Preview only show first 10 pages with watermark. For full document please download

Smp5ctx Series Power Supply Configuration Reference Chart:

   EMBED


Share

Transcript

SMP5CTX Series - Installation Guide Overview: These units convert a 115VAC or 230VAC, 50Hz/60Hz input into a regulated 12VDC or 24VDC output up to 4 amps of continuous load current (see specifications). Number of Outputs 1 1 1 4 4 8 8 16 16 Fused Outputs x x x - PTC Outputs x x x Supervised Altronix Model Number SMP5CTX SMP5PMCTX SMP5PMCTXX SMP5PMP4 SMP5PMP4CB SMP5PMP8 SMP5PMP8CB SMP5PMP16 SMP5PMP16CB Accessory Power Distribution Module(s) PD4 PD4CB PD8 PD8CB PD16W PD16WCB Individual Output Rating (amp) SMP5CTX Series Power Supply Configuration Reference Chart: 3.5 2.5 3.5 2.5 3.5 2.5 x x x x x x x x 115VAC/ 230VAC Input Current (amp) 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 0.95 / 0.5 12/24VDC Total Output Current (amp) 4 4 4 4 4 4 4 4 4 Specifications: Features: Input: • Universal 115/230VAC input. Battery Backup: • Maximum charge current 0.5 amp. • Filtered and electronically regulated outputs. • Built-in charger for sealed lead acid or gel type batteries. • Automatic switch over to stand-by battery when AC fails (zero voltage drop). • AC input and DC output LED indicators. • Short circuit and thermal overload protection. • Complete with power supply, power distribution module (when applicable), enclosure, cam lock & battery leads. • Power on-off switch. Supervised Models Only: • AC fail supervision (form “C” contacts). • Low battery supervision (form “C” contacts). Power Supply Voltage Output Specifications: * Output VDC Switch Position 12VDC SW1 - Closed (Fig. 1b, pg. 3) 24VDC SW1 - Open (Fig. 1b, pg. 3) Max. Load DC 4 amp 4 amp *Specified at 25˚ C ambient. Installation Instructions: The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations. 1. Mount the unit in the desired location. 2. Set SW1 on the power supply board to the desired DC output voltage (Power Supply Voltage Output Specification Chart). 3. Connect AC power to the terminals marked [L & N]. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). Keep power-limited wiring separate from non power-limited wiring (115/230VAC / 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. SMP5CTX Series - 1 -­ 4. Connect devices to be powered: a. For Power Supply Board: connect to the terminals marked [– DC + ]. b. For Power Distribution Module(s): connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N through 4P & 4N] (Fig. 2, pg. 4) or 1 to 8 marked [1P & 1N through 8P & 8N] (Fig. 3, pg. 4) or 1 to 16 marked [1P & 1N through 16P & 16N] (Fig. 4, pg. 4), carefully observing correct polarity. Note: Measure output voltage before connecting devices. This helps avoiding potential damage. Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit, AC mains should be removed. 5. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: When batteries are not used, a loss of AC will result in the loss of output voltage. 6. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1a, pg. 3). LED Diagnostics: Red (DC) ON ON OFF OFF Green (AC) ON OFF ON OFF Power Supply Board: Terminal Legend L, G, N – DC + AC FAIL NC, C, NO Low Battery NC, C, NO. – BAT + Power Supply Status Normal operating condition Loss of AC. Stand-by battery supplying power No DC output Loss of AC. Discharged or no stand-by battery. No DC output. Terminal Identification: Function/Description Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral. 12VDC / 24VDC @ 4 amp continuous non power-limited output. Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 120VAC / 28VDC Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 120VAC / 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC. Stand-by battery connections. Maximum charge rate 0.5 amp. PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module: Terminal Legend PD4/PD4CB PD8/PD8CB PD16W/PD16WCB 1P to 4P 1P to 8P 1P to16P 1N to 4N 1N to 8N 1N to 16N - 2 -­ Function/ Description Positive DC power outputs. Negative DC power outputs. SMP5CTX Series CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating. Switch disables power mains line voltage input. ON OFF If stand-by battery (batteries) are connected, the DC output remains on. OFF ON 5A 250V L LOW BAT NC C NO NC C NC INPUT NC C Power Distribution Module(s) AC DC AC FAIL 115/230VAC power mains AC FAIL NC C NO Fig. 1a Green Lead N Wire Strap (from Enclosure to Door) G NO LOW BAT LED Diagnostics OPEN - 24VDC CLOSED - 12VDC Green Power Supply Status (AC) ON Normal operating condition. OFF Loss of AC. Stand-by battery (batteries) supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery (batteries). No DC output. --- DC + Red (DC) ON ON --- BAT + Fig. 1 SWITCH OPEN Fig. 1b SWITCH CLOSED SW1 24VDC output - OPEN 12VDC output - CLOSED Optional Rechargeable Stand-by Battery Optional Rechargeable Stand-by Battery CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. SMP5CTX Series - 3 -­ Power Distribution Module(s): Fig. 2 Fig. 3 F1 Used on PTC Models F2 F3 F4 Used on PTC Models 1P, 2P, 3P, 4P = FUSED OUTPUTS 1N, 2N, 3N, 4N = COMMON OUTPUTS 1 2 3 4 5 6 7 8 P D1 FUSED POWER OUTPUTS R1 LED LED N INPUT COMMON 1P 1N COMMON 2P 2N POWER 3N 3P 4P common outputs protected outputs OUTPUTS DC Output to devices From Power Supply Board (Factory Installed) From Power Supply Board (Factory Installed) 9 10 11 12 13 14 15 16 N P P P N N 1 2 3 4 5 6 7 8 POWER INPUT OUTPUTS DC Output to devices Fig. 4 4N XFMR Input S Used on PTC Models 3.5A 250V - 4 -­ For continuous protection against risk of fire replace fuses with same type and rating. SMP5CTX Series Enclosure Dimensions for: • SMP5PMCTX • SMP5PMP4 • SMP5PMP8 • SMP5PMP8CB • SMP5PMP4CB • SMP5PMP16 • SMP5PMP16CB 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) Enclosure accommodates up to two (2) 12VDC/7AH batteries. Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix). 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 1.0” (25mm) SMP5CTX Series 10.5” (267mm) 1.0” (25mm) - 5 -­ Enclosure Dimensions for: • SMP5PMCTXX 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) Enclosure accommodates up to two (2) 12VDC/12AH batteries. 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.79” (20.06mm) 1.25” (31.75mm) 1.75” (44.45mm) 1.5” (38.1mm) - 6 -­ 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) SMP5CTX Series Notes: SMP5CTX Series - 7 -­ Notes: Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected], Made in U.S.A. IISMP5PMCTX - Rev. 093003 - 8 -­ G08N MEMBER SMP5CTX Series