Sizing, Installation, Dimensions and Weights
The charts and tables in this documentation are intended for use as a general survey. Exact sizing can be carried out in the ProUnit air handling unit selection program.
Contents Prerequisites for Sizing...................................................................................................... 45 GOLD RX, One-piece air handling units with rotary heat exchanger............................ 46 GOLD PX, One-piece air handling units with plate heat exchanger.............................. 94 GOLD CX, One-piece air handling units with coil heat exchanger............................... 114 GOLD SD, Supply air and extract air handling units..................................................... 130
20160422
We reserve the right to alter specifications.
43
GOLD
44
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights Prerequisites for Sizing Fan Diagrams
The SFPV diagram on the pages that follow shows the electric power efficiency rating of the air handling unit calculated according to the procedure defined by SwedVent, the Swedish Association of Air handling Industries (V Publication 1995:1, Rev. 2000). The SFPV-value is calculated according to the V publication under the load conditions that exist when the air filters are clean. GOLD RX/PX/CX The SFPV diagrams and Extract air fan are calculated with the assumption that the supply air and extract air fans have the same airflow and available total pressure rise. The leakage and purging air flow and the extra pressure drop in the extract air have been taken into consideration in order to ensure the correct direction of air leakage at a pressure ratio that corresponds to a normal installation for a certain available pressure.
Acoustic calculations The sound emitted by Swegon products is measured according to the method defined in ISO 5136, the most widely used method in Europe. Acoustic measurements are sometimes taken using other methods. The total sound power level LW, tot emitted from the fan outlet to the ducting can be read from each of the fan diagrams. The following formula can be used for breaking down the total sound power level into octave bands: LW, ok = LW, tot + Kok. Kok can be obtained from tables on the pages that follow.
The Extract air fan and Supply air fan diagrams indicate the available total pressure rise to cover duct pressure drop and external functional sections, and total sound power level, LW, tot emitted to a connecting outlet duct, dB (relative to 10 -12 W), in the 125 – 8,000 Hz octave band frequencies. The available pressure rise calculated for the design pressure drop across filters is specified in all the diagrams. The blue broken line defines the limits of the numbered ranges (1,2,3,4) for particulars of the correction factors KOK in a separate table. Range 1 is the most favourable range from an acoustic point of view. GOLD SD The Fan Charts indicate the total pressure rise to cover possible internal total pressure losses for, e.g. filters, duct pressure drop and external functional sections, and total sound power level LW, tot emitted to a connecting outlet duct, dB (relative to 10 -12 W), in the 125 – 8,000 Hz octave band frequencies. The total pressure loss for an optional filter (all sizes), coil heat exchanger and droplet eliminator (sizes 14-80) are specified in the lower chart. The blue broken line defines the limits of the numbered ranges (1,2,3,4) for particulars of the correction factors KOK in a separate table. Range 1 is the most favourable range from an acoustic point of view.
20160422
We reserve the right to alter specifications.
45
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 04 Airflow, m3/h SFP v
2.5 2.0 1.5
Available total pressure rise, Pa
Extract air fan
4
85
80
2
1
3
L w,tot 70dB
75
Supply air fan
4 3
85
1
80
2 L w,tot 70dB
75
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
04
Min. airflow (on airflow regulation) m3/s m3/h 288 0.08
Max. airflow m3/h 1620
m3/s 0.45
Correction factors KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -12 -17 -14 -12 -29 -31 -29 -28
-8 -8 -15 -13 -22 -18 -27 -22 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -31 -29 -35 -34 -40 -40 -47 -46
6 -7 -9 -16 -14 -33 -31 -39 -36 -40 -42 -49 -47
7 -12 -13 -22 -20 -38 -37 -44 -42 -46 -47 -56 -54
8 -15 -16 -25 -25 -37 -38 -43 -43 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
46
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 04 Delivery and Transport within the Site
The GOLD RX 04 is produced in one single variant. All of its components are arranged at their given physical location inside the air handling unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
The design makes it necessary to mount the GOLD RX 04 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors.
Right-hand version
Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Installation/duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The air handling unit can be installed up ended (does not apply to units installed outdoors).
Left-hand version Outside air Supply air Extract air Exhaust air Power connection
403 91
91 GOLD
GOLD
52
52
J
50
50
Base beams are optional. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
04
750
825
240
345
230
460
920
561
1500
315
214-243
Clear Space for Inspection
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 0.8 kW (0.41 kW)* motor control system, 1 x 230 V, 50 Hz *The motor control system limits the power of the take-off to the value specified.
20160422
We reserve the right to alter specifications.
47
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 04 Left-hand version
Right-hand version Airflow, m3/h
Airflow, m3/h
SFP v
SFP v
2.5
2.5
2.0
2.0
1.5
1.5
85
80
4 3 L w,tot 65dB
1
2 75
70
Supply air fan
80
4
3
Extract air fan Available total pressure rise, Pa
Available total pressure rise, Pa
Extract air fan
80
2
3
1
L w,tot 70dB
Supply air fan
85
75
3
2
1
75
4
L w,tot 65dB
4
2
1
70
Airflow, m3/s
80
L w,tot
70dB
75
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows
The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size Min. airflow Max. airflow (on airflow regulation) m3/s m3/h m3/s m3/h 04 288 0,08 1620 0,45
To outlet duct
To inlet duct*
To air handling unit surroundings**
48
Sound path To outlet duct
To inlet duct*
Correction factors, KOK , dB. Fan in lower level. Sound path
Correction factors KOK , dB. Fan in upper level.
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
6 14 4 7 1 5 -1 2 -5 3 -7 -4
-2 -1 -1 -2 -6 -5 -6 -2 -16 -15 -15 -16
-5 -8 -8 -4 -10 -14 -13 -9 -28 -31 -31 -27
-13 -14 -21 -15 -23 -27 -34 -29 -34 -35 -42 -36
4
We reserve the right to alter specifications.
5 -21 -22 -31 -26 -36 -37 -46 -39 -54 -55 -64 -59
6 -26 -26 -35 -31 -42 -46 -53 -49 -59 -59 -68 -64
7 -35 -39 -46 -45 -43 -54 -58 -59 -69 -73 -80 -79
8 -24 -34 -36 -41 -29 -43 -43 -48 -55 -65 -67 -72
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
4 4 1 3 -1 -1 -5 -5 -7 -7 -10 -8
-1 -1 -1 -1 -5 -7 -6 -6 -15 -15 -15 -15
-6 -9 -10 -7 -11 -13 -16 -11 -29 -32 -33 -30
-15 -14 -23 -17 -24 -21 -34 -25 -36 -35 -44 -38
4
5 -24 -22 -32 -27 -39 -38 -48 -42 -57 -55 -65 -60
6 -29 -27 -37 -32 -45 -44 -55 -50 -62 -60 -70 -65
7 -41 -40 -49 -45 -49 -56 -61 -62 -75 -74 -83 -79
8 -32 -36 -41 -42 -37 -47 -48 -53 -63 -67 -72 -73
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 04 Delivery and Transport within the Site
The GOLD RX Top 04 is produced in one single variant. All of its components are arranged at their given physical location inside the air handling unit. The GOLD RX Top 04 is always supplied as one unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
Left-hand version
The design makes it necessary to mount the GOLD RX Top 04 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Right-hand version
Outside air Supply air Extract air Exhaust air
Installation/duct connection options
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal. 403 91 GOLD
GOLD
Base beams are optional. 52
52
J
50
50
Power connection
Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
04
750
825
233,5
1033
237,5
350
920
561
1500
315
247
Clear Space for Inspection
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 0.8 kW (0.41 kW)* motor control system, 1 x 230 V, 50 Hz *The motor control system limits the power of the take-off to the value specified. 20160422
We reserve the right to alter specifications.
49
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 05 Airflow, m3/h SFP v
95
90
Available total pressure rise, Pa
Ca Ca
4 3
p.
2.5
2.0
1.5
Extract air fan p.
va
va
r. 2
r. 1
2
1
L w,tot 70dB
75
80 95
90
4
Ca
85
Supply air fan Ca
p.
p.
va
va
r. 2
r. 1
85
2 3
1L
w,tot
70dB
75
80
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit lines for Ecodesign are calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Correction factors KOK , dB
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
05
Min. airflow (on airflow regulation) m3/s m3/h 288 0.08
Sound path To outlet duct
Max. airflow m3/h 2340
m3/s 0.65
To inlet duct*
To unit’s surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -12 -17 -14 -12 -29 -31 -29 -28
-8 -8 -15 -13 -22 -18 -27 -22 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -31 -29 -35 -34 -40 -40 -47 -46
6 -7 -9 -16 -14 -33 -31 -39 -36 -40 -42 -49 -47
7 -12 -13 -22 -20 -38 -37 -44 -42 -46 -47 -56 -54
8 -15 -16 -25 -25 -37 -38 -43 -43 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
50
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 05 Delivery and Transport within the Site
The GOLD RX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
The design makes it necessary to mount the GOLD RX 05 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors.
Right-hand version
Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Installation/duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The air handling unit can be installed up ended (does not apply to units installed outdoors).
Left-hand version Outside air Supply air Extract air Exhaust air Power connection
403 91
91 GOLD
GOLD
52
52
J
50
50
Base beams are optional. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
05
750
825
240
345
230
460
920
561
1500
315
214-243
Clear Space for Inspection
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz
20160422
We reserve the right to alter specifications.
51
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 05 Left-hand version.
Right-hand version. Airflow, m /h 3
Airflow, m3/h
SFP v
SFP v
2.0
1.5
2.5
2.0
1.5
Available total pressure rise, Pa
90
85
4 3
2
1
L w,tot 65dB
70
80
75
Supply air fan 85
85
4 3
2 1
L w,tot 70dB
90
85
4 3
L w,tot 65dB
75
Supply air fan
2
1
80
80
4 3
Extract air fan Available total pressure rise, Pa
Extract air fan
2.5
70
75
2 1
Airflow, m3/s
L w,tot 70dB
75
80
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. For Ecodesign, the mean value for supply air and extract air must be within the limit line. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows
The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size Min. airflow Max. airflow (on airflow regulation) m3/s m3/h m3/s m3/h 05 288 0,08 2340 0,65
Correction factors, KOK , dB. Fan in lower level Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
52
Correction factors, KOK , dB. Fan in upper level. Sound path To outlet duct
To inlet duct*
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
6 14 4 7 1 5 -1 2 -5 3 -7 -4
-2 -1 -1 -2 -6 -5 -6 -2 -16 -15 -15 -16
-5 -8 -8 -4 -10 -14 -13 -9 -28 -31 -31 -27
-13 -14 -21 -15 -23 -27 -34 -29 -34 -35 -42 -36
4
We reserve the right to alter specifications.
5 -21 -22 -31 -26 -36 -37 -46 -39 -54 -55 -64 -59
6 -26 -26 -35 -31 -42 -46 -53 -49 -59 -59 -68 -64
7 -35 -39 -46 -45 -43 -54 -58 -59 -69 -73 -80 -79
8 -24 -34 -36 -41 -29 -43 -43 -48 -55 -65 -67 -72
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
4 4 1 3 -1 -1 -5 -5 -7 -7 -10 -8
-1 -1 -1 -1 -5 -7 -6 -6 -15 -15 -15 -15
-6 -9 -10 -7 -11 -13 -16 -11 -29 -32 -33 -30
-15 -14 -23 -17 -24 -21 -34 -25 -36 -35 -44 -38
4
5 -24 -22 -32 -27 -39 -38 -48 -42 -57 -55 -65 -60
6 -29 -27 -37 -32 -45 -44 -55 -50 -62 -60 -70 -65
7 -41 -40 -49 -45 -49 -56 -61 -62 -75 -74 -83 -79
8 -32 -36 -41 -42 -37 -47 -48 -53 -63 -67 -72 -73
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 05 Delivery and Transport within the Site
The COMPACT Top 05 unit is produced in one variant in which all the components are arranged at their given physical location inside the unit. The GOLD RX Top 05 is always supplied as one unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
Left-hand version
The design makes it necessary to mount the GOLD RX Top 05 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Right-hand version
Outside air Supply air Extract air Exhaust air
Installation/duct connection options
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal. 403 91 GOLD
GOLD
Base beams are optional. 52
52
J
50
50
Power connection
Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
05
750
825
233,5
1033
237,5
350
920
561
1500
315
247
Clear Space for Inspection
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power 0.8 kW motor control system, 1 x 230 V, 50 Hz
20160422
We reserve the right to alter specifications.
53
GOLD
Sizing, installation, dimensions and weights GOLD RX, rotary heat exchanger, size 07 Airflow, m3/h SFP v
2.5
2.0 1.5
Available total pressure rise, Pa
95
90
Ca
4
Ca
p.
Extract air fan p.
va
va
r. 2
r. 1
2
3
1
L w,tot 70dB 95
75
80
90
85
Supply air fan Ca
4
Ca
p.
va
p.
va
r. 2
r. 1
2 3
1
L w,tot 70dB
75
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
07
Min. airflow (for airflow regulation) m3/s m3/h 288 0,08
Max. airflow m3/h 2700
m3/s 0,75
Correction factors, KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -12 -17 -14 -12 -29 -31 -29 -28
-8 -8 -15 -13 -22 -18 -27 -22 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -31 -29 -35 -34 -40 -40 -47 -46
6 -7 -9 -16 -14 -33 -31 -39 -36 -40 -42 -49 -47
7 -12 -13 -22 -20 -38 -37 -44 -42 -46 -47 -56 -54
8 -15 -16 -25 -25 -37 -38 -43 -43 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
54
We reserve the right to alter specifications.
20160422
GOLD
Sizing, installation, dimensions and weights GOLD RX, rotary heat exchanger, size 07 Delivery and transport within the site
The GOLD RX 07 is produced in one single variant. All of its components are arranged at their given physical location inside the air handling unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
The design makes it necessary to mount the GOLD RX 07 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors.
Right-hand version
Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Installation/duct connection options
A: Specify right-hand or left-hand version when ordering. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The air handling unit can be installed up ended (does not apply to units installed outdoors).
Left-hand version
Outdoor air Supply air Extract air Exhaust air
Power connection
403 91
91 GOLD
GOLD
52
52
J
50
50
Base beams are optional. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
07
800
995
277,5
440
271
543
1085
730
1600
400
262-301
Clear space for inspection
A clear space of 800 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) or 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz
20160422
We reserve the right to alter specifications.
55
GOLD
Sizing, installation, dimensions and weights GOLD RX Top, rotary heat exchanger, size 07 Left-hand version
Right-hand version Airflow, m3/h
Airflow, m3/h
SFP v
SFP v
2.5
2.5
2.0
2.0
1.5
Extract air fan
85
4 2 3
1 L w,tot 65dB
70
75
80
85
Supply air fan 85
80
4 3
1
85
Available total pressure rise, Pa
Available total pressure rise, Pa
90
1.5
4 2 3
1 L w,tot 70dB
75
80
Supply air fan 90
85
4
2
2 3
L w,tot 65dB
Extract air fan
80
70
75
1
80
L w,tot 70dB
Airflow, m3/s
75
80
85
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows
The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
07
Min. airflow (for airflow regulation) m3/s m3/h 288 0,08
Max. airflow m3/h 2700
To inlet duct*
To outlet duct
To inlet duct*
To air handling unit surroundings**
56
Octave band, no./mid-frequency, Hz
Region in diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
6 14 4 7 1 5 -1 2 -5 3 -7 -4
-2 -1 -1 -2 -6 -5 -6 -2 -16 -15 -15 -16
-5 -8 -8 -4 -10 -14 -13 -9 -28 -31 -31 -27
-13 -14 -21 -15 -23 -27 -34 -29 -34 -35 -42 -36
4
We reserve the right to alter specifications.
5 -21 -22 -31 -26 -36 -37 -46 -39 -54 -55 -64 -59
6 -26 -26 -35 -31 -42 -46 -53 -49 -59 -59 -68 -64
7 -35 -39 -46 -45 -43 -54 -58 -59 -69 -73 -80 -79
Sound path To outlet duct
m3/s 0,75
Correction factors, KOK , dB. Fan in lower level Sound path
Correction factors, KOK , dB. Fan in upper level.
8 -24 -34 -36 -41 -29 -43 -43 -48 -55 -65 -67 -72
To air handling unit surroundings**
Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
4 4 1 3 -1 -1 -5 -5 -7 -7 -10 -8
-1 -1 -1 -1 -5 -7 -6 -6 -15 -15 -15 -15
-6 -9 -10 -7 -11 -13 -16 -11 -29 -32 -33 -30
-15 -14 -23 -17 -24 -21 -34 -25 -36 -35 -44 -38
4
5 -24 -22 -32 -27 -39 -38 -48 -42 -57 -55 -65 -60
6 -29 -27 -37 -32 -45 -44 -55 -50 -62 -60 -70 -65
7 -41 -40 -49 -45 -49 -56 -61 -62 -75 -74 -83 -79
8 -32 -36 -41 -42 -37 -47 -48 -53 -63 -67 -72 -73
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** T otal sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
20160422
GOLD
Sizing, installation, dimensions and weights GOLD RX Top, rotary heat exchanger, size 07 Delivery and transport within the site
The GOLD RX Top 07 unit is produced in one variant in which all the components are arranged at their given physical location inside the unit. The GOLD RX Top 08 is always supplied as one unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
The design makes it necessary to mount the GOLD RX Top 07 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors.
Left-hand version
Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Right-hand version
Outdoor air Supply air Extract air Exhaust air
Installation/duct connection options
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal.
403 91 GOLD
GOLD
52
52
J
50
50
Base beams are optional.
Power connection
Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
07
800
995
276
1048
280
435
1085
730
1600
400
306
Clear space for inspection
A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz
20160422
We reserve the right to alter specifications.
57
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 08 Airflow, m3/h SFP v 2.5 2.0
1.5 90
Extract air fan
Available total pressure rise, Pa
Ca
Ca
4 3
p.
p.
va
va
r. 2
r. 1
2 1
L w,tot 75dB
80
85
Supply air fan
90
Ca
Ca
p.
va
4 3
1
p.
va
r. 2
r. 1
2 L w,tot 75dB
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Correction factors KOK , dB
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
08
Min. airflow (on airflow regulation) m3/s m3/h 720 0.20
Sound path To outlet duct
Max. airflow m3/h 3600
m3/s 1.00
To inlet duct*
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -12 -17 -14 -12 -29 -31 -29 -28
-8 -8 -15 -13 -22 -18 -27 -22 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -31 -29 -35 -34 -40 -40 -47 -46
6 -7 -9 -16 -14 -33 -31 -39 -36 -40 -42 -49 -47
7 -12 -13 -22 -20 -38 -37 -44 -42 -46 -47 -56 -54
8 -15 -16 -25 -25 -37 -38 -43 -43 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
58
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 08 Delivery and Transport within the Site
The GOLD RX 08 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
The design makes it necessary to mount the GOLD RX 08 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors.
Right-hand version
Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Installation/duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The air handling unit can be installed up ended (does not apply to units installed outdoors).
Left-hand version
Outside air Supply air Extract air Exhaust air
Power connection
403 91
91 GOLD
GOLD
52
52
J
50
50
Base beams are optional. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
08
800
995
277,5
440
271
543
1085
730
1600
400
270-309
Clear Space for Inspection
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
Capacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz 20160422
We reserve the right to alter specifications.
59
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 08 Left-hand version.
Right-hand version. Airflow, m3/h
Airflow, m3/h
SFP v
SFP v 2.5 2.0
1.5
Available total pressure rise, Pa
90
4 2
1
L w,tot 70dB
75
80
85
Supply air fan 85
85
4 3
2
1 L w,tot 75dB
80
Supply air fan 90
4
4 3
2.5
Extract air fan Available total pressure rise, Pa
Extract air fan
3
2.0
1.5
1 L w,tot 70dB
2 75
2
3 1
80
Airflow, m3/s
L w,tot 75dB
80
85
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. For Ecodesign, the mean value for supply air and extract air must be within the limit line. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Correction factors KOK , dB
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop.
Sound path To outlet duct
Size
08
Min. airflow (on airflow regulation) m3/s m3/h 720 0.20
Max. airflow m3/h 3600
m3/s 1.00
To inlet duct*
To unit’s surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -10 -15 -12 -10 -29 -31 -29 -28
-8 -8 -15 -13 -19 -15 -24 -19 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -25 -23 -29 -28 -40 -40 -47 -46
6 -7 -9 -16 -14 -23 -21 -29 -26 -40 -42 -49 -47
7 -12 -13 -22 -20 -25 -24 -31 -29 -46 -47 -56 -54
8 -15 -16 -25 -25 -22 -23 -28 -28 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
60
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 08 Delivery and Transport within the Site
The GOLD RX Top unit is produced in one variant in which all the components are arranged at their given physical location inside the unit. The GOLD RX Top 08 is always supplied as one unit. The air handling unit is supplied on a wooden pallet.
Base beams/Stand/Foundation
Left-hand version
The design makes it necessary to mount the GOLD RX Top 08 on base beams, a stand or some other form of foundation. Otherwise it will not be possible to open the inspection doors. Prefitted base beams are obtainable as optional equipment; a separately supplied stand is available as an accessory.
Right-hand version
Outside air Supply air Extract air Exhaust air
Installation/duct connection options
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors). B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal. 403 91 GOLD
GOLD
Base beams are optional. 52
52
J
50
50
Power connection
Size
A
B
C
D
F
G
H
J
L
Ø
Weight, kg
08
800
995
276
1048
280
435
1085
730
1600
400
310
Clear Space for Inspection
A clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power 1.15 kW motor control system, 1 x 230 V, 50 Hz
20160422
We reserve the right to alter specifications.
61
GOLD
Sizing, installation, dimensions and weights GOLD RX, rotary heat exchanger, size 11 Airflow, m3/h SFP v
2.5 2.0 1.5 90
Extract air fan
Available total pressure rise, Pa
Ca
Ca
4 3
p.
p.
va
va
r. 2
r. 1
2 1
L w,tot 75dB
80
85
90
Supply air fan Ca
Ca
4 3
p.
va
p.
va
r. 2
r. 1
2
1
L w,tot 75dB
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
11
Min. airflow (for airflow regulation) m3/s m3/h 720 0,20
Max. airflow m3/h 3960
m3/s 1,10
Correction factors, KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -12 -17 -14 -12 -29 -31 -29 -28
-8 -8 -15 -13 -22 -18 -27 -22 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -31 -29 -35 -34 -40 -40 -47 -46
6 -7 -9 -16 -14 -33 -31 -39 -36 -40 -42 -49 -47
7 -12 -13 -22 -20 -38 -37 -44 -42 -46 -47 -56 -54
8 -15 -16 -25 -25 -37 -38 -43 -43 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
62
We reserve the right to alter specifications.
20160422
GOLD
Sizing, installation, dimensions and weights GOLD RX, rotary heat exchanger, size 11 Delivery and transport within the site
The GOLD RX 11 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors.
Fan arrangement 2
Fan arrangement 1
Right-hand version
The air handling unit is delivered on wooden beams.
Duct connection options
A: Specify right-hand or left-hand version when ordering. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Left-hand version Outdoor air Supply air
Extract air
Exhaust air
Power connection K
403
16
K 91
91
GOLD
J
50
50
GOLD
52
52
J
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
F
G
H
J
K
L
Ø
Weight, kg
11
655
1199
324
550
324
647
1295
935
551
1860
500
444-496
Division into sections for transport
A
D+19 mm
A
Power connection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 141-167 kg, D = 162 kg.
Clear space for inspection
A clear space of 800 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Capacity variant 1: 1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Capacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
63
GOLD
Sizing, installation, dimensions and weights GOLD RX Top, rotary heat exchanger, size 11 Left-hand version
Right-hand version Airflow, m3/h
Airflow, m3/h
SFP v
SFP v
2.5
2.5
2.0 1.5
Available total pressure rise, Pa
2
3
1
L w,tot 70dB
75
80
85
90
Supply air fan 85
4 3
Extract air fan Available total pressure rise, Pa
Extract air fan 90
4
85
4 3
2 1 L w,tot 75dB
80
85
Supply air fan 90
4
2
1 L w,tot 70dB
2.0
1.5
3 75
80
85
2 1L
Airflow, m3/s
w,tot
75dB
80
85
90
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. For Ecodesign 2018, the mean value for supply air and extract air must be within the limit line. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and max. airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
11
Min. airflow (for airflow regulation) m3/s m3/h 720 0,20
Max. airflow m3/h 3960
m3/s 1,10
Correction factors, KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 4 1 2 3 4 1 2 3 4
-1 -1 -1 -2 -6 -7 -6 -7 -12 -12 -12 -13
-6 -5 -2 -3 -9 -10 -4 -5 -20 -19 -16 -17
-6 -8 -6 -5 -10 -15 -12 -10 -29 -31 -29 -28
-8 -8 -15 -13 -19 -15 -24 -19 -29 -29 -36 -34
4
5 -7 -7 -14 -13 -25 -23 -29 -28 -40 -40 -47 -46
6 -7 -9 -16 -14 -23 -21 -29 -26 -40 -42 -49 -47
7 -12 -13 -22 -20 -25 -24 -31 -29 -46 -47 -56 -54
8 -15 -16 -25 -25 -22 -23 -28 -28 -46 -47 -56 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
64
We reserve the right to alter specifications.
20160422
GOLD
Sizing, installation, dimensions and weights GOLD RX Top, rotary heat exchanger, size 11 Delivery and transport within the site
The GOLD RX Top 11 unit is produced in one variant in which all the components are arranged at their given physical location inside the unit. The GOLD RX Top 11 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors.
Left-hand version
Right-hand version
The air handling unit is delivered on wooden beams.
Duct connection options
Outdoor air Supply air
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
Extract air
Exhaust air
B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal. 403
16
16
GOLD
91
GOLD
52
52
J
50
50
Power connection
C
K
C
Size
A
B
C
D
F
G
H
J
K
L
Ø
Weight, kg
11
655
1199
332
550
333
533
1295
935
1196
1860
500
488
Division into sections for transport
A
D+19 mm
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 163 kg, D = 162 kg.
A clear space of 800 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz 20160422
We reserve the right to alter specifications.
65
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 12 Airflow, m3/h SFP v 2.5
2.0
1.5
Extract air fan
90
Available total pressure rise, Pa
Ca
Ca
p.
p.
va
va
r. 2
r. 1
3
2 1
L w,tot 75dB
80
85 90
Supply air fan Ca
Ca
3
p.
p.
va
va
r. 2
r. 1
2
1 L w,tot 75dB
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
12
Min. airflow (on airflow regulation) m3/s m3/h 720 0.20
Max. airflow m3/h 5040
m3/s 1.40
Correction factors KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 1 2 3 1 2 3
-1 -1 -1 -6 -7 -6 -12 -12 -12
-6 -5 -2 -9 -10 -4 -20 -19 -16
-6 -8 -6 -12 -17 -14 -29 -31 -29
-8 -8 -15 -22 -18 -27 -29 -29 -36
4
5 -7 -7 -14 -31 -29 -35 -40 -40 -47
6 -7 -9 -16 -33 -31 -39 -40 -42 -49
7 -12 -13 -22 -38 -37 -44 -46 -47 -56
8 -15 -16 -25 -37 -38 -43 -46 -47 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
66
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 12 Delivery and Transport within the Site
The GOLD RX 12 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.
Fan arrangement 2
Fan arrangement 1
The air handling unit is delivered on wooden beams.
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal. B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!
Fan arrangement 1
Fan arrangement 2
Left-hand version Outside air
Supply air
Extract air
Exhaust air
Power connection K
403
16
K 91
91
GOLD
J
50
50
GOLD
52
52
J
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
Size
A
B
C
D
F
G
H
J
K
L
Ø
Weight, kg
12
655
1199
324
550
324
647
1295
935
551
1860
500
466-518
Division into sections for transport
A
D+19 mm
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 152-178 kg, D = 162 kg.
A clear space of 800 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
67
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 12 Left-hand version.
Right-hand version. Airflow, m /h 3
Airflow, m3/h
SFP v
SFP v 2.5
2.5
2.0
1.5
90
2 1
L w,tot 75dB
80
85
Supply air fan
Extract air fan Available total pressure rise, Pa
Available total pressure rise, Pa
Extract air fan
3
85
3
2
1 L w,tot 75dB
80
Supply air fan
85
90
2 3
2
3
1 L w,tot 70dB
75
2.0
1.5
80
1 L w,tot 75dB
Airflow, m3/s
80
85
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode. For Ecodesign, the mean value for supply air and extract air must be within the limit line. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
12
Min. airflow (on airflow regulation) m3/s m3/h 720 0,20
Max. airflow m3/h 5040
m3/s 1,40
Correction factors KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 1 2 3 1 2 3
-1 -1 -1 -6 -7 -6 -12 -12 -12
-6 -5 -2 -9 -10 -4 -20 -19 -16
-6 -8 -6 -10 -15 -12 -29 -31 -29
-8 -8 -15 -19 -15 -24 -29 -29 -36
4
5 -7 -7 -14 -25 -23 -29 -40 -40 -47
6 -7 -9 -16 -23 -21 -29 -40 -42 -49
7 -12 -13 -22 -25 -24 -31 -46 -47 -56
8 -15 -16 -25 -22 -23 -28 -46 -47 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
68
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX Top, rotary heat exchanger, size 12 Delivery and Transport within the Site
The GOLD RX Top unit is produced in one variant in which all the components are arranged at their given physical location inside the unit. The GOLD RX Top 12 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.
Left-hand version
Right-hand version
The air handling unit is delivered on wooden beams.
Duct connection options
A: All the duct connections are arranged from the top of the air handling unit (the unit must not be installed outdoors).
Outside air
Supply air
Extract air
Exhaust air
B: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by selecting the appropriate version in the hand-held micro terminal. 403
16
16
GOLD
91
GOLD
52
52
J
50
50
Power connection
C
K
C
Size
A
B
C
D
F
G
H
J
K
L
Ø
Weight, kg
12
655
1199
332
550
333
533
1295
935
1196
1860
500
504
Division into sections for transport
A
D+19 mm
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 171 kg, D = 162 kg.
A clear space of 800 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan
Motor shaft power: 1.6 kW, motor control system, 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
69
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 14 Airflow, m3/h SFP v
2.5 2.0 1.5
Extract air fan Available total pressure rise, Pa
Ca
Ca
3
p.
p.
va
va
r. 2
r. 1
2
1 L w,tot 75dB
80
85
90
90
Supply air fan Ca Ca
3
p.
va
p.
va
r. 2
r. 1
2
1 L w,tot 75dB
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
14
Min. airflow (on airflow regulation) m3/s m3/h 720 0,20
Max. airflow m3/h 5940
m3/s 1,65
Correction factors KOK , dB Sound path To outlet duct
To inlet duct*
To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1 2 3 1 2 3 1 2 3
-1 -1 -1 -6 -7 -6 -12 -12 -12
-6 -5 -2 -9 -10 -4 -20 -19 -16
-6 -8 -6 -10 -15 -12 -29 -31 -29
-8 -8 -15 -19 -15 -24 -29 -29 -36
4
5 -7 -7 -14 -25 -23 -29 -40 -40 -47
6 -7 -9 -16 -23 -21 -29 -40 -42 -49
7 -12 -13 -22 -25 -24 -31 -46 -47 -56
8 -15 -16 -25 -22 -23 -28 -46 -47 -56
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
70
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 14 Delivery and Transport within the Site
The GOLD RX 14 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Upward
Upward
Forward
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 2
Fan arrangement 1
The air handling unit is delivered on wooden beams.
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal.
Upward
Upward Forward
Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 2
Left-hand version
D: Specify when placing orders whether the unit shall have an air intake from above for outdoor air or extract air. (not for units installed outdoors).
Outside air
Supply air
Extract air
Exhaust air
Power connection 403
E 91
91 M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
14
765
1400
1136
550
208
400
1000
1395
298
109
200
2080
188
521-589
Division into sections for transport
A
D+19 mm
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 175-209 kg, D = 171 kg.
A clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A
Rated data per fan Rated data per fan
Motor shaft power: 1.6 alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422
We reserve the right to alter specifications.
71
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 20 Airflow, m3/h SFP v
2.5
2.0 1.5
Extract air fan Available total pressure rise, Pa
Ca
Ca
2
p.
p.
va
va
r. 2
r. 1
1 L w,tot 70dB
75
80
85
Supply air fan Ca
Ca
p.
p.
va
va
r. 2
r. 1
1
2 L w,tot 70dB
75
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
20
Min. airflow (on airflow regulation) m3/s m3/h 1080 0.30
Max. airflow m3/h 7560
m3/s 2.1
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
72
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 20 Delivery and Transport within the Site
The GOLD RX 20 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Upward
Upward
Forward
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 2
Fan arrangement 1
The air handling unit is delivered on wooden beams.
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal.
Upward
Upward Forward
Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 2
Left-hand version
D: Specify when placing orders whether the unit shall have an air intake from above for outdoor air or extract air. (not for units installed outdoors).
Outside air
Supply air
Extract air
Exhaust air
Power connection 403
E 91
91 M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
20
765
1400
1136
550
208
400
1000
1395
298
109
200
2080
188
557-625
Division into sections for transport
A
D+19 mm
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 193-227 kg, D = 171 kg.
A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz 20160422
We reserve the right to alter specifications.
73
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 25 Airflow, m3/h SFP v
2.5
2.0 1.5
Extract air fan Available total pressure rise, Pa
Ca Ca
2
p.
va
p.
va
r. 2
r. 1
1 L w,tot 70dB
75
80
85
90
Supply air fan Ca Ca
2
p.
va
p.
va
r. 2
r. 1
1 L w,tot 70dB
75
80
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
25
Min. airflow (on airflow regulation) m3/s m3/h 1080 0,30
Max. airflow m3/h 9000
m3/s 2.50
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
74
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 25 Delivery and Transport within the Site
The GOLD RX 25 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Upward
Upward
Forward
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 2
Fan arrangement 1
The air handling unit is delivered on wooden beams.
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal.
Upward
Upward Forward
Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 2
Left-hand version
D: Specify when placing orders whether the unit shall have an air intake from above for outdoor air or extract air. (not for units installed outdoors).
Outside air
Supply air
Extract air
Exhaust air
Power connection 403
E 91
91 M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
25
835
1600
1336
550
193
500
1200
1595
298
94
200
2220
203
666-746
Division into sections for transport
A
D+19 mm
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 225-265 kg, D = 216 kg.
A clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.
Power connection
3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 H 20160422
We reserve the right to alter specifications.
75
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 30 Airflow, m3/h SFP v
2.5 2.0
1.5
Extract air fan Available total pressure rise, Pa
Ca Ca
p.
p.
va
va
r. 2
r. 1
1
2 L w,tot 70dB
75
80
85
90
Supply air fan Ca Ca
p.
p.
va
va
r. 2
r. 1
1
2 L w,tot 70dB
75
80
90
85
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
30
Min. airflow (on airflow regulation) m3/s m3/h 1800 0.50
Max. airflow m3/h 11520
m3/s 3.20
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
76
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 30 Delivery and Transport within the Site
The GOLD RX 30 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Upward
Upward
Forward
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 2
Fan arrangement 1
The air handling unit is delivered on wooden beams.
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site by selecting the appropriate version in the hand-held micro terminal.
Upward
Upward Forward
Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! Fan arrangement 1
C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 2
Left-hand version
D: Specify when placing orders whether the unit shall have an air intake from above for outdoor air or extract air. (not for units installed outdoors).
Outside air
Supply air
Extract air
Exhaust air
Power connection 403
E 91
91 M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
30
835
1600
1336
550
193
500
1200
1595
298
94
200
2220
203
706-786
Division into sections for transport
A
D+19 mm
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 245-285 kg, D = 216 kg.
A clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 A
Rated data per fan
Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
77
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 35 Airflow, m3/h SFP v
2.5
2.0 1.5
Extract air fan Available total pressure rise, Pa
Ca
Ca
p.
p.
va
va
r. 1
r. 2
1
2 L w,tot 70dB
75
80
85
90
Supply air fan Ca
Ca
p.
1
2 L w,tot 70dB
75
80
p.
va
va
r. 2
r. 1
85
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
35
Min. airflow (on airflow regulation) m3/s m3/h 1800 0,50
Max. airflow m3/h 14040
m3/s 3.90
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
78
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 35 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 35 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams.
Fan arrangement 1
Fan arrangement 2
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, Upward the version can be changed at the building site by selecting the Forward appropriate version in the hand-held micro terminal.
Upward Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 1
Fan arrangement 2
Left-hand version
Outside air
Supply air
Extract air
Exhaust air
Power connection
34
M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
35
948
1990
1726
550
200
600
1400
1985
392
153
295
2446
240
956-1070
Division into sections for transport
A
D+19 mm
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 322-379 kg, D = 312 kg.
A clear space of 900 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 A
Rated data per fan
Motor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
79
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 40 Airflow, m3/h SFP v 2.5 2.0
1.5
Extract air fan Available total pressure rise, Pa
Ca
Ca
2
p.
va
p.
va
r. 2
r. 1
1 L w,tot 75dB
80
85
90
Supply air fan Ca
Ca
2
p.
1 L w,tot 75dB
80
va
p.
va
r. 2
r. 1
85
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows
Correction factors KOK , dB
The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
40
Min. airflow (on airflow regulation) m3/s m3/h 2700 0,75
Max. airflow m3/h 140401/180002
Capacity variant 1. 2 Capacity variant 2. 1
m3/s 3,901/5,002
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
To air handling unit surroundings**
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
Sound path
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
80
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 40 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 40 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Forward
The three sections are joined together by bolts and the electrical and control cables have quick connectors. The air handling unit is delivered on wooden beams.
Fan arrangement 1
Fan arrangement 2
Right-hand version
Duct connection options
A: Specify right-hand or left-hand version when ordering! If the air handling unit is supplied with all the end connection panels, Upward the version can be changed at the building site by selecting the Forward appropriate version in the hand-held micro terminal.
Upward Forward
B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders! C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 1
Fan arrangement 2
Left-hand version
Outside air
Supply air
Extract air
Exhaust air
Power connection
34
M GOLD
GOLD
M 50
52
50
52
50
50
The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted. * The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
C
D
E
F
G
H
I
J
K
L
M
Weight, kg
40
948
1990
1726
550
200
600
1400
1985
392
153
295
2446
240
1006-1120
Division into sections for transport
A
D
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 347-404 kg, D = 312 kg.
A clear space of 900 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 20 A (capacity variant 1) alt. 25 A (capacity variant 2)
Rated data per fan
Motor shaft power: 5.0 kW (3.9 kW*) alt. 6.5 kW, motor control system: 3 x 400 V, 50 Hz *The motor control system limits the power of the take-off to the value specified.
20160422
We reserve the right to alter specifications.
81
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 50 Airflow, m3/h 2.5
SFP v
2.0
1.5
Available total pressure rise, Pa
Ca
Ca
p.
va
Extract air fan p.
va
r. 2
r. 1
1
2 L w,tot 75dB
80
85
90
Supply air fan Ca Ca
p.
va
p.
va
r. 2
r. 1
1
2 L w,tot 75dB
80
85
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
50
Min. airflow (on airflow regulation) m3/s m3/h 2160 0,60
Max. airflow m3/h 18000
m3/s 5.00
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
82
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 50 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 50 is always supplied as one unit.
Forward
The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 1
The unit is supplied on 100 mm high support feet made of steel.
Fan arrangement 2
Right-hand version
Duct connection options
Upward
A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!
Upward
Forward
Forward
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors) Fan arrangement 1
Fan arrangement 2
Left-hand version
Outside air
Supply air
Extract air
Exhaust air
34 28*
GOLD
Power connection
GOLD
28 76
Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. The unit has provision for fitting the adjustable support feet.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
D
E
F
G
H
I
J
K
L
Weight, kg
50
1050
2318
570
150
800
1600
2253
423
115
360
2670
1294-1418
Division into sections for transport
A
76
D
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 440-502 kg, D = 414 kg.
A clear space of 1,100 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 20 A (capacity variant 1) alt. 32 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2 x 2.4 kW alt. 2 x 3.4 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
83
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 60 Airflow, m3/h SFP v 2.5 2.0
1.5
Extract air fan Available total pressure rise, Pa
Ca
Ca
1
2 L w,tot 75dB
80
p.
va
85
p.
va
r. 2
95
r. 1
90
Supply air fan Ca Ca
1
2 L w,tot 75dB
80
p.
va
p.
va
95
r. 2
r. 1
85
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
60
Min. airflow (on airflow regulation) m3/s m3/h 3600 1.00
Max. airflow m3/h 23400
m3/s 6.50
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
84
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 60 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 60 is always supplied as one unit.
Forward
The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors. Fan arrangement 1
The unit is supplied on 100 mm high support feet made of steel.
Fan arrangement 2
Right-hand version
Duct connection options
Upward
A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!
Upward
Forward
Forward
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors). Fan arrangement 1
Fan arrangement 2
Left-hand version
Outside air
Supply air
Extract air
Exhaust air
34 28*
GOLD
Power connection
GOLD
28 76
Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. The unit has provision for fitting the adjustable support feet.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
D
E
F
G
H
I
J
K
L
Weight, kg
60
1050
2318
570
150
800
1600
2253
423
115
360
2670
1374-1498
Division into sections for transport
A
76
D
A
Clear space for inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 480-542 kg, D = 414 kg.
A clear space of 1,100 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 A (capacity variant 1) alt. 50 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
85
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 70 Airflow, m3/h SFP v
2.5
2.0 1.5
Extract air fan p.
Available total pressure rise, Pa
Ca va
1
2 L w,tot 75dB
80
85
2 r.
Ca
p.
va
r. 1
90
95
Supply air fan Ca p.
L w,tot 75dB
80
85
p.
2 r.
1
2
va
Ca
va
r. 1
95
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign 2018 is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. The air handling unit complies with requirements to Ecodesign 2016. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
70
Min. airflow (on airflow regulation) m3/s m3/h 3600 1,00
Max. airflow m3/h 27000
m3/s 7.50
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
86
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 70 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 70 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Forward
Fan arrangement 1
Fan arrangement 2
Right-hand version
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Upward
The unit is supplied on 100 mm high support feet made of steel.
Upward
Forward
Forward
Duct connection options
A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!
Fan arrangement 1
Fan arrangement 2
Left-hand version
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors) Outside air
Supply air
Extract air
Exhaust air
52*
Power connection GOLD
GOLD
52 76
Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. The unit has provision for fitting the adjustable support feet.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
D
E
F
G
H
I
J
K
L
Weight, kg
70
1275
2637
570
164
1000
1800
2640
319
161
419
3120
2059-2211
Division into sections for transport
A
76
D
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 740-816 kg, D = 579 kg.
A clear space of 1,100 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 32 A (capacity variant 1) alt. 50 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
87
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 80 Airflow, m3/h SFP v
2.5 2.0
1.5
Extract air fan Ca va
Available total pressure rise, Pa
p. 2 r.
Ca
p.
va
r. 1
1
2 L w,tot 75dB
80
85
90
95
Supply air fan Ca
Ca
p.
va
1
2 L w,tot 75dB
80
85
p.
va
r. 1
r. 2
95
90
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
80
Min. airflow (on airflow regulation) m3/s m3/h 5400 1.50
Max. airflow m3/h 34200
m3/s 9.50
Correction factors KOK , dB Sound path To outlet duct To inlet duct* To air handling unit surroundings**
Octave band, No. / mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
88
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, rotary heat exchanger, size 80 Delivery and Transport within the Site
Upward
Upward
Forward
The GOLD RX 80 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. The air handling unit can be split into three sections to facilitate transporting it within the building site.
Forward
Fan arrangement 1
Fan arrangement 2
Right-hand version
The three sections are joined together by bolts and the electrical and control cables have quick connectors. Upward
The unit is supplied on 100 mm high support feet made of steel.
Upward
Forward
Forward
Duct connection options
A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!
Fan arrangement 1
Fan arrangement 2
Left-hand version
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors) Outside air
Supply air
52*
Extract air
Exhaust air
137
Power connection
Applies to capacity variant 2 only
GOLD
GOLD
52 76
Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. The unit has provision for fitting the adjustable support feet.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size
A
B
D
E
F
G
H
I
J
K
L
Weight, kg
80
1275
2637
570
164
1000
1800
2640
319
161
419
3120
2159-2435
Division into sections for transport
A
76
D
A
Clear Space for Inspection
The unit can be divided into three sections at the building site. Dimensions: See A and D in the table above. Weight: A = 790-928 kg, D = 579 kg.
A clear space of 1,100 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 50 A (capacity variant 1) alt. 80 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
89
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, size 100 Airflow, m3/h SFP v
2.5
2.0 1.5
Extract air fan p.
Available total pressure rise, Pa
Ca va 2 r.
Ca
p.
va
1
2 L w,tot 75dB
80
85
r. 1
90
95
Supply air fan Ca
p.
va
r. 2
Ca p. va 1 r.
1
2 L w,tot 75dB
80
85
90
95
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The diagram shows air handling units including standard the end connection panels. The air handling unit complies with requirements to Ecodesign 2016/2018. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
100
Min. airflow (on airflow regulation) m3/s m3/h 5400 1,50
Max. airflow m3/h 39 600
m3/s 11.0
Correction factors KOK , dB Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To the inlet duct*
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
To air handling unit surroundings**
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
Sound path
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
90
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, size 100 Upward
Delivery and Transport within the Site
Upward
Forward
The GOLD RX 100 is supplied in five separate sections: two fan sections, two filter sections and one heat exchanger section. The heat exchanger section can also be supplied split into two casing sections and rotor, in which case the rotor is supplied tilted in a transport cradle (transport height = 2,930 mm, minimum transport width = 2,350 mm). After the heat exchanger has been assembled, if required, the five sections are installed at the building site.
Forward
Fan arrangement 1
Fan arrangement 2
Right-hand version Upward
The five sections are joined together by bolts and the electrical and control cabling between the parts have quick-fit connectors.
Upward
Forward
Forward
Duct connection options A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Left-hand version
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors) N.B.! Duct connection size: 2500 x 800 mm.
Outdoor air Supply air
Extract air
Exhaust air
137 M 56*
N
N
O
P
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
GOLD
GOLD
P
Power connection GOLD
45
56 1048
122 77
1000
1048 77
3186
Size
A
B
D
E
F
G
H
I
J
K
L
M
N
O
P
Weight, kg
100
1126
3340
1070
191
1200
2400
3440
520
210
470
3322
800
170
2500
1720
3540-3900
Transport at building site, dim. and weights filter and fan sections See dimensions A and P in the table above. Weight: fan section = 713-834 kg, filter section = 470-529 kg. Heat exchanger section, mounted See dimensions D and H in the table above. Weight: heat exchanger section = 1,174 kg. Heat exchanger section, two casing sections + rotor See transport dimensions in the Delivery and at-site transport section above. Weight: casing lower section = 494 kg, casing upper section = 270 kg, rotor = 410 kg, transport cradle = 190 kg
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 50 A (capacity variant 1) alt. 80 A (capacity variant 2)
Rated data per fan
Motor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.
91
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, size 120 Airflow, m3/h SFP v
2.5
2.0
1.5
Extract air fan Ca va
Available total pressure rise, Pa
p.
2
2 r.
Ca
p.
va
r. 1
1
L w,tot 80dB
85
90
95
Supply air fan Ca
Ca
2
p.
va
p.
va
r. 2
r. 1
1 L w,tot 80dB
85
90
95
Airflow, m3/s The lower limit for the airflow when the unit is operating in the airflow regulation mode. The limit line for Ecodesign is calculated with capacity variant 2 and full face end connection panels (accessories). The mean value for supply air and extract air must be within the limit line. Other values in diagrams are calculated for air handling units with standard end connection panels. Recommended working range for sizing. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Limit line, Ecodesign, 2016 Limit line, Ecodesign, 2018
Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are determined by the external pressure drop. Size
120
Min. airflow (on airflow regulation) m3/s m3/h 9000 2.50
Max. airflow m3/h 50 400
m3/s 14.0
Correction factors KOK , dB Octave band, no./mid-frequency, Hz
Range in the diagram
1
2
3
63
125
250
To the outlet duct
1
-4
-9
-7
-5
-8
-9
-11
-11
2
2
-4
-7
-7
-10
-12
-16
-17
To inlet duct*
1
-9
-10
-10
-21
-29
-32
-36
-33
2
-4
-3
-10
-22
-31
-34
-41
-38
1
-15
-23
-30
-26
-41
-42
-45
-42
2
-9
-18
-30
-28
-43
-45
-50
-48
Sound path
To air handling unit surroundings**
4
5
6
7
8
500 1000 2000 4000 8000
* The integral attenuation of filters and rotary heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.
92
We reserve the right to alter specifications.
20160422
GOLD
Sizing, Installation, Dimensions and Weights GOLD RX, size 120 Upward
Delivery and Transport within the Site
Upward
Forward
The GOLD RX 120 is supplied in five separate sections: two fan sections, two filter sections and one heat exchanger section. The heat exchanger section can also be supplied split into two casing sections and rotor, in which case the rotor is supplied tilted in a transport cradle (transport height = 2,930 mm, minimum transport width = 2,350 mm). After the heat exchanger has been assembled, if required, the five sections are installed at the building site.
Forward
Fan arrangement 1
Fan arrangement 2
Right-hand version Upward
The five sections are joined together by bolts and the electrical and control cabling between the parts have quick-fit connectors.
Upward
Forward
Forward
Duct connection options A: Specify right-hand or left-hand version when ordering! B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Left-hand version
C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors) N.B.! Duct connection size: 2500 x 800 mm.
Outdoor air Supply air
Extract air
Exhaust air
137 M 56*
N
N
O
P
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
GOLD
GOLD
P
Power connection GOLD
45
56 1048
122 77
1000
1048 77
3186
Size
A
B
D
E
F
G
H
I
J
K
L
M
N
O
P
Weight, kg
120
1126
3340
1070
191
1200
2400
3440
520
210
470
3322
800
170
2500
1720
3746-4168
Transport at building site, dim. and weights filter and fan sections See dimensions A and P in the table above. Weight: fan section = 816-968 kg, filter section = 470-529 kg. Heat exchanger section, mounted See dimensions D and H in the table above. Weight: heat exchanger section = 1,174 kg. Heat exchanger section, two casing sections + rotor See transport dimensions in the Delivery and at-site transport section above. Weight: casing lower section = 494 kg, casing upper section = 270 kg, rotor = 410 kg, transport cradle = 190 kg
Clear space for inspection
A clear space of 1,000 mm should be provided in front of the unit.
Power connection
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 A (capacity variant 1) alt. 125 A (capacity variant 2)
Rated data per fan
Motor shaft power: 3 x 6.5 kW alt. 3 x 10 kW, motor control system: 3 x 400 V, 50 Hz
20160422
We reserve the right to alter specifications.