Smoke Detector Reversing Relay Module
D132A
Installation Instructions 1.0
Introduction
2.0
The D132A Smoke Detector Reversing Relay Module allows compatible control panels to sound all smoke detectors connected to Point or Zone 1 when a single smoke detector on the loop goes into alarm. To restore the smoke detectors to normal, reset the smoke detectors.
1.
Mount the D132A
Align the D132A with an available three-hole module mounting location in the enclosure. Refer to the control panel’s installation instructions for locations inside the enclosure.
Figure 1: Three-hole Mounting Pattern
Refer to Table 1 for a list of control panels that are compatible with the D132A.
1
Table 1: Compatible Control Panels Control Panel ICP-EZM2 DS7240/ DS7220 D6412/ D4412 D2812 D2412U/ D2412UE D2212B/ D2212BE D2212
Document Title Easy Series 2 Installer Guide DS7240/DS7220 Reference Guide D6412/D4412 Installation Guide D2812 Installation Guide D2412U/D2412UE Installation Guide D2212B/D2212BE Installation and Operation Guide D2212 Installation Manual
Part Number F01U025147 49720 45349 33120
1-
Three-hole mounting pattern
35115
2. 39934 74-07361-000
For compatible smoke detectors, refer to the appropriate smoke detector compatibility list for the control panel you are using with the D132A. Test according to NFPA. cUL: Install according to CAN/ULC-S540.
Fasten the D132A to the enclosure with the three supplied screws.
D132A
3.0
Wire the D132A Connect the TRBL PT- and TRBL PT + terminals on the D132A to an on-board point on the control panel.
1.
Refer to Table 2 to ensure you are using the proper wire gauge for the number of smoke detectors used, and for the length of the smoke detector circuit.
Table 2: Wire Gauge Specifications Maximum Smoke Detector Circuit Length Number of Smoke Detectors 1 2 3 4 5 6 7 8 9 10
0.8 mm (22 AWG) 285 m (935 ft) 285 m (935 ft) 142 m (465 ft) 95 m (310 ft) 70 m (230 ft) 56 m (185 ft) 47 m (155 ft) 40 m (130 ft) 35 m (115 ft) 30 m (100 ft)
1.0 mm (20 AWG) 454 m (1490 ft) 454 m (1490 ft) 227 m (745 ft) 150 m (495 ft) 113 m (370 ft) 90 m (295 ft) 75 m (245 ft) 64 m (210 ft) 56 m (185 ft) 50 m (165 ft)
1.1 mm (18 AWG) 722 m (2370 ft) 722 m (2370 ft) 722 m (1185 ft) 241 m (790 ft) 180 m (590 ft) 143 m (470 ft) 120 m (395 ft) 103 m (335 ft) 90 m (295 ft) 79 m (260 ft)
1.3 mm (16 AWG) 1149 m (3770 ft) 1149 m (3770 ft) 575 m (1885 ft) 383 m (1255 ft) 287 m (940 ft) 229 m (750 ft) 191 m (625 ft) 163 m (535 ft) 143 m (470 ft) 127 m (415 ft)
D132A Installation Instructions 35567E
Page 2
© 2006 Bosch Security Systems, Inc.
D132A 2.
Connect the D132A to the control panel as shown in the following figures:
Figure 2: D132A to D2000 Series Control Panels 1 STANDBY
BLK RED
Ext1 Ext2 1+
1- Com 2
3 Com
4
5
Com 6
7 Com 8
T
T1 R1
R
3 (-)
TRBL PT -
(+)
TRBL PT + REVERSE TRIGGER
(-)
AUX PWR -
(+)
AUX PWR +
2
FIRE PT FIRE PT + DETECTOR DETECTOR +
(-) (+) 5
4
12345-
D2000 Series Control Panel (D2212BE pictured) D132A Module End-of-Line (EOL) resistor Smoke Detectors (maximum of 10) EOL resistor
D132A Installation Instructions © 2006 Bosch Security Systems, Inc.
Page 3
35567E
D132A
Figure 3: D132A to D6412/D4412 and DS7240/DS7220 1
JP1 AUXILIARY Installer
R R1 JP2-PO1 Select
T1
R Y G B
T
Alrm +
A
PO1
B
+
L-1
-
Com
L-2
L-3
(+) (-)
Com
L-4
L-5
Com
L-6
L-7
Com
L-8
3 (-)
TRBL PT -
(+)
TRBL PT + REVERSE TRIGGER
(-)
AUX PWR -
(+)
AUX PWR +
2
FIRE PT FIRE PT + DETECTOR DETECTOR +
(-) (+) 5
4
12345-
D6412/D4412 or DS7240/DS7220 Control Panel D132A Module End-of-Line (EOL) resistor Smoke Detectors (maximum of 10) EOL resistor
D132A Installation Instructions 35567E
Page 4
© 2006 Bosch Security Systems, Inc.
D132A
Figure 4: D132 to ICP-EZM2 Control Panel 1
3 (-)
TRBL PT -
(+)
TRBL PT + REVERSE TRIGGER
(-)
AUX PWR -
(+)
AUX PWR +
(-)
FIRE PT -
(+)
FIRE PT +
2
DETECTOR DETECTOR +
(-) (+) 5
4
12345-
ICP-EZM2 Control Panel D132A Module End-of-Line (EOL) resistor Smoke Detectors (maximum of 10) EOL resistor
D132A Installation Instructions © 2006 Bosch Security Systems, Inc.
Page 5
35567E
D132A
4.0
Program the Control Panel
The following tables identify the parameters to program for each control panel when using a D132A. Table 3: D2000 Series Control Panel Programming Parameter Relay 1 Logic Relay 1 Function 1
Setting Function 1 Only Alarm Point 1: Yes Points 2 to 24: No 413##
Relay Parameter Recommended Point Code for Trouble Point
Table 4: D6412/D4412 and DS7240/DS7220 Control Panel Programming Steady Output Parameter PO3 Output Function PO3 Output Mode L-1 Point Type L-2 Point Type
Setting 1, 12 (Fire Alarm, Latching) Steady 24-Hour Fire 24-Hour Fire
Temporal Code 3 Parameter PO3 Output Function PO3 Output Mode L-1 Point Type L-2 Point Type
Setting 1, 11 (Fire Alarm) Pulse 24-Hour Fire 24-Hour Fire
Table 5: ICP-EZM2 Control Panel Programming Point 1 Parameter Point Type Circuit Style
Setting Fire Verified or Fire Instant Single 2.2 kΩ alarm circuit
Point 2 Parameter Point Type Circuit Style
PO2 (or PO3 or PO4) Parameter Setting Output Type Fire Latching
Setting Fire Instant Single 2.2 kΩ alarm circuit
D132A Installation Instructions 35567E
Page 6
© 2006 Bosch Security Systems, Inc.
D132A
5.0
Specifications Table 6: D132A Specifications Specification Dimensions Mounting Operating Voltage Current Draw (not including smoke detector current) Operating Temperature Non-condensing Relative Humidity Trouble PT Reverse Trigger Listings and approvals
Value 7.6 cm H x 7.6 cm W (3 in. H x 3 in. W) Three-hole mounting pattern 10.2 VDC to 13.9 VDC supplied by the control panel. Idle: 10 mA maximum Alarm: 70 mA maximum 0°C to +49°C (+32°F to +120°F) 5% to 93% at +30°C (+86°F) Normal Operation: Normally Closed (NC) Trouble Condition: Normally Open (NO) Requires a low input (short to ground) to activate. - UL985 Household Fire Warning System Units - CAN/ULC-S545, Residential Fire Warning System Control Units
D132A Installation Instructions © 2006 Bosch Security Systems, Inc.
Page 7
35567E
© 2006 Bosch Security Systems, Inc. 130 Perinton Parkway, Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096; Technical Support: (888) 886-6189
35567E Installation Instructions
11/06 D132A Page 8 of 8