Transcript
SLT 100
10.04 -
G
Operating instructions 50451882 11.15
SLT
100
SLT
100
Foreword The safe operation of the charger requires the application of expertise contained in the present ORIGINAL OPERATING INSTRUCTIONS. The information is presented in a precise and clear manner. The chapters are arranged by letter. Our equipment is subject to ongoing development. We reserve the right to alter the design, features and technical aspects of the equipment. No guarantee of particular features of the truck should therefore be assumed from the present operating instructions. Safety instructions and important explanations are indicated by the following graphics:
F
Used before safety instructions which must be observed to avoid danger to personnel.
M Z
Used before notices which must be observed to avoid material damage.
t
Used to indicate standard equipment.
o
Used to indicate optional equipment.
Used before notices and explanations.
Copyright Copyright of these operating instructions remains with JUNGHEINRICH AG.
Jungheinrich Aktiengesellschaft Friedrich-Ebert-Damm 129 D-22047 Hamburg - Germany Tel: +49 (0) 40/6948-0
11.15.GB
www.jungheinrich.com
V1
Table of contents A B
Correct use and application
1
F
Charger Maintenance
1
Operational safety and environmental protection Safety instructions to be observed during servicing Cleaning operations Working on the SLT 100 charger Fuses Small battery charger Large battery charger
Description of battery charger
2
2
1 2 3 4
Technical description Charging electronics Protection / Ambient conditions Identification label,
2 4 4 4
3 4
C
Transportation and Commissioning
5
1 2 3
Transporting the charger Charger Assembly Starting up the charger
5 5 5
D
Battery - Servicing, recharging, replacement
6
Safety regulations governing the handling of lead-acid batteries
6
E
Operation
7
1
Safety regulations relating to the operation of battery chargers 7 Description of the operating controls and indicating elements 8 Commissioning the battery charger 9 Connecting the charger 9 Starting the charging operation 9 Battery charging sequence 9 Mains supply 9 Fault indication (safety cut-out) 9 Manual charging interruption 10 Boosting charge 10 Manual Compensation Charge 10 Automatic equilising charge function 10 Charging state indicator 10
1
2 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
11 11 11 11 11 11 12
G
Internal electrolyte stirrer (EUW) 13
1 2 3 4 5 5.1 6 7 7.1
Correct use and application Charger Assembly Electrolyte circulation (EUW) Description of the device Commissioning Air volume flow presetting Maintenance of the filter Aid for malfunctions Malfunction: Pump does not react during charging. Malfunction: Charging time is not reduced Malfunction: Loud pump noises
7.2 7.3
13 13 13 13 15 15 15 16 16 16 16
H
“LIS” charge information 17 system (o)
I
Sample data plate
18
0709.GB
4
5 5.1 5.2
11
I1
I2
0709.GB
A
Correct use and application The SLT 100 battery charger is designed for the fully automatic charging of lead batteries and may only be operated for this purpose. The charger operates in accordance with the Wa characteristic specified in DIN 41774. This characteristic is optimized by current pulses at the end of the charge. This current characteristic curve, which slopes downwards as the battery charge level rises, allows for optimal charging. Safe functioning of the battery charger is ensured by the reliable charging electronics monitoring the battery charging operation. The technical data and specifications regarding the connection requirements can be found on the identification plate and in the operating instructions. These specifications must always be heeded. Operation of the battery chargers is subject to the provisions contained in the relevant legislation and regulations, from industry association guidelines (VDE), from the EMC directive (2004/108/EC) and directives issued by local authorities. Excerpts of such provisions are given in chapter E1. The battery charger must only be used for charging batteries which are of the type stipulated by the manufacturer. The battery charger must always be operated with the housing closed. It is forbidden to loosen and remove parts of the housing or any type of suppressor elements. Do not place any objects on the charger or climb onto it.
The user is responsible for choosing the assembly location. He must check whether the battery charger will affect any devices that are sensitive to electromagnetic interference. The assembly location of the charger must be chosen so that operation (high DC currents generate magnetic interference fields) does not affect the functioning of sensitive electromagnetic devices and magnetic data media, such as pacemakers, monitors, disks, magnetic tapes, magnetic cards, watches, see “Charger Assembly” on page 5. The user must ensure that the SLT 100 battery charger is used only within its design limits and that all danger to life and limb of the operator and third parties is avoided. Furthermore, applicable accident prevention and other health and safety regulations, along with the operating and maintenance guidelines, must be observed at all times.
M
The battery charger must only be operated when stationary. The user must also ensure that all persons operating the battery chargers have read and understood these operating instructions.
Additional components may only be installed after a written approval by the manufacturer has been obtained. User obligations: User within the meaning of these operating instructions is any natural person or legal person who either uses the battery charger himself, or on whose behalf it is used.
1115.GB
In special cases (e.g. leasing or renting), the user is deemed to be the person, who, in accordance with existing contractual agreements between the owner and the user of the SLT 100 battery charger, is charged with the observance of the operating duties.
1
B
Description of battery charger
1
Technical description The SLT 100 battery charger is designed for the fully automatic charging and recharging of lead batteries and is equipped with a special electronic charging system (1, 2). The rated charging current specified flows at a charging voltage of 2.0 volts per cell. The battery must be assigned so that the initial charging current is approx. 16 Amperes per 100 Ah of battery capacity.
1
The difference lies in the initial charging current – see data plate (3).
00
1 SLT
Initial charging voltage: 24, 48, 80 volt depending on type Initial charging current: 20 A-160 A, depending on type The battery charger is protected on the secondary side by a fuse (5) acting as a short circuit protection and by a sensor to limit the transformer temperature.
2 3
To ensure the operational safety of the system, only self-cooled stacked silicon rectifier elements (4) are used. Stray field transformers (6) are used to comply with the specified charging characteristic. The stray field transformers are equipped with additional primary tapping to DIN 41 774, corresponding to +10 %, +5 %, 0 % and -5 % to allow for mains voltage deviations.
Z
4
6 5
Modifications should only be carried out by the manufacturer’s service department.
1115.GB
SLT 100
2
Z
Charging electronics extra option (Aquamatic)
Z
The Aquamatic serves to control an external solenoid valve of an automatic water refilling system. When a cell voltage of 2.4 V/cell is reached, a relay contact (normally open contact, contact rating 5 A) is triggered by the following pulse train:
Characteristic curve: Wa Charging characteristic Uz Cell voltage (V/cell)
- 6-7 pulses with a duration of 3 sec., then maintained contact for 7 min.
IL
The contact is potential-free, a 230 V power connection of the battery charger is available.
Charging current (in % of rated current)
IdN Rated battery current The curve of the Wa characteristic is determined by points 1), 2) and 3):
Electrolyte circulation:
Z M
If the battery remains attached to the charger at the end of the charging time (T3), there will follow an 8 minute trickle charge every 8 hours and after 24 hours a one-off compensation charge lasting 2 hours.
The charger has an option for controlling an electrolyte circulation pump. Observe the respective manufacturer’s guidelines! It should only be connected by the manufacturer’s service department.
1)
100 %
IdN
at V = 2.0V/cell
2)
50 %
IdN
at V = 2,4V/cell
3)
25 %
IdN
at V = 2,65V/cell
The Aquamatic and electrolyte circuluation systems are monitored. Any faults are displayed on the front panel.
2,8V
M
The connection of external additional equipment may only be carried out by skilled electricians.
2,4
Z
To attach additional external equipment, contact the manufacturer’s service department.
U
Z 2,2 1)
1,8
Z
T2 T3
2)
0
U, I
3)
2,0
Charging curve / pulse charging:
T1
2,65
2,6
25 50 I / I L dN
75
100%
A controlled thorough acid mixing by means of current pulses is carried out at the end of the recharging phase.
T
1115.GB
- T1 = Battery gassing phase reached. Start of the recharging phase - T2 = Start of the pulse charging phase (1-5 pulses depending on the main charging time) - T = End of battery charge. 3
3
2
Charging electronics
3
Protection / Ambient conditions Protection:
7
13
8
12 11
10
Minimum ambient temperatures: - for storage -20 °C - for operation 0 °C If the charger thaws due to sudden temperature changes, leave the charger for a least 3 hours before switching it on again.
9
The SLT 100 charging electronics monitor and control the charging operation. Progress of the charging operation is shown by the light-emitting diodes (7). An electronic monitoring unit detects the gassing time and determines the optimum recharging time from the charged capacity (Ah balancing). Charging starts automatically with a time delay (approx. 10 sec. to protect the plug contacts) after the battery has been connected to the charger. The control key (12) can be used to cancel operation at any time. The standby (13), charging (7), charging completed (9), and compensation charge (8) conditions are indicated by the LEDs (13,7,9,8). An automatic safety cut-out is provided, when the gassing voltage has not been reached within an initial charging phase of 12 hours.
Z
IP 22
Ambient conditions: The charger is self-cooled and is designed for a max. ambient temperature of 40 °C and a max. relative humidity of 80 %.
M
The charger must only be stored in enclosed areas. Operation of the battery charger is only permitted in spaces specially provided for this purpose.
4
Identification label, e.g. E230 G24/50 SLT 100 (see “Sample Data Plate” on page 18)
Z
The identification label is located on the rear wall of the unit. E 230 G 24 / 50
B SLT 100
D = 3-phase curr E = Alternating curr Mains voltage (V) Charging rectifier Initial charging voltage (V) Initial charging current (A) Battery load
The automatic safety cutout is displayed by the yellow warning display LED (11) (flashing code): 3x / interval / 3x. If the transformer overheats, a warning is indicated (11) (flashing code: 4x / interval / 4x). As soon as the transformer temperature is in the permissible range again, charging will be continued and the LED goes off.
1115.GB
Optimum battery charging requires adaptation to the mains supply. The charging electronics are zero-voltage proof, i.e. no malfunctions are possible as a result of mains failures, as all times are stored and charging will recommence at the point the failure had occurred.
4
C
Transportation and Commissioning
1
Transporting the charger
F
Always wear solid leather safety boots and gloves when transporting and assembling the charger.
Charging cable connection:
Before starting the charger make sure it is complete and in satisfactory working order.
The charging cable connections with strain relief can be accessed when the yellow panel is opened.
2
Charger Assembly
F
The battery charger must not be operated outdoors.
M
Fire hazard Flammable materials must not be located in the immediate vicinity of the battery charger. This includes transport and packaging material delivered with the unit. - No flammable materials must be located within 2.5 metres of the battery charger
3
The SLT 100 charger is supplied with a charging cable.
M
F
It is forbidden to store food in the vicinity of battery chargers.
Z
The VDE 0510 safety regulations must be observed. Operations to be carried out before assembly or installation of the battery charger
1115.GB
Z Z
Use only the charging cables provided by the manufacturer. Mains connection:
M
All operations involving the opening of the charger must be performed solely by trained and authorized electricians.
F
Remove the battery and mains plugs before opening the charger. The mains voltage must correspond with the mains voltage indicated on the identification label. The identification label is located on the rear wall of the unit.
Choose the assembly location so that: - There is sufficient ventilation. - The flow of cooling air through the charger is not restricted. It must not be installed close to radiators or similar heat sources. - No flammable gases or dust mixtures can penetrate inside the charger. - The charger is placed only on a solid and secure surface. The surface must not consist of flammable material.
Starting up the charger
M
Fuse protection of the mains cable to the battery charger is the responsibility of the customer. The fuse must have a delayaction release characteristic. Where automatic cut-outs are used, they must have a D, S or K rating (for the rated current consumption of the charger see data plate). To ensure adequate selectivity, the backup fuse should at least be 10 % above the current consumption of the charger. The charger must be protected against excessive contact voltage in accordance with the regulations of the local electricity provider.
Procedure - Remove packaging material (film or cardboard). - If the battery charger was delivered on a transport pallet, lift the battery charger from the transport pallet This does not apply to pallets on which the battery charger is permanently mounted. These pallets have a fireproof base. - Packaging material is to be disposed of correctly. In addition to the restrictions listed in the operating instructions, national requirements must be observed when choosing the place of installation.
5
D
Battery - Servicing, recharging, replacement
1
Safety regulations governing handling of lead-acid batteries
the
Maintenance personnel: Recharging, servicing and replacing of batteries must only be performed by qualified personnel. The instructions contained in this operating manual, and the instructions as prepared by the battery supplier must be observed, when performing the above operations.
F
Metal watch bracelets, bracelets and necklaces must not be worn when handling batteries!
F
Batteries contain dissolved acid, which is toxic and caustic. For this reason protective clothing and goggles must be worn whenever work is undertaken on batteries. Avoid physical contact with battery acid. If clothing, skin or eyes accidentally come into contact with battery acid, liberally rinse the affected parts with clean water. If it has come into contact with the skin or eyes, seek medical attention. Spilled battery acid should be neutralised immediately with plenty of water.
Fire protection measures: Smoking and open flames are not permitted when handling batteries. There must be no flammable substances within at least 2.5 metres and no equipment capable of creating sparks (e.g. machine tools) within at least a 1 metre radius of the truck when it is parked for battery recharging. It is forbidden to operate devices with a high surface temperature (e.g. soldering irons, heater blowers, etc.). Place the charger only on a solid and secure surface.
M F
The surface must not consist of flammable material. Charging batteries leads to the generation of explosive gases. Sufficient ventilation must be provided during charging and at least for one hour after charging has been completed. The room must be ventilated. Check the ventilation system each time before you charge. Fire fighting equipment must be held ready.
M
Parts that can be sucked in due to the suction of the ventilation fans must not be stored in the vicinity of the battery charger. Clogged ventilation slits cause overheating and fire hazard.
F
Do not use water to cool overheated battery chargers.
1115.GB
Battery servicing: The battery cell screw caps must be kept dry and clean. Terminals and cable shoes must be clean, lightly greased with pole grease and must be securely tightened.
6
E
Operation
1
Safety regulations relating operation of battery chargers
to
the
Charger assignment: The charging procedures, or charging characteristics, as well as the charging equipment must be adapted to the operating conditions and technical data of the batteries.
To ensure the safety of a battery charger, the equipment (charger, cables, battery) must be in good working order. Operation must be in such a way that no danger is posed to persons.
F
Battery charging: The connector must only be disconnected from the socket after the battery charger has been switched off. The top of the battery cells must be exposed during recharging to ensure adequate ventilation. Do not rest any metal objects on the batteries.
Check the insulation before using the charging cables and connectors. Faults and defects must be rectified immediately by trained personnel (see “Safety instructions to be observed during servicing” on page 11). The following items are taken from the legal requirements and guidelines of German and international associations and organizations. Ventilation: Battery chargers must be set up so that they are not exposed to charging gases and electrolytic mist.
Z M
Note the regulations.
battery
manufacturer’s
Do not exceed the temperature limits stipulated by the battery supplier. This applies also to any heating that may occur as the battery is recharged.
Chargers and batteries must therefore be housed in separate locations wherever possible. If this is not possible, adequate natural and artificial ventilation must be provided to ensure that the gas mixture generated during charging will lose its explosiveness. Functional test: When commissioning new charging equipment, and thereafter at adequate intervals, checks must be performed to ensure correct operation of the battery charger, and especially correct functioning of automatic charging switches and measurement instrument display. At the start of charging, the amperage and voltage must be checked in order to detect any irregularities in the patterns of the battery or charging equipment. Mains supply: If, in the event of mains voltage fluctuations lasting over a long period of time, the output voltage changes, the battery chargers must be readjusted ensuring that the admissible limits as indicated by the battery supplier are observed (e.g. final charging current in the case of lead batteries). Short-time mains voltage fluctuations may be ignored.
1115.GB
Z
7
2
Description of the operating controls and indicating elements
2
1
Item
Operating control / indicating element
1
“Standby” LED (green)
2
“Charging” LED (yellow)
3
Control key
4
3
5
6
7
Function
t lights up when the battery charger is ready for operation t indicates the charging process t The control key has the following functions: - Stop / Continue charging (break function) - Manual equilising charge - Charging state indicator
4
LED ”Compensation charge”
t indicates the equilising charge
5
LED “Warning messages” (yellow)
t Indicates faults that affect charging, via a flashing code.
6
7
LED “Service messages” (red)
“Charging completed” LED (green)
Flashing pulses: Meaning: 2 Incorrect battery voltage 3
Safety charge exceeded (Main charging time or recharging time in case of pulse charging)
4
Excess temperature
5
Mains failure (is only indicated when the charging state indicator is queried)
6
Warning requested by the optional board. The exact error is indicated on the optional board.
t Indicates problems, via a flashing code, that can only be rectified by repair work
Flashing pulses: Meaning: 2
Charging switch or current measurement defective
3
Voltage coding/setting incorrect
4
Service message requested by the options board. The exact error is indicated on the optional board.
t Charging complete, battery is fully charged. o = Optional equipment 1115.GB
t = Standard equipment
8
3
Commissioning the battery charger
3.1
Connecting the charger
M
When connecting the charger, make sure the contact of the charging cable is secure. A poor contact, for instance at the charging connection, can result in constant charging current fluctuations which will affect the charging electronics and show an incorrect charging current display.
3.2
All LED displays go out. When the mains supply is restored the LEDs display the previous condition. The battery charge continues. The stored charging indication, however, will be lost, when a mains failure occurs without a battery being connected. Low voltage: Dropping below the admissible charging current, for instance as a result of low mains voltage, requires longer charging periods or can result in insufficient charging (warning message).
Starting the charging operation When the mains plug is connected, the green “Standby” LED (1) lights up.
3.5
Gassing voltage: If the battery does not reach the gassing voltage within 12 hours, the safety system interrupts the charging operation. The yellow warning LED (5) flashes (3x / interval / 3x). Disconnect the battery from the battery charger and check it.
The battery charger automatically switches on when the charger and the battery are connected. The first yellow LED (2) on the charge display lights up.
Z
Charging is delayed by approx. 5 to 7 seconds in order to prevent charging connector sparking.
Battery voltage: In the event of battery overvoltage or undervoltage, the charge switch will not start up charging. The yellow warning LED (5) flashes (2x / interval / 2x). Observe a short pause, until the battery voltage is within the expected range. Check the voltage class of the battery, if necessary.
Charging will not start, as long as the battery voltage is outside the expected range. 3.3
Battery charging sequence Charging is indicated by the ascending yellow “Charge” LED's (2) on the charge indicator.
Transformer overheating: A sensor interrupts charging in the event of excessive transformer temperature. The yellow warning LED (5) flashes (4x / interval / 4x). When the transformer cools down to the permissible temperature, the error indication goes off and charging is continued.
When the battery is fully charged, the green “Charging completed” LED (7) lights up. The battery charger automatically stops charging. Trickle charging: When the battery remains connected, every 8 hours, following the completion of the charging operation, a trickle charge is initiated lasting for 8 minutes. The yellow LEDs (2) light up. The green LED (7) for “Charging complete” goes off during the trickle charge phase.
Z 3.4
The battery charger automatically terminates charging when the charging time has elapsed. This process is repeated for as long as the battery is connected to the charger. Mains supply
Charging switch error: The red “Service message” LED (6) flashes. Disconnect the battery from the mains, then restart the charging operation. Check the battery assignment and adjust if necessary. Otherwise notify the manufacturer’s authorised customer service department and withdraw the charger from use.
Z
The operating state “Charging completed” (7) can only be cancelled, when the battery connector is removed from the charging socket. This will prevent unintentional double chargings.
1115.GB
Mains failure: If the battery is connected, a mains failure will stop the time basis of the charging switch and store the position of the charging program.
Fault indication (safety cut-out)
9
3.6
Manual charging interruption
M
The battery charger must only be switched off using the control key (3) if charging is to be interrupted manually. This procedure will avoid malfunctions and the charging connector cannot be damaged by sparking.
3.8
The battery charger has a compensation charge” function.
Z
If charging has been interrupted with the control key (3) it can be continued by pressing the key (3) again provided the battery has not been disconnected. 3.7
“manual
Compensation charging should be carried out regularly (1x a week) in order to compensate the charge differences between the individual cells. When the compensation charge is complete, the recharging time is increased on a single occasion by 2 hours. When you press the control key (3) for 10 sec., prior to connecting the battery, the compensation charge function is activated once for the following charging operation. The “Equilising charge” LED (4) lights up.
Boosting charge - Start the charging operation by connecting the battery requiring recharging (mains connector switched on). - The yellow “Charging” LEDs (2) light up when battery charging is in progress. - When the battery is fully charged, the green “Charging complete” LED (7) lights up. The battery and charging cable can be disconnected. - If you wish to disconnect the battery from the battery charger while it is “half-full”, first press the control key (3) (see “Manual charging interruption” on page 10).
Manual Compensation Charge
If the battery is not connected within 2.5 min., the “Equilising charge” function is deleted. 3.9
Automatic equilising charge function If the battery charger remains connected to the battery for more than 24 hours after charging operation is completed (weekend), the compensation charge is carried out automatically for 2 hours. The “Equilising charge” LED (4) lights up when the automatic equilising charge function is carried out.
Z
When applying a manual compensation charge (see “Manual Compensation Charge” on page 10), automatic compensation charge will not be performed for the following charging operation.
4
Charging state indicator
Z
If no battery is connected, the final charging state of the last charging operation can be viewed on the display. Press down on the control key (3) for a maximum of 2 seconds and then release it. The final condition of the last charge is displayed.
1115.GB
The display goes out either automatically or by briefly pressing the control key (3).
10
F
Charger Maintenance
1
Operational safety and environmental protection The SLT 100 charger is maintenance-free. It does not need to be cleaned regularly.
F
Any modification to the SLT 100 charger, in particular its safety mechanisms, is strictly prohibited.
M
Only original spare parts have been passed by our quality assurance service. In order to ensure safe and reliable operation, exclusively use spare parts supplied by the manufacturer. Old parts, oils and fuels must be disposed of in accordance with the applicable environmental protection regulations.
2
Safety instructions to be observed during servicing
5
Fuses
Z 5.1
Small battery charger
The fuses used depend on the model.
14 F3
15 F2
Maintenance personnel: Maintenance and repair of SLT 100 chargers must only be carried out by qualified personnel. The manufacturer’s service department has field technicians specially trained for these tasks. 3
Cleaning operations
F
Disconnect the unit from the mains before starting cleaning work.
16 F1
- Primary: F2 fuse (15) - Secondary: F1 fuse (16) - electrolyte circulation pump/ Aquamatik (o): F3 fuse (14)
Do not use flammable liquids to clean the charger. Working on the SLT 100 charger
F
Operations of any kind on the battery chargers must only be performed by qualified electricians. Prior to the commencement of any work on a battery charger, all required measures must be taken to prevent electric shocks.
M
Version and rated value of the fuses must not be changed. Refer to label showing the rated values.
1115.GB
4
11
5.2
Large battery charger
17 F3 18 F2
19 F12
3 F1
- Primary: F2 control fuse contactors (18) Secondary: F1 fuse (3) electrolyte circulation pump/ Aquamatik (o): F3 fuse (17) - D400V devices conductor: F12 fuse (19)
neutral
Version and rated value of the fuses must not be changed. Refer to label showing the rated values.
1115.GB
M
without
12
G
Internal electrolyte stirrer (EUW)
1
Correct use and application
Z
See also Chapter A ,“Correct use and application”.
During charging the electrolyte circulation pump is switched on for approx. 2.5 min. and off for approx. 7 min.
The battery charging device with a built-in pump and hose system is suitable only for batteries with electrolyte stirring.
Charging is recognised by the charge switch insofar as it:
3
- Detects the connected battery. - Detects a charge current.
User obligations: The user must make sure that only batteries with electrolyte stirring or with a hose system are permitted to be charged.
M
The pump must not be operated without counterpressure.
2
Charger Assembly
F
The battery charger must not be operated outdoors.
During the pulse charge phase there is no electrolyte circulation. The pump is switched off. 4
It is forbidden to store food in the vicinity of battery chargers.
Z
The VDE 0510 safety regulations must be observed.
Internal electrolyte circulation: Internal electrolyte stirring is automatically switched on at the beginning of the charging procedure. Electrolyte stirring mixes the acid before the gassing phase.
Z
In the main charging phase, the battery’s energy consumption increases so that the recharging phase can be shortened. The internal charging electronics detect via the sensor that the pump is switched on and reduce the recharging time. This shortens the total charging time at the same battery charge level.
1115.GB
F
Description of the device During the main charging phase, batteries without electrolyte circulation generate acid layers. The charging factor is set according to the charging device.
Choose the assembly location so that: - There is sufficient ventilation. - The flow of cooling air through the charger is not restricted. It must not be installed close to radiators or similar heat sources. - No flammable gases or dust mixtures can penetrate inside the charger. - The charger is placed only on a solid and secure surface. The surface must not consist of flammable material. - The bottom of the charger is approx. 0.5 m above the battery to be charged.
Electrolyte circulation (EUW)
13
The internal electrolye stirrer consists of the following parts: - An additional switch contact to switch on the pump; - A sensor to switch or adapt the charging factor; - A membrane pump with an air filter and air pressure monitor. The pump delivers a constant pressure of 100 mbar and overcomes an acid level of ca. 80 cm in the main charging phase; - A connecting hose with an air plug connection in the pilot contacts of the charging connector. Air pressure monitor:
1
2
3
4
If the system is working correctly and the recharging time is reduced, the green LED (1) is lit on the control board.
Z
A defective hose system can be identified via the air pressure monitor. Service message flashes: (4x / break / 4x). Air volume flow: The air volume flow can be adjusted within the range of 2 l/min to 12 l/min. It is independent of the hose system and thus of the number of cells. The air volume flow can be set according to requirements with the switch (3): Switch setting top = 1
Volume in l/min
Volume in l/h
0000
2
120
1000
4
240
0100
6
360
0010
8
480
0001
10
600
1111
12
720
5 6
Item
Description
1
Green LED
2
Fuse (1 AT)
3
Switch
4
Cable to the charging switch Filter
6
Air hose
1115.GB
5
14
Figure: Large battery charger
5
Commissioning
Z
For transport and assembly see chapter C on page 5. For chargers with electrolyte circulation the air volume flow must also be adapted to the battery, see "Air volume flow presetting” on page 15.
5.1
4
Air volume flow presetting
5
Switch (3) has the following factory settings for all SLT 100 large battery chargers:
6
6
Voltage class in V
Volume in l/min
24
4
48
8
80
12
Figure: Small battery charger 6
Maintenance of the filter
4
5
The blue suction filter (5) on the bottom of the pump must be checked for soiling at regular intervals. In strongly dusty areas, it is to be replaced every 3 months, otherwise at least every 6 months. To replace the suction filter (5) tip the blue insertion sleeve to the side and replace the polishing cotton.
Item 4
Description Cable to the charging switch Filter
6
Air hose
1115.GB
5
15
7
Aid for malfunctions
F
Faults may only be rectified by skilled electricians in compliance with safety regulations. Remove the battery and mains plugs before opening the charger.
Z
7.2
2
Charging
time
is
not
Possible causes: - The hose system is defective (see “Air pressure monitor” on page 14). - Filter (5) is clogged.
This chapter enables the user to localize and rectify basic faults or the results of incorrect operation himself.
1
Malfunction: reduced
Elimination measures: - Replace the hose system. - Replace filter (5).
3 7.3
Malfunction: Loud pump noises Possible causes:
4
- The hose system is defective (see “Air pressure monitor” on page 14). - Filter (5) is clogged.
5
Elimination measures:
6
- Replace the hose system. - Replace filter (5).
Z 7.1
Malfunction: Pump does not react during charging. Possible causes: - The cables are not connected tightly enough. - Fuse (2) faulty.
If the charger cannot be restored to operational status after carrying out the remedial operations, contact the manufacturer’s service department. Further remedial work should only be carried out by the manufacturer’s trained service personnel. The manufacturer’s service department has field technicians specially trained for these tasks.
Elimination measures:
1115.GB
- Connect the cables tightly. - Check fuse (2) and replace if necessary (1 AT).
16
H
“LIS” charge information system (o) Chargers with the charge information system (LIS) store the data from the last 200 charges. The curves for the individual charges can be viewed on a PC. The necessary software is supplied on a CD with the charge information system. For information on operating the charge information system, software installation instructions and PC connection to the charger, see “Charge information system” operating instructions.
1115.GB
Z
17
I
Sample data plate
1
2
3
4
5
8
9
6 7 10 11
Designation
Item
Designation
1
Series
7
No. of cells/type
2
Type
8
Protection class
3
Serial No.
9
Output
4
Year of manufacture
10
Battery capacity
5
Fuse
11
Manufacturer
6
Input
1115.GB
Item
18