Preview only show first 10 pages with watermark. For full document please download

Site Supervisor Display - Emerson Climate Technologies

   EMBED


Share

Transcript

Site Supervisor Display Installation Guide The Site Supervisor Display (P/Ns 818-9022 and 818-9023) is a remote user interface for the Site Supervisor (P/N 860-1200) that connects to the controller using RS485 network to Serial Port D, and shows a simplified UI that allows users to perform critical actions in the controller quickly and easily such as overriding lights, heating and cooling stages, viewing alarms, and status information. General Warnings and Safety Precautions • This guide is part of the product and should be kept near the instrument for quick and easy reference. • The Display should not be used for purposes different from those described in this guide. It cannot be used as a safety device. • Check the application limits before proceeding. • Emerson Retail Solutions reserves the right to change the composition of its products, even without notice, ensuring the same and unchanged functionality. • When using an external power supply, it is necessary to separate the power of the device from the rest of the electrical devices connected inside the electrical panel. The secondary of the transformer must never be connected to earth ground. • Disconnect all electrical connections before any kind of maintenance is performed. Do not open the Site Supervisor Display. • Check that the supply voltage is correct before connecting. • Do not expose to water or moisture: use the controller only within its operating limits to avoid sudden temperature changes with high atmospheric humidity to prevent condensation. • Wire polarity must be observed: A wrong connection may cause possible malfunctioning and damage to the controller or Display. Panel Mounting Document Part # 026-4158 Rev 1 11-JAN-2017 Page 1 of 5 ©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates. Wall Mounting Installing The Wall-Mount Display 1. 2. 3. 4. 5. 6. 7. Pull the Display body off the Display base. Forcing or prying on the Display will cause damage to the unit. Place the base over the wall opening and mark the mounting hole locations on the wall using the Display base as a template. Move the base out of the way and drill the mounting holes. If the mounting holes are too large and do not allow the base to be tightened securely, use the plastic screw anchors to secure the base. Fasten the base snugly to the wall using the mounting holes shown in the figure above and two mounting screws. Leveling is for appearance only and will not affect Display operation. Connect wires to the terminal block on the base using the appropriate wiring schematic. Push excess wire into the wall opening and plug the opening with a fire resistant material to prevent drafts from affecting Display operation. Carefully line up the Display with the base and snap into place. Note: size in mm Document Part # 026-4158 Rev 1 11-JAN-2017 ©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates. Page 2 of 5 Electrical Connections Observe the connection polarity of the Display: A wrong connection can cause malfunctioning and possible damage to the controller or the Display. An external power supply is necessary to separate the power of the device from the rest of the electrical devices connected inside the electrical panel. The secondary of the transformer must never be connected to earth ground. Panel Version Wall Version DIP Switch Configuration Document Part # 026-4158 Rev 1 11-JAN-2017 ©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates. Page 3 of 5 Serial Line Cable Connection The serial line cable can be 3-wire plus shielding, with a minimum section of 0.5 sq mm (for example, Belden 8772). This cable is recommended for its technical characteristics and because it maintains the quality of the electrical signal. The shield wire should be clipped. Firmware Upgrade - Remote Access 1. 2. Download the latest firmware update file (for example, “SS_2.02F08_Firmware_Update) to a location on your PC. Connect a standard Ethernet cable from the Site Supervisor (ETH 0 port) to a router and enter the Site Supervisor IP address into a browser. 3. Login and select Configure System>File Management from the main menu. 4. 5. Before proceeding with the firmware update, click Backup (to back up configuration files). Once the backup is complete, click Upgrade Firmware and click Select. Browse and locate the latest firmware update file. Select the file and click Open or double-click the file to load. A Loading file message will appear (wait for several seconds). Once loaded, the Revision and File Size will display. Click Upgrade. A progress bar will appear with the percentage completed. The system will reboot and restart automatically when the upgrade is complete. Note that both the Display and Site Supervisor firmware will be updated simultaneously. The new firmware version number will appear in the lower right corner of the screen. Note that all setpoints and configurations will remain the same. If there are discrepancies, use the backup file to restore previous settings. 6. 7. 8. 9. Firmware Upgrade - USB Drive 1. 4. Copy the latest firmware update file (for example, “SS_2.02F08_Firmware_Update) to the root folder of a USB thumb drive (the USB thumb drive must be format FAT16). Verify the Display is completely powered up. Plug the USB thumb drive into the USB port (located on the back of the Display). An Application update? message will appear. Touch OK on the Display and the update will start. Audible tones will sound immediately to indicate the firmware has successfully updated. Remove the USB thumb drive. 5. Touch the system configuration icon 2. 3. and PRODUCT INFO to view the Site Supervisor and the Display version numbers to verify the update. Document Part # 026-4158 Rev 1 11-JAN-2017 ©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates. Page 4 of 5 Technical Data Housing Self extinguishing ABS Mounting Panel mounting or wall mounting Frontal IP Protection • IP54 without UR/NTC sensor • UL Type 1 enclosure Rear IP Protection IP20 Pollution Degree 2 Impulse Voltage Overvoltage category II Connections Type • Panel version: Pitch 5mm 90° screw or disconnectable type connect • Wall version: PIN STRIP screw connectors Cable Sizes (AWG) • Wirings max 2.5 mm2 (14 to 30 AWG SOL/STR) with screw type connectors • Wirings max 4 mm2 (12 to 24 AWG SOL/STR) with disconnectable type connectors Testing Torque • 0.45 Nm (4.0 TQ Lb In.) with screw type connectors • 0.55 Nm (5.0 TQ Lb In.) with disconnectable type connectors Power Supply • 12-24 Vac/dc ±15% 50/60 Hz • Class 2 power source • Type 1 action Power Absorption 5W – 5VA Buzzer TFT Yes 4.3” Resolution 480x272 px Colors Touch 256(8 bit) ResistiveF Operating Temperature Storage Temperature -4°F to 140°F (-20 to 60°C) -4° to 158° (-20 to 70°C) Relative Humidity 20 to 85% (Non- Condensing) Purpose of Control Construction of Control Operating Control Independently Mounted Control Document Part # 026-4158 Rev 1 11-JAN-2017 Page 5 of 5 This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates. Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. 026-4158 11-JAN-2017 Emerson is a trademark of Emerson Electric Co. ©2017 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.