Preview only show first 10 pages with watermark. For full document please download

Sm-6474a

   EMBED


Share

Transcript

IUNION SWITCH & SIGNAL l[ml 645 Russell Street , Batesburg, SC 29006 Service Manual 6474-A PD-1 Style Vital Plug-In Relays Field Maintenance June, 1992 © 1992, Union Switch & Signal Inc. Printed in U.S.A. .. I An ANSALDOI Affiliated Company UNION SWITCH & SIGNAL CONTENTS PAGE NO. SECTION I 1.1 1. 2 1. 3 1.4 1. 5 1.6 1.7 1.8 1. 9 1.10 1.10.1 1.10.2 1.11 1.12 1.13 1.14 1.14 .1 1.14. 2 1.15 II 2.1 2.2 2.3 2.4 2.5 2.6 2.6.l 2.6.2 2.7 2.8 2.9 III INTRODUCTION ....• ·. . . • . . . . . . • . . . ~ ....••.•...••.••.•• 1-1 GENER.U DESCRIPTION •••.••...•.....•.•••.•••••..•.••. 1-2 PD-1 RELAY PRODUCT FEATURES •..•....•.•••.•••.•••...•• 1-2 PD-1 RELAY MOUNTING OPTIONS •....•.••.•••••.•••...•••• 1-3 MAGNETIC CIRCUIT ••••..•.•.•.•......•.••••••.•.....••• 1-3 CONTACTS .•..••.••...•.•••.•••••....••.••••••..••..••• 1-3 COVER ..•..•••..••••.•..••..•.•.•....••••.•••.•.•.•••• 1-3 FRONT TEST PO INT . . . . . . . . . . . . . . . . . . . . . . • . . . • . . • . . . • • • • 1-3 RELAY VOLTAGE ••••••.••..•••.••.••..•••.••••••.....•.• 1-3 PLUG COUPLER • • • • • . . • • • • • • • • . • . . • . . • . • • • . . • . . • • . . . . . • • 1-3 Rear Service Plug Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4 Front Service Plug Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 INDEXING . . . • . • • • • • • • . • . • • . • • • . • . . • • . . • . . • . • • • . . • • • • 1- 6 TERMINATION ••.••••••••••••.••..•.••.••••••.••....••• 1-7 TERMINATION NOMENCLATURE .••••••..••••....••.•••..•••. 1-7 PLUG COUPLER MOUNTING PRRANGEMENT .•.•••••..••..••.•.• 1-8 Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8 Shelf Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 TOOLS A.ND ACCESSORIES •.•...•...•..•.••.•••...•....••• 1-9 FUNCTIONAL DESCRIPTION INTRODUCTION ..•.•..•...•••....•.....••.•..•••...•.••• DC VITAL RELAY GENERAL OPERATION . . . . . . • . . • . • • . . . . • . . . DC BIASED VITAL RELAYS ••••.•...••...••••.••.•..•.•••• LIGHT OL"'T RELAYS .••.••.••..•.....•.••..•......•.•.•.• MAGNETIC STICK RELAYS .....••••.•....•••.•...••.•••.• MAGNETIC P'.EAVY-DUTY AND HEAVY DUTY CONTACTS • . . . . • • . . . • . • . . • • . . . . . . . . . • . . • • . . • . . • . • . • • 2 -1 2-1 2-1 2-5 2-6 2-7 Magnetic Blowout Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Heavy-Duty Contact Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 SLOW PICKUP AL'ID SLOW RELEASE (DROPAWAY) RELAYS •......•........•••••..••.•••••••.••...••••• 2-8 SWITCH OVERLAY RELAYS . . . . • • • . . . . . . • . • • . . . . . . . . . • • • . 2-9 FLASHER RELAYS ....•..••.•..•.........•••..••..••••• 2-10 INSPECTION AND TEST 3.4 3.5 3.6 INTRODUCTION ••..•.••.••.••..••..•••••••••••••••••••• 3-1 RECOMMENDED TEST EQUIPME!,i"T ••..........••••••••••••.•• 3-1 FIELD INSPECTION ...•.•....••.••.•..•••••.•..•••••••• 3-1 Static Insoection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Dynamic !nspec tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 TEST PERFORMANCE . • . . . . • . . . . . . . . . . . . . . . • • • . • • • . • • • • . • . 3 -2 DC RELAY TEST STA...'J'D •......•••...•..•.••.•.•••••.•..• 3-2 TESTS . • . . . . . . . . . . • . . . . . . • . • • . . . . • • . • • . . . . • . • . . • . . . • . 3-8 3.6.1 Biased Relay Perfor.ilance Tests . . . . . . . . . . . . . . . . . . . . . . . 3-8 3.1 3.2 3.3 3.3.1 3.3.2 _( GENERAL INFORMATION A-1 SM6474-A UNION SWITCH & SIGNAL CONTENTS (Cont'd) SECTION 3.6.1.1 3.6.1.2 3.6.1.3 3.6.2 3.6.2.1 3.6.2.2 3.6.2.3 3. 6. 3 3.6.3.1 3.6.3.2 3.6.3.3 3.6.4 3.6.4.1 3.6.4.2 3.6.4.3 3.6.5 3.6.5.1 3.6.5.2 3.6.6 3.6.6.1 3.6.6.2 3.6.7 3.6.7.1 3.6.7.2 PAGE NO. Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Biased Relay Test Stand Procedure . . . . . . . . . . . . . . . . . . . . 3-9 Slow Release (Drop-Away) Relay Test . . . . . . . . . . . . . . . . . 3-11 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 Slow Release Test With Test Stand . . . . . . . . . . . . . . . . . . . 3-11 Slow Release Test Without Test Stand . . . . . . . . . . . . . . . . 3-13 Slow Pick-Up Relay Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Slow Pick-Up Test With Test Stand . . . . . . . . . . . . . . . . . . . 3-14 Slow Pick-Up Test Without Test Stand . . . . . . . . . . . . . . . . 3-14 Magnetic Stick Relay Test .... ~ . . . . . . . . . . . . . . . . . . . . . . 3-15 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 Magn~tic Stick Relay Test With Test Stand . . . . . . . . . . . 3-15 Magnetic Stick Relay Test Without Test Stand ......... 3-16 Switch Overload Relay Test . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 OS Relay Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 7 Flasher Relay Performance Test . . . . . . . . . . . . . . . . . . . . . . 3-18 Recommended Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 -19 Flasher Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19 Lightout Relay Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20 Lightout Relay Test Procedure . . . . . . . . . . . . . . . . . . . . . . . 3-10 APPENDIX APPLICATION INFORMATION SHEETS A. l INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 A. 2 TYPES OF PD-1 RELAYS ••••••••••••••••••••••••••••••••• A-1 A.3 ABBREVIATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 LIST OF TABLES PAGE NO. TABLE NO 3-1 A-1 DC Relay Test Stand, Controls and Indicators . . . . . . . . . . 3-5 Ordinary Acting, Biased Neutral, Low Voltage PD-1 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3 A-2 SM6474-A UNION SWITCH & SIGNAL LIST OF ILLUSTRATIONS fIGURE NO. 1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 3-lA 3-2 3-3 3-4 3-5 3-6 3-7 3-8 PAGE NO. PD-1 Vital Relay, With Mounting Bracket .............. 1-1 PD-1 Plug Couplers ................................... 1-4 PD-1 Front Service Plug Couplers ..................... 1-5 Rear Service Plug Coupler Indexing ................... 1-6 Plug Connectors and Plug Coupler Tabs ................ 1-7 Rear Service Plug Coupler Nomenclature ............... 1-7 Rear Service Plug Couplers, Typical Mounting .......... 1-8 Front Service Plug Couplers, Typical Mounting ......... 1-8 Simplified Vital Relay Arrangement ................... 2-2 PD-1 Relay Arrangement ............................... 2-2 Biased Relay, No Voltage Applied ..................... 2-3 Biased Relay, Voltage of Normal Polarity Applied ...... 2-4 Biased Relay, Voltage of Reversed Polarity Applied .... 2-4 AC Operated Relay Coil ............................... 2-5 Magnetic Stick Relay, Normal Polarity Voltage Applied ............................................. 2-6 Magnetic Stick Relay, Reversed Polarity Voltage Applied ............................................ 2-7 Typical Slow Release Snubbing Circuit ................ 2-9 Flasher Relay Driver Unit ........................... 2-11 Biased Relay Test Setup .............................. 3-3 Plug Coupler Adapter ................................. 3-3 DC Relay Test Stand Controls and Indicators ........... 3-5 Basic Contact Indicators Configuration ............... 3-7 Operating Time Measurement, Test Setup .............. 3-12 Time Interval Meter, US&S 911A, Front Panel .......... 3-12 Switch Overload Relay, Test Setup ................... 3-18 Flasher Relay, Test Setup ........................... 3-19 Light Out Relay, Test Setup ......................... 3-20 ( A-3 SM6474-A UNION SWITCH & SIGNAL SECTION I ( GENERAL INFORMATION 1.1 INTRODUCTION This service manual contains field maintenance data for PD-1 Vital Relays (Figure 1-1). The purpose of the manual is to provide signal maintenance personnel with the data needed to understand PD-1 relay operation and how to perform field maintenance inspection and testing of the relays. Vital relay scheduled maintenance consists of periodic inspections and tests. The inspections and tests verify the relays are performing within the minimum In-Service Application Limits as specified on the Application Information Sheets for the relays. These sheets are contained in the Appendix at the rear of this manual. Relays not meeting the In-Service Application Limits must be replaced. Relays removed from service must be shopped for further testing and repair. ( Figure 1-1. PD-1 Vital Relay, With Mounting Bracket 1-1 SM6474-A UNION SWITCH & SIGNAL 1.2 GENERAL DESCRIPTION The PD-1 vital relays described in this manual are de vital relays of the following types: a. Biased Neutral, including the following: 1. Ordinary Acting with Low Voltage contacts 2. Ordinary Acting with High Voltage contacts 3. Slow Release and Slow Pickup 4. Ordinary Acting with Magnetic Blowout contacts 5. Light Out b. Magnetic Stick c. Switch Overload Stick d. Flasher All PD-1 Vital Relay types are plug-in relays designed for railroad and transit signal applications and manufactured to meet AAR requirements for vital s;i:gnal relays:. 1.3 PD-1 RELAY PRODUCT FEATURES Each PD-1 Vital Relay possesses the following product features: a. Mounting with either rear or front-service plug couplers. b. Wire connectors with commercially available plug connectors (Faston) for easy wiring. c. Wide selection of coil resistance and contact configurations d. Contact protection by a transparent dust cover for visual inspection. e. Contacts that can be easily replaced when necessary. f. Relay that locks securely in its working position. g. Coded index pins to assure correct relay-type insertion. h. Test point accessible from the front of the relay. i. Plug coupler that accepts two plug connectors per contact point . .. .. · ·_... ~ .. : ~ 1-2 - :· . ' .._ SM6474-A ( UNION SWITCH & SIGNAL 1.4 PD-1 RELAY MOUNTING OPTIONS PD-1 relays satisfy the special needs of vital circuits in railroad and transit signal systems. PD-1 plug couplers are available for both front and rear service. This enables the PD-1 relays to be mounted in relay racks where rear service is possible, or on a· wall or shelf where front service is necessary. For shelf mounting, a support bracket is combined with a front service plug coupler. All wires are terminated on the plug coupler by removable solderless plug connectors. The plug connectors are available with or without a locking feature. 1.5 MAGNETIC CIRCUIT Magnetic circuits are constructed of non-aging material. The magnetic air gap is not disturbed when the coil or contacts are removed 1.6 CONTACTS Contact fingers and springs are manufactured of spring-tempered phosphore bronze. Individual contacts are removable and easily replaced. Movement of the armature operates the heel spring and assures proper contact wiping. Plug connectors are tin-plated. Contact material for low voltage front contacts is silver carbon. Heel and back contacts are made from fine silver. Heavy duty contacts are silver-to-silver. ( . 1.7 " COVER ' ' ,.Y A cover of transparent molded non-yellowing material houses the relay contacts and armature structure. The cover is sealed to its frame by pressure against a gasket, providing a tight dust-proof moisture-protected assembly. 1.8 FRONT TEST POINT This testing facility is in series with the coil control circuit to permit deenergization of the relay while in service without disturbing the relay or wiring. The test point permits measuring of the relay coil current by insertion of a PD-1 current test probe. 1.9 RELAY VOLTAGE PD-1 relays are manufactured for different input or control voltages. For specific voltage values refer to the relay's Application Information Sheet contained in the Appendix at the rear of this manual. Higher voltages can be used, but the maximum dissipating power of the coil should not exceed lOW. 1.10 ( PLUG COUPLER Plug couplers must be ordered separately. As stated, two types of plug couplers are available: rear service and front service (Figure 1-2) . 1-3 SM6474-A UNION SWITCH & SIGNAL 1.10 .1 Rear Service Plug Coupler Rear service plug couplers are permanently mounted onto a relay rack. The wires are attached to the plug coupler with plug connectors from the rear. FRONT SERVICE PLUG COUPLER REAR SERVICE PLUG COUPLER Figure 1-2. PD-1 Plug Couplers 1-4 SM6474-A UNION SWITCH & SIGNAL Front Service Plug Coupler 1.10. 2 The PD-1 Relay with a front service plug coupler lFigure 1-3} is supported by two rods. These rods are secured to the shelf or wall. When in its working position, the relay is secured by two nuts. For service, the two nuts are removed and the relay is pulled forward on the support rods until the plug coupler contacts are accessible. The design offers maximum space utilization, since relays can be mounted on a wall or on both sides of a relay rack I SHELF MOUNTING I SUPPORT ROD PD·1 RELAY I The lower diagram shows the PD·1 relay in the test position .<........ -, •••••, ........ ·.••. ·:--....-· ••·:..··· ... • ........ -: ....,:,-.:; • .\+." •. !-1:A. ( Figure 1-3. PD-1 Front Service Plug Couplers 1-5 SM6474-A UNION SWITCH & SIGNAL 1.11 INDEXING PD-1 vital relays and plug couplers are supplied with indexing (Figure 1-4). A code plate, unique to the relay, is furnished with the relay independent of type-of plug coupler for rear service (B, Figure 1-2) . REAR SERVICE PLUG COUPLER ADAPTER \ PD·1 RELAY REAR SERVICE PLUG COUPLER ADAPTER CODEPLATE \ Figure 1-4. Rear Service Plug Coupler Indexing 1-6 SM6474·A UNION SWITCH & SIGNAL 1.12 TERMINATION ( Plug coupler wire contacts can be terminated by solder connection or by plug (Faston) connectors with or without a locking feature (Figure 1-5). The solderless connectors with insulated sleeves are normally used. POSITIVE LOCK CONNECTOR STANDARD PLUG CONNECTOR TABS AT THE PLUG CONNECTOR Figure 1-5.Plug Connectors and Plug Coupler Tabs 1.13. TERMINATION NOMENCLATURE Rear service plug couplers are marked with nomenclature as shown in Figure 1-6. Plug couplers are equipped with 20 (2x10) double blade contacts {Tabs at the Plug Coupler, Figure 1-5) for easy termination. 0 COIL CONNECTORS 1--11--l&F 1--16 1--1& 1--14F 1--14 +1--1 5FI--I 1--12 1--12e 161--1 1s1--1 Hl--1 Bl--1 Fl--1 0 Figure 1-6. Rear Service Plug Coupler Nomenclature 1-7 SM6474-A UNION SWITCH & SIGNAL 1.14 PLUG COUPLER MOUNTING ARRANGEMENTS 1.14.1 Rack Mounting PD-1 relays are secured in their plug couplers and can be easily removed. Plug couplers are mounted onto relay racks in signal cases central instrument houses, and relay rooms. Typical mounting arrangements are shown in Figures 1-7 and 1-8. ,____....__ 1-Y.t (44.45 mm) . ..I Figure 1-7. Rear Service Plug Couplers, Typical Mounting I I l 1/w I I 1/w I I - - - , 2 - 724 - - - . ' 1/w ' --,14r- ' I I I I I I I 1 L_ _ Figure 1-8. Front Service Plug Coupler, Typical Mounting 1-8 SM6474-A UNION SWITCH & SIGNAL 1.14. 2 ( Shelf Mounting For wall and shelf mounting of P0-1 relays, a shock mounting base is available. For such mounting arrangements, a front service plug coupler must be used, or the wires can be connected directly to the relay terminals with plug connectors. 1.15 TOOLS AND ACCESSORIES A broad range of tools and accessories are available, including test plugs, plug connectors, crimping tools,etc. Also available is a relay test stand. The relay test stand facilitates testing of individual de relays out of the relay racks. The relay test stand is sufficiently portable for use in the field or in the shop. ( 1-9 SM6474-A UNION SWITCH & SIGNAL This page intentionally left blank 1-10 SM6474-A UNION SWITCH & SIGNAL SECTION II ( FUNCTIONAL DESCRIPTION 2.1 INTRODUCTION This section contains functional descriptions of each type of PD-1 vital relay. Description of general operation of the relays is presented first. This is followed by brief descriptions of specific relay types. 2.2 DC VITAL RELAY GENERAL OPERATION Figure 2-1 illustrates the structure of a typical de vital relay. The arrangement shown in Figure 2-1 is a simplified drawing of a vital relay. Figure 2-2 illustrates the PD-1 style of vital relay. The major difference between the two illustrations is the location of the relay's coil and armature. The PD-1 style of vital relay has its coil mounted vertically in the rear of the relay structure and its armature installed on the bottom of the relay structure, as shown in Figure 2-2. The electrical and magnetic operation of most styles of vital relays is the same. 2.3 DC BIASED VITAL RELA VS A biased relay is equipped with a permanent magnet and arranged so that the relay armature picks up only when de current is flowing in the coil in a prescribed direction. The AAR defines a biased relay as: "A relay that will operate to its energized position by current of one polarity only, and will return to its deenergized position when current is removed". The schematic symbol for the biased relay is: SINGLE COIL OR DOUBLE COIL OR .--------------------. +T* ,_ - -- +A I I -A __, I. I I I I I --+ OR +B --+ -- -B I I I I -~B OR -~A * "T" IS A FRONT TESTING CONTACT WHICH IS INTERNALLY WIRED IN SERIES WITH +A 2-1 SM6474-A UNION SWITCH & SIGNAL HINGE SPRING ,/· CORE / POLE PIECE ARMATURE PIVOT SPRING 'f~=~~:::::'.~b=:!:::::::i._~:i=:i~~-- STOP PIN ARMATURE / CONTACT DRIVER BRACKET HINGE BLOCK ··----.........._ ·-i-----~ FRONT CONTACT INSULATED CONTACT DRIVER HEEL CONTACT BACK CONTACT CONTACT BLOCK Figure 2-1. Simplified Vital Relay Arrangement BACK STRAP CONTACT BLOCK FRONT CORE SLUG TOP COVER CODED---'PLATE -11 TAPER PIN CONTACT DRIVER PIVOT SHAFT I ARMATURE / BOTTOM COVER I MAGNET ARMATURE BACK STOP CONTACT DRIVER ARM FACTORY DATA TAG Figure 2-2. PD-1 Relay Arrangement 2-2 SM6474-A UNION SWITCH & SIGNAL NOTE The illustrations in Figures 2-3 through 2-5 are functionally applicable to all styles of vital relays. Remember, however, the physical arrangements can be different. With no current passing through the coil, the permanent magnet is positioned so that its magnetic flux passes through the armature, permanent magnet, pole pieces, and core, as shown in Figure 2-3. This condition holds the armature in the deenergized or dropped position. The high reluctance (magnetic resistance) of the air gap prevents magnetic flux from flowing between the armature and the pole piece extension. Assume that current is applied to the coil circuit, and current flow through the coil is in the direction in which its magnetism opposes the magnetism of the permanent magnet, as shown in Figure 2-4. This condition is comparable to a high reluctance in the path of the permanent magnet flux. The resulting magnetic flux path is through the core, pole piece, pole piece extension, and the armature. As a result, the relay is energized with the armature in the energized or picked position. HINGE SPRING CORE COIL / ,--- POLE PIECE / POLE PIECE EXTENSION ARMATURE PIVOT SPRING ... ___ , CONTACT DRIVER BRACKET HINGE BLOCK ARMATURE ~ PERMANENT MAGNET MAGNETIC FLUX ----~- INSULATED CONTACT DRIVER Figure 2-3. Biased Relay, No Voltage Applied 2-3 SM6474-A UNION SWITCH & SIGNAL The armature remains up as long as the coil is energized. When the coil circuit is opened, the magnetic force opposing the permanent magnet is destroyed. Once more, the flux of the permanent magnet resumes the low reluctance path through the pole piece and armature. Since there is no force to hold the armature up, it drops away from the pole pieces. Assume voltage of the opposite (reverse} polarity is applied to the coil {Figure 2-5}. This creates a magnetic force, which aids the magnetic force of the permanent magnet, and the flux remains through the permanent magnet, armature, and pole pieces. Thus, with vo_ltage of the opposite polarity, the armature is not picked up. I ____ .... _ MAGNETIC FLUX ----- I I I I • ~ I I •.. __ I I .-----' I I • ,----' N s Figure 2-4. Biased Relay, Voltage of Normal Polarity Applied MAGNETIC FLUX (COMBINATION OF BOTH COIL AND • • • • .... • PERMANENT MAGNET FLUXES) I I I I I I I I .. I I I I I __ ------, . \. Figure 2-5. Biased Relay, Voltage of Reverse Polarity Applied 2-4 SM6474-A UNION SWITCH & SIGNAL 2.4 LIGHT OUT RELA VS The PD-1 Light Out Relay is designed for signal light-out detection applications. The relay is energized when the signal lamp being monitored is lit. It is deenergized when the lamp is burnt out. The relay is a biased neutral relay with two coils, that are electrically separate but magnetically coupled. The schematic symbol for the light out relay is: LOR OR N12---4 One of the coils (0.15 or 0.37 ohms) is wired between relay terminals LlO and RlO. Connected between these terminals and in parallel with the relay coil is a diode rectifier. In a signal lighting circuit, the signal's ac voltage is applied through this light out relay coil and rectifier circuit to the signal lamp. When a signal lamp's filament is not open, ac current flows through the 0.15 and 0.37 ohm coil and rectifier circuit. Polarity of the rectifier with respect to the coil must be correct for the relay to operate when the ac voltage is applied. As shown in Figure 2-6, energy is applied to the relay coil during the positive excursions of the ac power source. Being a biased relay, when the coil polarity is correct, the relay energizes. RECTIFIER AC SOURCE Figure 2-6. RELAY COIL AC Operated Relay Coil 2-5 SM6474-A UNION SWITCH & SIGNAL After the relay energizes, a path is completed through a set of front contacts of the Light Out Relay. Through these front contacts, de voltage of the correct polarity is applied to the second coil (350 or 0.086 ohms) through terminals L8 and L9 of the relay. After the relay is energized by ac lamp current flowing through the first coil, energizing of the second coil holds the relay energized. 2.5 MAGNETIC STICK RELAYS The magnetic stick relay is similar in construction and operation to the biased relay. However, the armature is pivoted at its center and uses two permanent magnets; one at each end of the armature. The schematic symbol for the magnetic stick relay is: The design is such that the armature remains in the last operated position with full contact pressure after energy is removed from the relay coil. The relay moves to the alternate position when de voltage of opposite polarity is applied. I I I I I I I ... ... ___,---'_., I I ARMATURE ~ --------------------------· 0 MAGNETIC FLUX -------- CENTER PIVOT N H R NORMAL CONTACT - -+--------...... . . ._ CONTACT DRIVER HEEL CONTACT -.....----------~ REVERSE CONTACT CONTACT BLOCK Figure 2-7. Magnetic Stick Relay, Normal Polarity Voltage Applied 2-6 SM6474-A UNION SWITCH & SIGNAL ( With polarity of the permanent magnets as shown in 2-7, and current flowing in the coil as indicated, the armature rotates counterclockwise. This action pulls up the contact driver, which, in turn, closes the heel and normal contacts. When the polarity of the voltage across the coil is reversed, the resultant magnetic flux, as shown in Figure 2-8, forces the armature to rotate clockwise. This pushes the contact driver down, which, in turn, opens the normal contacts and closes the heel and reverse contacts. I • . I I I I I I I '·--' • • ARMATURE MAGNETIC FLUX ----Ila--- CENTER PIVOT Figure 2-8. Magnetic Stick Relay, Reverse Polarity Voltage Applied 2.6. MAGNETIC HEAVY-DUTY AND HEAVY-DUTY CONTACTS 2.6.1 Magnetic Blowout Relay The biased magnetic blowout relay is similar in structure and operation to the de biased relay. The exception is the use of magnetic blowout heavy duty contacts. Small permanent magnets are affixed to the contact springs, behind and close to the heavy duty tips. The purpose and effect of these magnets is to disperse or blow out an electric arc before it has the chance to grow and burn and otherwise damage the contacts. The coil symbol for the biased magnetic blowout relay is the same as that of the standard biased relay described in paragraph 2.3. The schematic symbol for the magnetic blowout heavy-duty contact is: • OR 2-7 • • SM6474-A UNION SWITCH & SIGNAL This type relay is used in conjunction with other relays to control electric switch machines. 2.6.2 Heavy-Duty Contact Relay The heavy-duty contact relay is a biased relay with heavy-duty contacts. The relay is similar in structure and operation to the de biased relay with the exception of having heavy-duty contacts which can carry loads up to 15 amperes. Standard contacts are designed to carry loads up to 4 amperes. The coil symbol for the heavy-duty contact relay is the same as the biased relay, but its contact symbol is: CJ 2.7 OR l CJ • SLOW PICKUP AND SLOW RELEASE (DROPAWAY) RELAYS The slow pickup and slow release relays are biased relays, having special timing characteristics. Slow pickup and slow release refers to the relative timing of relay action. The desired pickup and release timing characteristics are achieved through the use of RC circuits. The schematic symbols for these relays is: SLOW PICKUP +A SLOW DROPAWAY +A -A OR OR Timing characteristics are changed externally by combinations of coil connections, and snubbing of coil circuits by combinations of rectifiers, capacitors, and resistors (Figure 2-9). As stated on the PD-1 Application Information Sheets for slow pickup and slow release relays, the snubbing components may be external or built into a plug coupler. 2-8 SM6474-A UNION SWITCH & SIGNAL ( + SERIES COIL CONNECTION WITH SHUNT RECTIFIER. -A +A - -B + PICKUP NORMAL DROPAWAY SLOW SERIES COIL CONNECTION WITH RESISTOR AND CAPACITOR SNUB. o-----+A -A - -B PICKUP NORMAL DROPAWAY SLOWER THAN ABOVE. Figure 2-9. Typical Slow Release Snubbing Circuit. 2.8 SWITCH OVERLOAD RELAYS Switch overload relays are used to provide protection from overload currents for de switch machine motors. The operation time for these type relays is inversely proportional to the magnitude and duration of the overload current. The schematic symbol for the overload relay is: ----------------I -A ...... I +A + 0 +B -B s 1H 2H ( I I I 28 I I I I I I I I I I I I I ----------------J 2-9 SM6474-A UNION SWITCH & SIGNAL The switch overload relay is placed in the switch machine motor circuit. The relay is constructed with two coils; an operating winding and a stick winding. The operating winding is wired in series with the switch machine motor. When current is excessive, the operating winding energizes the relay. The relay is held energized by the stick winding, causing deenergization of switch control relays that directly control the motor circuit. The activation time, hence the sensitivity of the overload relay, is determined by a low resistance element connected across the operating winding. The resistance element has a positive temperature coefficient so that a substantial increase in current causes a proportional increase in resistance. During normal current conditions, most of the current passes through the resistance element with little or no current through the operating coil. An increase over the normal current level increases the resistance of the element, causing more current to flow through the operating coil. If the overload persists, the operating coil receives sufficient current to activate the relay armature. 2.9 FLASHER RELAY The PD-1 flasher relay is a biased neutral relay with heavy duty front and back contacts. When the relay is used with an external electronic driver unit (Figure 2-10), it will provide between 41 and 45 flashes per minute when the voltage applied is 8-18V de. The driver unit is assembled in a package that plugs into a standard octal socket. The driver unit contains shop-adjustable controls to set the on-time and off-time of the flasher. The schematic symbol for a flasher relay is: F OR -A ( 2-10 SM6474-A UNION SWITCH & SIGNAL SECTION Ill ( INSPECTION AND TEST 3.1 INTRODUCTION This section contains procedures to be used to periodically inspect and test PD-1 Vital Relays at their field locations. How often each type of vital relay is to be inspected and tested is specified in its Application Information Sheet contained in the Appendix at the rear of this manual. 3.2 RECOMMENDED TEST EQUIPMENT DC Relay Test Stand Source of 120V, 60Hz power 0-72Vdc Power Supplies (2) 0-40Vdc Power Supplies (2) DC Voltmeter DC Ammeter AC Voltmeter AC Ammeter 912B Low Resistance Ohmmeter 911A Time Interval Meter 912A Code Rate Monitor Simpson TS-111 On-Time Meter Test Leads, minimum of 2 sets, color coded (Red and 3.3 Black) FIELD INSPECTION 3.3.1 Static Inspection The following static inspection can be performed with the relay mounted in its operating position, or removed from its plug coupler. Check each inactive relay for the following a. b. c. d. e. f. Abnormally pitted and/or burned contacts Contact misalignment. Corrosion or other contamination of relay parts. Loose parts inside cover. Broken seal . Cracked or broken cover. 3.3.2 Dynamic Inspection With the relay installed in its operating position or in the Relay Test Stand, check the following while operating the relay: .( 3-1 SM6474-A UNION SWITCH & SIGNAL ( HAMETAG RELAY DRIVER FRO PART NO. 75335001 CC DUST COVER ~ FREQ. 43 •2 PPM INPUT 10 ·14 voe LOAD 250 • ADC PIH 1 ·DC INPUT PIN40UTPUT PIH 6 +DC INPUT TRANSCONTROL NEW YORK CC HEADER 8COHTACT TEFLON TUBING FLATTAG, DIGIT 4 OR& 14 X7/16" SCREWS ( ·. '-- Figure 2-10. Flasher Relay Driver Unit 2-11 SM6474-A UNION SWITCH & SIGNAL This page intentionally left blank ( 2-12 SM647..-A UNION SWITCH & SIGNAL Armature moves freely and that moving heel contacts meet the front and back contacts squarely and practically simultaneously. 3.4 TEST PERFORMANCE The PD-1 relay tests can be performed without the DC Relay Test Stand. But the test stand simplifies the test setup and reduces the time needed to test the relays. The following paragraphs describe how to test each type of relay with and without the test stand. Whether or not the test stand is used, the basic test setup is as shown in Figure 3-1. . NOTE As a general rule when testing de relays, such as the PD-1 relays, an ammeter is used to test relays with a coil resistance under 100 ohms, and a voltmeter is used to test relays with a coil resistance over 100 ohms. 3.5 DC RELAY TEST STAND The DC Relay Test Stand is manufactured by US&S. Its formal title is Relay Test Stand PN-150/PN-250 Relays. To enable its use to test PD-1 relays, a Plug Coupler Adapter is provided with the test stand. The Plug Coupler Adapter is wired to a PN-250 frame which is inserted into the PN-250 mounting base on the test stand. The Plug Coupler Adapter sits on a test bench or other flat surface and the PD-1 relay to be tested is then inserted into the Plug Coupler Adapter. The DC Relay Test Stand is described in detail in US&S Service Manual 6360. The manual describes the test stand and contains detailed procedures for the testing of PN type de relays. To reduce frequent reference to the manual, the following information is included in this manual. Refer to Table 3-1 and Figure 3-2 for the location and function of each test stand control and indicator. It must be remembered that all of the test stand controls and indicators are not used for the testing of PD-1 relays. Located in the center of the test stand (Figure 3-2, item 19) are 30 contact indicators. The contact indicators are arranged in five rows of six indicators per row. During the tests, the indicators provide a visual indication of the relay's contact configuration and whether they are open or closed. During PD-1 relay testing, as shown in Figure 3-3, the contact indicators in colu,."tlils 1 through 3 only are used. Row A and D indicate Front contact closure, Row B and E indicate Back contact closure. The Heels (H) can be imagined 3-2 SM6474-A c· , UNION SWITCH & SIGNAL as located between rows A and B, and also between rows D and E. In this basic six Front and six Back contact configuration, ro3.6 TE TSJ.6.1 Biased Relay Performance Tests M1 (Current Monilor) 81 (SPDTP .--~~~A>--~~~~~~~~- + POWER SUPPLY M2 RELAY UNDER TEST C) z (VottaQe Monitor) Figure 3-1. +A .... ia: Biased Relay Test Setup RELAY TEST STAND"' PN·250 MOUNTING BASE PH-250 FRAME PlUG COUPLER ADAPTER \ - . .@®:=::::. 00 <& (o> t& '11· -PD-1 RELAY UNDER TEST -- 10' 4' .... -· Figure 3-lA. Plug Coupler Adapter 3-3 SM6474-A UNION SWITCH & SIGNAL Table 3-1. DC Relay Test Stand, Controls and Indicators REF ITEM FUNCTION 1 Relay Mounting Base PN-250 Provides the proper position and connections for testing the PN250 and PF-256 style relays. * 2 PN-250 Switch (S2) In the WITH TEST JACK position, the input to the r~lay coil is applied to the TEST contact. In WITHOUT position, input to coil is directly to the coil receptacle. 3 VARIAC Control (Vl) Varies the ac pbwer input for testing the light out and power transfer relays.The variable input is the left ac jacks (15 and 16) 4 AC POWER Switch (Sl) In ON position, 115Vac line is connected to VARIAC (3) and transformer that powers the lights. In OFF, power is cut. 5 Power Indicator (Ll) Lights when ac power is available to light the Contact Indicators (L2) (19). 6 PN-250 LIGHT SELECTION SWITCHES (S12) In 1 position, with rotary switch Sll (7), connects PN-250 base for testing other than PN250B relays. In 2 position, base is connected to test PN-250B relays. In OFF position, two front bottom row contacts are disconnected. 7 PN-250 LIGHT SELECTION SWITCHES (Sll) In 1 position, with toggle switch S12 (6), connects PN-250 base for testing 6FB-6F-3B PN250B relay. In 2 position, base is connected for testing 8FB-4F2B PN-250B and PF-256 flasher relays. 8 Relay Coil Block Jacks A+/A- Provides connections to single coil relays or, with item 10 (Jacks B+/B-) connects two coil relays in series or parallel. 9 Coil Polarity Switch (SlO) When using a power supply with Jacks A+/A- (8) and B+/B- (10), the NORMAL position applies positive(+) voltage to A+ (B+) terminals and negative(-) voltage to A- (B-) terminals of biased, timer, light out, or power transfer relays. In REVERSE position, voltage to the A (B) terminals are reversed. In OFF position, voltage is removed from both coil terminals. ( * Used to connect the PD-1 relay under test to the test stand via the Plug Coupler Adapter 3-4 SM6474-A UNION SWITCH & SIGNAL ( 21 22 1 20 19 S2 qy WITHOUT PMAWL OFF V1 17 leeseee PN-110f' S4 S5 S6 S7 qy qy qy IGGGGGG 3 le e e e e e IGGGGGG 16 15 2 PN-25GI SIIIGI.£ 18 ~ WITH TEST JACII COII.S OfF REMOVE JUMPER TO READ CURIIENT S13@ L1 AC JIOWER ON 4 00 ctys1 TIMER sa S9 S10 23 10 .C Figure 3-2. 10 DC Relay Test Stand, Controls and Indicators 3-5 SM6474-A UNION SWITCH & SIGNAL Table 3-1. DC Relay Test Stand, Controls and Indicators (Cont'd) REF ( FUNCTION ITEM 10 Relay Coil Block Jacks B+/B- Provides connection to the second coil of two coil relays or, with item 8, connects two coil relays in series or parallel. 11 Fuse (Fl) Protects the VARIAC (3) and lights (Ll and L2) transformer. 12 PN-150 Contact Configuration Switch (S9) In position 2, the PN-150 base is connected for testing relays with 6 Front/Back contacts. In position l, the base is connected to test relays with 4 Front/Back, 2 Front, and 1 Back contacts. 13 Only PN-lSOT Switch (S8) In the ONLY PN-lSOT position (up), the proper PN-150 base contacts are connected to the +DC/-DC jacks (14). The 2 position is used for all other PN-150 type relays. 14 DC +I- Jacks Used with ONLY PN-150T switch (13) to supply input power to PN-lSOT relay. 15 AMPS or JUMPER Jacks When using AC current for Power Transfer or Lightout relay tests the AC ammeter connects between these jacks. When voltage only is used, the jacks are jumpered. 16 AC VOLTMETER Jacks Used for connecting an AC voltmeter across relay coil in conjunction with four switches (17). 17 PN-lSOL (Light out)/ PN-lSOP (Power Transfer) Switches (S4,5,6,7) In PN-150BL position (down), the PN-150BL/PN-150P base is connected to test the PN-150BL relay. In the PN-150P position, base is connected to test the PN-lSOP relay. OFF position must be used to test all other PN-150 and PN250 type relays. 18 Coils Switch (S2) In parallel position, the A and B relay coils are placed in parallel. In the single position they are separate. 19 Contact Indicators (L2) Visually indicates the relay's contact configuration and when they are open or closed. ( 3-6 SM6474-A UNION SWITCH & SIGNAL Table 3-1. DC Relay Test Stand, Controls and Indicators (Cont'd) ( REF ITEM FUNCTION 20 Relay Mounting Base PN-150, PN-150T (Rl) Provides proper position and connections for testing PN-150 and PN-lSOT style relays. 21 Relay Mounting Base PN-150P, PN-150BL (R2) Provides proper position and connections for testing PN-150P and PN-150BL style relays. 22 F/H/B 23 TIMER Switch Jacks Used with TIMER switch (23) to provide access to set of front, heel, and back contacts. In OFF position, voltage is fed to lights in column 1, Rows D and E, to light the lights. In TIMER position, voltage is removed to allow flash rate, on-time, and timing measurements to be made. 10 0 C0 C0 C0 C0 ~ ( 0 00 10 0 (0(0 C0 0 10 C0 C0 C0 C0 C0 I l I I 6FB ~ ( 0 (0(0 j I I I I B A Figure 3-3. ~000 10 0 C0 C0 C0 C0 10 0 C00 0 C0 ~ 0 C00 IC0 0 C00 C0 C0 Basic Contact Indicators Configuration 3-7 SM6474-A UNION SWITCH & SIGNAL 3.6 TESTS 3.6.1 Biased Relay Performance Tests The following procedures determine the Drop-Away (Release), Pickup, and Working values of PD-1 types of biased neutral relays. 3.6.1.1 Recommended Test Equipment Power Supply 0-40Vdc DC Voltmeter DC Ammeter DC Relay Test Stand or similar test setup per Figure 3-1. 3.6.1.2 Test Setup. When a DC Relay Test Stand is used, the following procedure creates the test setup required. When the test stand is not used, the test setup shown in Figure 3-1 must be created. The non-test-stand setup can use the rack mounted plug coupler/relay but all system wiring connections must first be removed from the plug coupler. All test connections can then be made to the rack mounted plug coupler. In the following test stand setup procedure, the item numbers are those used on Figure 3-2: a. Ensure the AC POWER switch (4) and TIMER switch (23) are set to OFF. b. Ensure the power switch on the de power supply is set to off, and adjust its output voltage control to the OV output position. NOTE As a general rule when testing relays, such as the PD-1 relays, an ammeter is used to test relays with a coil resistance under 100 ohms, and a voltmeter is used to test relays with a coil resistance over 100 ohms. c. Using test leads, connect either the de voltmeter or ammeter (per above Note) to both the power supply output and the relay coil block jacks A+/A- (8), observing the correct polarity. NOTE The above connections are for single coil relays. For double coil relays, whose coils are wired in series, the meter is connected to the A+ and Bjacks with A- and B+ jacks jumpered. 3-8 SM6474-A UNION SWITCH & SIGNAL ( d. Set the PN-150BL/PN-150P switches (17) to OFF {center). e. Set the COILS switch (18) to the SINGLE position. f. Set the PN-250 LIGHT SELECTION SWITCH (7) to the 1 position. g. With the PD-1 Plug Coupler Adapter seated on a flat surface, insert its cable's PN-250 frame into the PN250B base on the test stand. h. Insert the PD-1 relay to be tested into the Plug Coupler Adapter. i. Set the AC POWER switch (4) to ON and the de power supply to on. j. Set the Coil Polarity switch (9) to the NORMAL (up) position. k. Set the PN-250 switch (2) to the WITH TEST JACK position. 3.6.1.3 ( Biased Relay Test stand Procedure. a. Slowly adjust the power supply output control to increase the output, as indicated on the de voltmeter or ammeter, as appropriate, to Charge the relay. (The Charge value is four times the relay's working value, which is specified on the relay's Application Information Sheet.} The Contact Indicators should change from those lit in Figure 3-3A to those shown lit in Figure 3-3B. b. Insert a "stick" into the front test jack. Observe the relay deenergizes (Figure 3-3A). c. Remove the "stick" and observe the relay energizes (Figure 3-3B) . d. Set the Coil Polarity switch {9) to the REVERSE position and observe the relay deenergizes. e. Set the Coil Polarity switch to the NORMAL position and observe the relay again energizes. f. Slowly adjust the de power supply controls to reduce the output until the relay deenergizes. Note the value indicated on the meter. This is the Minimum Release (DropAway) value, and should not be less than the InService Application Limit value specified on the.relay's Application Information Sheet. g. Further reduce the power supply output, if necessary, until the relay armature rests on the permanent magnet extension. Note the value indicated on the meter. This 3-9 SM6474-A UNION SWITCH & SIGNAL is the Minimum Full Release {Drop-Away) value, and should not be less than the In-Service Application Limit value specified on the relay's Application Information Sheet. h. Using the de power supply controls, reduce the output to zero. Then set the Coil Polarity switch (9) to the OFF position for 1 second, and then move it back to the NORMAL position. i. Slowly increase the power supply output until the relay energizes (stop pin closes against the pole face). Note the meter value. This is the Pickup Maximum value and should not be greater than the Inservice Application Limit value specified on the relay's Application Information Sheet. 3.6.1.4 Biased Relay Test Without Test Stand. Refer to paragraph 3.5, and create test setup per Figure 3-1. Proceed as follows: a. Set switch Sl to Normal. NOTE As a general rule when testing relays, such as the PD-1 relays, an ammeter is used to test relays with a coil resistance under 100 ohms, and a voltmeter is used to test relays with a coil resistance over 100 ohms. b. Turn on the de power supply. c. To Charge the relay, observe the meter per the above Note, and slowly adjust the power supply output control to increase the output to four times the relay's working value, which is specified on the relay's Application Information Sheet. The Contact Indicators should change from those lit in Figure 3-3A to those shown lit in Figure 3-3B. Note the ;elay stays ene~gized as the output is increas~d. d. Set switch Sl to Reverse. Observe the relay deenergizes. e. Set switch Sl to Normal. Observe the relay energizes. f. Slowly adjust the de power supply controls to reduce the output until the relay deenergizes. Note the value indicated on the meter. This is the Minimum Release (DropAway) value, and should not be less than the InService Application Limit value specified on the relay's Application Information Sheet. g. Further reduce the power supply output, if necessary, until the relay armature rests on the permanent magnet extension. Note the value indicated on the meter. This 3-10 SM6474-A UNION SWITCH & SIGNAL is the Minimum Full Release (Drop-Away) value, and should not be less than the In-Service Application Limit value specified on the relay's Application Information Sheet. ( h. Using the de power supply controls, reduce the output to zero. i. Slowly increase the power supply output until the relay energizes (stop pin closes against the pole face). Note the meter value. This is the Pickup Maximum value and should not be greater than the In-Service Application Limit value specified on the relay's Application Information Sheet. 3.6.2 Slow Release (Drop-Away) Relay Test A slow release PD-1 relay is a biased relay. Its release, pick-up, and working values are tested in the same manner described in paragraph 3.6.1. Additionally, the release time must be checked, as described in the following procedure. As with the biased relay tests, the slow release timing can be checked with or without the de relay test stand. Both ways are described in the following paragraphs. 3.6.2.1 Recommended Test Equipment, DC Relay Test Stand 0-40Vdc Power Supply DC Voltmeter DC Armneter Time Interval Meter US&S 911A NOTE Release Time is the time from opening of the relay coil circuit until the front contacts open. In performing each check of release time, the circuit shall first be opened and the voltage then be brought up from zero to the value specified, but not beyond. 3.6.2.2 Slow Release Test With Test stand, a. With the relay mounted as described in paragraph 3.6.1.3 upon conclusion of the biased relay tests, set the TIMER switch (23) to the TIMER position (down). b. Using a Time Interval Meter (TIM) US&S Model 911A, disconnect the jumper leads from the A+/A- jacks (8) and connect them to the corresponding EXTERNAL POWER jacks (+)and(-) on the rear of the TIM, as shown in Figure 3-4. 3-11 SM6474·A UNION SWITCH & SIGNAL c. Connect the TIM COIL jacks (Figure 3-5) to relay coil jacks A+/A- (8) (red to A+ and black to A-). d. Connect the TIM CONTACTS jacks across the F and H jacks (22} • e. On the TIM, set the START/STOP switch to the STOP position and adjust the power supply output from zero up to the pick-up value specified on the relay's Application Information Sheet, but not beyond. Leave the power on the coil and proceed to the next step. US&S 911A TIME INTERVAL METER POWER SUPPLY JUMPER + + Figure 3-4. CONTACTS OPerating Time Measurement, Test Setup 0 PICK·UP 0 PU DROP·AWAY 0 START 0 STOP ON 0 OFF DA 0 RELAY CONTACTS Figure 3-5. 0 © COIL e 0 CURRENT{ VOLTAGE SET Time Interval Meter, US&S 911A, Front Panel 3-12 SM6474-A UNION SWITCH & SIGNAL f. ( On the TIM, set the START/STOP switch to the START position, and when the relay deenergizes (front contacts open}, note the release time on the TIM. The time should not be less than the release time specified on the relay's Application Information Sheet. 3.6.2.3 Slow Release Test without Test stand. a. After completing the biased relay tests per paragraph 3.6.1.4, connect the relay into the test circuit shown in Figure 3-4. b. On the TIM (Figure 3-5), set the switches as follows: 1. PICK-UP/DROP-AWAY switch to the DROP-AWAY position. 2. START/STOP switch to the STOP position. 3. ON/OFF switch to the ON position. c. Set the START/STOP switch to the START position. The display will start timing, then stop, and the DA indicator will light when the relay drops. The value should not be less than the release time specified on the relay's Application Information Sheet. 3.6.3 Slow Pick-Up Relay Test A Slow Pick-Up PD-1 relay is also a biased relay. Its release,pick-up, and working values are tested as described in paragraph 3.6.1. Additionally, the pick-up time must be checked, as described in the following paragraphs. As with the biased relay tests, the slow release timing can be checked with or without the de relay test stand. Both ways are described in the following paragraphs. 3.6.3.1 Recommended Test Equipment. DC Relay Test Stand 0-40Vdc Power Supply DC Voltmeter DC Ammeter Time Interval Meter US&S 911A NOTE Pick-Up Time is the time from closing of the relay coil circuit until the front contacts close. There shall be a minimum of series resistance in the circuit, and the specified voltage shall be measure with the circuit closed. 3-13 SM6474-A UNION SWITCH & SIGNAL 3.6.3.2 slow Pick-up Test with Test stand. a. With the relay mounted as described in paragraph 3.6.1.3 upon conclusion of the biased relay tests, set the TIMER switch (23) to the TIMER position (down). b. Using a Time Interval Meter (TIM) US&S Model 911A (Figure 3-5), disconnect the jumper leads from the A+/Ajacks (8) and connect them to the corresponding EXTERNAL POWER jacks (+) and(-) on the rear of the TIM, as shown in Figure 3-4. c. Connect the TIM COIL jacks (Figure 3-5) to relay coil jacks A+/A- (8) (red to A+ and black to A~). d. Connect the TIM CONTACTS jacks across the F and H jacks ( 22) . e. On the TIM, set the START/STOP switch to the STOP position and the DROPAWAY/PICKUP switch to the PICKUP position. Set the power switch to the ON position. f. On the TIM, set the START/STOP switch to the START position, and when the relay energizes (front contacts close,) note the pick-up time on the TIM. The tirnne should be not be less than the pick-up time specified on the relay's Application Information Sheet. 3.6.3.3 ( slow Pick-up Test without Test stand. a. After completing the biased relay tests per paragraph 3.6.1.4, connect the relay into the test circuit shown in Figure 3-4. b. On the TIM (Figure 3-5), set the switches as follows: 1. PICK-UP/DROP-AWAY switch to the PICK-UP position. 2. START/STOP switch to the STOP position. 3. ON/OFF switch to the ON position. c. Depress the CURRENT/VOLTAGE SET pushbutton on the TIM and charge the relay in the normal direction as described in paragraph 3.6.1.3 step a, then reduce the voltage to that specified in step i. d. Set the START/STOP switch to the START position. The display will start timing, then stop, and the PU indicator will light when the relay picks. The value should not be less than the relay's pick-up time specified on the relay's Application Information Sheet. ( 3-14 SM6474-A UNION SWITCH & SIGNAL 3.6.4 Magnetic Stick Relay Test ( 3.6.4.1 Recommended Test Equipment. DC Relay Test Stand 0-40Vdc Power Supply DC Voltmeter DC Ammeter 3.6.4.2 a. Magnetic Stick Relay Test with Test Stand. Create test setup as follows (see Figure 3-2 for item locations) : 1. Ensure that the AC POWER switch ( 4} and TIMER switch (23) are set to OFF. 2. Ensure the de power supply is off and its controls set for zero output. NOTE As a general rule when testing de relays, such as the PD-1 relays, an ammeter is used to test relays with a coil resistance under 100 ohms, and a voltmeter is used to test relays with a coil resistance over 100 ohms. ( 3. Using jumpers, connect the de voltmeter or ammeter per the preceding Note, to both the de power supply output and the relay coil jacks A+/A- (8), observing correct polarity. 4. Set the PN-150BL/PN-150P switches (17) to the OFF (center) position. 5. Set the COILS switch (18) to the SINGLE position. 6. Set the PN-250 LIGHT SELECTION switches (7) to the 1 position. 7. With the PD-1 Plug Coupler Adapter seated on a flat surface, insert its cable's PN-250 frame into the PN250B base on the test stand. 8. Insert the PD-1 relay to be tested into the Plug Coupler Adapter. 9. Set the AC POWER switch (4) to ON and the de power supply to on. 10. Set the Coil Polarity switch (9) to the REVERSE (down) position. 3-15 SM6474-A UNION SWITCH & SIGNAL 11. Set the PN-250 switch (2) to the WITH TEST JACK position. b. Test the relay as follows: 3.6.4.3 1. Slowly adjust the power supply output control to increase the output, as indicated on the de voltmeter or ammeter, as appropriate, to Charge the relay. (The Charge value is four times the relay's working value, which is specified on the relay's Application Information Sheet.) The Contact Indicators should change from those lit in Figure 3-3A to those shown lit in Figure 3-3B. 2. Insert a "stick" into the front test jack. Observe the relay and lights do not change condition. 3. Remove the "stick" and observe the relay does not change. 4. Set the Coil Polarity switch (9) to the NORMAL position and observe the relay armature again reverses position (bottom contacts close). 5. Set the Coil Polarity switch to the REVERSE position and observe the relay armature again reverses position (upper contacts close). 6. Reduce the de power supply output to zero and set the Coil Polarity switch to NORMAL. 7. Slowly increase the de power supply output until the relay armature reverses position and note the value. It should be between the Maximum and Minimum Pick-up and working values. 8. Reduce the power supply output to zero and set the Coil Polarity switch to REVERSE. 9. Slowly increase the de power supply output until the relay armature reverses position. Note the value indicated on the meter. It should not be more than the Pick-up In-Service Application Limit value specified on the relay's Application Information Sheet. Magnetic stick Relay Test without Test stand. a. Create test setup as shown in Figure 3-2: 1. Ensure that switch Sl is set to Reverse. 2. Ensure the de power supply is off and its output set to zero. 3-16 SM6474-A ( UNION SWITCH & SIGNAL NOTE As a general rule when testing de relays, such as the PD-1 relays, an arruneter is used to test relays with a coil resistance under 100 ohms, and a voltmeter is used to test relays with a coil resistance over 100 ohms. 3. Slowly adjust the power supply output control to increase the output, as indicated on the de voltmeter or arruneter, as appropriate, to Charge the relay. (The Charge value is four times the relay's working value, which is specified on the relay's Application Information Sheet.) 4. Reduce the power supply output to zero and set Sl to Normal. b. Test the relay as follows: 1. Slowly increase the de power supply output until the relay armature reverses position and normal (bottom) contacts close. Note the value. It should be no greater than the Pick-up Maximum In-Service Application Limit value specified on the relay's Application Information Sheet. 2. Reduce the power supply output to zero and set Sl to REVERSE. 3. Slowly increase the de power supply output until the relay armature reverses position and reverse (upper) contacts close. Note the value. It should be no greater than the Pick-up Maximum In-Service Application Limit value specified on the relay's Application Information Sheet. 3.6.5 Switch Overload Relay Performance Test The Switch overload PD-1 relay cannot be tested usinq the DC Relay Test Stand. 3.6.5.1 Recommended Test Equipment. Power Supply, 0-40VDC DC Ammeter, 0-25A Heavy duty SPST switch Power Resistor, 1 ohm, 200W Stopwatch, capable of measuring 15 seconds with 0.1 sec accuracy . ('~. 3.6.5.2 os Relay Test Procedure. Test the operating characteristics of the switch overload relay as follows: 3-17 SM6474-A UNION SWITCH & SIGNAL + + SHORT DC SUPPLY S1 DC SUPPLY A 81 R SWITCH OVERLOAD RELAY UNDER TEST == HP&4348 = DC AMMETER (0-25 MIN) • HEAVY DUTY SWITCH = POWER RESISTOR Figure 3-6. Switch overload Stick Relay, Test Setup a. Connect the test setup as shown in Figure 3-6. b. Set the power supply output voltage control to O volts. c. Set switch Sl to the Short position. d. Adjust the de power supply output control to obtain a current measurement equal to the Operating Time Amps specified on the relay's Application Information Sheet. e. Using a stopwatch to make the time measurement, simultaneously set switch Sl to the Open position and start the stopwatch. f. Stop the watch the instant the overload relay energizes. Also, remove power as quickly as possible. The time should be in seconds within the Operating Time specified on the relay's Application Information Sheet. 3.6.6 Flasher Relay Performance Test The PD-1 Flasher relay is a biased relay inserted into a rear service plug coupler, that is equipped with a rear mounted octagonal socket into which a solid-state relay driver flashing unit is installed. The PD-1 Flasher Relay cannot be tested using the DC Relay Test Stand. 3-18 SM6474-A UNION SWITCH & SIGNAL 3.6.6.1 Recommended Test Equipment Power Supply, 0-40Vdc SPST switch Electro-mechanicalcounter Counter 0.1 second accuracy Stopwatch Simpson TS-111 On-Time Meter ( 3.6.6.2 Flasher Test Procedure. a. With the power supply off, connect the relay under test and the required test equipment as shown in Figure 3-7. b. With the Sl switch in its Off position, turn the power supply on, and slowly increase the output until the flasher starts to operate. The voltmeter should indicate between 10-lBV de. c. Simultaneously, set switch Sl to its On position and start the stopwatch. d. At the end of 3 minutes, set switch Sl to Off. e. Divide the counter indication by 3 to obtain a pulsesper minute reading. The reading should be between 41 and 45. With switch Sl set to Off and the flasher operating, connect an on-time meter between a heel and front contact pair and measure the on-time. Note this measurement. f. OFF H · ~ F(FRONT) ON (HEEL + M1 POWER SUPPLY + v LeH side looking from front) + COUNTER FLASHER UNDER TEST (Right side looking lrom front) ( Figure 3-7. Flasher Relay, Test Setup 3-19 SM6474-A UNION SWITCH & SIGNAL g. Connect the on-time meter between a heel and back contact pair and measure the on-time. Note this measurement. h. The two measurements should be within 20% of each other. 3.6.7 Lightout Relay Test The PD-1 Lightout Relay cannot be tested on the DC Relay Test Stand. 3.6.7.1 R,ecomrnended Test Equipment, Variable transformer (Variac) Tl Filament transformer T2 AC ammeter Resistor 120Vac, 60Hz input 12Vac, 60Hz secondary 0 - SA minimum 4 ohms 3.6.7.2 Lightout Relay Test Procedure. Connect test circuit, as shown in Figure 3-8, and proceed as follows: I WARNING Voltage and current dangerous to life are present. Use one hand to make connections. a. Set switch Sl to the Off position. b. Set Variac output control to the minimum setting. c. Connect circuit to 120Vac, 60Hz line. d. Set switch Sl to the On position. --Xi-0-F-F----. ON +R 120 VAC, 60 HZ (ISOLATED LINE) T2 (12 VAC) -R LIGHT-OUT RELAY UNDER TEST Figure 3-8. Lightout Relay, Test Setup 3-20 SM6474-A UNION SWITCH & SIGNAL e. Adjust Variac output control to Charge the relay until the ammeter indicates four times the Working value as specified on the relay's Application Information Sheet. The relay energizes. f. Reduce the Variac control setting until the front contacts open. Note the ammeter indication. It should be no less than specified on the relay's Application Information Sheet. g. Further reduce the Variac output to zero and then open the circuit momentarily. h. Increase the Variac output until the armature completes its pick-up motion and closes against the pole piece. i. Note the ammeter indication. It should be no greater than the Maximum Pick-up In-Service Application Limit specified on the relay's Application Information Sheet. 3-21 SM6474-A UNION SWITCH & SIGNAL This page intentionally left blank 3-22 SM6474-A UNION SWITCH & SIGNAL APPENDIX APPLICATION INFORMATION SHEETS A.1 INTRODUCTION This Appendix contains PD-1 relay Application Information Sheets. Each Application Information Sheet contains the following information for its related PD-1 relay: G;' a. Type of Relay b. Relay Part Number c. Quantity and Type of Contacts d. Relay Coil Resistance e. Plug Coupler Part Number and Type of Service (Front or Rear) f. Contact Data (Application, Max. Rating Volts, Max. Rating Amps) g. Operating Characteristics: 1. Operating Parameters (Volts and Amps for Normal, Min. and Max.) 2. Operating Time (Pick-Up and Release Times) 3. Factory Standard Calibration Values (Drop-Away, Pick-Up, and Working) 4. In-Service Application Limits (Pick-Up and DropAway) 5. Operating Temperature Range h. Contacts Arrangement i. A.2 ( Notes TYPES OF PD-1 RELAYS This Appendix contains Application Information Sheets for the following types of PD-1 relays: A-1 SM6474-A UNION SWITCH & SIGNAL a. Ordinary Acting, Biased Neutral, Low Voltage (Table A-1) b. Ordinary Acting, Biased Neutral, Low Voltage Front, Heavy Duty Back (Part No. 99255565) c. Ordinary Acting, Biased Neutral, Low Voltage, Car Carried (Part No. 99255675) d. A.3 ( Ordinary Acting, Biased Neutral, High Voltage Front, Low Voltage Back (Part No. 99260147) e. Ordinary Acting, Biased Neutral, High Voltage Front and Back (Part Nos. 99260389, 99260390, and 99260400) f. Slow Release, Biased Neutral, High Voltage (Part Nos. 99255103, 99260501, 99260502, and 99275882) g. Overload (Part Nos. 99275015 and 99275607) h. Flasher, Biased Neutral, Heavy Duty Front and Back (Part Nos. 99260389 and 99275037) i. Light Out, Biased Neutral, Low Voltage (Part Nos. 99275048 and 99275838) j. Magnetic Stick, Biased Neutral, Low Voltage (Part Nos. 99275070, 99275180, and 99275334) k. Power Off, Biased Neutral (Part Nos. 99260389 and 99275257) 1. Magnetic Blow-Out, Biased Neutral (Part Number 99275860) -· C. ABBREVIATIONS The Abbreviations used on the Application Information Sheets are defined below: ABBREVIATION AG B F FB H HD HV N PO R s MEANING Silver Back Contact Front Contact Front-Back Heel Contact Heavy Duty Contact High Voltage Contact Normal Contact (Magnetic Stick Relay) Power Off Reverse Contact (Magnetic Stick Relay) Silver A-2 SM6474-A ( UNION SWITCH & SIGNAL Table A-1. Ordinary Acting, Biased Neutral, Low Voltage PD-1 Relays \ PART NO. COIL OHMS CONTACT QTY. PLUG COUPLER TYPE 99255004 500 6FB Front 99255092 125 6FB Rear F 99255114 500 6FB Rear F (Carbon Silver/Silver) B (Silver/Silver) 99255180 200 6FB Rear F 99255290 200 6FB Rear F (Carbon Silver/Silver) B {Silver/Silver) 99255499 2.0 6FB Front (Carbon Silver/Silver) (Silver/Silver) B 99255686 800 6FB Rear F (Carbon Silver/Silver) B (Silver/Silver) 99255719 3500 6FB Rear F (Carbon Silver/Silver) B (Silver/Silver) 99255893 500 6FB Rear (Carbon Silver/Silver) (Silver/Silver) B A-3 CONTACT TYPES F (Carbon Silver/Silver) B (Silver/Silver) {Carbon Silver/Silver) B (Silver/Silver) (Carbon Silver/Silver) B (Silver/Silver) F F SM6474-A UNION SWITCH & SIGNAL This page left intentionally blank A-4 SM6474-A JU:LAY ENOINEERINO APPLICATION INFORMATION Slll'.:ET THIS SHEET PROVIDES GENERAL INFORMATION CONCERNING THE CONTACTS, COIL A.MD OPERATING CHARACTERISTICS FOR THIS RELAY. TYPE OF RELAY. PD-1 Ord, Accinq,81aeed Neutral. Low Volt. RELAY PART NUMBER. 99255004 DRAWING NUMBER SC559 REV-C QTY. AND TYPE OF CONTACTS:~ [(Carbon Silver to Silver) 8(Silver to Silver) RELAY COIL RESISTANCE. ~ l.l!! WIRE SIZE, OHMS, INDEX H::Ii 13,000 TURNS. ( J REAR SERVICE (] SHELF MOUNT [XJ FRONT SERVICE 7467SOJSHL ( J TRAIN CARRIED - - - - PLUG COUPLER PART NO. CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. (X) ( S) SAFETY. UP TO 30 [) (HD) HEAVY DUTY. UP TO 30 10 4 r~ () OPERATING CHARACTERISTICS. OPERATING PARAMETERS c ;;· • '>¥7 OPERATING TIME AT NORMAL VOLTAGE ( X) AMPS. ( J INSERVICE APPLICATION LIMITS. voe AMPS HIN. J..:.2. voe AMPS MAX. .ll2 voe AMPS INTERMITTENT I 10 (-)COII.f'"'Y'""\..(+)COIL 9 §F fS} SH lL..U SECOND 8 6H SH RELEASE .9..:..Q1. SECOND 7 68 SB PICK-UP FACTORY STANDARD CALIBRATION VALUE HIGH VOLTAGE. CONTACTS ARRANGEMENT AS VIEWED FROK REAR LEFT SIDE 500 Ohm RIGHT SI Of ll&. I l (HV) ts) DROP-AWAY _l.:..Q voe AMPS 6 4'f' CS) 3P' {Sl PICK-UP ___Lj_ voe AMPS 5 41:1 JI:! WORKING ___Lj_ voe AMPS 4 48 38 -1...ll voe 0.0143 AMPS 3 n: CS) l[ DROP-AWAY HIN.L.ll voe 0.0027 AMPS 2 2K lH 21.l n PICK-UP MAX. OPERATING TEMPERATURE RANCE. -40°F to +l85°F. l !SI NOTES 1. 2. J. This relay shall be teated on a periodic basis, not exceeding 2 year• or current FR.A-required testing interval. When f&lay operate out side the inservice application limits value, it shall be reconditioned aa per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is baaed on resistive loads only, derata 60\ for inductive and 40\ for motor load. ( A-5 RELAY ENGINEERING APPLICATION INFORMATION SHEET THIS SHEET PROVIDES GENEltAL INFORMATION CONCERNING THE CONTACTS, COIL AND OPERATING CHARACTERISTICS FOR THIS RELAY • .... PD-1 Ord. Acdng 1Biased Neutral L.V. 99255092 RE.A Y PART NtJt.48EA, arv. AND TYPE OF CONTACTS. DRAWING NUMSER. ..m_ COIL. 1woex C·M F{Ca;rbon Silyc:r tg SjJver) DCSUver ta SiJverl _ _.1....,2.,.5_ _ OHMS, AG.AV COIL RESISTANCE. SCSOJ REY. 0 127 2165500ZCM 6, 100 WIAIE SIZE, TURNS. D ....,. IIOINf - - - - O TIWII C..-. - - - - - CONT ACT DAT A liJ (S) ...,...t.lCA TIOH MAX. AA TING VOt. TS. 0 SAF£TY. 10 OPERA TING CHARACTERISTICS. 12. 0 lll:W4AL. - 310 { 120 ' MAX. AS VIEWED FROM MM i, DC - - ..u.41"1 y oc: - - - ,._.. TB l'ICIC~ { J..J2Z. 0 MCDND II ~ w.x. INSERVICE APPICATIOH { 7 I I I U I J C ~ KCOMl FACTORY STANDARD. CALIBAA TIOH VALUE. 3.0 3.0 3.30 o..,•....,61__ CMICf'-AWAY . _ _ _ l2/I A ...., - 10 ( • ) C O l ~ • ) C O l l . ' Y DC - - - IMl'S IHfUMTT1Df1'. 1.0 L1M1Ts. CONT ACTS ARFMHGEMENT Ull'T NIC OPERATING PARAMETERS OPERA TING TIME: ,. HOflMAL VOLT ACK. AMPS, (HY) HIOH VOLTACNE. UP TO 30 ... MAX. AA TINO ».PS. 0 (HD) HEAVY DUTY. UP TO 30 _6f _(~ Sf_~.l ..61:f. - Sil. - - ..§! __ e .,!if .(S) Y,DC _ _. Y,DC _ _. V,DC N4'11 ... V, DC 0.0264 ..... 3 V, DC ~ » f t 2 5 •-40• F TO • 11ts• F. 1 4H 4B ---]f._(~ .ia __ j@. __ .' ~-- 3.F.CSl !H___ ---- · 38 !_F_C§!. u, ___ us__ - NOTES ,. THIS lln..AY SHALL • TIESTI HO NTEIIVAL, n:sn:o ON A PERIODIC IASIS, MOT EICCHOINO z YCAIIS Oft CUlllll:NT ,M•REOUUIID z. ?s"~tt"~;Y 11CVtl~~g~Jd0 ,.lJ!t,re::"'fio"~ii~~ ,lg ,~~slOv:~ftlJo1~1f'c.U.~l°&Drt.~. 3. CONTACT AMPF:IIE IIATINO IS IAHO ON IIUl!TIV£ LOADS ONLY, DEii.ATE 10% l'Olt INOUCTIVE AND 40% ,Ofll MOTOII LOAD, A-6 RELAY ~OIN'!!ERINO APPLICATION INFORMATION SBEZ'r THIS SKEET PROVIDES 01!:NERJU. INFORMATION CONCERNINO TBE COHTAC'rS, COIL ANO OPERATING CllAJtACTERISTICS FOR TBIS RELAY. TYPE OF RELAY. P0-1 Slow Release Blaeed Neutral Low Volt, RELAY PART NUMBER. 99255103 DRAWING NUMBER QTY. AND TYPE OF CONTACTS:~ SC506 REV-E INDEX .11:.1 FlCarbon Stlver to Sllv9r) BlSllv9r to SLlver} .tl.i RELAY COIL RESISTANCE. 1.Q.9... OHMS, (X) REAR SERVICE 6,500 WIRE SIZE, 74655002 TURNS. ( J SHELF MOUNT PLUG COUPLER PART NO. ( J TRAIN CARRIED ( J FRONT SERVICE CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. ( X J ( S) SAFETY • UP TO JO (HO) HEAVY DUTY. UP TO JO (J {) CONTACTS ~CZXZNT AS VIEWED FROM UAR ;::~ l::: MAX. OPERATING TIME AT NORMAL VOLTACE [XJ AMPS. ( J FACTORY STANDARD CALIBRATION VA.LUE .llQ. l voe AMPS voe AMPS voe AMPS INTERMITTENT LEFT SIDE 200 Ohm RIGHT SIDI 9 6F fS) SF SH PICK-UP 2..:..31i SECOND 8 §If RLLEASE .Q..J_ SECOND at l2V 7 68 tS\ \ OROP-AWAle __L.Q. voe AMPS 6 4F CS) 3F 1s1 { PICK-UP __L.l voe - - - AMPS s 4H 3H __L.l voe - - - AMPS 4 48 38 -1....ll voe 0.036 AMPS 3 2F CSJ lf 1s1 DROP-AWAY MIN.l.:J.! voe 0.067 AMPS 2 2H lff I WORKING INSERVICE APPLICATION LIMITS. HICH VOLTACS. 10 4 OPERATING CHARACTERISTICS. OPERATING PARAMETERS (KV) PICK-UP MAX. OPERATING TEMPERATURE RANGE. l 28 18 NOTES l. 2. J. Thie relay shall be teated on a periodic basis, not exceeding 2 years or current FRA-required testing interval. When relay operate out aide the inservice application limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. contact ampere rating is based on resistive loads only, derate 60\ for inductive and 40\ for motor load. ( A-7 R.ELAr ENOINEERINO APPLICATION INFORMATION SHE~ THIS SHEET PROVIDES GEN1!:RAL INFORMATION CONCER.KINO THE CONTACTS, COIL AND OPEllATIHO CllAJ'U\CTERISTICS FOR THIS REI.Ar. TYPE OF RELAY. P0-1 Ord. acting,Biaged RELAY PART NUMBER. 9925511§ QTY. AND TYPE OF CONTACTS: Neutral. DRAWING NUMBER §.I.a Low Volt. 5C507 REV-f FlCarbon stlver to Sllyer) COIL INDEX li::I.t B(Silver DQ WIRE SIZE, RELAY COIL RESISTANCE.~ OHMS, to Sllver) 13,000 TURNS. (XJ REAR SERVICE 7465500~HL { } SHELF MOUNT ( ) FRONT SERVICE [ ) TRAIN CARRIED - - - - PLUG COUPLER PART NO. CONTACT DATA APPLICATION MAX. RAT INC VOLTS. MAX. AATING AMPS. ( l (HD) HEAVY DUTY. (X) (S) SAFETY. ( ) OPERATING CHARACTERISTICS. ro= OPERATING PARAMETERS MIN. l MAX. OPERATING TIME AT NORMAL VOLTAGE [X} AMPS. ( J FACTORY STANDARD CALIBRATION VA.LUE 12. 0 voe AMPS ~ voe AMPS ll.Q. voe AMPS INTERMITTENT 10 (-)COI~+)COIL 9 u §!:I {SI SH (SI SECOND 8 REL.EASE 2.:..Ql SECOND 7 68 SB DROP-AWA? -1..,..Q voe AMPS 6 4f (Sl 3f PICK-UP ~ voe AMPS s 4H 3H ~ voe AMPS 4 48 38 l WORKING INS ERV ICE APPLICATION LIMITS. CONTACTS AJUlANCEHENT AS VIEWED FROM UAR LEFT SIDE 500 Ohm RIGHT SIDI JL..ll PrCK-UP j (HV) HIGH VOLTAGE. UP TO JO 10 UP TO JO 4 C> Sfl I' ts I PICK-UP MAX. 1.....U voe o.ou;i AMPS 3 2[ cs> lf [SI DROP-AWAY MIN. L.ll voe 0.0027 AMPS 2 2H lH 28 111 OPERATING TEMPERATURE RANGE. -40°F to +1SS°F. l NOTES 1. 2. 3. This relay shall.be tested on a periodic basis, not exceeding 2 years or current FRA-required testing interval. When relay operate out side the inservice application limits value, it shall be re~onditioned as per PD-1 relay shopping procedure and calibrate to !actor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60\ !or inductive and 40\ for motor load. A-8 RELAY EHOIHEERIHO APPLICATION IHFORMA~IOH Sln!:ET THIS SHEET PROVIDES GENERAL INFORMATION COHCERNINO THE CONTACTS, COIL AND OPERA~IHO CHARACTERISTICS FOR THIS RELAY. TYPE oF RELAY. eo-1 Slow Pick-Up e1aeed. Neutral Low volt, RELAY PART NUMBER. 99255180 QTY. AND TYPE OF CONTACTS: DRAWING NUMBER SCSlJ REV-8 COIL INDEX~ i.Di [(Carbon SLlver to Sllver) e,s1iver to Sllver) tl2, WIRE SIZE, RELAY COIL RESISTANCE. 1QQ_ OHMS, 6.SQQ TUR.NS. (XJ REAR SERVICE ( J SHELF MOUNT ( I FRONT SERVICE [ l TRAIN CARRIED PLUC COUPLER PART NO. CONTACT DATA APPLICATION HAX. RATING VOLTS. MAX. RATING AMPS. (X) ( S) CI (HD) HEAVY DUTY. UP TO 30 SAFETY. IJP TO 30 4 [J F~:: MAX. OPERATING TIME AT ~ : , NORMAL VOLTAGE [X] ·'1iW AMPS. [ I FACTORY STANDARD CALIBRATION VALUE INSERVICE APPLICATION LIMITS. llQ l HICH VOLTAGE. 10 OPERATING CHARACTERISTICS. OPERATING PARAMETERS (HV) CONTACTS ARJUUCCEKENT ·---·AS VIEWED FROM REAR LEFT SIDE 200 Ohm RIGHT SID. voe AMPS voe AMPS voe AMPS INTERMITTENT 10 (-)COIL 9 6[ CS) SF CS> (+)COIL PICK-UP .Q....1.i SECOND 8 6H SH RELEASE Q.& SECOND 7 68 SB - - - AMPS 6 4[ CS) 3F CS) ) :::::::AY L.Q.Q. voe - - - AMPS 5 4H 3H WORKING L.Q.Q. voe - - - AMPS 4 48 38 ~ PICK-UP MAX. .2..:..iQ. voe 0.049 AMPS 3 2F (SJ lF tSJ l DROP-AWAY MIN. 2.34 voe Q.Oll AMPS 2 2H lH OPERATING TEMPERATURE RANGE. l 2a u NOTES l. 2. J. This relay shall be tested on a periodic basis, not exceeding 2 year• or current FRA-required testing interval. When relay operate out side the inservice application limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60\ for inductive and 40\ for motor loa9. ( A-9 RELAY ENOIN!:ERINO APPLICATION INFORMATION SBEtr THIS SHEET PROVIDES OENEIUU. INFORMATION CONCER.NINO TBE CONTACTS, COIL AH1> OPEKATIHO ClUUlACTERISTICS FOR THIS RELAY. TYPE OF RELAY. PQ-1 Slow Pick-Up Blased, Neutral Low Volt. SCS23 BEV-e RELAY PART NUMBER. 99255290 DRAWING NUMBER QTY. AND TYPE OF CONTACTS: 6FB FCCarbon Silver to Silver) BISilver l12. WIRE SIZE, RELAY COIL RESISTANCE • .lQQ_ OHMS, (XJ REAR SERVICE 74§55002 COIL INDEX~ to Silveri 6 1 500 TUR.HS. ( J SHELF MOUNT PLUG COUPLER PART NO. ( l FRONT SERVICE CI TRAIN CARRIED CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. Cx I (S) SAFETY. UP TO 30 HEAVY DUTY. UP TO 30 10 CI (HD) 4 CI OPERATING CHARACTERISTICS. ro= OPERATING PARAMETERS OPERATING TIME AT NOR.MAL VOLTAGE (XI AMPS. c J INSERVICE APPLICATION LIMITS. HIGH VOLTAGE. CONTACTS ARRANGE.KENT AS VIEWED FROM UAR LEFT SIDE 200 Ohm RIGHT SIO ll.,.Q voe AMPS HIN. -2..& voe AMPS MAX. llQ voe AMPS INTERMITTENT 10 (-)CO~+)COIL 9 §[ cs1 Sf !Sl ~ PICK-UP L2.Q SECOND a 6H 56 l RELEASE SECOND 7 68 SB j FACTORY STANDAJU> CALIBRATION VALUE (HV) O. 60 DROP-AWAY l.:..L voe AMPS 6 4f (SI 3f 1s1 PICK-UP .2.:..Q_ voe AMPS s 41:f 31:1 WORKING 2.:..Q_ voe AMPS 4 48 38 9,90 voe 0.0495 AMPS J 2F O,Oll§ AMPS 2 2H lH iB u 1 PICK-UP MAX, DROP-AWAY M:N. 1..,_ll .OPERATING TEMPERATURE RANCE • voe -40°F to +l8S°F. l [S) u: (SI NOTES 1. 2, 3. Thia relay shall be tested on a periodic basis, not exceeding 2 year• or current FRA-required testing interval. When relay operate out side the inservice application limits value, it shall be reconditioned as per PD-l relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derata 60\ for inductive and 40\ for motor load. ( A-10 Rl!:LAY l!!NOIHl!:ERINO APPLICATION IN1"0RMA'.rION SIIEET THIS SHEET PROVIDES OEHl!:RAL INFORMATION CONCERNING THE CONTACTS, COIL A.HD OPERA'.rIHO CBAJlACTERISTICS roa TRIS Rl!:LAY. TYPE OF RELAY. P0-1 Aetinq.B1ased Meueral. Low Volt: Ord. R.£LAY PART NUMBER. 99255499 DRAWING NUMBER~ QTY. ANO TYPE OF CONTACTS: 6FB F(Carbon L..Q... RELAY COIL RESISTANCE. ( Silver to S1lverl B(Silver fil WIRE SIZE, OHMS, 925 to Silver) TURNS. ( J SHELF MOUNT J REAR SERVICE PLUG COUPLER PA.RT NO. 746752§1 (XJ FRONT SERVICE ( J TRAIN CARRIED CONTACT DATA APPLICATION (XJ HAX. RATING VOLTS. MAX. RATING AMPS. CI (HO) HEAVY DUTY. UP TO 30 10 SAFETY. UP TO JO 4 (S) ( J (KV) HIGH VOLTAGE. CONTACTS A.RRABCEMZNT AS VIEWED FROM REAR LEFT SIDE 2.0 Ohm RIGHT SID: OPERATING CHARACTERISTICS. voe ) NO-L OPERATING PARAMETERS MIN. OPERATING TIME AT l AMPS. j FACTORY' STANDARD CALIBRATION VALUE IN SERVICE APPLICATION LIMITS. voe Q.170 AMPS voe AMPS INTERMITTENT 10 (-)COIL__l"""\__(+)COIL SH cs> 6f SECOND 8 §U SH RELEASE 0.025 SECOND 7 68 SB PICK-UP ( J (XJ AMPS 9 MAX. NORMAL VOLTAGE 0.680 J!...ll l. 70 tS) DROP-AWAY voe 0.057 AMPS 6 4F IS) 3[ PICK-UP VDC Q.170 AMPS s 4H JH WORKING voe 0.170 AMPS 4 48 38 0.374 voe o.up AMPS 3 n: rs1 u: 0.076 voe 0.038 AMPS 2 2H lH )'ICK-UP MAX. DROP-AWAY' MIN. OPERATING TEMPERATURE RANGE. -40°F to +185°F. l 2B (S) 38 tHQl PICK-UP MAX. .L1.Q_ voe ,02u AMPS l 2[ £f:U2l u: DROP-AWAY MIN. 0.67 voe .OQS,2 AMPS 2 2H lH l WORKING INS ERV ICE APPLICATION LIMITS. CONTACTS A.RRANCEHENT AS VIEWED !'ROK REAR LEFT SIDE 125 Ohm RIGHT SIDf voe HIN. MAX. OPERATING TIME AT NORMAL VOLTAGE ( XJ AMPS. ( ) (HV) HIGH VOLTAGS. OPERATING TEMPERATURE RANCE. -40°F to +185°F. 1 ,§ (HP) CHPl (HQ! la CHQ) NOTES 1. Thia relay shall be teated on a periodic basis, not exceeding 2 year• er current FR.A-required testing interval. 2. When relay operate out aide the inservice application limits value, it shall be re~onditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. 3. Contact ampere rating ls based on resistive loads only, derate 60\ tor inductive and 40\ for motor load. 4. When this relay is used with Tranacontrol Relay Driver Style (F.R.D.) Part No. 75335009, it will provide 43-2 flashes per minute, starting at 10 voe. *This relay can be replaced by P/N 99260389 ( A-13 IU:t.Ar ENOIN']';ERIHO APPLICATION IHFORHllTION SHEE'.r THIS SHEET PROVIDES OENERAI. INFORMATION CONCER.NIHO TBE CONTACTS, COIL AND OPERATIHO CBA.RACTERISTICS FOR TRIS REI.Ar. TYPE OF RELAr. PQ-1 Ord, Acting, Biased Neutral, Low Volt RELAr PART NUMBER. 99255675 Olt.l\WING NUMBER~ QTY. AND TYPE OF CONTACTS: §..Ell f(Carbon Stlver to Silveri B(Sllver l l i WIRE SIZE, RELAY COIL RESISTANCE. l.:iQ..Q OHMS, to Silver) 35,00Q TUR.NS. (J SHELF MOUNT REAR SERVICE PLUG COUPLER PART NO. ( J FRONT SERVICE (XJ () TRAIN CARRIED (No plug coupler is used on Train carried Relay) CONTACT DATA APPLICATION RATING VOLTS. MAX. RATING AMPS. (X) l'!AX. (S) SAFETY. UP TO JO [I 4 {HO) HEAVY DUTY. UP TO JO 10 () OPERATING CHARACTERISTICS. ro= OPERATING PARAAETERS OPERATING TIME AT NORMAL VOLTAGE ( A.MPS. ( FACTORll' STANDARD CALIBRATION VALUE INSERVICE APPLICATION LIMITS. (HV) HIGH VOLTACE. CONTACTS ~CEMENT AS VIEWED FROM REAR LEFT SIDE RIGHT SIDE 3500 Ohm 10 (-)COIL (+)COIL ~ voe AMPS HIN. ll.,JL voe AMPS MAX. .ll!L voe AMPS INTERMITTENT ,s,Wsr 1s, 9 u: SECOND 8 §H iH._ \ RELEASE 2.:.QL SECOND 7 68 a_ j PICK-UP Q..:.ll I 12K,2W DROP-AWAY 2-:.ll voe AMPS 6 4f CS) Jf PICK-UP l1..:..Q voe AMPS s ~H lH.__ WORKING l1..:..Q voe AMPS 4 4B .n__ rICK-UP HAX. DROP-AWA JI' HIN. OPERATING TEMPERATURE RANCE. ll:.1.Q voe .OQS AMPS 3 n -1....ll voe .001 AMPS 2 2H -40°F to +1SS°F. l 2§ (Sl u: cs1 (jl llL_ "--- HO'rES 1. 2. J. 4. 5. This relay shall be tested on a periodic basis, not exceeding 2 years or current FAA-required testing interval. When relay operate out side the inservice application limits value, it ahall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60\ for inductive and 40\ for motor load. All calculations are based on 3,500 Ohm coil. 12K, 2 Watts resistor is connected in parallel to coil. A-14 .R.1':LAY ENOINl!ERINO APPLICATION INFORMATION SHEET TBIS SHEET PROVIDES GENl!:RA.L INFORMATION CONCERHINO THE CONTACTS, COIL CaARACTERISTICS FOR THIS RELAY. OPERA.TINO A.N'O TYPE OF RELAY. P0-1 Ord. Acting, Biased Neutral, Low Volt RELAY PART NUMBER. 99255686 DRAWING NUMBER~ QTY. AND TYPE OF CONTACTS: 6F6 ~ RELAY COIL RESISTANCE, F{Carbqn Silver t.ll. OHMS, to Silver) 17,500 WIRE SIZE, 74655002 (XJ REAR SERVICE S(Silver to Sllver) TUR.NS. ( J SHELF MOUNT PLUG COUPLER PART NO, J FRONT SERVICE ( (] TRAIN CAR.RIED CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX, RATING AMPS, (XJ CI (HO) HEAVY DUTY', UP TO 30 10 (S) SAFETY, UP TO 30 4 [J OPERATING CHARACTERISTICS. 1:::-L !::: OPERATING PARAMETERS MAX. OPERATING TIME AT tlORM.AL VOLTAGE (XJ AMPS, [ J FACTORY STANDARD CJI.LIBRATION VALUE INSERVICE APPLICATION LIMITS, llQ... :: voe HIGH VOLTAGE, CONTACTS ARRANGEMENT AS VIEWED FROM REAR LEFT SIDE RIGHT SIDE - - - AMPS aoo otun 10 - - - AMPS (-)COir....t'"'\...i+)COIL 9 6F SECOND a 6H RELEASE .9.:..Q1_ SECOND 7 ) PICK-UP~ l (HV} - - - - AMPS INTERMITTENT CS) SH (SI SK SB } DROP-AWA:! voe - - - AMPS 6 4f tSl JH l VDC - - - AMPS s 4H JH VDC AMPS 4 PICK-UP WORKING !L..Q_ PICK-UP MAX, ~voe .011 AMPS 3 DROP-AWAY MIN, Ll.Q..... voe .002 AMPS 2 l OPERATING TEMPERATURE RANCE, 1 4B 2F IS) lf ISi lH 2a 18 NOTES 1, 2. 3. Thia relay shall be teated on a periodic basis, not exceeding 2 years or current FRA-required testing interval. When relay operate out side the inservice applicaticn limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to !actor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60\ for inductive and 40\ for motor load. ( A-15 RELAY ENOINEERINO APPLICATION INFORMATION SB%~ THIS SHEET PROVIDES CEN'Z:JllU. INFORMATION CONCER.NIHO TBE CONTACTS, COIL AND OPERATING CZIARACTERISTICS FOR THIS RELAY. TYPE OF RELAY. P0-1 Ord, Acting, Biaeed RELAY PART NUMBER. 99255719 Neutral, Low Volt DRAWING NUMBER~ QTY. ANO TYPE OF CONTACTS: UJ! FICarbon Si.lver to Sllver) B!Silver to l l ! WIRE SIZE, RELAY COIL RESISTANCE. 3500 OHMS, 51.lvu:) JS,000 TURNS. [X) REAR SERVICE-------- ( J SHELF MOUNT ( J FRONT SERVICE [XJ TRAIN CARRIED PLUG COUPLER PART NO. 74675211 W/Bracket CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. (X) ( S ) SAFETY. [J UP TO JO 4 (HD) HEAVY DUTY. UP TO JO 10 [I OPERATING CHARACTERISTICS, ) NORMAL 1fL..Q l OPERATING PARAMETERS OPERATING TIME AT NORMAL VOLTAGE (XJ AMPS. ( J voe _ _ _ AMPS AHPS MIN. .u..JL voe MAX. lJl.O... voe INSERVICE APPLICATION LIMITS. CONTACTS ARRANGEMENT AS VIEWED FROM REAR LEFT SIDE RIGHT SIDE 3500 Ohm 10 (-)CO~)COIL <~> 6F SECOND 8 6H SH £:L.Ql_ SECOND 7 ...6JL.. 58 - - - - - AMPS INTERMITTENT Sf cs1 5.25 voe AMPS 6 4[ fS) JF PICK-UP ll..:.Q. voe AMPS 5 4H 3H WORKING 11.0 voe AMPS 4 )PICK-UP MAX. 1a.10 voe .0053 AMPS J 2F fSl lf IS) l -1..:..ll voe .001 AMPS 2 2ff lff DROP-AWAY FACTORY STANDARD CALIBRATION VALUE HIGH VOLTAGE. 9 ) PICK-UP Q.:.ll 1RELEASE (HV) t DROP-AWAY HIN. OPERATING TEMPERATURE RANCE. -40°F to +185°F. 1 ~ 2D Sf lffDl !L..!!.I SECOND 8 §H 5H RELEASE 0.04 SECOND 7 68 (HD) SB (HQ> JF CHQ> ) PICK-UP l (HV) HIGH VOLTAGE. SAFETY UP. TO SO OC/llOV AC 15 (J DROP-AWAY .L.Q_ VDC AMPS 6 4F PICK-UP .LlL voe AMPS s ~H JH WORKING .LlL voe AMPS 4 48 CHP> 38 CHDJ PICK-UP MAX. L..1.Q_ voe 0.026 AMPS J u u: DROP-AWAY HIN. 0.67 0.005 AMPS 2 iH l OPERATING TEMPERATURE RANGE. voe -40°F to +18S°F. l (HO! HI 18 (HQ) NOTES 1. 2. J. 4. This relay shall be tested on a periodic basis, not exceeding 2 years or current FRA-required testing interval. When relay operate out aide the inservice application limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is baaed on resistive loads only, derate 60\ for inductive and 40\ for motor load. -Relay used with PO. Rectifier Unit #7880588 has Plug Coupler #74655123CJ. As Po~e Off/W Rectifier, Relay operates@ 6/7VAC Drop-Away & 9VAC Pick-Up & Work. -Relay used W/Flasher Relay Driver(FRD)#7SJJS009 has Plug Coupler#74655123CJ. As Flasher Relay it provides 43 ~ 2 Flashes/Min, starting@ lOVDe. ( A-19 RELA y E MGIMEEAIHG ( APPl.lCA TION ltFOIIMA T10N SHEET THIS SHEET PAOVIDCS CJENIERAL INFORMATION CONCERNING THE CONTACTS. COIL AND OPIERATING OfA· RACTERISTICS FOR THIS l{ELAY. TYP£ OF RELAY. PD-1 Ord. Acting, Biased Neutral, ':'9260400 AELA Y PART NUMBER. A&:LAY COIL RESISTANCE. _t1_3_o__ WIAIE SIZE, 74655002 "'°"' REV. (.' 5C64 3 Ecoat & BacJdS fl ver Graz:,bte to SI Jver) CHY} 5_0_0_ _ _ OHMS, PlUG COUPLER PART NO. Volt Front and Back ORA WING NUMBER. 6EB QTY. ANO TYPE OF CONTACTS: High SIIIWICS - - - - - _ _ _ TURNS. 13 _ ,000 D ...., MaUNr - - - - - 0 1'IWN Cl RIIII - - - - - - CONT ACT DAT A ::J APPLICATION (S) SAF&:TY. MAX. RA TING VOL TS. 0 ... 25 10 OPERA TJNG CHARACTERISTICS. 12.0 N09oW. OPERATING PARAMETERS ...., { OPERA TING TIME AT NORMAL VOL TAG£. CJ AMPS, C FACTORY STANDARD CALIBRA TfON VALUE. INSERVICE .APPICA TION LIMITS. MAX. 6 so _l_20__ {-., .... 0.25 0.02 {-···· CONT ACTS ARRANGEMENT AS VIEW£1> FROM AIEAR YDC--- y DC - - - SIECCM ltlClt.QI 6 .::>O Y.DC WOM... 6. ::>O Y. DC ~AWAY MK OPERA TING TEMPERATURE RANGE. l.34 v. DC Y.DC ...,. ,... ..6.FCHi.-S) 51.!ll.V.:.S) SH 7 6H --_ji_H!:_S) 8 _4I(FL-SJ :J..FJ.liY-:.S) !5 --- - 3H AWS INTtRMITTIMT9 I Y. DC soo.ll- 10 (·)COlf=-J~•)C(:;; sacoD 2.0 {....... _,,_ ...,...,. lfOC--- 7.15 HIGH VOLTAG£. SAFETY UP TO 30 UP TO 30 UP TO 30 MAX. RA TING AMPS. llJ (HY) (HD) HEAVY DUTY. .,..... .,..... 4H M4'S 4' .AB 4HU.. S) .Ut43 N4'S 3 .0026 N4'S .J.E Clti.-S) 31!, __ ·<40• F TO •18!S• F. 2 1 2B(HV-S) ---- --- - !B!f!.V:_S) --- - . lB.!JiY-:..c; > 1100:..S) !.H_ -lB(HV-S) --- - NOTES I. 2, 3· THIS RELAY SH.&lL BE TESTED ON A PERIODIC BASIS, NOT EXCEEDING 2 YEARS OR CURRENT FRA·REOUIRED TEST! NG INTERVAL. WHEN RELAY OPERATE OUT SIDE THE INSERVtCE APPLICATION LIMITS V.&WEf IT SHALL IE R!CONDITIONED AS PER PO-I REUY SHOPPING PROCEDURE AND CALIBRATE TO FACTORY S ANDARD CAL18MTION VALUE. CONTACT AMPERE RATING IS BASED ON RESISTIVE LOADS ONLY, OERATE 10°/o FOR INDUCTIVE ANO 40°/0 FOR MOTOR LOAD. ( .. A-20 RELAY ENOINl!:ERINO APPLICATION INFORMATIOH SBZET THIS SHEET PROVIDES OEN!!RA.L INFORMATION CONCERNING TBE CONTACTS, COIL AHl> OPERATING CJIJUlACTERISTICS FOR THIS RELAY. TYPE OF RELAY. po-1 Slow Release Biased RELAY PART NUMBER. 99260501 DRAWING NUMBER QTY. AHO TYPE OF CONTACTS: §.Ei HLgh Neutral Voltage 5C659 REV-F INDEX CODE 1:J. FIAC Craphite to Silver) B(AC to AG Graphite) i l l WIRE SIZE, RELAY COIL RESISTANCE. 1QQ_ OHMS, 74655156 (X) REAR SERVICE 6.SOQ TURNS. ( J SHELF MOUNT PLUC COUPLER PA.RT NO. FRONT SERVICE--~----~ ( J TRAIN CARRIED - - - - CONTACT DATA FRO»!T CONTACTS APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. I ) ( S) SAFETY. UP TO JO () (HD) HEAVY DUTY. UP TO JO 10 4 ' FRONT CONTCTS (HV-S) (HV) HIGH VOLTAGE. SOVDC/llOV AC lSA (X) OPERATING CHARACTERISTICS. r= OPERATING PARAMETERS l L voe AMPS CONTACTS ARRANGEMENT AS VIEWED FROM REAR LEFT SIDE 200 Ohm RIGHT SIDE HIN. ~ voe AMPS MAX. ll.:..Q. voe AMPS INTERMITTENT 10 9 (-)COIL~+)COIL 6F HV-s .SF Kv-s 1X,2W OPERATING TIME AT NORMAL VOLTAGE ( AMPS. ( rICK-UP l!.,.M RELEASE L.6...... 1DROP-AWAY FACTORY STANDARD CALIBRATION VALUE IN SERVICE APPLICATION LIMITS. SECOND 8 61:1 SECOND 7 68 HV-s SB 1:1v-s .fill._ voe AMPS 6 4F HV-s 3f KV-S PICK-UP LL voe AMPS s 4lf Jlf WORKING L.l_ voe AMPS 4 48 HV-s 38 HV-s HV-s u: 1:1v-s ~ rICK-UP MAX. DROP-AWAY MIN. OP.ERATINO TEMPERATURE RANCE. 1..:..lL voe 0.035 AMPS J JF J.....ll.. voe 0.0067 AMPS 2 2H -40°F to +18S°F. 1 26 m!-:i lH UI HV-§ NOTES 1. 2. J. This relay shall be teated on a periodic basis, not exceeding 2 years or current FRA-required testing interval. When relay operate out side the inservice application limits value, it shall .be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Plug coupler part# 74655156 has built-in capacitor 4100 MFD 50V in aeries with l ohm, SW resistor, to give a minimum total delay drop of 3.0 sec. ( A-21 RELAY ENOIH!!ERINO APPLICATION INFORMATION sazr.r TBIS SKEET PROVIDES OEN'EJtAL INFOtu(ATION CONCERHIHO THE CONTACTS, COIL A.ND OPEJtATINO CltAR.ACTERISTICS FOR TBIS IU!:LAY. TYPE OF RELAY. P0-1 Slow Btlt1•• Biaeed Neutral High Voltage RELAY PA.RT NUMBE~. 99260502 DRAWING NUMBER~-~~~- QTY. AND TYPE OF CONTACTS: §.I.Jl F[Sllver to Sllver) fil RELAY COIL RESISTANCE. l.Q.SL. OHHS, INDEX CODE C-S HO WIRE SIZE, (XJ REA.a SERVICE 6.500 TURNS. f I SHELF MOUN'l' PLUG COUPLER PART NO. rI FRONT SERVICE CONTACT DATA TRAIN CARRIED FRONT CONTACTS APPLICATION HAX. RAT INC VOLTS. HAX. RATING AMPS. { J (S) SAFETY. (X UP TO 30 4 r~ J (HD) HEAVY DUTY. UP TO 30 10 FRONT CONTCTS (HV-S) ( l (HV) HICH,VOt.TACI:. 50VDC/ll0V AC lSA OPERATING CHARACTERISTICS. OPEMTING PARAMETERS MIN. ! MAX. OPERATING TIME AT NORMAL VOLTAGE ( AMPS. ( ··---· .u_ voe AMPS -3..:...i voe AMPS ll.& voe AMPS INTERMITTENT INSERVICE APPLICATION LIMITS. 10 9 (-)COI~(+)COIL 6[ HD ..J.l..J!l2 1X,2W ...m_ SECOND 8 §H RELEASE .l..,_§__ SECOND 7 69 HQ 58 HD Hp PICK-UP ll.,.iS l.:.Q_ voe AMPS 6 4[ HQ 3[ §.....L voe AMPS s ~H 31S WORKING §.....L voe AMPS 4 48 HQ 38 ttP PICK-UP MAX, 1.:...1.L voe 0.035 AMPS J n u: DROP-AWAY HIN. .ldL VDC 0.0067 AMPS 2 2H rROP-AWU FACTORY STANDARD CALIBRATION VALUE CONTACTS A.RRAN'GEMEHT AS VIEWED FROM REAll LEFT SIDE 200 Ohm RIGHT SIO: PICK-UP l OPERATING TEMPERATURE RANCE. -40°F to +185°F. l HP 28 1:1'2 HQ lH u l:!Q HOTZS 1. 2. 3. Thi• relay shall be teated on a periodic ba•i•, not exceeding 2 year• or current FRA-required testing interval. When relay operate out side the inservice application limit• value, it ahall be re~onditionad as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Plug coupler part I 74655156 has built-in capacitor 4100 MFD SOV in aerie• with l ohm, SW resistor, to give a minimum total delay drop of J.O sac. ( A-22 RJ!:LAY ENOIN!:ERIHO APPLICATION INFORMATION SHEET TBIS SBEET PROVIDES OEHERAL INFORMATION CONCERNINO TBE CONTACTS, COIL AND OPEJUI.TIXO Cl!A.lu.CTERISTICS FOR THIS RELAY. TYPE OF R!:LAr. P0-1 Overload DRAWING NUMBER 5C61J REV-B RELAY PART NUMBER. 99275015 QTY. AND TYPE OF CONTACTS: ( J ( S ) SAFETY • 4 J::~ OPERATING PARAMETERS MAX. ·:;:l :: IDROP-•••• (] SHELF MOUNT ( J TRAIN CARRI.ED - - - - (HD) HEAVY DUTY. UP TO JO 10 [XJ 150 WATT (3A MAX.) CONTACTS ARRANCEKEHT AS VIEWED FROM REAR LEFT SIDE RIGHT SIDE AMPS AMPS 1201120 voe OPERATING TIME AT ~7-10 SEC. NORMAL VOLTAGE [ AT AMPS. (X 12 AMPS FACTORY STANDARD CALIBRATION VALUE [J UP TO JO OPERATING CHARACTERISTICS. WITHOUT 0.046 OHM RES. ~ "lH-18. lHFB Make Before Break. f & 8 (Palladlum-Silve, Non-Vitali RELAY COIL RESISTANCE. 25/200 OVERLOAD/STICK ( ) REAR SERVICE PLUC COUPLER PART NO. {X] FRONT SERVICE 74675244 CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. INDEX AMPS INTERMITTENT WITH 0.046 OHM RESISTOR 0,1/0.2 v o e _ AMPS PICK-UP Jl§ voe AMPS s WORKING 3/8 voe AMPS 4 INSERVICE APPLICATioficK-UP MAX. 3.3/8/8 voe .132/.044 AMPS 3 LIMITS, ~ROP-AWAY MIN •. 067/.134 VOC.002/.0007 AMPS 2 1_ OPERATING TEMPERATURE RANGE. NOTES l. 2. 3. Thia relay ahall be teated on a periodic ba•i•, not exceeding 2 years or current FR.A-required testing interval. When relay operate out side the inservice application limita value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derata 60, !or inductive and 40\ for motor load. ( A-23 RELAY ENOIH!:ERIHO APPLICATION INFORMATION SB'EET THIS SBEET PROVIDES GENERAL IN~ORMATION CONCERNING THE CONTACTS, COIL AN'D OPEJtATINO CKARACTERISTICS FOR THIS R.!:LAY. TYPE OF RELAY. P0-1 fla1her e1a,ed N2utral W/Heavy outy Front & Back RELAY PART NUMBER. 99275037 DRAWING NUMBER~ f&B,{Sllver to Sllver) QTY. AND TYPE OF CONTACTS: irJl 11.1 RELAY COIL RESISTANCE. tl2. WIRE SIZE, OHMS, (XJ REAR SERVICE 74§55026 6,700 TURNS. ( ) SHELF MOUNT PLUG COUPLER PART NO. ( J FRONT SERVICE ( J TRAIN CARRIED - - - - CONTACT DATA ( J ( S ) SAFETY. APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. (XJ UP TO 30 4 (HD) HEAVY DUTY. UP TO JO 10 OPERATING CHARACTERISTICS. r::~ 1::: :: OPERATING PARAMETERS LMAX • -1.lQ. voe [) HIGH VOLTAGB. AMPS CONTACTS Al\RANGZHl!HT AS VIEWED FROM REAR LEFT SIDE 125 Ohm RIGHT SIDE AMPS 10 (-)COI~(+)COIL AMPS INTERMITTENT 9 8 OPERATING TIME AT /ICK-UP !k.Q.l..SECOND NORMAL VOLTAGE (X AMPS. ( RELEASE 0.04 SECOND FACTORY STANDARD CALIBRATION VALUE KV 7 ) DROP-AWAY .L.Q_ voe A.MPS 6 4FlRPl 3FCHPl PICK-UP LJL voe AMPS s 4H lH.._ WORKING LJL voe AMPS 4 4F8(HQ) 3BfHPl l IN SERVICE APPLICATIOyicK-UP MAX. l.:.lQ_ LIMITS. lDROP-AWAY MIN.0.67 OPERATING TEMPERATURE RANGE. -40°F voe 0.264 AMPS 3 nunn lt!HJ2) voe 0.0053 A.MPS 2 2H ~- to +lSS°F. l 2B!HDl ll.L.W2 NOTES l. 2. 3. 4. Thia relay shall be teated on a periodic baaia, not exceeding 2 year• or current FRA-required testing interval. When relay operate out side the inservice application limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60, for inductive and 40, for motor load. When this relay la used with Transcontrol Relay Driver Style (F.R.D.D) Part Number 75335009, it will provide 43 ± 2 Flaahea per minut•, starting at 10 VDC. ( A-24 RELAY l!:NOIN!:ERIHO APPLICATION INFORMATION SHEET TBIS SHF.r.t' PROVIDES ODfERAL INFORMATION CONCERNING THE CONTACTS, COIL CllJUtACTERISTICS FOR THIS R.!:I.AY. TYPE OF RELAY. P0-1 Light Out. Blaged Neutral RELAY PA.RT NUMBER. 99275048 JUfl) OPEJlA.TIMO Low Volt, CR.AWING NUMBER SC517 COIL INDEX .E:.=fl [(Silver Carbon to Sllver)BtSllver to Sllverl A-Coil- .15 A-coil #14 A-Coil 180 RELAY COIL RESISTANCE.a-coil- J.251 OHMS, a-coil tJ.1. WIRE SIZE,B-Coil ~ TURNS. QTY. AND TYPE OF CONTACTS:~ (x J REA.I\ SERVICE 74655Q;J7 [ I SHELF MOUNT PLUG COUPLER PA.RT NO. [ ( l TRAIN CARRIED J FRONT SERVICE CONTACT DATA APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. (x J (J (S) SAFETY. UP TO 30 4 (HOJ HEAVY DUTY. 10 CONTACTS A.RRAKGEH.ENT AS VIEWED FROM REAR LEFT SIDE A-Coil RIGHT SIDE OPERATING CHARACTERISTICS. B A NORMAL l l _ voe OPERATING PARAMETERS KIN. MAX • .L.filL AMPS __rr('""\_ !L.ll voe 2..:.filL AMPS ....ll.Q B 10 (-)COIL voe _l._ AMPS INTERMITTENT A OPERATING TIME AT PICK-UP ___,_il ~SECOND NORMAL VOLTAGE (XJ B A AMPS. (XJ RELEASE .....Ql.Q ...9l.i SECOND a-coil FACTORY STANDARD CALIBRATION VALUE [] HV HIGH VOLTACZ. UP TO 30 (+)COIL .15 Ohm >-Col~3 JSO Ohm 7 DROP-AWAY l.:..ll A-Coil voe .Q.J.Q.Q AMPS PICK-UP L.ll voe .Q.J.Q.2 WORKING L.U voe 0.800 AMPS 4 48 voe o.aso AMPS J 2F llJ. voe 0.201 AMPS 2 2H lH_ INSERVICE APPLICATION PICK-UP MAX. 2..:..Q.L LIMITS. DROP-AWAY MIN. 2. 17 OPERATING TEMPERATURE RANGE. AMPS 6 4F llJ. s lfl.._ 1 4ff 2a .ll ll HO'l'!:S 1. 2. 3. Thia relay shall be teated on a periodic basis, not exceeding 2 year• or current FRA-required testing interval. When relay operate out aide the inservice application limits value, it shall be reconditioned as per PD-1 relay shopping procedure and calibrate to !actor standard calibration value. Contact ampere rating is baaed on resistive loads only, derate 60\ for inductive and 40\ for motor load. A-25 suzrr RELAY ENOINl;ERIHO APPLICATION INFORMATION THIS SKEET P~OVIDES O~JUU. INFORMATION CONCERHIHO THE CONTACTS, COIL AllD OPE~IHO CIVUtACTERISTICS FOR THIS RELAY. TYPE or RELAY. ro-1 Magnetic stick, Biased Neutral, Low volt RELAY PART NUMBER. 99275070 DRAWING NUMBER 5C521 QTY. AND TYPE OF CONTACTS:~ F&B !Carbon Sllver 134/31 RELAY COIL RESISTANCE. 3500/220 OHMS, REY-1 to IND!X CODE 6:.1. Silver) WIRE SIZE, 35,000/6,750 TURNS. ( J REAR SERVICE ( J SHELF MOUNT (] FRONT SERVIcg ----------- (XJ TRAIN CARRIED 74675292 PLUC COUPLER PART NO. CONTACT DATA APPLICATION HA.JC. RATING VOLTS. MAX. RATINC AMPS. ( X) () (HD) HEAVY DUTY, UP TO 30 10 ( S) SAFETY. UP TO 30 4 OPER>.TING CHARACTERISTICS, OPER>.TINC PAM.METERS OPER>.TING TIME AT[(. ICK-UP NORMAL VOLTAGE (X AMPS, ( J RELEASE FACTORY STANDARD CALIBRATION VALUE }:~=G l REVERSE WORKING CONTACTS AR.RAMGEMENT AS VIEWED !'ROM REAR LEFT SIDE 3,500 Oh.me RICHT SIDE voe AMPS voe AMPS voe AMPS INTERMITTENT 10 (-)COIL~(+)COIL 220 Ohm 9 ~<-!./"'('""\•.(+) ______ ~ SECOND 8 2.:..1.Q SECOND 7 15.8/5.75 voe AMPS 15.8/5,75 voe AMPS 4P'fSl 6 s 48 INSERVICE APPLICATIOk NOR.MJI..L LIMITS, ~WORKING 17.38/6.32 l (] (HV) HIGH VOLTAGE. voe 4 48ts). ,005/.287 AMPS REVERSE WORKING.17.38/6.32 voe .005/.0287 AMP OPERATING TEMPERATURE RANGE. 2 lL_ l llill NOTES 1. 2. 3. This relay shall be tested on a periodic basis, not exceeding 2 year• or current FR.A-required testing interval. When relay operate out side the inaervice application limits value, it shall be reconditioned aa per PD-l relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating i• baaed on resistive loads only, derate 60\ for inductive and 40\ for motor load. ( A-26 RELAY ENGINEERING APPLICATION INFORMATION SHEET THIS SHEET PROVIDES GENERAL INFORMATION CONCERNING THE CONTACTS, COIL AND OPER.~TING CHARACTERISTICS FOR THIS RELAY. TYPE oF RtaAY. PD-I Magnetic Stick. Biased. Neutral. tow Yolt 99275180 RELAY PART NUMS£R. QTY. ANO TYPE OF CONTACTS: RELAY COIL RESISTANCE. PLUG COUPLER PART NO. DRAWING NUMBER. 4N-4R _1.......2...... 5_ 5C538 Re'(. C F&B(Carbon Silver to Silver) 127 OHMS, 74655002 (I) ,c,IJI SGMOi: O f'ROHT SQMCE - - - - - .. 6 , 700 WIRE SIZE, TURNS. D SHEU" MOUKr - - - - - O TRAIN~----- CONT ACT DAT A oc] APPLICATION (S) SAFETY. D (HO) HEAVY DUTY. 0 UP TO 30 MAX. RATING VOL TS. 10 4 MAX. RA TING AMPS. CONTACTS ARRANGEMENT OPERA TfNG CHARACTERISTf CS. 12.Q ll oc {~ OPERATING PARAMETERS 8 OPERA TING TIME AT NORMAL VOLTAGE. AMPS, FACTORY STANDARD CALIBRATION VALUE. 5.0 120 { ''°':"'' A£I EASE ,.,..ps V DC AM'S IHTEl!MITTE:HT. g ...7 Reverse PIO:..(Jfl MAX. DROP-AWAY MlH. 5.0 V. DC 5.0 V.DC 5.r.o 5.so -40• F TO NoPS AM"S v.oc ~ v. DC 0. 044 N4>S •18!5• F. 1:zs.n. IIICIHf SIDC 10 ( - ) C O l ~ • } C O I L O.lOsi;:00t0 W~z:k~g OPERA TING TEMPERATURE RANGE. LDT SIC&: V DC a {-1 { AS VIEWED FROM REAR ,.,..ps 0.10 SE:COK> WOAltlHCI JNSERVICE APPi CATION l..fMfTS. (HV) HIGH VOLTAGE. UP TO 30 --- ---- ---- a JEJ~ ~ _1fi_ - 4 j~J~ .3 l!:.J~ 2 1 -2B2H--(S) ---- --------- -Jf.(~ 3H --.-- _3!. (SJ J.1:1~ lH -lB --(S) --- - NOTES I. 2. 3. THIS .RELAY SHAU. 8€ TESTED ON A PERIODIC BASIS, NOT EXCEEDING 2 YEARS OR CURRENT FRA•REOUIRED TESTING INTERVAL. WHEN RELAY OPERATE OUT SIDE THE INSERVICE APPLICATION LIMITS VAWEt IT SHALL SE RECONDITIONED AS PER PO-I RELAY SHOPPING PROCEDURE AND CALISRA.TE TO FACTOR¥ S AffOARD CALIBRATION VALUE. CONTACT AMPERE RATING IS BASED ON RESISTIVE LOADS ONLY, CERATE 60% FOR INDUCTIVE AND 40% FOR MOTOR LOAD. A-27 RELAY ENOIHE!:ltIHO APPLICATION IHFORMA:tIOK SUff THIS SHEET PROVIDES OEHERJU. INFORMATION CONCER.HIHO THE CONTACTS, COIL AJfD OPERATING CHARACTERISTICS FOR THIS RELAY, TYPE OF RELAY. P0-1 Power off. 8Laeed N9ytral RELAY PART NUMBER. 99275257 DRAWING NUMBER~ QTY. AND TYPE OF CONTACTS: !l.Il F&B(Carbon Silver to Silver) S__ OHMS, RELAY COIL RESISTANCE. _.,.l.-.2.... (X) 127 REAR SERVICE 74655048 B HD (Sllyer to Sllyer) WIRE SIZE, .2..c..2.Q.Q TURNS. (] SHELi' MOUNT PLUG COUPLER PART NO. ( J FRONT SERVICE-----~ {J TRAIN CARRIED 74§75299 CONTACT DATA APPLICATION ( X) ( S) SAFETY, [XJ UP TO JO MAX. RATING VOLTS. MAX. RATING AMPS, 4 (HD) HEAVY DUTY, UP TO JO 10 OPERATING CHARACTERISTICS. ) NORMAL 1LJL voe - - AMPS voe AMPS l OPERATING PARAMETERS MIN. -2:..Q MAX. -1l.Q_ voe -- AMPS () {HV) HIGH VOLTAOS. CONTACTS ARRAMGZHZNT AS VIEWED l'ROK UAR LEFT SIDE 125 Ohm RIGHT SID! 10 (-) COIV-V-V-U +) COIL INTERMITTENT 9 OPERATING TIME AT [ICX-UP Q,Q7 SECOND NORMAL VOLTAGE (X JU.tPS. ( J RELEASE 0.04 SECOND FACTORY STANDARD CALIBRATION VALUE J 8 7 DROP-AWAY -1...Q. voe AMPS 6 .il.Lll PICK-UP ....hQ. voe AMPS s .m._ 1.:..2. voe AMPS 4 WORKING INSERVICE APPLICATI01PICK-UP MAX. 1.:..1.!2 LIMITS. ROP-AWAY MIN.0.67 OPERATING TEMPERATURE RANGE. 4B{H,D,) voe ..t.1..§j_AMPS 3 ll'..Lll voe .:..2Q1._AMPS 2 .lli -40°F to +l8S°F, l l!UH :12 • l 3l{S) ...m.. JBlH.p. J lUll -1.lL UUH,12, l NOTES l. 2. 3, 4. S. Thia relay shall be tested on a periodic baaia, not exceeding 2 year• or currant FAA-required teating interval. When relay operate out aide the inaervice application limita value, it ahall be reconditioned as per P0-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resiativa loada only, derata 60\ for inductive and 40\ for motor load. When P.O. Rectifier unit Part no. 78805088 1• in circuit, min. drop-away value is 6.70V,AC. and max. pick-up & work at 9.0V.·AC. When th.I.a relay is used for other application, plug coupler P/N 74655002 •hall be used. ( A-28 RELAY ENOINEERINO APPLICATION INFORMATION SBEET TBIS SHEET PROVIDES Ol:H'ICJUU. INFORMATION CONCER.NINO TBE CONTACTS, COIL AND OPEJIATIHO C!UUlACTERISTICS roR TBIS RELAY. ( TYPE OF R.ELAr. PQ-1 Magnetic Stick Low Volt RELAY PART NUMBER. 22275334 DRAWING NUMBER 5C573 QTY. AND TYPE OF CONTACTS: .i1L..!8 _ ...s-o.o. __ R.ELAY COIL R.ESISTANCE. REV.-E CODE INDEX~ F&B(Carbon Silter to Silver) oHMs, 130 (XJ REAR SERVICE 74655002CK 13,000 TURNS. WIRE SIZE, ( J SHELF MOUNT PLUG COUPLER PART NO. ( J FRONT SERVICE ( J TRAIN CARRIED - - - - CONTACT DATA ( J ( X J (SJ APPLICATION SAFETY. UP TO 30 HAX. RATING VOLTS. HAX. RATING AMPS. (HD) HEAVY DUTY. 4 OPERATING CHARACTERISTICS. NORMAL ll.:..Q_ I OPERATING PA.RAH.ETERS voe AMPS - - AMPS MIN. ~ voe MAX. ll.Q_ voe OPERATING TIME AT ~PICK-UP NORMAL VOLTAGE (X AMPS. ( R.ELEASE 0,10 0.10 () (HV) HIGH VOLTAGE. UP TO 30 10 CONTACTS AR.RAHGEKEHT AS VIEWED FROM UAR LEFT SIDE 500 Ohm RIGHT SIDE AMPS INTERMITTENT 10 (-)COIG+)COIL 2K,2W 9_ - SECOND 8 SECOND 7 NORMAL FACTORY STANDARD CALIBRATION VALUE [ WORKING .1Q....Q voe AMPS 6 REVERSE WORKING 12...:..Q. voe AMPS 5 .4lL_ INSERVICE APPLICATIO~ PICK~UP MAX. 1.1.:..Q LIMITS. fROP-AWAY MIN.11.0 OPERATING TEMPERATURE RANGE. .il:..Lll 3BCS) .u:.w ll.Lll J v o e ~ AMPS 2 1H l _jJL 4 4BCS) voe 0.022 A.MPS -40°F to +18S°F. 3P'(S) 28(§) ··---· ·- -1JL 18/S) NOTES l. 2. J. 4. s. 6. This relay ahall be tested on a periodic basis, not exceeding 2 years or current FAA-required testing interval. When relay operate out side the inaervice application limits value, it shall be reconditioned aa per PD-1 relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating is based on resistive loads only, derate 60\ for inductive and 40\ tor motor load. All capacitors are baaed on 500 ohm coil. 2K resistor ia connected in parallel to coil. F- NORMAL a-REVERSE ( A-29 RELAY !NOIH!!ERIHO APPLICATION INFORMATION SBEET TIIIS SBEtr PROVIDES OEN!:JlAL IHFORMATIOH COHCER.NIHO THE CONTACTS, COIL AND OPERATIHO CKAJlACTZRISTICS roa THIS lU!:LAY. TYPE OF RELAY. P0-1 Overload RELAY PART NUMBER. 99275607 DRAWING NUMBER SC~40 BIY-C RELAY COIL RESISTANCE. 25/200 OVERLOAD/STICK (XJ REAR SERVICE 74655101 PLUG COUPLER PART NO. ( J FRONT SERVICE--~----~ CONTACT DATA r~= HIN. voe _ AMPS _UL voe _ AMPS = MAX. 120/120 OPERATING TIME AT r-10 SEC. NORMAL VOLTAGE [ J AT AMPS. (X) f ( J TRAIN CARRIED voe ( X] 150 WATT (3A MAX.) CONTACTS AJlRANGZMENT AS VIEWED FROM UAR LEFT SID! RIGHT SIDE AMPS INTERMITTENT WITH 0.046 OHM RESISTOR 12 AMPS ROP-AWAY FACTORY STANDARD CALIBRATION VALUE (J SHELF MOUNT () (HD) HEAVY DUTY. UP TO JO 10 ( ) ( S ) SAFETY • UP TO 30 4 OPERATING CHARACTERISTICS. WITHOUT 0.046 OHM RES. OPERATING PARAMETERS £::1: lH-18. lHFB Hake 8e(or9 Break. F & B {Palltdlum-Sllyer Non-Vitali QTY. A.NO TYPE OF CONTACTS: APPLICATION MAX. RATING VOLTS. MAX. RATING AMPS. INDEX 0.1/0.2 voe _ - - AMPS PICK-UP 3/§ voe WORKING 3/8 voe_ AMPS AMPS INSERVICE LIMITS. 1 __ ~PERATING TEMPERATURE RANGE. NOTES l. 2. J. 4. Thi• relay shall be teated on a periodic ba•i•, not exceeding 2 year• or current FRA-required testing interval. When relay operate out side the inservica application limits value, it ahall be reconditioned as per P0-1 relay shopping procedure and calibrate to factor standard calibration value. · Contact ampere rating is based on resistive loada only, derata 60, tor inductive and 40\ for motor load. •lF contact is internally wired and this tab ia not brought out on the plug coupler. j ( A-30 Jt.ELAY EHOIN1':ERINO APPLICATION INFOIUCATION sazrr THIS SHEET PROVIDES 01!:HERAL INFORMATION CONCERHIHO TBB COH'.rACTS, COIL AND OPEltATIXO CIL\.RACTERISTICS FOR TBIS RELAY. TYPE OF RELAY. PD-1 Light Out Biased Neutral Low RELAY PART NUMBER. 99275838 DRAWINC NUMBER Voltage SC§42 Rey, B COIL INDEX D.:s;: QTY. AND TYPE OF CONTACTS: ill. [(Silver carbon to Silveri B (Silver to Sllyerl A-Coil ....l1 A-Coil tl.J. A-Coil .i§.S2 RELAY COIL RESISTANCE.a-coil~ OHMS, a - c o i l ~ WIRE SIZE, B-Coil l.10. TURNS. (XJ REAR SERVICE 14§55134 (] SHELi' MOUNT PLUC COUPLER PART NO. ( ] TRAIN CAUIED ( I FRONT SERVICE - - CONTACT DATA (XJ APPLICATION MAX. RATINC VOLTS. MAX. RATINC AMPS. ( S ) SAFETY • r OPERATINC CHARACTERISTICS. OPE RAT INC PARAMETERS l () (HD) HEAVY DUTY. UP TO 30 10 UP TO 30 4 NORMAL HIN. MAX. Coil• A' In Serie• VDC = Vl>C _ _ VDC a AMPS 1..J1L AMPS INTERMITTENT OPERATINC TIME AT ~PICK-UP _....Q~·-2-4_ SECOND NORMAL VOLTAGE ( SECOND AMPS. (XJ RELEASE 0 1 2 I FACTORY STANDARD PICK-UP CALIBRATION VALUE GRADUAL INCREASE, WORK INC DECREASE OF INPUT DC VOLTAGE INSERVICE APPLICATIOJPICK-UP MAX. LIMITS. ROP-AWAY MIN.~ (HV) HICK VOLTACa. CONTACTS AJ\RAHCZMENT AS VIEWED FROM REAR LEFT SIDE A-Coil RIGHT SIDE 0.37 Ohma 10 (-)COI~+)COIL ~ >MPS DROP-AWA'.i () 9 8 a-cou 7 4FCS> VDC .a.12.Q AMPS 6 VDC .:..ilSt 5 il_ VDC .,_12.Q AMPS 4 48 a_ VDC ..:..U.Q_AMPS 3 ll:.Lll l.t.Lll voe AMPS 2 .2lL__ 1211 OPERATING TEMPERATURE RANGE. ll..W. 1lL_ l1i_ l.L... NOTES 1. This relay shall be teated on a periodic baaia, not exceeding 2 year• or current FRA-required testing interval. 2. When relay operate out 1ide the in1arvica application limit, value, it 1hall 3. be reconditioned•• par PD-1 relay shopping procedure and calibrate to factor standard calibration value. See application circuit for light-out. ( A-31 RELAY ENOIN!!ERINO APPLICATION INFORMATION SJIZZ'r THIS SHEET PROVIDES 01!:Nl!:RAL INFORMATION COHCERHINO TBE CONTACTS, COIL AND OPERATING CllARACT!!:JlISTICS P'OR THIS Rl!:LAY. TYPE OF RELAY. PQ-1 Magnetic Blow-Out Blase~ Neutral RELAY PART NUMBER. 99275860 DRAWING NUMBER _.,.,s...o...o__ INDEX CODE ll::.§. Fiscs11ver cragh1te to s11ver) CHY> QTY. AND TYPE OF CONTACTS: .2.f:::ll RELAY COIL RESISTANCE. SC655 Rey-0 oHMs, (XJ REAR SERVICE 13.000 WIRE SIZE, 130 746551128§ TURNS. (] SHELi' MOUNT PLUC COUPLER PART NO. ( J TRAIN CARRIED - - - - ( ) FRONT SERVICE - - - - CONTACT DATA APPLICATION ( ] [XJ (HD) HEAVY DUTY. ( S ) SAFETY. MAX. RATING VOLTS. MAX. RATING AMPS. UP TO JO 15 OPERATING CHARACTERISTICS. } NORMAL l.L..!L voe AMPS l OPERATING PARAMETERS MIN. 1....Q.Q. voe - - AMPS MAX. 120 voe - - AMPS INTERMITTENT OPERATING TIME AT {ICK-UP NORMAL VOLTAGE [X AMPS. ( RELEASE FACTORY STANDARD CALIBRATION VALUE 0, 16 SECOND 0,03 SECOND (KV) HIGH VOLTACB. UP TO llOV 25 (NOTE l) CONTACTS ARRANCEMJ!NT AS VIEWED FR.OK REAR LEFT SIDE 500 Ohm RICHT SIDE (XJ ::: ,~ 7 } DROP-AWAY voe AMPS 6 .ll.Lll PICK-UP VDC AMPS 5 .ill_ 11L WORKING voe AMPS 4 l INSERVICE APPLICATIONSPICK-UP MAX. 7,70 LIHITS. ~ROP-AWAY HIN.1...:.li 4BtHV-s) voe 0.015 AMPS J 2f(HV-S) voe 0.002 AMPS 2 OPERATING TEMPERATURE RANCE. l 2H 38(6,P,I ;t ULH,P, l NOTES 1. 2. 3. 4. This relay shall be tested on a periodic basis, not exceeding 2 years or currant FRA-required testing interval. When relay operate out side the inservica application limits value, it •hall be reconditioned as par PD-1 relay shopping procedure and calibrate to factor standard calibration value. In connection with arc quenching magnet, intarmittant duty. Applications switch machine llOV DC load control. ./ .l\-32 R.EI.Ar ENOIN'EEKIHO APPLICATION INl"OJUIATIOH SBZt.r TBIS SHEET PROVIDES OEKJ!!JUU. INFORMATION COHCEJUfIHO TBS COHTACTS, COIL AND OPEJlATIHO CJIARACTERISTICS FOR rBIS RELAY. TYPE or RELAY. Po-1 slow B•l•••• Biased Neutral Low yoltage, R£LAY PART NUMBER. 99275§82 DRAWING NUMBER QTY. AND TYPE OF CONTACTS: .§LI 5C557 BEY-A INDEX 1::.1 ,,carbon Sllver to Silver) B(Sllver to Silyerl n.1 R£LAl' COIL R.ESIST.ANCE • .i.Q5L OHMS, (XJ REAJ\ SERVICE 6.500 WIRE SIZE, 746§5002 TURNS. ( J SHELF MOUNT PLUC COUPLER PAJ\T NO. ( ) FRONT SERVICE--~~~- (J TRAIN CARRIED CONTACT DATA APPLICATION MAX. RATINC VOLTS. MAX. RATING AMPS. (XJ ( S) (J (HD) HEAVY DUTY. SAFETY. (J 4 OPERATING CHARACTERISTICS. r= OPERATING PARAMETERS (HV) HICK VOLTAGE. UP TO 30 10 UP TO 30 CONTACTS ARRANGEHEN't AS VIEWED FROM UM LEFT SIDE 200 Ohm RIGHT SIDI ll.J2 voe _ AMPS MIN. _g,.:.i voe _ AMPS MAX, .ll.2 voe _AMPS INTERMITTENT 10 9 (-)COI~+)COIL 6F (S) Sf CS) lX,2W OPERATING TIME AT NORMAL VOLTAGE (X) AMPS. ( J I'ICK-UP 2.JJ. RELEASE $L.L J FACTORY STANDAltD CALIBRATION VALUE INSERVICE APPLICATION LIMITS, SECOND 8 6H SH SECOND at 12V 7 68 58 DROP-AWAX _LQ voe AMPS 6 4F CS) JP' cs> PICK-UP __L.i voe AMPS s 411 311 WORKING ~ voe AMPS 4 48 38 fPICX-UP MAX • ..1...ll VDC 2:Q36 AMPS 3 n: DROP-AWAY MIN • .L..li voe 0.067 AMPS 2 2J:1 OPERATING TEMPERATURE RANGE. -40°F to +185°F. l 211 CS) lf CS) lH 111 NOTES l, 2. 3. 4. s. Thia relay shall be teated on a periodic baais, not exceeding 2 yeara or currant FRA-required teating interval. When relay operate out aide the inaervice application limits value, it ahall be rec~nditionad as par PD-l relay shopping procedure and calibrate to f&ctor stand~rd calibration value. Contact ampere rating is based on resistive loada only, derata 60\ for inductive an~ 40\ for motor load. All calculation• are baaed on 200 ohm coil. lK reaiator la connected in parallel to coil. J ( A-33 JU!'LAY EHOINEERINO APPLICATION INFORMATION SJIEE'r TJIIS SBEET PAOVIDES 01!:H'El'lAI. INFORMATION CONCERNINO THE CONTACTS, COIL AND OPZ~INO CJ!JUtACTJ!!RISTICS FOK THIS RELAY. TYPE or RELAY. pp-1 Ord. Actlng Blastd Neutral Low voltage. RELAY PART NUMBER. 99275893 DRAWING NUMBER 5C658 REV-& QTY. AND TYPE OF CONTACTS: §.DI [(Carbon Sllyer to Sllyer) B(Sllywr tq Silver) RELAY COIL RESISTANCE • .i2.2.._ (X) i.1.2 WIRE OH.MS, REAR SERVICE INDEX Jl::l 13.000 TtntNS. SIZE, [ J SHELF MOUNT 74655QQ2 PLUG COUPLER PART NO. ( l TRAIN CAR.RIED J FRONT SERVICE ( CONTACT DATA APPLICATION AATINO VOLTS. MAX. RATING AMPS. (XJ MAX. ( J (HDJ HEAVY DUTY. SAFETY. UP TO 30 (S) 4 r~ ( J CHV) HIGH VOLTACJ:. UP TO 30 10 CONTACTS AIU\ANOSHZHT AS VIIWBD FROM UAR LEFT SIDB 500 Ohm RIGHT OPERATING CHARACTERISTICS. VDC ~ voe .ll2. voe MIN. OPERATING PARAMETERS l MAX, OPERATING TIME AT NORMAL VOLTAGE (X) AMPS. ( I PICK-UP FACTORY STANDARD CALIBRATION VALUE INSERVICE A.PPL I CATION AMPS _ AMPS 10 AMPS INTERMITTENT (-JCOI~L 9 §1: t:U SECOND B §fJ SIJ SECOND at 12V 7 68 58 cs) DROP-AWAY voe AMPS 6 4l PICK-UP --L.i voe AMPS 5 411 3H WORKING --L.i voe AMPS 4 48 38 AMPS 3 2t {U lP' l!l .0027. AMPS 2 2H lff PICK-UP """· ..l.,.ll voe DROP-AWAY MIN,L.li voe OPERATING TEMPERATURE RANGE. d2143 -40°F to +185°!'. 1 211 CJ> 31' <§> --1.& I SIOJ 2JC,2W Jl...ll RELEASE .2..a...Q1 J .. LIMITS. ll....Q u MOTES 1. 2. 3. 4. S. Thia relay •hall be tested on a periodic basis, not exceeding 2 year• or current FAA-required testing interval, When relay operate out side the inaervice application limit• value, it ahall be reconditioned aa per PD-l relay shopping procedure and calibrate to factor standard calibration value. Contact ampere rating ia based on resistive load• only, derate 60\ for inductive and 40\ for motor load. All calculation• are baaed on 500 Ohm coil. 2K reaiator is connected in parallel to coil. I ( A-34