63 63/63 63/63 63/63 63/63 63/63 40/63 40/40
A/B(1) 80/80 80/80 80/80 80/80 80/80 63/63 80/80 63/80 40/40
A/B(1) 100/100 100/100 100/100 100/100 100/100 80/80 100/100 80/100 63/63
A/B(1) 125/125 125/125 125/125 125/125 125/125 100/100 125/125 100/125 63/63
Operational power in AC-23 (kW) At 400 VAC without pre-break in AC-23 (kW)(1)(2) At 500 VAC without pre-break in AC-23 (kW)(1)(2) At 690 VAC without pre-break in AC-23 (kW)(1)(2)
7.5 7.5 7.5
9 9 11
11 11 15
15 15 15
18.5 18.5 15
30 30 30
37 37 37
45 45 45
55 55 55
Fuse protected short-circuit withstand (kA rms prospective) 50 Prospective short-circuit (kA rms)(3) Associated fuse rating (A)(3) 16
50 20
50 25
50 32
50 40
50 63
50 80
25 100
25 125
Short-circuit capacity (Ue 415 VAC) Rated short-time withstand current 0.3 s. ICW (kA eff.) Rated peak withstand current (kA peak)(3)
2.5 6
2.5 6
2.5 6
2.5 6
2.5 6
3 9
3 9
5 12
5 12
Connection Minimum Cu cable section (mm²) Maximum Cu cable section (mm2) Tightening torque min/max (Nm)
1.5 16 2 / 2.2
1.5 16 2 / 2.2
1.5 16 2 / 2.2
1.5 16 2 / 2.2
1.5 16 2 / 2.2
2.5 35 3.5 / 3.85
2.5 35 3.5 / 3.85
10 70
10 70
Mechanical characteristics Durability (number of operating cycles) Operating effort (Nm) Weight of a 3 pole device (kg)
100 000 0.8 0.16
100 000 0.8 0.16
100 000 0.8 0.16
100 000 0.8 0.16
100 000 0.8 0.16
100 000 1 0.26
100 000 1 0.26
100 000
100 000
0.7
0.7
(1) Category with index A = frequent operation - Category with index B = infrequent operation. (2) The power value is given for information only, the current values vary from one manufacturer to another. (3) For a rated operational voltage Ue = 400 VAC.
26
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV ‹ Characteristics according to IEC 60947-3
SIRCO MV - 100 to 160 A Thermal current Ith (40°C) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV)
100 A
125 A
160 A
800 8
800 8
800 8
Rated operational currents Ie (A) Rated voltage Load duty category 415 VAC AC-21 A / AC-21 B 415 VAC AC-22 A / AC-22 B 415 VAC AC-23 A / AC-23 B 500 VAC AC-21 A / AC-21 B 500 VAC AC-22 A / AC-22 B 500 VAC AC-23 A / AC-23 B 690 VAC AC-20 A / AC-20 B 690 VAC AC-21 A / AC-21 B 690 VAC AC-22 A / AC-22 B 690 VAC AC-23 A / AC-23 B
A/B(1) 100/100 100/100 100/100 100/100 100/100 80/80 100/100 100/100 63/80 63/63
A/B(1) 125/125 125/125 125/125 125/125 125/125 100/100 125/125 125/125 80/100 80/80
A/B(1) 160/160 160/160 125/160 160/160 125/160 100/100 160/160 160/160 100/125 80/80
Reactive power (kvar) At 400 VAC (kvar)(2)
45
55
75
Operational power in AC-23 (kW) At 400 VAC without pre-break in AC-23 (kW)(1)(2) At 500 VAC without pre-break in AC-23 (kW)(1)(2) At 690 VAC without pre-break in AC-23 (kW)(1)(2)
45 45 45
55 55 75
75 75 75
Fuse protected short-circuit withstand (kA rms prospective) Prospective short-circuit (kA rms)(3) Associated fuse rating (A)(3)
100 100
65 125
50 160
Short-circuit capacity (Ue 415 VAC) Rated short-time withstand current 0.3 s. ICW (kA eff.) Rated peak withstand current (kA peak)(3)
7 12
7 12
7 12
Connection Minimum Cu cable section (mm²) Maximum Cu cable section (mm2) Tightening torque min/max (Nm)
10 70 4 / 4.4
10 70 4 / 4.4
10 70 4 / 4.4
Mechanical characteristics Durability (number of operating cycles) Operating effort (Nm) Weight of a 3 pole device (kg) Weight of a 4 pole device (kg)
50 000 4 0.7 0.9
50 000 4 0.7 0.9
50 000 4 0.7 0.9
(1) Category with index A = frequent operation - Category with index B = infrequent operation. (2) The power value is given for information only, the current values vary from one manufacturer to another. (3) For a rated operational voltage Ue = 400 VAC.
SOCOMEC General Catalogue 2011-2012
27
‹ SIRCO M and MV - Dimensions
SIRCO M SIRCO M 16 to 80 A Direct operation with handle
1
1.97 50
0.24 6
2
2
N AC
G 2.68 68
sircm_052_b_1_gb_cat
2
1
0.35 F1 8.8 M5
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
External front operation
0.24 6
1.97 50
F1 0.35 8.8
T
F M
1
1
2
G 2.67 68
F M
2.95 75 2.52 64
sircm_053_b_1_gb_cat
3.19 81 2.87 73 2.52 64
N AC
Toggle operation
0.35 8.8
F1 M5
T
F1
0.35 8.8
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
External side operation
E D
64 50.6
F M J
1
2
sircm_054_c_1_x_cat
T M5
50
Rating (A)
Overall dimensions D min D max
E min
16…40 63…80
30 30
100 100
235 235
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
F1 8.8
8.8 F1
6
36
1
G 68
2
D
ø 71
36
81
N AC
36
E max
Terminal shrouds AC
Switch body F F1
G
J
Switch mounting M N
Connection T
372 372
110 110
45 52.5
68 76
15 17.5
30 35
15 17.5
Direct front operation for 6/8-pole load break switches or 3/4-pole changeover switches
15 17.5
75 85
External front operation for 6/8-pole load break switches or 3/4-pole changeover switches
F 1
3.50 89 3.07 78
2
E
sircm_055_c_1_gb_cat
1.42 36
1.77 45
2 79
2.06 52.5
N G 2.67 68
2
1
J F2 X M
0.35 F1 T T 8.8 2.06
0.29 7.5
0.24 6
F1 0.35 8.8
1.69 43
1.36 34.7
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
28
Rating (A)
Overall dimensions E min E max
Switch body F
F1
F2
G
J
Switch mounting M N
Connection T
X
16…40 63…80
105 105
97.5 105
15 17.5
45 52.5
68 76
48.75 52.5
30 35
15 17.5
7.5 8.75
372 372
75 85
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV
SIRCO M 100 to 125 A External front operation
2.95 75 2.52 64 1
37
30 min. 201 max.
30 min. 201 max. 1
78 26 13
1
0.35 1.02 8 8 26
1.02 26
8.8
53
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
131.4 189
124.6 6
1.02 0.35 26 8 8
37
2
2
sircm_057_b_1_x_cat
0.24 6
2
51.73 131.4
sircm_056_c_1_gb_cat
2 09
100 min. 372 max. 81 64 50.6
37 1
49.05 124.6
2
3.07 78 1.02 26
External side operation
26
26 M5
26
ø 71 88
Direct operation with handle
8.8
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact. 2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
SIRCO MV SIRCO MV 100 to 160 A Direct front operation
2 76 64
External front operation
2
A 109 35 26
110 min. 357 max. 69,9 29,5
B 135 61
8,8
sircm_058_c_1_x_cat
70
ø 71 88
131,4 189
124,6
8,8
D 44
C 37
1 6
26 M5
53
1
A. 3 pole B. 4 pole
C. S0 type handle D. S1 type handle
1. Maximum 4 "M" type auxiliary contacts 2. Maximum 2 "U" type auxiliary contacts
External side operation A
B
C
69,9 50,6
109 26 57
135
30 min. 300 max.
D
69,9
83
8,8
F 44
E
37
sircm_059_c_1_x_cat
70
ø 71 88
124,6
189 131,4
8,8
1 6 53
26 M5
2
A. Right side operation B. 3 pole C. 4 pole
SOCOMEC General Catalogue 2011-2012
1
2 D. S0 type handle E. Left side operation F. S1 type handle
1. Maximum 4 "M" type auxiliary contacts 2. Maximum 2 "U" type auxiliary contacts
29
‹ SIRCO M and MV - Dimensions (continued)
‹ Dimensions for external handles
SIRCO M SIRCO M 16 to 80 A Front operation
Side operation
Direction of operation
Direction of operation
S00 type Load break switches
Door drilling
°
90
40
40
I
90
° 2Ø7
0
4Ø7
28
71
Ø71
0
IP65 with 4 fixing screws
IP55 with 2 fixing clips
Right side operation I
36
28
Handle type
Ø 31
Ø 37
Left side operation
With fixing nut
3
I
sircm_177_a_1_gb_cat
13.5
°
90
0 Ø 22.5
Front operation Direction of operation
Typ S00 Changeover switches I 0 II and I - I+II - II
Door drilling IP55 with 2 fixing clips
0 or I+II
With fixing nut
13.5
Ø 37
90
Ø 37
Ø 22.5
° 3
sircm_180_a_1_gb_cat
71
40
90 °
Ø71
IP65 with 4 fixing screws
40
Handle type
I
II
36
2Ø7
28
28
4Ø7
SIRCO M 100 to 125 A Front operation
Side operation
Direction of operation
Direction of operation
S0 type Load break switches
Door drilling
I °
90
° 2Ø7
0
4Ø7
28
88
Ø71
0
40
40
I
90
IP65 with 4 fixing screws
IP55 with 2 fixing clips
Right side operation
37
28
Handle type
Ø 31
Ø 37
Left side operation With fixing nut
I
3
13.5
°
90
sircm_178_a_1_gb_cat
0
30
Ø 22.5
General Catalogue 2011-2012 SOCOMEC
Load break switches for machine control
SIRCO M and MV
SIRCO MV SIRCO MV 100 to 160 A Front operation
Side operation
Direction of operation
Direction of operation
S0 type Load break switches
Door drilling
°
90
° 2Ø7
0
4Ø7
28
88
Ø71
0
40
40
I
90
IP65 with 4 fixing screws
IP55 with 2 fixing clips
Right side operation I
37
28
Handle type
Ø 31
Ø 37
Left side operation With fixing nut
I
3
13.5
°
90
I Ø 22.5
S1 type Load break switches
IP55 with 2 fixing clips
Right side operation
IP65 with 4 fixing screws
40
40
0
I 90
°
90 °
2Ø7
4Ø7
Ø78
28
28
0
70
I
Ø 37
44
Ø 31
Left side operation
I
sircm_179_a_1_gb_cat
° 90
0
SOCOMEC General Catalogue 2011-2012