Preview only show first 10 pages with watermark. For full document please download

Solahd Ups Lrt Temperature Sensor Kit User Manual

   EMBED


Share

Transcript

S5KC Series Quick-Start Guide SolaHD UPS LRT Temperature Sensor Kit User Manual 1. Introduction The SolaHD UPS LRT (Long Run Time) Temperature Sensor Kit, P/N: S5KCLRTTEMPKIT, is used to monitor battery temperature in external third party battery cabinets, so that the SolaHD UPS can provide temperature compensated battery charging to prolong battery life. The sensor kit is shown in Figure 1. Top View Front View Bottom View Battery Connection Cable UPS Connection Cable Figure 1: SolaHD UPS LRT Temperature Sensor Kit 2. Installation The LRT Temperature Sensor Kit has two interfaces: One is a plug in terminal block connector and is connected to the rear of the SolaHD S5KC UPS; the other is a small sensor that is attached to the external battery using a screw or thermal adhesive connection. See Figure 2 for an image of these connections. Figure 2: Temperature Sensor Kit Connections S5KC Series Quick-Start Guide 3. Viewing Battery Temperature The SolaHD S5KC UPS provides a display on its front for control and status. As shown in Figure 3, the display has an LCD, menu buttons (F1 ~ F5), six LEDs, and two control buttons. Figure 3: SolaHD UPS Front Display From the home screen, press the F4 menu button in sequence until the Battery set screen is displayed, as shown in Figure 4. Confirm ‘External battery AH’ is ok (This value is based on the external battery specification). If the AH of external long back-up battery is set to 0AH the UPS will assume no external battery is present and the temperature sensor will not work. 10 Min. 8 weeks Sunday 06:00 14 AH NO 1 ▲ ▲ Low battery warning Auto batt test interval Auto batt test start day Auto batt test start time External battery AH Load factory default Battery set 2013- 08 -01 10:45:20 ▲ SolaHD S5KC Series Figure 4: Battery set screen From the home screen, press the F3 menu button, the battery screen will be displayed, as shown in Figure 5. From the first battery status screen, press the F5 menu button and the function of F3/F4 menu button switches from ‘Left/Right’ to ‘Up/Down’. At this point press the F4 menu button to scroll down to display the remaining battery data. If this battery screen displays Batt temp, the external battery temperature sensor is communicating correctly, as shown in Figure 6. 2013- 08 -01 10:45:20 Batt temp (°C) Discharge count Discharge hour (H) Ext batt-cab count ESC Figure 5: First battery status screen ▲ ▲ ESC Figure 6: Second battery status screen United States: 1.800.377.4384 | Asia/Pacific: + 65.6891.7600 | Australia: + 61.3.9721.0348 Brazil: São Paulo/SP + 55.11.2122.5777 | Brazil: Camaçari/BA + 55.71.3496.4427 | Canada: + 1.888.765.2226 China: + 86.21.3418.3888 | Europe: + 33.3.2254.1390 | Mexico/Latin America: + 52.55.5809.5049 Middle East/Africa/India: + 971.4.811.8100 www.solahd.com P/N: A272-267 Rev. 0 06/2015 25.0 303 9.4 0 Battery While every precaution has been taken to ensure the accuracy and completeness of this literature, SolaHD Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2015 SolaHD Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ® SolaHD is a registered trademark of SolaHD Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Appleton Grp LLC d/b/a Appleton Group. The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Office. All other product or service names are the property of their registered owners. © 2015, Appleton Grp LLC. All rights reserved. 2013-08-01 10:45:20 ▲ ▲ ▲ Batt voltage (V) 157.0 Batt current (A) 0.03 Remain time (Min.) 407 Batt capacity (%) 100 Batt state Fullcharged Batt string count 0 Battery SolaHD S5KC Series ▲ SolaHD S5KC Series