Selection guide Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
Coordination T2 a T3
Installation
<5m
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275
PIII-275/3+0
PIII-275/3+0
PIII-275/1+1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275/1+1
PIII-275/3+1
Selection guide
LIGHTNING PROTECTION LEVEL I
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
SPD + EMI filter SPD type
PIIIM-275/3+1
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
Step 3
SPD type
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
Additional SPD
Installation
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
ZS-1P
PDU
PK2
PI-k8 PIII-275/3+0
Art. No. 24 001
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL I ( Iimp = 100 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
1
1+0
Hospitals
HS50-50
Banks Transmission point for GSM,BTS
Follow the right direction ... step by step ...
TNC
Water stations
3
3+0
HS50-50/3+0
Aerodrome control tower
<5m
Substation Switchboard (kWh) Main switchboard
5 metres cable or decoupling element PI-L (16-120 A )
Substation Switchboard (kWh) Main switchboard
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
1+1 Bigger industrial buildings
1
Buildings with particular importance
5 metres cable or decoupling element PI-L (16-120 A )
2+0 HS50-50/2+0
TNS
Type 1, Type 2, Type 3
3+1
Lighting Protection Level I Lighting Protection Level II Lighting Protection Level III Lighting Protection Level IV
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)
4+0 SPC25/4+0
Step 1
Step 2
(object selection)
(property protection)
(selection of SPD T1)
Surge Protection Device
Art. No. 30 080
Installation
Buildings with danger of explosion
SPD SELECTION GUIDE
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Power plants
100 %
(selection of SPD T3)
System
Installation
ZS-1DSM
Step 4
(selection of SPD T2)
Classification of typical objects
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
LIGHTNING PROTECTION LEVEL I
Lightning arrester Type 1
EQUIPMENT ZS-1P
HS50-50/3+0
Art. No. 32 006
Art. No. 10 090
EBB Surge arrester Type 2
PIIIM-275/3+1
H-SV-21-09-2016-EN-sales
Surge arrester Type 3
EQUIPMENT
Art. No. 27 022
PI-3k120
Art. No. 30 307 the queen of power
HAKEL spol. s r.o. Bratri Stefanu 980 500 03 spol. Hradec HAKEL s r.o. Kralove Czech Republic Bratří Štefanů 980 500 03 Hradec Králové tel.: +420 494 942 300 Česká republika fax: +420 494 942 303 e-mail: tel.:
[email protected] 494 942 300 www.hakel.com fax: +420 494 942 303 www.isolguard.com e-mail:
[email protected] www.hakel.cz
Lightning arrester Type 1 + Type 2
EBB
SPC25/4+0
Art. No. 10 651
the queen of power
Selection guide Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
Coordination T2 a T3
Installation
<5m
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275
PIII-275/3+0
PIII-275/3+0
PIII-275/1+1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275/1+1
PIII-275/3+1
Selection guide
LIGHTNING PROTECTION LEVEL I
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
SPD + EMI filter SPD type
PIIIM-275/3+1
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
Step 3
SPD type
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
Additional SPD
Installation
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
ZS-1P
PDU
PK2
PI-k8 PIII-275/3+0
Art. No. 24 001
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL I ( Iimp = 100 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
1
1+0
Hospitals
HS50-50
Banks Transmission point for GSM,BTS
TNC
Water stations
3
3+0
HS50-50/3+0
Aerodrome control tower
<5m
Substation Switchboard (kWh) Main switchboard
5 metres cable or decoupling element PI-L (16-120 A )
Substation Switchboard (kWh) Main switchboard
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
1+1 Bigger industrial buildings
1
Buildings with particular importance
5 metres cable or decoupling element PI-L (16-120 A )
2+0 HS50-50/2+0
TNS
Type 1, Type 2, Type 3
3+1
Lighting Protection Level I Lighting Protection Level II Lighting Protection Level III Lighting Protection Level IV
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)
4+0 SPC25/4+0
Step 1
Step 2
(object selection)
(property protection)
(selection of SPD T1)
Surge Protection Device
Art. No. 30 080
Installation
Buildings with danger of explosion
SPD SELECTION GUIDE
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Power plants
100 %
(selection of SPD T3)
System
Installation
ZS-1DSM
Step 4
(selection of SPD T2)
Classification of typical objects
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
LIGHTNING PROTECTION LEVEL I
Lightning arrester Type 1
EQUIPMENT ZS-1P
HS50-50/3+0
Art. No. 32 006
Art. No. 10 090
EBB Surge arrester Type 2
PIIIM-275/3+1
H-SV-21-09-2016-EN-sales
Surge arrester Type 3
EQUIPMENT
Art. No. 27 022
PI-3k120
Art. No. 30 307 the queen of power
HAKEL spol. s r.o. Bratri Stefanu 980 500 03 spol. Hradec HAKEL s r.o. Kralove Czech Republic Bratří Štefanů 980 500 03 Hradec Králové tel.: +420 494 942 300 Česká republika fax: +420 494 942 303 e-mail: tel.:
[email protected] 494 942 300 www.hakel.com fax: +420 494 942 303 www.isolguard.com e-mail:
[email protected] www.hakel.cz
Lightning arrester Type 1 + Type 2
EBB
SPC25/4+0
Art. No. 10 651
the queen of power
Selection guide Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
Coordination T2 a T3
Installation
<5m
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275
PIII-275/3+0
PIII-275/3+0
PIII-275/1+1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275/1+1
PIII-275/3+1
Selection guide
LIGHTNING PROTECTION LEVEL I
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
SPD + EMI filter SPD type
PIIIM-275/3+1
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
Step 3
SPD type
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
Additional SPD
Installation
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
ZS-1P
PDU
PK2
PI-k8 PIII-275/3+0
Art. No. 24 001
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL I ( Iimp = 100 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
1
1+0
Hospitals
HS50-50
Banks Transmission point for GSM,BTS
TNC
Water stations
3
3+0
HS50-50/3+0
Aerodrome control tower
<5m
Substation Switchboard (kWh) Main switchboard
5 metres cable or decoupling element PI-L (16-120 A )
Substation Switchboard (kWh) Main switchboard
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
1+1 Bigger industrial buildings
1
Buildings with particular importance
5 metres cable or decoupling element PI-L (16-120 A )
2+0 HS50-50/2+0
TNS
Type 1, Type 2, Type 3
3+1
Lighting Protection Level I Lighting Protection Level II Lighting Protection Level III Lighting Protection Level IV
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)
4+0 SPC25/4+0
Step 1
Step 2
(object selection)
(property protection)
(selection of SPD T1)
Surge Protection Device
Art. No. 30 080
Installation
Buildings with danger of explosion
SPD SELECTION GUIDE
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Power plants
100 %
(selection of SPD T3)
System
Installation
ZS-1DSM
Step 4
(selection of SPD T2)
Classification of typical objects
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
LIGHTNING PROTECTION LEVEL I
Lightning arrester Type 1
EQUIPMENT ZS-1P
HS50-50/3+0
Art. No. 32 006
Art. No. 10 090
EBB Surge arrester Type 2
PIIIM-275/3+1
H-SV-21-09-2016-EN-sales
Surge arrester Type 3
EQUIPMENT
Art. No. 27 022
PI-3k120
Art. No. 30 307 the queen of power
HAKEL spol. s r.o. Bratri Stefanu 980 500 03 spol. Hradec HAKEL s r.o. Kralove Czech Republic Bratří Štefanů 980 500 03 Hradec Králové tel.: +420 494 942 300 Česká republika fax: +420 494 942 303 e-mail: tel.:
[email protected] 494 942 300 www.hakel.com fax: +420 494 942 303 www.isolguard.com e-mail:
[email protected] www.hakel.cz
Lightning arrester Type 1 + Type 2
EBB
SPC25/4+0
Art. No. 10 651
the queen of power
Selection guide Classification of typical objects
System
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL II ( Iimp = 75 kA)
1
1+0 HS50-50
Industrial buildings Administrative buildings
Selection guide
LIGHTNING PROTECTION LEVEL II
TNC
Schools 3
Supermarkets
3+0
HS50-50/3+0
Coordination T1 and T2
Installation Substation Switchboard (kWh) Main switchboard Substation Switchboard (kWh) Main switchboard
<5m
5 metres cable or decoupling element PI-L (16-120 A )
Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
PIIIM-275
Objects connected by buried cable.
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
PIII-275/3+0
1+1 1
5 metres cable or decoupling element PI-L (16-120 A )
PIII-275/1+1
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
2+0 PIIIM-275/1+1
HS50-50/2+0
TNS 3+1
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
Coordination T2 a T3 <5m
PIII-275/3+0
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Cathedrals
Installation
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Selection guide
LIGHTNING PROTECTION LEVEL II Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter SPD type
Installation
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PI-k(8-150A)
Additional SPD SPD type
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Classification of typical objects
System
No. of phases
Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Objects with the main back-up fuse up to 63A connected by buried cable.
1
1+0 SPC25
LPL III Apartment houses Small administartive buildings
TNC
Family houses
PIIIM-275/3+1
Step 2
PI-3k(16-120A)
Step 3
(selection of SPD T1)
Lightning and surge arrester Type 1 + Type 2
PI-k8 PIII-275/3+0
SPC25/3+0
Art. No. 24 001
(property protection)
3
3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A )
PIV12.5/3+0
LPL IV Buildings and halls without occurrence of persons and internal equipment
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
SPD type
PIIIM-275
SPC25/1+1
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Installation
<5m
PIII-275/3+0
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PIIIM-275/1+1
SPC25/2+0 Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
3+1 SPC12,5/3+1
3
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A)
Main switchboard
Step 1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
PIIIM-275/3+1
Art. No. 32 006
PIV 12,5-275/3+0
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
ZS-1DSM
Pk2
ZS-1I
(In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
100 %
(selection of SPD T3)
Art. No. 24 001
Installation
ZS-1DSM
PI-k8
EQUIPMENT
SPD type
Step 4
(selection of SPD T2)
(selection of SPD T1)
Additional SPD
Installation
PI-3k(16-120A)
Step 3
Step 2
(object selection)
PIII-275/1+1
SPD + EMI filter SPD type
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIII-275/3+0
Art. No. 10 736
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
2+0 TNS
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
Lightning arrester Type 1
ZS-1P
Coordination T2 a T3
PIII-275/3+0
1+1 1
LIGHTNING PROTECTION LEVEL III a IV
Type 2 - at boundaries of LPZ 1-2 (surge arrester)
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Agricultural structures
Art. No. 30 080
(property protection)
Art. No. 30 080
EQUIPMENT ZS-1P
Art. No. 10 152
Art. No. 32 006
EBB
EBB Surge arrester Type 2
Lightning arrester Type 1 + Type 2
EBB
<5m
PIV12,5/4+0
100 %
(selection of SPD T3)
Installation
Main switchboard
ZS-1DSM
Step 4
(selection of SPD T2)
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
4+0 SPC25/4+0
(object selection)
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
4+0
Step 1
Circuit
Installation Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Selection guide
LIGHTNING PROTECTION LEVEL III a IV
SPC25/4+0
Art. No. 10 651 the queen of power
Surge arrester Type 3
PIIIM-275/3+1
Surge arrester Type 2
Lightning arrester Type 1
EQUIPMENT
Art. No. 27 022
PIIIM-275/3+1 PIV 12,5-275/4+0
PI-3k120
Art. No. 30 307
EQUIPMENT
Art. No. 27 022
Art. No. 10 195 PI-3k120
EBB the queen of power
Surge arrester Type 3
the queen of power
Art. No. 30 307 the queen of power
Selection guide Classification of typical objects
System
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL II ( Iimp = 75 kA)
1
1+0 HS50-50
Industrial buildings Administrative buildings
Selection guide
LIGHTNING PROTECTION LEVEL II
TNC
Schools 3
Supermarkets
3+0
HS50-50/3+0
Coordination T1 and T2
Installation Substation Switchboard (kWh) Main switchboard Substation Switchboard (kWh) Main switchboard
<5m
5 metres cable or decoupling element PI-L (16-120 A )
Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
PIIIM-275
Objects connected by buried cable.
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
PIII-275/3+0
1+1 1
5 metres cable or decoupling element PI-L (16-120 A )
PIII-275/1+1
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
2+0 PIIIM-275/1+1
HS50-50/2+0
TNS 3+1
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
Coordination T2 a T3 <5m
PIII-275/3+0
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Cathedrals
Installation
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Selection guide
LIGHTNING PROTECTION LEVEL II Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter SPD type
Installation
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PI-k(8-150A)
Additional SPD SPD type
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Classification of typical objects
System
No. of phases
Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Objects with the main back-up fuse up to 63A connected by buried cable.
1
1+0 SPC25
LPL III Apartment houses Small administartive buildings
TNC
Family houses
PIIIM-275/3+1
Step 2
PI-3k(16-120A)
Step 3
(selection of SPD T1)
Lightning and surge arrester Type 1 + Type 2
PI-k8 PIII-275/3+0
SPC25/3+0
Art. No. 24 001
(property protection)
3
3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A )
PIV12.5/3+0
LPL IV Buildings and halls without occurrence of persons and internal equipment
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
SPD type
PIIIM-275
SPC25/1+1
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Installation
<5m
PIII-275/3+0
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PIIIM-275/1+1
SPC25/2+0 Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
3+1 SPC12,5/3+1
3
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A)
Main switchboard
Step 1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
PIIIM-275/3+1
Art. No. 32 006
PIV 12,5-275/3+0
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
ZS-1DSM
Pk2
ZS-1I
(In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
100 %
(selection of SPD T3)
Art. No. 24 001
Installation
ZS-1DSM
PI-k8
EQUIPMENT
SPD type
Step 4
(selection of SPD T2)
(selection of SPD T1)
Additional SPD
Installation
PI-3k(16-120A)
Step 3
Step 2
(object selection)
PIII-275/1+1
SPD + EMI filter SPD type
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIII-275/3+0
Art. No. 10 736
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
2+0 TNS
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
Lightning arrester Type 1
ZS-1P
Coordination T2 a T3
PIII-275/3+0
1+1 1
LIGHTNING PROTECTION LEVEL III a IV
Type 2 - at boundaries of LPZ 1-2 (surge arrester)
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Agricultural structures
Art. No. 30 080
(property protection)
Art. No. 30 080
EQUIPMENT ZS-1P
Art. No. 10 152
Art. No. 32 006
EBB
EBB Surge arrester Type 2
Lightning arrester Type 1 + Type 2
EBB
<5m
PIV12,5/4+0
100 %
(selection of SPD T3)
Installation
Main switchboard
ZS-1DSM
Step 4
(selection of SPD T2)
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
4+0 SPC25/4+0
(object selection)
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
4+0
Step 1
Circuit
Installation Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Selection guide
LIGHTNING PROTECTION LEVEL III a IV
SPC25/4+0
Art. No. 10 651 the queen of power
Surge arrester Type 3
PIIIM-275/3+1
Surge arrester Type 2
Lightning arrester Type 1
EQUIPMENT
Art. No. 27 022
PIIIM-275/3+1 PIV 12,5-275/4+0
PI-3k120
Art. No. 30 307
EQUIPMENT
Art. No. 27 022
Art. No. 10 195 PI-3k120
EBB the queen of power
Surge arrester Type 3
the queen of power
Art. No. 30 307 the queen of power
Selection guide Classification of typical objects
System
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL II ( Iimp = 75 kA)
1
1+0 HS50-50
Industrial buildings Administrative buildings
Selection guide
LIGHTNING PROTECTION LEVEL II
TNC
Schools 3
Supermarkets
3+0
HS50-50/3+0
Coordination T1 and T2
Installation Substation Switchboard (kWh) Main switchboard Substation Switchboard (kWh) Main switchboard
<5m
5 metres cable or decoupling element PI-L (16-120 A )
Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
PIIIM-275
Objects connected by buried cable.
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
PIII-275/3+0
1+1 1
5 metres cable or decoupling element PI-L (16-120 A )
PIII-275/1+1
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
2+0 PIIIM-275/1+1
HS50-50/2+0
TNS 3+1
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
Coordination T2 a T3 <5m
PIII-275/3+0
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Cathedrals
Installation
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Selection guide
LIGHTNING PROTECTION LEVEL II Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter SPD type
Installation
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PI-k(8-150A)
Additional SPD SPD type
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Classification of typical objects
System
No. of phases
Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Objects with the main back-up fuse up to 63A connected by buried cable.
1
1+0 SPC25
LPL III Apartment houses Small administartive buildings
TNC
Family houses
PIIIM-275/3+1
Step 2
PI-3k(16-120A)
Step 3
(selection of SPD T1)
Lightning and surge arrester Type 1 + Type 2
PI-k8 PIII-275/3+0
SPC25/3+0
Art. No. 24 001
(property protection)
3
3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A )
PIV12.5/3+0
LPL IV Buildings and halls without occurrence of persons and internal equipment
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
SPD type
PIIIM-275
SPC25/1+1
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Installation
<5m
PIII-275/3+0
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PIIIM-275/1+1
SPC25/2+0 Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
3+1 SPC12,5/3+1
3
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A)
Main switchboard
Step 1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
PIIIM-275/3+1
Art. No. 32 006
PIV 12,5-275/3+0
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
ZS-1DSM
Pk2
ZS-1I
(In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
100 %
(selection of SPD T3)
Art. No. 24 001
Installation
ZS-1DSM
PI-k8
EQUIPMENT
SPD type
Step 4
(selection of SPD T2)
(selection of SPD T1)
Additional SPD
Installation
PI-3k(16-120A)
Step 3
Step 2
(object selection)
PIII-275/1+1
SPD + EMI filter SPD type
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIII-275/3+0
Art. No. 10 736
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
2+0 TNS
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
Lightning arrester Type 1
ZS-1P
Coordination T2 a T3
PIII-275/3+0
1+1 1
LIGHTNING PROTECTION LEVEL III a IV
Type 2 - at boundaries of LPZ 1-2 (surge arrester)
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Agricultural structures
Art. No. 30 080
(property protection)
Art. No. 30 080
EQUIPMENT ZS-1P
Art. No. 10 152
Art. No. 32 006
EBB
EBB Surge arrester Type 2
Lightning arrester Type 1 + Type 2
EBB
<5m
PIV12,5/4+0
100 %
(selection of SPD T3)
Installation
Main switchboard
ZS-1DSM
Step 4
(selection of SPD T2)
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
4+0 SPC25/4+0
(object selection)
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
4+0
Step 1
Circuit
Installation Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Selection guide
LIGHTNING PROTECTION LEVEL III a IV
SPC25/4+0
Art. No. 10 651 the queen of power
Surge arrester Type 3
PIIIM-275/3+1
Surge arrester Type 2
Lightning arrester Type 1
EQUIPMENT
Art. No. 27 022
PIIIM-275/3+1 PIV 12,5-275/4+0
PI-3k120
Art. No. 30 307
EQUIPMENT
Art. No. 27 022
Art. No. 10 195 PI-3k120
EBB the queen of power
Surge arrester Type 3
the queen of power
Art. No. 30 307 the queen of power
Selection guide Classification of typical objects
System
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL II ( Iimp = 75 kA)
1
1+0 HS50-50
Industrial buildings Administrative buildings
Selection guide
LIGHTNING PROTECTION LEVEL II
TNC
Schools 3
Supermarkets
3+0
HS50-50/3+0
Coordination T1 and T2
Installation Substation Switchboard (kWh) Main switchboard Substation Switchboard (kWh) Main switchboard
<5m
5 metres cable or decoupling element PI-L (16-120 A )
Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
PIIIM-275
Objects connected by buried cable.
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
PIII-275/3+0
1+1 1
5 metres cable or decoupling element PI-L (16-120 A )
PIII-275/1+1
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
2+0 PIIIM-275/1+1
HS50-50/2+0
TNS 3+1
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
Coordination T2 a T3 <5m
PIII-275/3+0
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Cathedrals
Installation
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Selection guide
LIGHTNING PROTECTION LEVEL II Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter SPD type
Installation
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PI-k(8-150A)
Additional SPD SPD type
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Classification of typical objects
System
No. of phases
Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Objects with the main back-up fuse up to 63A connected by buried cable.
1
1+0 SPC25
LPL III Apartment houses Small administartive buildings
TNC
Family houses
PIIIM-275/3+1
Step 2
PI-3k(16-120A)
Step 3
(selection of SPD T1)
Lightning and surge arrester Type 1 + Type 2
PI-k8 PIII-275/3+0
SPC25/3+0
Art. No. 24 001
(property protection)
3
3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A )
PIV12.5/3+0
LPL IV Buildings and halls without occurrence of persons and internal equipment
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
SPD type
PIIIM-275
SPC25/1+1
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Installation
<5m
PIII-275/3+0
PIII-275/1+1
of SPD T2 is necessary, if the length is > 30 m from T1)
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
PIIIM-275/1+1
SPC25/2+0 Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
3+1 SPC12,5/3+1
3
of SPD T2 is necessary, if the length is > 30 m from T1)
5 metres cable or decoupling element PI-L (16-120 A)
Main switchboard
Step 1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
PIIIM-275/3+1
Art. No. 32 006
PIV 12,5-275/3+0
PI-k(8-150A)
To the switchboard, which is closest to the protected equipment (In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
ZS-1DSM
Pk2
ZS-1I
(In case of electronic control protection, the installation is directly to the appliance)
ZS-1P
PDU
PK2
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
100 %
(selection of SPD T3)
Art. No. 24 001
Installation
ZS-1DSM
PI-k8
EQUIPMENT
SPD type
Step 4
(selection of SPD T2)
(selection of SPD T1)
Additional SPD
Installation
PI-3k(16-120A)
Step 3
Step 2
(object selection)
PIII-275/1+1
SPD + EMI filter SPD type
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIII-275/3+0
Art. No. 10 736
(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
2+0 TNS
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
5 meters of cable or decoupling element PI-L(16-120 A)
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
Lightning arrester Type 1
ZS-1P
Coordination T2 a T3
PIII-275/3+0
1+1 1
LIGHTNING PROTECTION LEVEL III a IV
Type 2 - at boundaries of LPZ 1-2 (surge arrester)
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Agricultural structures
Art. No. 30 080
(property protection)
Art. No. 30 080
EQUIPMENT ZS-1P
Art. No. 10 152
Art. No. 32 006
EBB
EBB Surge arrester Type 2
Lightning arrester Type 1 + Type 2
EBB
<5m
PIV12,5/4+0
100 %
(selection of SPD T3)
Installation
Main switchboard
ZS-1DSM
Step 4
(selection of SPD T2)
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
4+0 SPC25/4+0
(object selection)
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
4+0
Step 1
Circuit
Installation Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Selection guide
LIGHTNING PROTECTION LEVEL III a IV
SPC25/4+0
Art. No. 10 651 the queen of power
Surge arrester Type 3
PIIIM-275/3+1
Surge arrester Type 2
Lightning arrester Type 1
EQUIPMENT
Art. No. 27 022
PIIIM-275/3+1 PIV 12,5-275/4+0
PI-3k120
Art. No. 30 307
EQUIPMENT
Art. No. 27 022
Art. No. 10 195 PI-3k120
EBB the queen of power
Surge arrester Type 3
the queen of power
Art. No. 30 307 the queen of power
Selection guide Type 2 - at boundaries of LPZ 1-2 (surge arrester) SPD type
Coordination T2 a T3
Installation
<5m
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275
PIII-275/3+0
PIII-275/3+0
PIII-275/1+1
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
Subsidiary switchboard, Switchboards on every floor of the object or in every control panel
PIIIM-275/1+1
PIII-275/3+1
Selection guide
LIGHTNING PROTECTION LEVEL I
If the distance from T1 is > 30 m, then it is necessary to install SPD T2
SPD + EMI filter SPD type
PIIIM-275/3+1
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
ZS-1DSM
Pk2
ZS-1I
To the switchboard, which is closest to the protected equipment
PI-k(8-150A)
(In case of electronic control protection, the installation is directly to the appliance)
PI-3k(16-120A)
Step 3
SPD type
To the switchboard, which is closest to the protected equipment
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
Additional SPD
Installation
5 meters of cable or decoupling element PI-L(16-120 A) (Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect SPD T3 against destruction. If there is a distance between T2 and T3 < 5 m, it is necessary to use decoupling elements. The recommended connection is in series, hence is required to know the nominal voltage of existing conductor.
ZS-1P
PDU
PK2
PI-k8 PIII-275/3+0
Art. No. 24 001
No. of phases
Circuit
Type 1-at boundaries of LPZ 0-1 (lightning arrester) SPD type
Buildings with considerable level of protection LPL I ( Iimp = 100 kA)
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
1
1+0
Hospitals
HS50-50
Banks Transmission point for GSM,BTS
TNC
Water stations
3
3+0
HS50-50/3+0
Aerodrome control tower
<5m
Substation Switchboard (kWh) Main switchboard
5 metres cable or decoupling element PI-L (16-120 A )
Substation Switchboard (kWh) Main switchboard
SPC25/3+0
of SPD T2 is necessary, if the length is > 30 m from T1)
HS50-50/1+1
Substation Switchboard (kWh) Main switchboard
1+1 Bigger industrial buildings
1
Buildings with particular importance
5 metres cable or decoupling element PI-L (16-120 A )
2+0 HS50-50/2+0
TNS
Type 1, Type 2, Type 3
3+1
Lighting Protection Level I Lighting Protection Level II Lighting Protection Level III Lighting Protection Level IV
SPC25/3+1
3
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)
4+0 SPC25/4+0
Step 1
Step 2
(object selection)
(property protection)
(selection of SPD T1)
Surge Protection Device
Art. No. 30 080
Installation
Buildings with danger of explosion
SPD SELECTION GUIDE
Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.
Coordination T1 and T2
Main switchboard Coordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation
Power plants
100 %
(selection of SPD T3)
System
Installation
ZS-1DSM
Step 4
(selection of SPD T2)
Classification of typical objects
Type 3 - at boundaries of LPZ 2-3 (surge arrester)
LIGHTNING PROTECTION LEVEL I
Lightning arrester Type 1
EQUIPMENT ZS-1P
HS50-50/3+0
Art. No. 32 006
Art. No. 10 090
EBB Surge arrester Type 2
PIIIM-275/3+1
H-SV-21-09-2016-EN-sales
Surge arrester Type 3
EQUIPMENT
Art. No. 27 022
PI-3k120
Art. No. 30 307 the queen of power
HAKEL spol. s r.o. Bratri Stefanu 980 500 03 spol. Hradec HAKEL s r.o. Kralove Czech Republic Bratří Štefanů 980 500 03 Hradec Králové tel.: +420 494 942 300 Česká republika fax: +420 494 942 303 e-mail: tel.:
[email protected] 494 942 300 www.hakel.com fax: +420 494 942 303 www.isolguard.com e-mail:
[email protected] www.hakel.cz
Lightning arrester Type 1 + Type 2
EBB
SPC25/4+0
Art. No. 10 651
the queen of power